Correspondence March 4, 2004 a Wyatt Fire Protection 9095 SW Burnham Tigard, OR 97223 RE: FIRE SPRINKLER SYSTEM @ PICTURE PEOPLE Building Permit: BUP2004 -00059 Construction Type: VN Tenant Name: Picture People Occupancy Type: M Address: 9653 SW Washington Square Road Occupant Load: 78 Hazard: Light The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. 1. A supply of spare sprinklers (never less than 6) shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. These sprinklers shall correspond to the types and temperature ratings of the sprinklers in the property. Standard 9 -1, section 2 -2.7.1 OSSC 2. A special sprinkler wrench shall be provided and kept in the cabinet along with the spare sprinklers to be used in the removal and installation of sprinklers. Standard 9 -1, section 2 -2.7.2 OSSC 3. A minimum of 18 inches shall be maintained between top of storage and ceiling sprinkler deflectors. Section 4 -4.1.6 and 4 -4.3.2 OSSC 4. Clearances shall be provided around all piping extending through walls, floors, platforms and foundations. Minimum clearance for pipe sizes 1 inch through 3 '/2 inches shall be not less than 1 inch. Standard 9 -1, section 4- 5.4.3.4 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. r: - plans shall be available to the Building Division inspectors throughout all ph. - s of • de( ctio i . 11 6.4.2 OSSC Respect 'r i Blalo Senior Plans Examiner