• — Portland General Electric Company
� GE
. 07/07/10 /
CONTACT: Bill Dixon W Accurate Electric, Inc N.
PHONE: 1 -360- 903 -8018
• CUSTOMER NAME. Commercail Buildin Remodel/Addition
ADDRESS: 12785 Sw Pacific Hwy, Tigard
•
SDC /ENGR: Milo Starr WR: 615459 •
PHONE: 503 - 570 -4414
3 -PHASE SECONDARY LINE -LINE FAULT CURRENT RMS
.;
' TRANSFORMER DATA _
i XFMR Impedance ( %): 1.3 % 3 -PHASE SUBMERSIBLE
r TRANSFORMER SIZE: 300 KVA XFMR ? — NO
"' ; Secondary VOLTAGE (L to L.): 208 v WYE
' + VAULT --> VAULT or Pole --> Pole SECONDARY
`.' i; Secondary Wire LENGTH: 0 Feet WIRE SIZE
,'I„ Number of SECONDARY RUNS: 1 Hun(s) of: , i
' Secondary WIRE Resistance R: 0.0180 Ohms/1000' .
• Secondary WIRE Reactance X: 0.0258 Ohms/1000'
r '' t VAULT ( or Pole) —> PANEL SECONDARY (or Svc Drop)
;' Service Wire LENGTH: 35 Feet WIRE SIZE
' i Number of Service RUNS: 3 Run(s) of: x350 GX UG j
Service WIRE Resistance R: 0.0600 Ohms /1000'
i Service WIRE Reactance X: 0.0330 Ohms/1000' .
i
i -- 1
I r
.' ' i MAXIMUM FAULT CURRENT*: 44,915 Amps
' Maximum fault current basedn transformers /conductors sized for 100% of electrical panel rating.
Based on a • anel size of: 800 am • Amps .
To Print This Page: 'Ctrl M" and choose "Print 3 -Phase Data"