Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Specifications
t. &120 Lvsr __. 3 - Global Project Values: Project Name:IVSP - SUITE 340 Standby Hours: 24 Project ID: 903 I Alarm Mins: 5 I • ` Prepared By: ADAM SWEET I Derating Factor: 1.2 (rji hnology Gf aup Inc. Date: 10/6/2009 I Voltage Drop Warning Threshold % : 10 utomation Fire Alarm Entertainment Panel ID: NAC3B I Model: Simplex 4009 IDNet Power Extender Max Circuit Current: 2 Amps Location: 3RD FLOOR ELEC ROOM I Volts: 24 VDC Max Panel Current: 8 Amps Current Draw Wire AWG Ohms Per Length(ft) Actual Volts Ckt.# @ %Drop Circuit Name /oDrop Standby Alarm & Type 1000 Ft. One -Way Ohms EOL i 1 V1 0.000 0.000 #14 Solid 2.52 0.00 20.40 0.00% 2 V2 0.000 0.741 #14 Solid 2.52 270 1.36 19.39 4.94% 3 V3 0.000 0.000 #14 Solid 2.52 0.00 20.40 0.00% 4 V4 0.000 0.000 #14 Solid 2.52 0.00 20.40 0.00% Aux 5495(1) Aux Power Out 0.000 0.000 #14 Solid 2.52 0.00 20.40 _ 0.00% - 4009 4009 NAC Extender 0.085 0.185 0.741 (Amps) Total Output Power Required Total Standby Current (Amps) 0.085 0.926 Total Alarm Current (Amps) Standby Time In Hours 24 0.083 Alarm Time In Minutes / 60 (5 Mins) Total Standby AH Required 2.040 0.077 Total Alarm AH Required Total Combined AH Required 2.12 Wire resistances are based upon an ambient temperature of 72 degrees F. Because of Multiply By The Derating Factor 1.20 the minimal difference between solid and stranded wire no differential was made. Minimum Battery AmpHours Required 2.54 Panel ID: 5495(2) Model: Silent Knight 5495 Power Expander Max Circuit Current: 3 Amps Location: Volts: 24 VDC Max Panel Current: 6 Amps Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ %Drop Ckt.# Circuit Name Drop Standby Alarm & Type 1000 Ft. One -Way Ohms EOL 1 5495(2) Circuit 1 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% 2 5495(2) Circuit 2 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% 3 5495(2) Circuit 3 0.000 0.000 #14 Solid 1.59 0.00 20.40 0.00% 4 5495(2) Circuit 4 0.000 0.000 #14 Solid 1.59 0.00 20.40 0.00% Aux 5495(2) Aux Power Out 0.000 0.000 #14 Solid 1.59 0.00 20.40 0.00% 5495 5495 Power Expander 0.075 0.205 0.000 (Amps) Total Output Power Required Total Standby Current (Amps) 0.075 0.205 Total Alarm Current (Amps) Standby Time In Hours 24 0.083 Alarm Time In Minutes / 60 (5 Mins) Total Standby AH Required 1.800 0.017 Total Alarm AH Required Total Combined AH Required 1.82 Wire resistances are based upon an ambient temperature of 72 degrees F. Because of Multiply By The Derating Factor 1.20 the minimal difference between solid and stranded wire no differential was made. . Minimum Battery AmpHours Required 2.18 O C T 07 2 0 09 N Circuit Configuration • Project Information Project Name: VSP - SUITE 340 Project ID: 903 Prepared By: ADAM SWEET Date: 10/6/2009 Ckt. Number: 1 Panel ID: NAC3B Ckt. Name: V1 Max Circuit Current: 2 Amps Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm Unknown 0.000 0.000 0.000 0.000 Unknown 0.000 0.000 0.000 0.000 I Unknown 0.000 0.000 0.000 0.000 Unknown 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Ckt. Number: 2 Panel ID: NAC3B Ckt. Name: V2 Max Circuit Current: 2 Amps Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 2 4906-9104 15cd 0.000 0.050 0.000 0.100 1 4906- 913015cd 0.000 0.057 0.000 0.057 1 4906 -9104 30cd 0.000 0.083 0.000 0.083 3 4906 -9130 75cd 0.000 0.167 0.000 0.501 0.000 0.000 Totals 0.000 0.741 Ckt. Number: 3 Panel ID: NAC3B Ckt. Name: V3 Max Circuit Current: 2 Amps Qty Device Current Draw Each Current Draw Total Standby _ Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Ckt. Number: 4 Panel ID: NAC3B Ckt. Name: V4 Max Circuit Current: 3 Amps Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 „Simplex LifeAlarm Fire Alarm Controls TM UL, ULC, CSFM Listed; FM Approved; 4009 IDNet NAC Extender for Control from 4010 or MEA (NYC) Acceptance* 4100U IDNet Communications; or from Conventional NACs Features Provides additional notification appliance circuit - - (NAC) capacity with flexible operation modes and ”" power - limited design Up to 8 NACs - ; mk Class B (Style Y) NACs are standard: 1 lor • Rated 2 A each for conventional reverse polarity 4009 IDNet 24 VDC notification appliances and providing NAC Extende m RECEIVED j � i1 multiple operation modes 1111111111i Ii ��li 11/ • Can be selected to provide synchronization for OCT 7 2009 Simplex visible notification strobe flashes i Optional IDNet • Capable of controlling TrueAlert non - addressable Channel Repeater notification appliances operating with SmartSyncTM 3 IGARD e I OFTIGARD two -wire control mode** I - / N N rt :o . Input control options: / �, • IDNet addressable communications from a Simplex 2 -Wire IDN •� � \ . \ Communications or \ model 4010 or 4100U Fire Alarm Control Panel ** i ■ Fiber Optic IDNet .. • Or from one or two conventional 24 VDC NACs with I Communications or ‘, multiple output control options ■ \ NAC Control IDNet communications control benefits: • i 1 , • Provides status monitoring and individual NAC control ® _ IDNet Fiber - using a single address per 4009 IDNet NAC Extender Optic Transmitter • Supports IDNet "Device Level" earth fault location 1 • WALKTESTTM operation is available with either 400(FheAlar p 4100U Fire Alarm ■..mm input choice Control Panel Internal 8 A power supply /battery charger: Fire Alarm Control Panel with • Charges internal batteries up to 12.7 Ah or up to 18 Ah Conventional NACs batteries in external cabinet • Provides status monitoring of battery, input power, and 4009 IDNet NAC Extender Connection Reference Drawing earth faults Introduction • Rated 8 A for "Special Application" appliances; including Simplex 4901, 4903, 4904, and 4906 Series ADA Compliance. Complying with the notification horns, strobes, horn/strobes, and speaker /strobes requirements of ADA (Americans with Disabilities Act) • Rated 6 A for "Regulated 24 DC" appliance power may require more notification appliance power than is available within the fire alarm control panel. When Optional 4009 IDNet NAC Extender modules: additional power is required, a Simplex 4009 IDNet NAC • IDNet Communications Repeater provides Class B Extender can provide up to 8 A of NAC power with up to (Style 4) or Class A (Style 6) output eight, supervised reverse polarity NACs. • IDNet Communications Fiber Optic Receiver/Repeater, Location Flexibility. The 4009 IDNet NAC Extender available as Class B or Class A can be mounted close to a compatible dedicated host • Four additional Class B NACs, rated 1.5 A for Special panel or can be located remotely for convenient power Application appliances; 1 A for Regulated 24 DC distribution. Multiple operation modes and multiple appliance power connection options further increase location flexibility. • Class A (Style Z), Two Circuit Adapter Module Additional Information. For additional operation detail • U L Listed to Standard 864 and application information, refer to Installation Instructions 574 -181 and field wiring diagram 842-068. External Accessories . • ULC listed model is 4009- 9202CA. This product has been approved by the California Slate IDNet communication fiber tic transmitters: Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. p See CSFM Listing 7300- 0026:214 for allowable values and/or conditions concerning • For applications requiring the data integrity available material presented in this document It is subject to reexamination, revision, and possible cancellation. Accepted fa use — Qty of New York Department of Buddings — MEA35.93E. with fiber optic communications Add bond listings may be applicable; contact your local Simplex product supplier for the • Available as Class B (Style 4) or Class A (Style 7) latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster. • Mounts in standard six -gang electrical box » SmartSync horNstrobe operation is protected under U.S. Patent No 6,281,789. IDNet External battery cabinet for 18 Ah batteries addressable communications are protected under U.S. Patent Nos 4,796,025; 5,966,002; and 6,034,601. 4100U requires revision 11 software or higher for t Simplex WALKTEST service testing is protected under U S Patent No 4,725,818 compatibility. 4010 requires revision 2 software or higher fa compabbf ity. 94009 -0002-0 8/2009 Application and Operation Information Hardwire Control Applications. For applications where an existing (or new) conventional NAC needs IDNet Addressable Communications Compatible. additional power, the 4009 IDNet NAC Extender can be Up to five, 4009 IDNet NAC Extenders can be controlled controlled directly from the NAC. Either one or two on a single IDNet communications channel. Each output NACs, from either the same, or from different host fire NAC can be individually controlled for general alarm or alarm control panels, can be connected to control the 4009 selective area notification requiring only one point IDNet NAC Extender output NACs. Multiple control address per Extender. Individual Extender NACs can also selections provide flexible operation. (Refer to page 4 for be manually controlled from the host panel. IDNet more detail.) Alarms from the host panel will activate the controlled extenders will inform the host panel of troubles four, 4009 IDNet NAC Extender NACs (or optionally, via IDNet communications. 4100U control panels control eight NACs) to extend the alarm. using multi -point rules, refer to data sheet 54090 -0011 for details. The 4009 IDNet Extender monitors itself and each of its output NACs for trouble conditions, including earth Optional IDNet Repeaters. IDNet communications faults. Extenders wired to conventional NACs will can be repeated with the optional IDNet Repeater Module indicate a trouble by opening the path to the NAC's or with the optional Fiber Optic Receiver Module. Up to end -of -line resistor, but retaining the ability to respond to 100 of the IDNet channel points can be repeated once alarms. Individual troubles are also annunciated by LEDs (refer to pages 3 and 5 for details). Repeated IDNet located on the 4009 IDNet NAC Extender main circuit communications also support the "device level" earth board. (Refer to page 7 for more diagnostic information.) fault location utility of the host panel. Product Selection Standard Models Model Description 4009 -9201 120 VAC input 4009 9202CA* 4009 IDNet NAC Extender with 4, Class B (Style Y) NACs and 8 A power supply 4009 -9301 240 VAC input ULC listed model Optional Modules (for on -site installation) Model Description Comments Additional four point NAC module, rated 1.5 A Special 4009 -9807 Application appliances; 1 A for Regulated 24 DC appliance One maximum power, Class B (Style Y), 4009 -9808 Dual Class A (Style Z) adapter (for two NAC outputs) Select as required (4 maximum) 4009 -9809 IDNet Repeater, output is Class A (Style 6) or Class B (Style 4) Select either an IDNet Repeater or a 4009 -9810 Fiber Optic Receiver Class B (Style 4) Fiber Optic Receiver as required 4009 -9811 Class A (Style 7 fiber, Style 6 IDNet) 4009 -9805 Red Applique for door Select if required 2975 -9801 Semi Flush Trim Kit Beige trim 1- 7/16" wide (78 mm), use if required for 2975 -9802 Red trim semi -flush installations Battery Selection (select battery size per system requirements) Model Description Comments 2081 -9272 6.2 Ah Battery, 12 VDC 2081-9274 10 Ah Battery, 12 VDC Two batteries are required, 24 VDC operation 2081 -9288 12.7 Ah Battery, 12 VDC 2081 -9275 18 Ah Battery, 12 VDC Requires external battery cabinet, two batteries are required, 24 VDC operation External Accessories (select per system requirements) Model Description Comments 4090 -9105 IDNet Fiber Optic Class B (Style 4) operation Mounts in six -gang electrical box, refer to 4090 -9107 Transmitter Class A (Style 7) operation page 4 for mounting details 4009 -9801 External battery cabinet for up to 18 Ah batteries, beige 16-1/4" W x 13-1/2" H x 5-3/4" D (413 mm x 343 mm x 146 mm) 4081 Series End -of -Line Resistor Harnesses; see data sheet S4081 -0003 for details 2 S4009- 0002 -6 8/2009 Typical IDNet Connection Example Typical IDNet compatible devices (Refer to individual devices for actual wiring requirements, some wiring is not shown.) e w r.. IDNet addressable communications channel, —,.... _ Class B (Style 4) Output NAC5, four standard, Conventional NAC operation (horns) eight with expansion option Select conventional or SmartSync I BIM @ -aaas I operation per NAC 4100U (shown) or 4010 Fire Alarm Control Panel I __ • ia , I SmartSync operation (horns and strobes) 4009 IDNet NAC Extender with =_ - -_ _ optional internal IDNet Repeater c°1 operation Conventional (strobes ) Repeated IDNet Channel: up to 100 devices maximum on repeater output, I®I c 250 devices total on IDNet Channel IDNet devices and additional 4009 IDNet NAC Extender(s) NOTE: Up to five (5) 4009 IDNet NAC Extenders may be connected to one IDNet channel. IDNet communications can be repeated only once (can pass through only one series connected repeater or one fiber optic receiver). Typical Fiber Optic System Connections Two fiber cables, 3000 ft Output NACs 4090 -9105, Class B (914 m) maximum distance (Style 4) Output Fiber i IMMIM I1 � R llllllllllllllllllllllllllllllllllllllllllllllllllllllllllll Optic Transmitter : I1 ( ! L J J I ... m m m I I I I I I II mr i k - a .. / _ IDNet addressable communications I" channel Class B (Style 4) or Class A (Style 6), Class B shown Repeated IDNet Channel: up to 100 devices maximum on repeater output, 250 devices total on IDNet Channel ■INIMMIi llll IIWlWlIUR■Itall Four fiber cables, 3000 ft 4010 or 4100U Fire (914 m) maximum distance Alarm Control Panel I •" miE 24 VDC power for 1 1111111!! ~1 fiber optic transmitters �� j r 4090 -9107, Class A (Style 7) . , Output Fiber Optic Transmitter r ow 4009 IDNet NAC Extenders with optional Output NACs internal IDNet Fiber Receivers NOTE: Up to five (5) 4009 IDNet NAC Extenders may be connected to one IDNet channel. IDNet communications can be repeated only once (can pass through only one series connected repeater or one fiber optic receiver). Fiber optic transmitters connect to only one 4009 IDNet NAC Extender. 3 S4009 -0002 -6 8/2009 Hardwire Control Connection Information Smart Sync Notification Appliance Control NAC Input Selections. The 4009 IDNet NAC The TrueAlert Notification Appliance product line Extender can be selected to: includes addressable and non - addressable operation. • Track input NAC operation or to provide a locally Non addressable models are available with 2 -wire generated code, selectable per NAC input SmartSync operation or conventional 4 -wire operation. The following details apply to use with the 4009 IDNet • If selected for local coding, NAC outputs can be either NAC Extender: Temporal Coded or 60 Beats /min March Time Coded, one code selection per extender (input NACs must be on • TrueAlert non - addressable models with Smart Sync continuous with Alarm) operation allow audible notification to be separately • Additionally, NAC outputs can be selected to provide controlled over the same wire pair that controls visible notification Simplex strobe synchronization signal. This signal fication (protected under U.S. Patent No. 6,281,789) will synchronize the flashes of synchronized strobes but • 4009 IDNet NAC Extenders can be selected to provide will be ignored by free -run strobes and audible devices. Smart Sync operation whether controlled by IDNet (Strobes are for operation by noncoded NACs.) communications or conventional NACs NAC input to NAC output control can be selected for • IDNet control allows output NACs to be individually standard and optional NACs per the following table: selected for conventional or Smart Sync operation Conventional NAC Output Operation Options • With NAC input control, all output NACs are selected Input A B C for either conventional or Smart Sync operation NAC 1 NACs 1 & 2, 5 & 6 NACs 1 - NACs 1 - • Refer to data sheet S4009 -0003 for TrueAlert NAC 2 NACs 3 & 4, 7 & 8 NACs 5 - None Addressable operation details, contact your local SmartSync NAC Output Operation Simplex product supplier for further information on Input NAC Control Function specific TrueAlert notification appliances NAC 1 Strobe Control NAC 2 Horn Control All MAC outputs (1 -8) Hardwire Control NAC Connection One -Line Reference Diagram Up to eight (8) output NACs total; hardwire control can be selected to map NAC inputs to different combinations of NAC outputs depending on system requirements NAC 1 input (see Note 1) • L Conventional NACs 6 1111111 With hardwire control, NAC outputs are all Output conventional orb Fire Alarm Control Panel NACs SmartSync operation 4009 IDNet NAC t Extender _ � with Conventional NACs SmartSync operation i Class A operation, either mode, requires NAC 2 input 4009 -9808 Dual Class A Adapter (optional, see Note 1) To additional 4009 IDNet NAC Extenders (up to four (4), 4009 IDNet NAC Extenders per NAC); see Note 2 Notes: 1. For separate audible and visible output NAC control, or SmartSync NAC output operation, two (2) input NACs are required. NAC 1 is "on until - reset and NAC 2 is "on-until-silenced." 2. To synchronize strobe flash outputs for up to four (4) 4009 IDNet NAC Extenders, use the synchronized strobe output from a Synchronized Flash Module (4905 -9914 for Class B operation, 4905 -9922 for Class A operation) or, if available, from a NAC selected to provide synchronized strobe flash output. NOTE: DO NOT USE a NAC selected for SmartSync operation for this function. Refer to Installation Instructions 574 - 181 for additional information and application guidance 1 4 S4009-0002-6 8/2009 4009 IDNet NAC Extender S • ecifications 120 VAC Input (4009 -9201) 3A @ 102 -132 VAC, 60 Hz Input 240 VAC Input (4009 -9301) 1.5A @ 204 -264 VAC, 50/60 Hz Ratings Hardwire Control from External Conventional reverse polarity operation NACs, Input Requirements 5 mA maximum; 16 to 33 VDC Total Rating 8 A, Special Application appliances 6 A, Regulated 24 DC appliance power Standard NACs 2 A each, Special Application or Regulated 24 DC appliance power Optional NACs 1.5 A each, Special Application appliances (requires 4009 -9807) 1 A each, Regulated 24 DC appliance power Special Application Simplex 4901, 4903, 4904, and 4906 Series non - addressable horns, strobes, Output Ratings Appliances and combination horn /strobes and speaker /strobes (contact your Simplex product representative for compatible appliances) Regulated 24 DC Power for other UL listed appliances; use associated external synchronization Appliances modules where required Strobe Operation Up to 33 strobes per NAC can be synchronized; output NACs configured for Simplex synchronized strobe operation are synchronized to each other Auxiliary Output 500 mA @ 24 VDC nominal Optional Modules Ratings Input Power 70 mA @ 24 VDC, system supplied IDNet Input, One Address Maximum distance from IDNet source is 2500 ft (762 m) IDNet Repeater Repeated IDNet output for up to 100 devices (total IDNet devices not to exceed Module 250 per channel) (4009 -9809) IDNet Output Specifications Maximum distance to farthest device is 2500 ft (762 m) Total distance including "T- taps" is 10,000 ft (3048 m) Class A (Style 6) loop maximum distance is 2500 ft (762 m), no "T" taps Fiber Optic Receiver Modules Input Current 4009 -9810, Class B (Style 4), 65 mA @ 24 VDC, system supplied 4009 -9811, Class A (Style 7), 80 mA @ 24 VDC, system supplied IDNet Output Specifications Same as those for Repeater Module (see above) Fiber Optic Transmission Distance 3000 ft (914 m) maximum General (LED status indicators are listed on page 7, dimensions and mounting details are on page 6) Operating Temperature 32° to 120° F (0° to 49° C) Operating Humidity Range 10% to 90% RH from 32° F to 104° F (0° C to 40° C) Wiring Connections* Terminal blocks for 18 AWG (stranded) to 12 AWG (solid) Fiber Optic Transmitter Specifications Input Voltage 18.9 -32 VDC from compatible listed fire alarm supply 4090 -9105, Class B (Style 4), 30 mA @ 24 VDC Input Current 4090 -9107, Class A (Style 7), 35 mA @ 24 VDC Multimode, graded index, 50/125pm, 62.5/125 pm, 100/40 pm, or 200 pm Fiber Optic Connections and cable Type ST connectors requirements 4090 -9105, Class B (Style 4) operation, two fiber cables required 4090 -9107, Class A (Style 6) operation, four fiber cables required Module Size (with mounting bracket) 6- 13/16" W x 3 -3/4" H x 1 -1/8" D (173 mm x 95 mm x 29 mm) Green LED flashing = transmit On -board Status Indicators Red LED flashing = receive Separate red LED on 4090 -9107 = Class A (Style 7) receive Communications Simplex IDNet Fiber Optic Transmission Distance 3000 ft (914 m) maximum Wiring Connections' Terminal blocks for 18 AWG (stranded) to 12 AWG (solid) Operating Humidity 10% to 90% RH from 32° to 104° F (0° to 40° C) Operating Temperature 32° F to 120° F (0° to 49° C) ' Metric wire equivalents: 18 AWG = 0.82 mm 12 AWG = 3.31 mm 5 S4009 -0002 -6 8/2009 4009 IDNet NAC Extender Mounting and Module Placement Information h Cabinet depth 16 -1/4" (413 mm) �{ 4 -1/4" (108 mm) I WWW 10- 29/32" (277 mm) 1 Door, 5/8" — O 0 • • (16 mm) thick �„ [ ° 177771 c--_-:! E' ®® • • I . I I _I ° 8 o . it lid r iil t ri.: i Optional Class A 4009 -9807 Additional Four 13 -1/2" adapter modules point module (shown with `^' ill (343 mm) ® ` Class A adapters) L ® Exposed cabinet ffi l I I dimension for —I.' • ffi ( System Module J • OI flfl semi -flush mount �j 1" (25.4 mm), Knockouts for screw IDNet repeater pl 1 -3/8" (35 mm) with or nail mounting holes Fiber optic receiver semi - flush trim O • OIU —O • i — • • I c• - I � 1 12" (305 .4 I � G 1.5 " -- ----- Battery location, no conduit entry or wiring in I this area (12.7 Ah battery outline shown) I CO 1 O OI fil Semi -flush trim option Non -power limited wiring area (AC input) 1- 3/16" wide (30 mm), -----1 3/8" (9.5 mm) thick — Wall surface reference for semi - flush mount NOTE: Recommended conduit entrance varies with module selection. Refer to general installation instructions 574 -181, specific module installation instructions, and to field wiring diagrams 842 -068 before locating conduit entrance. 4009 IDNet NAC Extender Cabinet with Door Detail . Optional red applique (4009 -9805) 4009 IDNet" NAC EXTENDER Sir 6 S4009 -0002 -6 8/2009 4090 - 9105/9107 IDNet Fiber Optic Transmitter Mounting Information Surface mount box: — Simplex model 2975 -9217 (ordered separately) • • • • I Flush mount masonry box: o 0 0 0 0 0 I use 6 -gang box, RACO # 960, 2 -1/2" deep 0 0 0 0 0 0 (64 mm), or RACO # 965, 3 -1/2" (89 mm) g • • • • • •' I deep, or equal (supplied by others) Flush mount ganged boxes: _ - . • • 0 use 6 -gang box, 1 -1/2" (38 mm) u • I I I minimum depth; six, RACO # 400 �� °' I/ , , M= or equal, (supplied by others) [_7 I 0 0 roll 0 1 .-.3 0 0 0 0 0 0 / IDNet fiber optic transmitter: 4090 -9107, Shown, Class A (Style 7) output 4090 -9105, Not shown, Class B (Style 4) output INSTALLATION NOTE: Fiber optic cable bend radius should be 2" (51 mm) minimum, or per Manufacturer's specification. 0 0 0 0 0 0� Six -gang blank cover plate Mulberry Metal Products 97156 or equal (by others) Service Diagnostic Features Power -up Self- Diagnostics. Upon power -up, the LED Status Indicators are provided for the following: 4009 IDNet NAC Extender tests each module and • Each NAC (standard and optional) has a dedicated performs earth fault diagnostics. Trouble conditions are yellow LED that: communicated to the host control panel and are also - During supervision provides a slow flash to indicate displayed on diagnostic status LEDs in the 4009 IDNet a short circuit condition and a fast flash to indicate NAC Extender. When connected via IDNet an open circuit communications, detailed status information is available at the host. When controlled with conventional NAC - During an alarm, the LED follows the NAC output inputs, common troubles are signaled by providing a (on steady or flashing with coded output) polarized open circuit that disconnects the NAC wiring • Four, general status yellow LEDs provide nine from its end -of -line resistor but still allows a reversed separate indications listed in priority of urgency. As a polarity alarm to be received. trouble is eliminated, any remaining trouble(s) will Door Mounted Reference Label. The 4009 IDNet then be indicated until the 4009 IDNet NAC Extender NAC Extender has a detailed programming and is returned to normal operation. diagnostic label inside the front door that provides a quick • AC power status is indicated by a green LED that is • reference for both installation and checkout. on when AC is normal. During low AC (brownout) conditions or with no AC, the LED is off. Additional power and battery status is indicated by the general status LEDs. 7 S4009 -0002 -6 8/2009 4009 IDNet NAC Extender Current Chart Panel Module Selection (shaded model numbers are optional modules) Model Description Supervisory Actual Alarm Current Actual Alarm Current Supervisory 4009 -9201 120 VAC input Basic Panel 85 mA 85 mA 185 mA 185 mA 4009 -9301 240 VAC input + NAC loads + NAC loads 4009 - 9807 Additional Four Point NAC 40 mA + (add below) (add below) 4009 Dual Class A Adapter (current — included in basic panel value) 4009 -9809* IDNet Repeater 70 mA 70 mA 4009- 9810 * Fiber Optic Receiver, Class B 65 mA + 65 mA + 4009- 9811 ' Fiber Optic Receiver, Class A 80 mA 80 mA IDNet Devices, 0.7 mA each, maximum of 100 Total devices + Total devices (A1) + (see note 5) x 0.7 mA each x 0.7 mA each Auxiliary Power Output, calculate per total 500 mA 500 mA (A2) + device requirements (see note 5) maximum maximum Total Supervisory Current = (A) + Total 4009 IDNet NAC Extender Panel Alarm Current = (B1) * Only one of these three modules can be chosen for a single 4009 IDNet NAC Extender. t NOTE: IDNet Fiber Optic Transmitter current is supplied from the host fire alarm control panel. NAC Loads NAC Type NAC Circuit # NAC Alarm Current Circuit 1 + Circuit 2 + Standard Panel NACS, 2 A maximum per NAC (see note 5) Circuit 3 + Circuit 4 + Circuit 5 + Circuit 6 + Optional Four Point NAC Module, 1.5 A maximum per NAC (see note 5) Circuit 7 + Circuit 8 + Total NAC Loads Alarm Current = (C) Total 4009 IDNet NAC Extender Panel Alarm Current (enter B1 from above) = (B2) + Procedure: Total Alarm Current = (D) 1. Calculate total panel supervisory current (A). 2. Calculate total panel alarm current (B1) [convert mA to A, example: 350 mA = 0.35 Al Copy (B1) into block (B2). 3. Calculate total NAC loads alarm current from notification appliance ratings (C). 4. Add (C) + (B2) to determine total alarm current (D). 5. Total of IDNet Device Current (A1) + Auxiliary Power Output Current (A2) + NAC Loads Alarm Current (C) is 8 A maximum. 6. Refer to Simplex battery selection document 900 -012 for recommended battery size for specific standby requirements (i.e. 24 hours supervisory, 5 minutes of alarm). Internal cabinet space is provided for batteries up to 12.7 Ah. Tyco is a registered trademark of Tyco Internatonal Services GmbH and is used under license. Simplex, the Simplex logo, LifeAlarm, IDNet, WALKTEST SmartSync, and TrueAlert are trademarks of Tyco International Ltd and its affiliates and are used under license. £; Simplex Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA S4009-0002-6 8/2009 ® www. tycosafetyproducts- usa -wm. com © 2009 To Safety Products Westminster. All rights reserved All specifications and other information shown were current as of document recision date and are subject to change without notice. 6 Simplex TrueAlert Multi - Candela Notification Appliances . UL, ULC, CSFM Listed; FM Approved; SmartSyncTM Operation AudibleNisible Notification MEA (NYC) Acceptance* with Horn and Synchronized Flash, Non - Addressable Features — ....M. a Audible /visible (AN) notification appliances with efficient electronic horn and high output xenon strobe, available for wall or ceiling mount: • Operation is compatible with ADA requirements (refer _ ^" to important installation information on page 3) e • Rugged, high impact, flame retardant thermoplastic housings are available in red or white with clear lens FIRE FIRE Operates over a two -wire SmartSync circuit to „. . provide: • Horns that are controlled separately from strobes on the FIRE same two -wire circuit . - . � • "On- until- silenced" and "on- until -reset" operation on V Iti the same two -wire pair • SmartSync horn activation of Temporal pattern, March FIRE , „ Time pattern (at 60 BPM), or on continuously = i • Strobe appliances on the same circuit operating at a _ I I,', synchronized 1 Hz flash rate , �m _ • Operation requires connection to a compatible SmartSync operation NAC or to SmartSync Control Wall and Ceiling Mount ANs Module (SCM) 4905 -9938 Descri • ti on Wall mount ANs features: • Wiring terminals are accessible from the front of the Multi - Candela TrueAlert ANs with horn and housing providing easy access for installation, synchronized strobe provide convenient installation inspection, and testing to standard electrical boxes. The enclosure designs are both impact and vandal resistant and provide a convenient • Covers are available separately to convert housing color strobe intensity selection. Since each model can be • Optional UL/ULC listed sound damper for locations selected for strobe intensity output, on -site model requiring attenuation of 5 to 6 dBA (stairwells, small inventory is minimized and changes encountered during rooms, highly reverberant areas, etc.) construction can be easily accommodated. Optional adapters and wire guards: Wall mount A/V housings arc a one -piece assembly • Wall mount AN adapters are available to cover surface (including lens) that mounts to a single or double gang, or mounted electrical boxes and to adapt to Simplex 4" square standard electrical box. The cover can be 2975 -9145 boxes quickly removed (a tool is required) and covers are • UL listed red wire guards are available for wall or available separately for color conversion. ceiling mount ANs* Ceiling mount ANs install using standard 4" electrical Visible notification appliance (strobe): boxes. Color choice is determined by model number. • 24 VDC xenon strobe; intensity is selectable as 15, 30, Strobe Intensity Selection 75, or 110 candela with visible selection jumper secured behind strobe housing During installation, a selection plug at the back of the • Regulated circuit design ensures consistent flash output housing determines the desired strobe intensity. An and provides controlled inrush current attached flag with black letters on a highly visible yellow background allows the selected intensity to be seen at the • Listed to UL 1971 and ULC S526 side of the strobe lens. Audible notification appliance (horn): • Refer to page 2 for guard listing. This product has been approved by the California State • Low current, 24 VDC electronic horn with harmonically Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safely Code. See CSFM Listing 7125-0026317 for allowable values andlor conditions concerning rich sound output suitable for either steady or coded material presented in this document. It is subject to re-examination, revision, and possible operation (Temporal or 60 BPM March Time pattern) cancellation. Accepted for use —City of New York Department of Buicings — MEA35 -93E Refer to page 2 for listing status of Are guards. Additional listings may be ap ticade, • Listed to UL 464 and ULC 5525 T contact your local Simplex product supplier for the latest status. Listings and approvals r r Ert ED under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster 1 •• Simplex multi—candela SmartSync two -wire horNstrobe appliance operation is protected under one or more of the fdlowing U.S. Patent Numbers: 5,559,492; 5,622,427, n r T O 7 2009 5 ,865,527, 5,865,527, 5,886,620; 6,281,789; 6,954,137; 7,005,971, and 7,006,003. l I 1 L 94906-0002 -5 9/2009 CITY OFTIG BUILDING DIVISION Strobe Application Selection Smart Sync Two -Wire Control Proper selection of visible notification is dependent on Smart Sync operation mode allows a two -wire circuit to • occupancy, location, local codes, and proper applications provide the ability to activate both the horn and strobe on of: the National Fire Alarm Code (NFPA 72), ANSI the same NAC and then allow the horn to be silenced A117.1; the appropriate model building code: BOCA, while the strobe remains flashing. The horn operates as ICBO, or SBCCI; and the application guidelines of the "on- until - silenced" while the strobe operation is Americans with Disabilities Act (ADA). "on- until - reset." Synchronized Strobes SmartSync Control Sources Multiple Strobes. When multiple strobes and their • 4006, 4008, 4100U, and 4010 Fire Alarm Control reflections can be seen from one location, synchronized Panels (refer to individual product data sheets for more flashes reduce the probability of photo- sensitive reactions information) as well as the annoyance and possible distraction of • 40091DNet NAC Extender (refer to data sheet random flashing. The multi - candela strobes of these A/Vs S4009 -0002) are synchronized by the controlling SmartSync operation • SmartSync Control Module (SCM) 4905 -9938 (refer to NAC. data sheet S4905 -0003) Additional SmartSync compatible notification appliances include separate horns and combination horn/strobe notification appliances. Product Selection Multi - Candela ANs Model Mounting Housing Color "FIRE" Lettering Description 4906 -9127 Red White Wall Horn with Multi- Candela Strobe; strobe intensity selectable as: 4906 -9129 White Red y 15, 30, 75, or 110 candela; operates with SmartSync two -wire 4906 -9128 Ceiling Red White control 4906 -9130 White Red Wall Mount AN Accessories Model Description Dimensions 4905 -9937 Red Surface Mount Adapter Skirt; use to cover 1 -1/2" (38 mm) deep 5 -3/8" H x 5 1/4" W x 1 -5 /8" D surface mounted boxes (136 mm x 133 mm x 41 mm) 4905 -9940 White depth with strobe = 4 -3/8" (111 mm) 4905 -9931 Red Adapter Plate for mounting to Simplex 2975 -9145 box (typically for 8- 5/16" x 5 -3/4" x 0.060" Thick retrofit, may be mounted vertical or horizontal) (211 mm x 146 mm x 1.5 mm) 2975 -9145 Red Mounting Box, requires Adapter Plate 4905 -9931 7 -7/8" x 5-1/8" x 2 -3/4" D (200 mm x 130 mm x 70 mm) Optional Sound Damper; package of 20; field installed adhesive backed 4905 -9838 horn output attenuator; reduces output 5 to 6 dBA 1 -3/4" Diameter (44.5 mm) NOTE: After Sound Damper installation, measure sound level to ensure with 0.31" (8 mm) sound opening compliance with applicable code requirements SmartSync Control Module Model Description Dimensions 4905 -9938 SmartSync Control Module with Class B or Class A output; mounts in 4" 4" x 4-1/8" x 1 -1/4" D (102 mm) square box; refer to data sheet 54905 -0003 for details (102 mm x 105 mm x 32 mm) Replacement Covers for Wall Mount A/Vs Model Description Dimensions 4905 -9994 Red cover with white "FIRE" lettering 5 -1/8" H x 5" W x 1 -1/2" D 4905 -9995 White cover with red "FIRE" lettering (130 mm x 127 mm x 38 mm) • Wire Guards and Ceiling Mount A/V Adapter Model Description Niumpimmtempusempinvor Dimensions 4905 -9961` Wall mount red wire guard with mounting plate, compatible with semi -flush 6- 1/16" H x 6- 1/16" Wx 3 -1/8" D or surface mounted boxes (154 mm x 154 mm x 79 mm) 4905 -9927` Red Wre Guard for mounting to flush mounted electrical box 8 -1/2" x 6-1/8" x 3" (216 mm x 156 mm x 76 mm) 4905.9928• Ceiling Red Adapter Plate, required to mount guard to surface 9" x 7" Mount mounted electrical box (229 mm x 178 mm) 4905 -9915 White Surface Mount Adapter Box Extension, use to cover 4 -3/4" x 6 -7/8" x 1 -1/2" deep, 4905 -9916 Red 1 -1/2" deep surface mounted boxes (121 mm x 175 mm x 38 mm) UL listed by Space Age Electronics Inc. 2 S4906- 0002 -5 9/2009 A/V S•ecifications Wall Mount or Ceiling Mount, Common Specifications Rated Voltage Range Regulated 24 DC; see Note 1 below Flash Rate and Synchronized NAC Loading 1 Hz; with up to 35 synchronized strobes maximum per NAC Environmental; Temperature and Humidity 32° to 122° F (0° to 50° C); 10% to 93%, non - condensing at 100° F (38° C) Connections Terminal blocks for 18 AWG to 12 AWG (0.82 mm to 3.31 mm ; two wires per terminal for in /out wiring Horn Output Characteristics 2400 to 3700 Hz sweep, modulated at 120 Hz rate Model Type Wall Mount Ceiling Mount Horn Output Sound Type (see Note 2) Steady Coded Steady Coded Ratings (see Note 2 for Reverberant Chamber Test, 86 dBA 82 dBA 87 dBA 83 dBA polar dispersion per UL 464 @ 10 ft ( -3 m) reference) Anechoic Chamber Test, per ULC S525 @ 3 m ( -10 ft) 88 dBA 94 dBA 90 dBA 98 dBA Housing Dimensions (with lens) 5 -1/8" H x 5" W x 2 -3/4" D (130 mm x 127 mm x 70 mm) Maximum RMS Current Rating per 15 cd 30 cd 75 cd 110 cd Wall Mount Strobe Setting (see Note 3 below) 75 mA 116 mA 221 mA 285 mA Reference RMS Currents 18 VDC 67 mA 103 mA 196 mA 253 mA at other voltages 24 VDC 50 mA 77 mA 147 mA 190 mA Housing Dimensions (with lens) 4 -3/4 L" x 6 -7/8" W x 2 -5/8" D (121 mm x 175 mm x 67 mm) Ceiling Maximum RMS Current Rating per 15 cd 30 cd 75 cd 110 cd Mount Strobe Setting (see Note 3 below) 86 mA 132 mA 250 mA 320 mA Reference RMS Currents 18 VDC 76 mA 117 mA 222 mA 284 mA at other voltages 24 VDC 57 mA 88 mA 167 mA 213 mA NOTES: 1. "Regulated 24 DC" refers to the voltage range of 16 to 33 VDC per UL Standard 1971, Signaling Devices for the Hearing Impaired, changes effective May 1, 2004. This voltage range is the absolute operating range. Operation outside of this range may cause permanent damage to the appliance. Please note that 16 VDC is the lowest operating voltage that is allowed at the last appliance on the NAC under worst case conditions. 2. Coded values are typical of the output measured with a Temporal coded or a March Time coded pulse and with a sound level meter reading on a "fast" setting. Polar dispersion per ULC S525 testing = -3 dBA at +/ -40° off -axis; -6 dBA at +/- 50° off -axis. 3. Currents are with horn on steady. The maximum RMS current listed is the device nameplate rating. Strobe designs are constant wattage and the maximum RMS current rating occurs at the lowest allowable operating voltage. (RMS is root mean square and refers to the effective value of a varying current waveform.) Installation Reference, Surface or Semi -Flush Mounting A II 1 1 iii E g 0 r i Mounting is compatible with single gang, double gang, and / ° 4" (102 mm) square boxes, Cl / 1 ° r 1 I IMPORTANT! WALL MOUNT 1 -112" (38 mm) deep, by others _ INSTALLATION HEIGHT REFERENCE Optional 4905 -9838 ��1 , ��1 — '— — Sound Damper, field attached I ■ Bottom of lens to attenuate sound 5 to 6 dBA I h, is either even I with, or slightly Electrical 0 I r ifO' O above bottom box outline Wring access hole i t IN i 1 of compatible k �'1 � ! • .. 1 boxes Wring terminals for e AMI SmartSync operation i INEMINNIMIliffill I � Mounting Holes S i square gang NFPA 72 requires 80" (2.03 m) ® Single gang (2) that the entire lens minimum " �g r Double gang (3) be not less than �11' 6 0" and not greater : than 96" above the Transparent housing finished floor and lens assembly Intensity selection plug, accessible only IF , ® I l t from rear of housing, I F [I n E factory setting is 15 cd dM Removable cover Strobe intensity (tool required) viewing slot 3 S4906 -0002 -5 9/2009 Ceiling Mount A/V and Guard Installation Reference Ceiling reference, 4" (102 mm) square box, Optional 4905 -9928 Adapter Plate, surface mounted box 1 -1/2" (38 mm) minimum depth required for surface mounted electrical box Four mounting clamps included, two each side � o 0 � iTimmil IIiI�II� ,, Ceilin reference, L� flush mounted box ' '_11______ jjii Optional 4905 -9915/ -9916 Adapter, recommended for surface mounted box Wiring terminals are Optional 4905 9927 located behind the housing Red Wire Guard 0-- F - 1 L End View Strobe intensity viewing slot ^Intensity selection plug, accessible only from rear of lens housing: factory setting is 15 cd Wall Mount Installation Reference; Adapter Plate, Guard, and Adapter Skirt Surface Mounting Reference 2975 -9145 Box with Optional Adapter Skirt and Optional Wire Guard -- j Surface mount conduit and 0 box shown for reference I '= I= I -I- -� �.` 4" (10 Profile, 1 -1/2" mm) square �I� l ( ' Wire Guard box " ' I II (38 mm) deep l � il � Iz.I-I Ilijul O O I Optional — 4905 -9961 1111 . I Air `-IL t 2 0 J II� — _ -� I' 4905 -9931 Adapter Plate `` = 1 Optional Surface Mount Adapter Skirt, O 4905 -9961 Optional Wire Guard 1 -1/2" deep: 4905 -9937, Red; (shown here for reference only, 4905 -9940, White (conduit knockouts • 4905 -9931 Adapter Plate can be used on other mounting options) are provided on all four sides) Tyco is a registered trademark of Tyco International Services GmbH and is used under license. Simplex, the Simplex logo, IDNet, TrueAlert and SmartSync are trademarks of Tyco International Ltd and its affiliates and are used under license. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection .Association (NFPA). E Simplex Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA S4906-0002-5 9!2009 ® www. tycosafetyproducts- usa -wm. com 0 2009 Tyco Safety Products Westminster. Al! rights reserved A11 spenfications and other information shown were current as ofdocuonent revision date and are subject to change without notice.