Loading...
Specifications T I SO 55 c� .'"k t 3 0 BV Plc i i -c) 1 COMcheck Softw Version 3.8.0 Mecha Comp Certificate Oregon Energy Efficiency Specialty Code Section 1: Project Information Project Type: New Construction Project Title : Construction Site: Owner /Agent: Designer /Contractor: Section 2: General Information Building Location (for weather data): Portland, Oregon Climate Zone: 4c Section 3: Mechanical Systems List Quantity System Type & Description 1 HVAC System 1: Split System Heat Pump, Heat Capacity 60 kBtu /h Cool Capacity 58 kBtu /h, Heat efficiency: 8.00 HSPF, Cool efficiency: 13.20 SEER, Cool efficiency: 13.20 SEER / Single Zone 1 HVAC System 2: Split System Heat Pump, Heat Capacity 60 kBtu/h Cool Capacity 58 kBtu /h, Heat efficiency: 8.00 HSPF, Cool efficiency: 13.20 SEER, Cool efficiency: 13.20 SEER / Single Zone 1 HVAC System 3: Cooling: Split System, Capacity 36 kBtu /h, Efficiency: 13.00 SEER, Air - Cooled Condenser / Single Zone Section 4: Requirements Checklist In the following requirements, the relevant code section reference is shown in [ J. ' +' denotes that more details exist in the specified code section. Requirements Specific To: HVAC System 1 : L7 ' • [503.2.3 +J Equipment meets minimum efficiency: Heat Pump: 7.7 HSPF 13.0 SEER Requirements Specific To: HVAC System 2 : (r1. [503.2.3 +J Equipment meets minimum efficiency: Heat Pump: 7.7 HSPF 13.0 SEER Requirements Specific To: HVAC System 3 : E(' • [503.2.3 +J Equipment meets minimum efficiency: Split System: 13.0 SEER R2. [503.3.1 +J Supply air economizers shall be provided on each cooling system and are capable of providing 100 - percent outdoor air, even if additional mechanical cooling is required to meet the cooling load of the building. Systems provide a means to relieve excess outdoor air during economizer operation to prevent overpressurizing the building. 'i xception: Cooling equipment less than 54,000 Btu /hr total cooling capacity. The total capacity of all such units without economizers shall not exceed 240,000 Btu /hr per building area served by one utility meter or service, or 10 percent of its total Installed cooling capacity, whichever is greater. That portion of the equipment serving dwelling units and guest rooms is not Included in determining the total capacity of units without economizers. Location In plans/specs where compliance can be identified (enter NA it not applicable)* 'e /4/, 0 Generic Requirements: Must be met by all systems to which the requirement is applicable: V . I. [503.2.1 +J Calculation of heating and cooling loads. Design loads are determined in accordance with the procedures described in the ASHRAE/ACCA Standard 183. Alternatively, design loads have been determined by an approved equivalent computation procedure. • 82. [503.2.2 +J Equipment and system sizing. Heating and cooling equipment and systems capacity do not exceed the loads calculated in accordance with Section 503.2.1. Project Title: Report date: 02/24/11 Data filename: W:IPACTRUST1PAC1101 YECURIS\Yecuris1COMCHECK MECH.cdc Page 1 of 9 01 Required standby equipment and systems provided with controls and devices that allow such systems or equipment to operate automatically only when the primary equipment is not operating. 'Exception: Multiple units of the same equipment type with combined capacities exceeding the design load and provided with controls that have the capability to sequence the operation of each unit based on lo 0 /� Location In plans/specs where compliance can be Identified (enter NA it not applicable). Sees / / v r V / 124. [503.2.3 +] HVAC Equipment Performance Requirements. Reported efficiencies have been tested and rated in accordance with the applicable test procedure. The efficiency has been verified through certification under an approved certification program or, if no certification program exists, the equipment efficiency ratings are supported by data furnished by the manufacturer. '4. [503.2.4.1 +] Thermostatic Controls. The supply of heating and cooling energy to each zone is controlled by individual thermostatic controls that respond to temperature within the zone. // 1 // /� Location In plans/speca where compliance can be Identified (enter NA If not applicable): / t� Cl% °� r O 0/5. [503.2.4.1.1] Heat pump supplementary heat. Heat pumps having supplementary electric resistance heat have controls that, except during defrost, prevent supplementary heat operation when the heat pump can meet the heating load. Location In plans/specs where compliance can be Identified (enter NA It not applicable)* / // O [503.2.4.2] Set point overlap restriction. Where used to control both heating and cooling, zone thermostatic controls provide a temperature range or deadband of at least 5 °F (2.8 °C) within which the supply of heating and cooling energy to the zone is capable of being shut off or reduced to a minimum. ❑ Exception: Thermostats requiring manual change over between heating and cooling modes. Location In plans/specs where compliance can be Identified (enter NA if not applicable)* ` ' D / D Err. [503.2.4.3] Optimum Start Controls. Each HVAC system has controls that vary the start-up time of the system to just meet the temperature set point at time of occupancy. /V f J /� • Location In plans/specs where compliance can be Identified (enter NA If not applicable). DG/ (/ Q lrtG � �OY� E143. [503.2.4.4 +] Off-hour controls. Each zone is provided with thermostatic setback controls that are controlled by either an automatic time clock or programmable control system. Erixception: Zones that will be operated continuously. ❑ Exception: Zones with a full HVAC load demand not exceeding 6,800 Btu /h (2 kW) and having a readily accessible manual shutoff switch. O Location in plans/specs where compliance can be identified (enter NA if not applicable) r '9. [503.2.4.5 +] Shutoff damper controls. Both outdoor air supply and exhaust are equipped with not less than Class I motorized dampers. ❑ Exception: Gravity dampers shall be permitted for outside air Intake or exhaust airflows of 300 cfm or less. Location N plans /specs where compliance can be identified (enter NA If not applicable): / �O O / /1 / / U '10. [503.2.4.6 +] Freeze Protection and Snow melt system controls. Freeze protection systems, such as heat tracing of outdoor piping and heat exchangers, Including self - regulating heat tracing, include automatic controls capable of shutting off the systems when outdoor air temperatures meet code criteria. Ai A Location In plans/specs where compliance can be Identified (enter NA if not applicable). 5j1 1. [503.2.4.8] Separate air distribution systems. Zones with special process temperature requirements and /or humidity requirements are served by separate air distribution systems from those serving zones requiring only comfort conditions; or shall include supplementary control provisions so that the primary systems may be specifically controlled for comfort purposes only. ❑ Exception: [503.2.4.8 +] Zones requiring only comfort heating or comfort cooling that are served by a system primarily used for process temperature and humidity control. 7 Location In plans/specs where compliance can be Identified (enter NA if not applicable): 4 2. [503.2.4.9.1] Humidity control. Where a humidity control device exists it is set to prevent the use of fossil fuel or electricity to produce relative humidity in excess of 30 percent. Where a humidity control device is used for dehumidification, it is set to prevent the use of fossil fuel or electricity to reduce relative humidity below 60 percent. ❑ Exception: Hospitals, process needs, archives, museums, critical equipment, and other non -comfort situations with specific humidity requirements outside this range. Location In plans/speca where compliance can be Identified (enter NA If not applicable). Or 8'13. [503.2.4.9.2] Humidity control. Where a humidity control device exists it is set to maintain a deadband of at least 10% relative humidity where no active humidification or dehumidification takes place. ❑ Exception: Heating for dehumidification is provided with heat recovery or heat pumping and the mechanical cooling system efficiency is 10 percent higher than required in section 503.2.3, HVAC equipment performance requirements. Project Title: Report date: 02/24/11 Data filename: W:\PACTRUSTIPAC1101 YECURISWYecurls \COMCHECK MECH.cck Page 2 of 9 Location In plans/spece where compliance can be Identified (enter NA If not applicable): ` ' D �4. [503.2.5] Ventilation. Ventilation, either natural or mechanical, is provided In accordance with Chapter 4 of the International Mechanical Code. Where mechanical ventilation Is provided, the system has the capability to reduce the outdoor air supply to the minimum required by Chapter 4 of the International Mechanical Code. / 1 Location In plans/specs where compliance can be Identified (enter NA If not applicable): V 4 [503.2.5.1 +] Demand controlled ventilation (DCV). DCV Is required for spaces larger than 500 ft2 for simple systems and spaces larger than 150 ft2 for multiple zone systems. ❑ Exception: Systems with energy recovery complying with Section 503.2.6 la Exception: Spaces less than 750 ft2 (69.7 m2) where an occupancy sensor turns the fan off, closes the ventilation damper, or closes the zone damper when the space is unoccupied. , Location In plans/specs where compliance can be Identified (enter NA it not applicable): N - B'16. [503.2.5.2 +] Kitchen hoods. Kitchen makeup is provided as required by the Oregon Mechanical Specialty Code. ❑ Exception: Where hoods are used to exhaust ventilation air that would otherwise be exhausted by other fan systems. ❑ Exception: Kitchen exhaust systems that include exhaust air energy recovery complying with section 503.2.6. Location In plans/specs where compliance can be Identified (enter NA If not applicable): a [503.2.5.3 +] Enclosed parking garage ventilation controls. In Group S -2, enclosed parking garages used for storing or handling automobiles employs automatic carbon monoxide sensing devices. /v A Location In plans/specs where compliance can be Identified (enter NA If not applicable) ❑ 18. [503.2.6 +] Energy recovery ventilation systems. Individual fan systems that have both a design supply air capacity of 5,000 cfm or greater and a minimum outside air supply of 70 percent or greater of the design supply air quantity have an energy recovery system. O Exception: Where energy recovery systems are prohibited by the International Mechanical Code. ❑ Exception: Systems serving spaces that are not cooled and are heated to less than 60 °F. ❑ Exception: Where more than 60 percent of the outdoor heating energy is provided from site - recovered or site solar energy. ❑ Exception: Type 1 kitchen exhaust hoods. ❑ Exception: Cooling systems in climates with a 1- percent cooling design wet -bulb temperature less than 64 °F (18 °C). ❑ Exception: Systems requiring dehumidification that employ series -style energy recovery coils wrapped around the cooling coil when the evaporative coil is located upstream of the exhaust air stream. ❑ Exception: Systems exhausting toxic, flammable, paint exhaust, corrosive fumes, or dust. ❑ Exception: Laboratory fume hood systems that include qualifying features. Location in plans /specs where compliance can be Identified (enter NA if not applicable) A/, 4 9. [503.2.7 +] Duct and plenum insulation and sealing. All supply and return air ducts and plenums are insulated with the specified insulation. When located within a building envelope assembly, the duct or plenum is separated from the building exterior or unconditioned or exempt spaces by a minimum of R -8 Insulation. All ducts, air handlers and filter boxes are sealed. Joints and seams comply with Section 603.9 of the International Mechanical Code. ❑ Exception: When located within equipment. La Exception: When the design temperature difference between the Interior and exterior of the duct or plenum does not exceed 15 °F (8 °C). u40. [503.2.7.1.1 +] Low - pressure duct systems. All longitudinal and transverse joints, seams and connections of low- pressure supply and return ducts are securely fastened and sealed with welds, gaskets, mastics (adhesives), mastic-plus- embedded - fabric systems or tapes installed in accordance with the manufacturer's installation Instructions. ❑ Exception: Continuously welded and locking -type longitudinal joints and seams on ducts operating at static pressures less than 2 inches w.g. pressure classification. r Location In plans/specs where compliance can be Identified (enter NA If not applicable) '21. [503.2.7.1.2 +] Medium- pressure duct systems. All ducts and plenums designed to operate medium- pressure are insulated and sealed in accordance with Section 503.2.7. Pressure classifications specific to the duct system are clearly indicated on the construction documents. Location In plans/specs where compliance can be Identified (enter NA if not applicable) "22. [503.2.7.1.3 +] High- pressure duct systems. Ducts designed to operate at high- pressure are Insulated and sealed in accordance with Section 503.2.7. In addition, ducts and plenums are leak- tested in accordalce with the SMACNA HVAC Air Duct Leakage Test Manual. Location in plans/specs where compliance can be Identified (enter NA if not applicable): /(�/ Project Title: Report date: 02/24/11 Data filename: W:\PACTRUST\PAC1101 YECURIS \Yecurls \COMCHECK MECH.cck Page 3 of 9 c 23. [503.2.9.1 +] Air system balancing. Each supply air outlet and zone terminal device is equipped with means for air balancing in • accordance with the requirements of IMC 603.17. Discharge dampers Intended to modulate airflow are prohibited on constant volume fans and variable volume fans with motors 10 horsepower. A � ✓ n /AJ Location In plans/specs where compliance can be Identified (enter NA if not applicable)* 4 ' ' J s�) / / / u24 [503.2.9.3 [503.2.9.3 +] Manuals. The construction documents require that an operating and maintenance manual be provided to the building owner by the mechanical contractor. See long description for specifications. a � Location to plans/specs where compliance can be Identified (enter NA if not applicable)* / ' D / a j(25. [503.2.10 +] Air System Design and Control. Each HVAC system having a total fan system motor nameplate hp exceeding 5 hp meets the provisions of Sections 503.2.10.1 through 503.2.10.2. Location In plans/specs where compliance can be Identified (enter NA if not applicable): / p'26. [503.2.10.1 +] Allowable fan floor horsepower. Each HVAC system at fan system design conditions does not exceed the allowable fan system motor nameplate hp (Option 1) or fan system bhp (Option 2) as shown and calulated In requirement details. [Exception: Hospital and laboratory systems that utilize flow control devices on exhaust and /or return to maintain space pressure relationships necessary for occupant health and safety or environmental control shall be permitted to use variable volume fan power limitation. ❑ Exception: Individual exhaust fans with motor nameplate horsepower of 1 hp or less. Location In plans/specs where compliance can be Identified (enter NA if not applicable): D,© "27. [503.2.10.2 +] Motor nameplate horsepower. For each fan, the selected fan motor is no larger than the first available motor size greater than the brake horsepower (bhp). ❑ Exception: For fans less than 6 bhp, where the first available motor larger than the brake horsepower has a nameplate rating within 50 percent of the bhp, selection of the next larger nameplate motor size Is allowed. ❑ Exception: For fans 6 bhp and larger, where the first available motor larger than the bhp has a nameplate rating within 30 percent of the bhp, selection of the next larger nameplate motor size is allowed. Location In plans/spece where compliance can be Identified (enter NA if not applicable): Nf r n it / , 1 ► f/ 1248. [503.2.10.3.1] Large Volume Fan Systems. Fan systems over 8,000 (7 m3 /s) cfm without direct expansion cooling coils that serve single zones reduce airflow based on space thermostat heating and cooling demand. A two -speed motor or variable frequency drive reduces airflow to a maximum 60 percent of peak airflow or minimum ventilation air requirement as required by Chapter 4 of the International Mechanical Code, whichever Is greater. ❑ Exception: Systems where the function of the supply air Is for purposes other than temperature control, such as maintaining specific humidity levels or supplying an exhaust system. Location in plans/specs where compliance can be Identified (enter NA if not applicable)* "29. [503.2.10.4] Series fan - powered terminal unit fan motors. Fan motors for series fan - powered terminal units are electronically- commutated motors and have a minimum motor efficiency of 70 percent when rated in accordance with NEMA Standard MG 1 -2006 at full load rating conditions. �� Location In plans/specs where compliance can be Identified (enter NA d not applicable) 1 30. [503.2.12] Hot Gas Bypass Limitation. For cooling systems <= 240 kBtu /h, maximum hot gas bypass capacity is no more than 50% total cooling capacity. Location In plans/specs where compliance can be Identified (enter NA if not applicable) - Section 5: Compliance Statement Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans, specifications and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the Oregon Energy Efficiency Specialty Code requirements in COMcheck Version 3.8.0 and to comply with the mandatory requirements In the Requirements Checklist. �vu c e fl R � -- � 2 Z¢ 1 Name - Title Signature f" Dat Project Title: Report date: 02/24/11 Data filename: WAPACTRUSTIPAC1101 YECURIS\Yecurls\COMCHECK MECH.cck Page 4 of 9 25HPA5H Performance'' 15 Series Heat Pump Cclj•f•iej• with Purono Refrigerant Turn to the Experts 2 to 5 Nominal Tons (Sizes 24 to 60) Product Data • INDUSTRY LEADING r 1 mo = t FEATURES /BENEFITS "" ° S` Jam i - j ENERGY EFFICIENCY 71 � ,4 t' 7 k' - 1 b • 15 SEER/13 EER /9 HSPF (Nominal) ' f s�Y F r IJI IJ II s AESTHETIC DESIGN g 1 ; .1 , 1 ,p I' � r l_ f r (1�ir11 1 i 1 X11 1 ' � i • ; • Weather,.rmor Ultra"" Ill! 1� 1 III 11 i -i � � , � 1_,31, �� � � � � . � � 1 , 1I • Baked -on powder paint -',111) Nl ��'1 1 li i , ' " � ` • Steel louver coil guard � ' { i r � ` 1I� ; F p�[, �I1I • Color matched cabinet screws `11 `111 j �� � i ��� 1 IJ I i I I 1' :,., O t t ' 01 11 1 1 n 1 )� f111 EXTRA QUIET OPERATION ., , , 1 I ` ' 1 l • r - E F 1 IJ 1 t ' • Silencer System II'" for sound as low as 68 dBA 1 : 1. s�i1��('1'4lt j t Il r• - Quietmountsplitpostcompressorgrommets ' d 1 .11' 11 , fIt' n [ 1 4 - ; ,. - — External silencer muffler 11 P l(111,,i,_. � I' 4 [i,f , j ,� 1, , ,� — Exclusive Silencer top design — 8 Pole PSC ball- bearing condenser fan motor — Forward -swept condenser fan blade - ' Performance - Compressor blanket ICV 1 f . ' v - Quiet shift defrost . , , RELI QUALITY AND TOUGHNESS Puron. • Scroll compressor the environmentally sand refrigerant • Field - installed 16 cu. in. filter drier • • Back - seating service valves Carrier's heat pumps with Puron® refrigerant provide a collection of features unmatched by any other family of equipment. The • High - pressure switch • 25HPA has been designed utilizing Carrier's Puron® refrigerant. • Loss -of- charge switch The environmentally sound refrigerant allows consumers to make a • Internal pressure- relief valve responsible decision in the protection of the earth's ozone layer. As an Energy Star® Partner, Carrier Corporation has determined • Internal thermal overload that this product meets the Energy Star® guidelines for energy • Suction line accumulator efficiency. Refer to the combination ratings in the Product Data for • Vapor fog eliminator system combinations that meet Energy Star® guidelines. CONTROLS AND DIAGNOSTICS • NOTE: Ratings contained in this document are subject to • Infinity" Control compatible change at any time. Always refer to the AHRI directory • On -board Carrier diagnostics (www.ahridirectory.org) for the most up -to -date ratings • Up to 14 point diagnostic capability information. • Long line accessory connections APPLICATIONS • Long -line - up to 250 feet (76.20 m) total equivalent length, up to 200 feet (60.96 m) condenser above evaporator, or up to 80 ft. (24.38 m) evaporator above condenser (See Longline Guide for more information) • Low ambient (down to - 20 °F /- 28.9 °C) with accessory I kit x' COMBINATION RATINGS (CONT.) 4' ,4 .r. High Temp Low Temp ARI Ref. No. Model Number Coll Model Number Furnace Model Number Cooling Capacity EER SEER HSPF E Capacity E COP H Capacity H COP ■ 1394218 25HPA548H30 CSPH•4812A•• 68MV(B,C)080 -20 47000 11.5 14.0 48000 3.88 8.4 30400 2.84 1395952 25HPA548H30 CSPH•4812A•• 58MV(B,C)100 -20 47000 12.0 14.6 48000 3.70 8.5 30400 2.64 1397743 25HPA548H30 C8PH•4812A'• 58MV(B,C)120 -20 47000 12.0 14.6 48000 3.70 8.4 30400 2.68 1 3016394 25HPA548H30 CSPH•4812A•• 58PH -16 47600 12.0 14.5 48000 3.78 8.7 30400 2.88 f 3018395 26HPA548H30 CSPH 56PH•110 -20 47000 12.0 14.8 48000 3.78 8.7 30200 2.70 3016398 25HPA548H30 CSPH'4812A•• 58PH'135 -20 47000 12.0 14.5 48000 3.74 8.7 30200 2.68 1125933 25HPA548H30 CSPH +TDR 47000 11.5 14.0 48000 3.68 8.4 30800 2.82 1125957 25HPA548H30 CSPH'6012A•• 58CV(A,X)090 -18 48000 12.5 15.0 48000 3.78 8.8 30400 2.70 1126959 25HPA548H30 CSPH•6012A•• 58CV(A,X)110 -20 48000 12.5 15.0 48000 3.80 8.6 30200 2.72 1125981 25HPA548H30 CSPH 58CV(A)X)135 -22 48000 12.5 15.0 48000 3.84 8.7 30200 2.74 1125963 25HPA548H30 C5PH•6012A•• 68CV(A,X)155 -22 48000 13.0 15.0 48000 3.88 8.7 30000 2.74 . 3107482 25HPA548H30 CSPH 58MEB080 -18 48000 12.0 14.5 48000 3.84 8.8 30800 2.70 3107483 25HPA548H30 CSPH•6012A•• 68MEB100 -20 46000 12.5 15.0 48000 3.88 8.9 30400 2.74 3107484 25HPA548H30 CSPH•6012A•• 58MEB120 -20 48000 12.5 15.0 48000 3.90 9.0 30400 2.78 1394219 25HPA548H30 CSPH•6012A•• 58MV(B,C)080 -20 47500 12.0 14.5 48000 3.78 8.5 30400 2.68 = 1395955 26HPA548H30 C8PH•6012A•• 68MV(B,C)100 -20 48000 12.5 15.0 48000 3.78 8.6 30400 2.70 Q 1397748 25HPA548H30 CSPH 58MV(B,C)120 -20 47600 12.5 15.0 48000 3.78 8.6 30400 2.68 O. 3016397 26HPA548H30 CSPH•8012A•• 68P11.090-18 48000 12.6 160 48000 3.88 8.8 30800 2.72 I 3018398 25HPA548H30 CSPH'6012A'• 58PH'110 -20 48000 12.5 15.0 48000 3.88 8.9 30200 2.74 rn N 3016399 25HPA548H30 CSPH•6012A•• 58PH•135 -20 48000 12.5 15.0 48000 3.88 8.9 30400 2.74 1125949 25HPA548H30 CSPH +TDR 47500 11.5 14.0 48000 3.72 8.5 30800 2.64 y Vi 7`s�� 2 1^ ii E S E'4Y�v 14' 1a.7.. :4'+"i 2h'.,. $�� :M•'. ., d F T`.- r,. .nF �+`s} -+•� ��.�' `X <�.,Fn'�� f�,9,'ry�r:..��4:t'•� ?� §« -7�', ��.ticF�. _� b��i. �''?� MAN ��%, 1169077 25HPA560H30 tFV4BN8006 69000 11.7 14.0 80000 3.72 8.7 38000 2.70 1125979 . 25HPA580H30 CAP• 56CV(A,X)110 -20 58000 11.2 13.5 60000 3.54 8.1 38000 2.62 3107485 25HPA560H30 CAP 58MEB100 -20 58000 11.0 13.6 80000 3.64 8.2 38000 2.62 3018400 25HPA560H30 CAP'•6021A" 58PH'090 -18 68000 11.2 13.5 60000 3.62 8.2 38000 2.60 3018401 25HPA560H30 CAP••6021A•• 58PH -20 68500 11.2 13.5 60000 3.68 8.3 38000 2.84 1125977 25HPA560H30 CAP 58000 11.0 13.2 60000 3.54 8.1 38500 2.80 1125983 25HPA560H30 CAP•'6024A•• 58CV(A,X)135 -22 58000 11.2 13.5 60000 3.58 8.2 38000 2.64 1125985 25HPA560H30 CAP••6024A•• 58CV(A,X)155 -22 58500 11.6 14.0 60000 3.60 8.2 38000 2.68 3107486 25HPA560H30 CAP 58MEB120 -20 58000 11.0 13.5 60000 3.58 8.2 37800 2.84 1\ 3016402 25HPA5601130 CAP••6024A•• 58PH•135 -20 58000 11.2 13.5 60000 3.54 8.2 38000 2.62 �yty 1125981 25HPA560H30 CAP••6024A•• +TDR 58000 1(.0 13.2 60000 3.54 8.1 38500 2.60 j/I 1125995 25HPA560H30 CNPH•6024A•• 58CV(A))110 -20 57500 11.2 13.5 60000 3.48 8.0 38000 2.60 1125997 25HPA560H30 CNPH•6024A•• 58CV(A,X)135 -22 58000 11.2 13.6 60000 3.60 8.1 37600 2.82 1125999 25HPA560H30 CNPH•6024A•• 58CV(A,X)155 -22 68000 11.6 14.0 60000 3.54 8.1 37800 2.64 3107487 25HPA560H30 CNPH•6024A'• 58ME8080 -16 57000 11.0 13.0 60000 3.40 8.0 38000 2.58 3107488 25HPA560H30 CNP1-1•6024A•• 58MEB100 -20 57500 11.0 13.5 60000 3.48 8.1 37800 2.60 3107489 25HPA560H30 CNPH 58MEB120 -20 56000 11.0 13.5 60000 3.50 8.2 37800 2.62 3018404 25HPA560H30 CNPH•6024A" 58PH -18 57500 11.2 13.5 60000 3.48 8.1 38000 2.60 1 P -Ii 3018405 25HPA560H30 CNPH•6024A•• 68PH•110 -20 58000 11.2 13.6 80000 3.52 8.2 38000 2.82 le_IP 3016408 25HPA560H30 CNPH 58PH•135 -20 67500 11.2 13.6 60000 3.48 8.1 38000 2.62 1125993 25HPA560H30 CNPH•6024A'• +TDR 68000 11.0 '133 60000 3.48 8.0) 38500 2.60 1125989 25HPA560H30 CNPV•6024A•• 58CV(A,X)135 -22 68000 11.2 13.5 60000 3.50 8.1 37800 2.62 1125991 25HPA560H30 CNPV•6024A'• 58CV(A,X)155 -22 68000 11.5 14.0 60000 3.54 8.1 37800 2.64 3107683 26HPA560H30 CNPV 58MEB120 -20 68000 11.0 13.5 60000 3.50 8.2 37800 2.82 3016403 25HPA560H30 CNPV•6024A•• 58PH -20 57500 11.2 13.5 60000 3.48 8.1 38000 2.62 1125987 25HPA560H30 CNPV•6024A" +TDR 58000 11.0 13.2 60000 3.48 8.0 38500 2.60 1126003 25HPA560H30 CSPH 58CV(A,X)110 -20 68000 11.2 13.5 60000 3.68 8.2 38000 2.84 1126005 25HPA560H30 CSPH•6012A•• 58CV(A,X)135 -22 58500 11.5 14.0 60000 3.60 8.2 38000 2.66 1126007 25HPA560H30 CSPH•6012A•• 58CV(A,X)155 -22 68500 11.5 14.0 60000 3.62 8.3 38000 2.88 3107490 25HPA560H30 CSPH'6012A'• 58MEB080 -18 57500 11.0 13.5 60000 3.48 8.1 38000 2.60 3107491 25HPA560H30 CSPH•6012A•• 58MEB100 -20 58000 11.0 13.6 60000 3.56 8.3 38000 2.84 3107492 25HPA560H30 CSPH'6012A•• 58MEB120 -20 68500 11.0 13.6 80000 3.58 8.3 37800 2.68 3018407 25HPA560H30 CSPH•6012A•• 58PH•090 -18 58000 11.2 13.6 60000 3.54 8.2 38000 2.82 3018408 25HPA560H30 CSPH•6012A•' 58PH•110 -20 58500 11.2 13.5 60000 3.62 8.4 38000 2.68 3018409 25HPA560H30 CSPH 58PH -20 58000 11.2 13.5 60000 3.58 8.3 38000 2.64 1126001 2511PA560H30 CSPH +T0R 58000 11.0 13.2 60000 3.58 Si 38500 2.82 See notes on pg. 23 • . 22