Specifications 3.0-e bt/. 4 4/ 0_20-68= o� 2 5 3 B Bulletin 110 Rev.S 1111111111 l ® 0 Model G c Reia R Automatic Sprinklers cTi Spray Upright 1 Spray Pendent o ... - ...::, ! .. .. , .... . - And Convent' ETVED JUL 2 2 2uus Product Description CITY OF TIGARD BUILDING njvlcjON The Reliable Model G Automatic Sprinkler utilizes the center strut solder in compression principle of - ; W ; __ construction. The fusible alloy is captured in the r: cylinder of the solder capsule by a stainless steel ball. �: "' ;:;a When the fusible alloy melts, the ball moves into the 1>1 t, cylinder allowing the cylinder to fall away from the ,. yj; }Y sprinkler. When this happens, the lever is released to 1:( f __. spring free from the sprinkler so that all of the operating ' ` •. fiasco parts clear from the waterway allowing the deflector t %. -= �: distribute the discharging water. i _ l' •' �, _:. Except for the parts in the cylinder as mentioned above, the sprinkler components are made from Upright Pendent copper based alloys for maximum corrosion protection. Lead plated, wax coated or wax over lead plated sprinklers are available for specially severe =` environments. Chrome plated sprinklers are available ` i for decorative purposes. �.,, �� All sprinklers are individually hydrostatically tested. f..,. , r li - All sprinklers are identified as to their fusing point by , _ i; t :;"!1 markings that appear on several of the operating parts I ` -� r and by an identifying color that appears on the frame. : i •.., • - Sprinider Types Standard Upright - This deflector configuration is Small Orifice Upright Conventional normally used with exposed piping installations. Water is distributed laterally and downward in a wide pattern approximating a hemisphere which is completely and uniformly filled with water in the form of small drops or spray. Standard Pendent This deflector configuration is Application and Installation I normally used where the space above the piping is Standard sprinklers are used in fixed fire protection limited or where a concealed piping installation is systems: Wet, Dry, Deluge or Preaction. Care must be employed. The discharge characteristics of the exercised that the orifice sizes, temperature ratings, standard pendent are virtually identical to the deflector styles and sprinkler spacings are in standard upright as described above. accordance with the latest published standards of the National Fire Protection Association or the approving Large and Small Orifice —By varying the orifice size, authority having jurisdiction. a large or small orifice sprinkler is created that will The sprinklers must be installed with the Reliable distribute as much as 40% more water or 65% less Model D Sprinkler Wrench. Any other type of wrench water than the normal' /2" (15mm) orifice sprinkler. may damage the sprinkler. The approvals or listings of Reliable Automatic Conventional —This deflector configuration is used Sprinklers by major approving organizations are primarily in those countries where the LPC installation shown in the tabulated list provided on the back of this rules have precedence. The sprinkler is designed to bulletin. distribute a portion of its water discharge upward against the ceiling with the balance downward. It may be installed in either the upright or the pendent position. Sprinklers with conventional deflectors are - available with orifice sizes corresponding to light, Patent No. 4,440,234 ordinary and extra -high hazard installations. The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552 Technical Data "K" Factor Sprinkler Identification Sprinkler Number (SIN) Sprinkler Type US Metric Height Approvals SSU SSP Standard - Upnght (SSU) and Pendent (SSP) Deflectors Marked to Indicate Position y" (15 mm) Standard Orifice with y" NPT (R,) Thread 5.62 81.0 2 %" (73 mm) 1, 2, 3, 4, 5, 6, 7 191025 R 1015 '/e" (11 mm) Small Orifice with NPT (R/2) Thread 4.24 61.0 2 Ye" (73 mm) 1, 3, 7 R1023 R1013 %' (10 rnm) Small Orifice with y" NPT (Ry) Thread 2.82 40.6 2 ,'e" (73 mm) 1, 2, 3, 7 R1021 R1011 g � /16" (8 mm) Small Orifice with y" NPT (R}r Thread 1.98 28 5 2 %" (73 mm) 1, 3, 7 R1022 R1012 ' %' (20 rims) Large Orifice with Yz" NPT (Ry) Thread 7.96 114.7 2' /s" (73 mm) 1,2,3,7 R1026 R1016 ' %" (20 mm) Large Orifice with %" NPT (RX)Thread 8.20 118.2 2'Xs " (75 mm) 1, 2, 3, 7 R1027 R1017 20 mm XHH with 20 mm Thread 8.20 118.2 75.4 mm 4, 5, 6 R1027 R1017 10 mm XLH with 10 mm Thread 4.10 59.1 73 mm 4, 5, 6 R1024 R1014 Conventional — Installed in Upright or Pendent Position 10mm XLH with 10mm Thread 4.10 59.1 73 mm 5 R1074 15mm Standard Orifice with (R)) Thread 5.62 81 0 73 mm 4, 5, 6 R1075 20mm XHH with (Re,) Thread 8.20 118.2 75.4 mm 4, 5 R1077 Temperature Ratings Maintenance Maximum Model G Sprinklers should be inspected quarterly and the Sprinkler Ambient sprinkler system maintained in accordance with NFPA 25. Do Rating Temperature Frame (1) not clean sprinklers with soap and water, ammonia or any other Classification °F °C °F °C Color cleaning fluids. Remove any sprinkler that has been painted Ordinary 135 57 100 38 Black (other than factory applied) or damaged in any way. A stock of Ordinary 165 74 100 38 Uncolored spare sprinklers should be maintained to allow quick replace - Intermediate 212 100 150 66 White ment of damaged or operated sprinklers. Prior to installation, High 286 141 225 107 Blue sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to Ill Frame color does not apply to painted or plated sprinklers sprinklers that would cause improper operation or -Use sprinkler rating as identified on operating parts. non-operation. Use only the Model D Sprinkler Wrench for sprinkler removal and installation. Any other type of wrench may damage the sprinkler. Finishes Standard Finishes Approval Organizations Bronze —All Temperature Ratings 1. Underwriters Laboratories, Inc. Chrorr —All Temperature Ratings 2. Factory Mutual Research Corporation White —All Temperature Ratings 3. Underwriters' Laboratories of Canada Only Frame and Deflector are Painted 4. Loss Prevention Council Special Application Finishes 5. Pleniere Assemblee Bright Brass Plated —Only frame, deflector and cap are plated 135 °F (57 °C), 165 °F 6. N.Y.C. S S BS&A No. 5 7-75 -SA or gg Bri g 7. N. BS &A No. 587 - (74 °C), 212°F (100 °C) Temp. Rating. N.Y.C. MEA 258 -93 -E Black Plated —Only frame, deflector and cap are plated. All Temp. Ratings. Polyester Coated (2) —Only frame and deflector are coated Lead Plated —165 °F (74 °C), 212 °F (100 °C) and 286 °F (141 °C) Temp. Ratings Ordering Information Wax- Coated 131 —165 °F (74 °C) Clear Wax, 212 °F (100 °C) Brown Wax. Specify Wax - Coated Over 1. Model G Lead Plated —165°F —165 °F (74 °C) Clear Wax, 212°F (100 °C) Brown Wax. 2. Deflector • Upright ( Other colors and finishes are available. Consult factory for details • Pendent (2) UL listed and NYC MEA Approved only. • Conventional (3) 212 ° F (100 °C) brown wax may be used on 286 °F (141 °C) 3. Nominal Orifice sprinklers when maximum ambient temperatures do not exceed 150 °F 4. Inlet Thread (66°C). UL Listed, FM Approved, NYC MEA 258 -93 -E. 5. Temperature Rating 6. Finish The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by .- - - ' . • The Reliable Automatic Sprinkler Co., Inc. ( Sales Offices r w eriab ° (800) 800) 431 848 - 1588 Sales Fax POD" (914) 668 - 3470 Corporate Offices Revision lines indicate updated or new data. wwwrehabiespnnkier cam Internet Address EG Pnntetl is u SA 11/04 P/N 9999970035 'R Bulletin 111M Reiiabld Model G co Recessed Automatic Sprinkler RECEIVED JUL 2 2 2008 CITY OFTIGARD BUILDING DIVISION The Most Compact Attractive ■ „ _ and Easily Installed Sprinkler • "NA Ever Designed! � �� `� Features 1. 1 (38mm) Total adjustment provided �r' 1 • by adjustable inlet versions. 2. 1 /2" (13mm) Total adjustment provided by economical standard inlet version. 3. Adjustable inlet version available with �•.• . - K. ,�� s• :,.•- either 1" NPT male or female threads eliminating costly reducing coupling. 4. Small diameter escutcheon. 5. Avail able in brass, chrome orwhitefin ish. le orificesizesfordesi nflexibilit The Model G Recessed Sprinkler's threaded 6. Multiple g y• two-piece construction makes initial field installation a 7. Listed by Underwriters Laboratories Inc. very easy task. It allows ceilings panels to be removed without shutting down the fire protection thus facilitating & Underwriters' Laboratories of Canada. maintenance of above ceiling services. The adjustable Approved by Factory Mutual Research one inch NPT in let versions have one and one half inches Corp. & Loss Prevention Council, NYC of adjustment which eliminates both the normally re- BS &A NO., 587- 75 -SA. quired reducing coupling and the need to accurately cut drop nipples. This sprin kler can be ad justed af ter the ceil- ing is in place and even while the system is pressurized • eliminating the final corrections to pipe hangers or ceil- Product Description ings that might otherwise be required. p The Reliable Model G Automatic Sprinkler is the heart Today's modern build ings demand theta sprin kler not of the Recessed Sprinkler. This sprinkler utilizes the cen- only provide the best fire protection but also achieve an ter strut solder in compression principle of construction. attractive appearance. Reliable's Model G Recessed The fusible alloy, captured in the cyl in der of a small sol der Sprinkler meets both criteria. It combines the fire fighting capsule by stainless steel ball, acts as the trigger of the capa bil ityof a proven sprin klerwith the small est practi ca- sprin kler. When the fusible alloy melts, the sprin kler op er- ble recessing unit. Its small profile does not disrupt the ating parts sprinkler free from the sprinkler clearing the over head aesthetics, and yet one verti cal glance up ward waterway and allowing the deflector to distribute the dis - gives a visual assurance of the finest in fire protection, an charging water. automatic sprinkler system. The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York10552 A 1 installation The Reliable Model G Recessed Sprinkler has been serted into the special Reliable Model RC -1 Installation designed with ease of installation in mind. A choice of Wrench. This wrench must be used. The wrenching - three inlets with up to one inch adjustment coupled with pads of the sprinkler easily slip into the rectangular the 1" (13mm) escutcheon adjustment enables most cut -outs of thewrench asthe out side di am eter lo catesthe system to be installed using pre -cut drop nipples. The threaded cup. A' /z" (13mm) drive ratchet can then be adjustment can be accomplished after the ceiling instal- used for installation and tightening. Iation and while the system is ores surized thereby provid- Figure 5 shows the removal of the wrench. Care ingsprinkler protection before con struction iscompleted. should be taken during this procedure to avoid hitting the The Non - Adjustable in letver sion (Fig ure 1) Con sists of de flec tor with thewrench. The wrench should be lowered the Reliable Model G Sprinkler with an attached cup re- until it clears the sprinkler. The installation completed by cessed in the ceiling. A ceiling hole of 21/2" (67mm) di am- threading the escutcheon on until it contacts the ceiling. eter is recommended. To avoid leaving smudge marks on the ceiling, the Reli- TheAdjustableinletversionusesthesamesprinkleras able Model FEA Flush Sprinkle Escutcheon Wrench the Non - Adjustable inlet version uses the same sprinkler should be used. See Bulletin 205 as the Non - Adjustable in lettype ex ceptthe l of ad di tional Note: adjustment is provided by a telescoping sprinkler inlet 1. Use hex wrench on Coupling Reducer to tighten Ad - section that threads in or out of a stationary Coupling Re- justable Sprinkler into fittings. Do not use RC -1 ducer (either 1 male or 1 fe male) as shown in fig ures 2 or Wrench for this purpose. 3. The Sprin kler-Cup as sem blyco mesattachedtothe in- 2 Do not install the Model G Recessed Sprinkler inceil let Coupling Reducer Comes attached to the inlet Cou- pling Reducer and is retained from separation past its ings which have positive pressure in the space above. maximum adjustment length by a snap ring. This combi- Maintenance nation is simply installed after the system drop nipple, el- The Model G Recessed Pendent Sprin klers should be bow or tee has been "roughed in" to the dimensions inspected quarterly and the sprinkler system maintained shown in figures 2 or 3. Wrenching means are provided in ac car dance with NFPA 20. Do not clean sprin klers with by hex flats on the coupling reducer as depicted in the soapandwater, ammoniaoranyothercleaningfluid. Re- figures -do not wrench on any other part of the sprinkler. move any sprinkler that has been painted (other that fac - After the ceiling tiles have been cut and in stalled in place (a 2' /a" {57mm }hole is recommended), the sprinkler can tory applied) or damaged in any way. A stock of spare be adjusted using the RC -1 Concealed Wrench. sprinklers should be maintained to allow quick replace - When using the wrench in this application, however, - tion mentsfdamagedoroperate rinklers should be maintaine maintaine h e in orrig do not over - torque beyond the adjustment stops. tion, sprinklers in n the ginal _ Figure 4 shows a W' NPT (R1/2) non-adjustable inlet cartons and packaging until used to minimize the poten- operation damage no to sprinklers that would cause improper sprinkler, with the attached sprinkler cup combination in- operation or non - operation. smxv f r ®seer '15110 VIC AN MAW CM — II f1 yam. v. r -41 flit +_1� I � _� -....I _ I r- -- e u j f I c; i I ti l l s J am . — it - -- ; !it -- 1 i f f lit rem I r i vu-M ` a S' re.,c°JCr_r at. li , , ii mMOx :a4 d.[:�'.(� aero 1.1 t. wt lattAll,n1Ln I ' , r IV ealwif.W ...1:4441 kg I .,.....7 ' s• ... r . A Ill i '''''".:.., W ADM1 �.�. • ' /z" NPT Non - Adjustable Inlet 1" NPT Male- Adjustable Inlet 1" NPT Female- Adjustable Inlet • Figure 1 Figure 2 Figure 3 2. 4 Technical Data _ "K" Factor Sprinkler Total Approval Identification Sprinkler Inlet Adjustment NominalOrifice U.S. Metric Thread Organizations Number (SIN) Non - Adjustable 1/2" (13rm) '/2" (15mm) 5 62 81 0 '/z' NPT (R1/2) 1, 2, 3, 4, 5, R1015 Non - Adjustable 1/2"(13rm) 1 (11mm) 424 61.0 /"NPT(R'h) 1,3,4 R1013 Non - Adjustable %z' (13rrn) %TOiuri) 2.82 406 1/2" NPT(R'h) 1, 3, 4 R1011 Non - Adjustable W (13mm) 17 / 32 " (20rrn) 796 114 7 /z" NPT (R1/2) 1, 3 R1016 Adjustable 1'/2" (38 -rrn) /e (15mm) 5.53 79 7 1" NPT Male or Fe male 1, 2, 3, 4 R1118 Adjustable 11/2"(3E3rurr) '/,G'(11mm) 4.24 610 1 "NPTMaleorFemale 1,3,4 R1113 Adjustable 1 /i' (3&rm) Ne' (10mm) 2.75 39.2 1" NPT Male or Fe male 1, 3, 4 R1117 Adjustable 11/2" (3aiuri) 15mm 553 79.7 R1 Male or Female 5 R1118 Sprinkler escutcheon provides Y (13mm) of the total adjustment. Adjustable inlets, when used, provide 1 (25mm) of the total adjustment. fl Identified by pintle extending above the deflector Temperature Ratings Ordering Information Maximum Ambient Specify: Sprinkler Rating Temperature 1. Temperature Rating Classification °F °C °F °C 2 Nominal Orifice Ordinary 135 57 100 38 3 Sprinkler Finish Ordinary 165 74 100 38 4 Escutcheon Finish Intermediate 212 100 150 ' 66 5. Sprin klerType: Ei ther Non - Adjustable In let (Fig. 1); 1" Male Adjustable Inlet (Fig. 2); 1" Female Adjustable Approval Organizations Inlet (Fig.3) 1. Underwriters Laboratories Inc. 2. Factory Mutual Research Corp. Finishes (1) • Light Hazard Occupancies - No limitations Standard Finishes • Ordinary Hazard Occuncies - Groups 1 & 2, Wet Sprinkler Escutcheon Systems Only Bronze Brass 3. Underwriters Laboratories of Canada Chrome Chrome 4. NYC BS & A No. 587 -75-SA WhrtePainted ° White Painted • 5. Loss Prevention Council Special Application • XLH, OHI and OHII Occupancies Only Sprinkler Escutcheon 6. NYC MEA 258-93-E Bnght Brass ° Bright Brass • Black Plated Black Plated Note: Unless otherwise indicated, Ordinary hazard op- Satin Satin provals are without limitations. '/,6" (11 mm) and /s" Polyester Coated ° Poyestercoated ( 10mm) or i fice sprin klers are lim ited to light haz ard oc cu- Other color Finishes avail able upon request Con suitFac toryfor pancies. details. ° Only frame, deflector and cap are plated ° Only frame and deflector are painted or coated. Operating parts are chrome plated. UL Listed and MEA Approvedonly. `t .;.) . J 1 l •' 1 f it ! • • • i r Figure 4 Figure 5 3.