Loading...
Specifications if . c;43&c. 7 or o $ RECEIVED VICO Fire & Building JAN 12 2009 Products CITY OFTI GARD BUILD D IVISION Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series RFII — 5.6 K- factor "Royal Flush II" Pendent Concealed Sprinklers Quick & Standard Response, Standard Coverage General Cap. The Protective Cap is temporarily removed for installation, and then it can be replaced to help protect the aft Description sprinkler while the ceiling is being in- stalled or finished. The tip of the Pro- _ The Series RFII Quick Response tective Cap can also be used to mark ^ _ (3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas- _ ._ mm bulb), 5.6 K- Factor, "Royal Flush ter board, ceiling tiles, etc. by gently •_ II" Concealed Pendent Sprinklers are pushing the ceiling product against theme '' decorative sprinklers featuring a flat Protective Cap. When the ceiling in- �� cover plate designed to conceal the stallation is complete the Protective sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate • tecturally sensitive areas such as hotel Assembly installed. lobbies, office buildings, churches, As an option, the Series RFII Standard and restaurants. Response (5 mm bulb) "Royal Flush II" Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be sembly that conceals the sprinkler op- fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175 erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM. The separable two -piece design of the intended for sensitive areas where it is Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical blies allows installation of the sprin- through the cover plate from the area - klers and pressure testing of the fire above the ceiling. Data protection system prior to installation WARNINGS of a suspended ceiling or application The Ser i es RFII Concealed Pendent Approvals for Series RFII of the finish coating to a fixed ceiling. Sprinklers described herein must be U L and C -UL Listed. FM App roved. They also permit removal of sus- p pended ceiling panels for access to installed and maintained in compli- NYC under MEA 353 -01 -E. LPCB (Ref. building service equipment without ance with this document, as well as No. 094a/09 for TY3551 & 094a/10 for having to first shut down the fire pro- ing with the applicable standards of the TY3531) Approved. having system and remove sprinklers. National Fire Protection Association, The approvals apply only to the serv- rwo piig in addition to the standards of any ice conditions indicated in the Design Also, the separable two -piece design f the the Sprinkler other authorities having jurisdiction. Criteria section and maximum pres- inch the th mm) of vertical p provides dees s for ign for 1/2 Failure to do so may impair the per sure ratings indicated in the formance of these devices. Model/Sprinkler Identification Num- to reduce the accuracy to which the P length of fixed pipe drops to the sprin The owner is responsible for maintain- tiers section. klers must be cut. i ng their fire protection system and de- Approvals for Air & Dust Seal vices in proper operating condition. Part #10908100 The Series RFII Sprinklers are The installing contractor or sprinkler U L and C -UL Li for use with the shipped with a Disposable Protective manufacturer should be contacted RFII (TY3551 & TY3504) Standard Re- with any questions. sponse Concealed Sprinkler. IMPORTANT Temperature Ratings Always refer to Technical Data Model /Sprinkler 155F/68C Sprinkler - 135F/57C Plate Sheet TFP700 for the `INSTALLER 200F/93C Sprinkler 165F/74C Plate WARNING" that provides cautions Identification Discharge Coefficient with respect to handling and instal- K = 5.6 GPM /psi / (80,6 LPM/bar /2 ) lation of sprinkler systems and corn- Numbers Adjustment ponents. Improper handling and in- 1/2 inch (12,7 mm) stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm Finishes a sprinkler system or its compo- bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass nents and cause the sprinkler to fail UL, C -UL, FM, LPCB and NYC. to operate in a fire situation or cause TY3504 (5 mm bulb) & TY3505 (3 mm Plated, or White Painted (Custom paint it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by matches and colors other than white are available on request.) Page 1 of 4 JULY, 2004 TFP181 Page 2 of 4 TFP181 a Physical Characteristics 1/2' NPT SEALING P i' Frame Bronze / ASSEMBLY Support Cup . Chrome Plated Steel Guide Pins Stainless Steel rib ` , , Deflector Bronze FRAME I / its__ CAP Compression Screw Brass 1"1 ins_ I Bulb Glass � Cap Bronze or Copper SUPPORT Sealing Assembly CUP WITH BULB Beryllium Nickel w/Teflon' ROLL FORMED 1 il" Cover Plate Brass THREADS _ , Retainer Brass A �I1 \ COMPRESSION Ejection Spring .... Stainless Steel , GUIDE �� I m1�i 111� SCREW Patents PINS (2) U.S.A. 4,014,388 � % = ' I Irl i -__ __. DEFLECTOR Operation - rti - i - I P (DROPPED D EFLECTOR i L __- _J �� OSITION) G Z When exposed to heat from a fire, the i SPRINKLER/SUPPORTCUP Cover Plate, which is normally sol- I ASSEMBLY dered to the Retainer at three points, falls away to expose the Sprinkler As- THREAD INTO I RETAINER SUPPORT CUP I WITH THREAD sembly. At this point the Deflector sup- UNTIL MOUNTING ` O 0 I DIMPLES ported by the Guide Pins drops down SURFACE IS to its operational position. FLUSH WITH EJECTION The glass Bulb contains a fluid that CEILING SPRING expands when exposed to heat. When • the rated temperature is reached, the fluid expands sufficiently to shatter then �, glass Bulb, activating the sprinkler and . allowing water to flow. SOLDER COVER TABS (3) COVER PLATE/RETAINER PLATE ASSEMBLY - Design FIGURE 1 Criteria SERIES RFII CONCEALED SPRINKLER ASSEMBLY The RFII (TY3551 & TY3504), 5 mm Bulb Type, Concealed Pendent Sprin- Step 1. The sprinkler must only be klers are UL and C -UL Listed as stand- Installation installed in the pendent position and and response - standard spray sprin- with the centerline of the sprinkler per - klers for use in accordance with the The Series RFII must be installed in pendicular to the mounting surface. current NFPA standard. They are FM accordance with the following instruc- Step 2. Remove the Protective Cap. Approved as standard response - tions: standard spray sprinklers for use in NOTES Step 3. With pipe thread sealant ap- accordance with the current FM Loss plied to the pipe threads, hand tighten Prevention Data Sheets. Do not install any bulb type sprinkler if the sprinkler into the sprinkler fitting. The RFII (TY3531 & TY3505) 3 mm the bulb is cracked or there is a loss of Step 4. Wrench tighten the sprinkler Bulb Type, Concealed Pendent Sprin- liquid from the bulb. With the sprinkler using only the RFII Sprinkler Wrench yp p held horizontally, a small air bubble klers are UL and C -UL Listed as quick should be present. The diameter of the (Ref. Figure 3). The RFII Sprinkler response - standard spray sprinklers air bubble is approximately 1/16 inch Wrench is to be applied to the Sprin for use in accordance with the current kler as shown in Figure 3. NFPA standard. They are FM Ap- (1,6 mm) for the 155 °F /68 °C and 3/32 Step 5. Replace the Protective Ca inch (2,4 mm) for the 200°F/93°C ter P P Cap proved as standard response - stand- perature ratings. (Ref. Figure 4) by pushing it upwards and spray sprinklers for use in accord- A leak tight 1/2 inch NPT sprinkler joint until it bottoms out against the Support Preventi Sheets current FM Loss should be obtained with a torque of 7 Cup. The Protective Cap helps prevent to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi damage to the Deflector and Arms The Series RFII Concealed Pendent mum of 21 ft.lbs. (28,5 Nm) of torque ing ceiling installation and /or during Sprinklers are only listed and ap- is to be used to install sprinklers. application of the finish coating of the proved with the Series RFII Concealed Higher levels of torque may distort the ceiling. It may also be used to locate , Cover Plates having a metallic or white sprinkler inlet with consequent leak the center of the clearance hole by painted finish. age or impairment of the sprinkler. gently pushing the ceiling material up against the center point of the Protec- The Series RFII must not be used in Do not attempt to compensate for in tive Cap. p applications where the air pressure sufficient adjustment in the Sprinkler above the ceiling is greater than that Assembly by under- or over - tightening NOTE below. Down drafts through the Sup the Sprinkler /Support Cup Assembly. A.s long as the Protective Cap remains port Cup could delay sprinkler opera Readjust the position of the sprinkler in place, the system is considered to tion in a fire situation. fitting to suit. be Out of Service ". ' Registered Trademark of DuPont TFP181 Page 3 of 4 f ; FACE OF CLEARANCE HOLE — CLEARANCE SPRINKLER DIAMETER — HOLE \ FITTING DIMENSION C J i =a . e. li i ii SPRINKLER I SUPPORT CUP ASSEMBLY ,....m.— Ag` E I 1/2° (12,7 mm) II THREADED D ADJUSTMENT l) 1 FACE OF CEILING, ; � RETAINING RING 1 ' r FIGURE 4 MOUNTING r / DISPOSABLE PROTECTIVE CAP SURFACE �/ I \ A \ 1- - ►� Step 6. After the ceiling has been corn- pleted with the 2 -1/2 inch (63,5 mm) diameter clearance hole and in prepa \ ; ; ; ; , ration for installing the Cover Plate As c __ � sembly, remove and discard the Pro - ~ r T i r tective Cap, and verify that the 3/16° to 11/16° MANUFACTURER DEFLECTOR COVER PLATE Deflector moves up and down freely. If (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER the Sprinkler has been damaged and REFERENCE 3/32° (2,4 mm) POSITION ASSEMBLY the Deflector does not move up and down freely, replace the entire Sprin- COVER PLATE COVER PLATE kler assembly. Do not attempt to mod- - PROFILE DEPTH DIAMETER — ify or repair a damaged sprinkler. • DIMENSION B DIMENSION A Step 7. When installing an Air and Dust Seal, refer to Figure 5, otherwise proceed to Step 8. To attach the Air and - A: 3 -1/4" (82,6 mm) C: 2 -3/8" to 2 -5/8" (60,3 to 66,7 mm) Dust Seal, verify the angle of the out - B: 3/16" (4,8 mm) D: 1 -3/4" to 2 -1/4° (44,5 to 57,2 mm) side edge of the seal is oriented ac- cording to Figure 5. Start the edge of FIGURE 2 the Retainer in the grooved slot of the SERIES RFII CONCEALED SPRINKLER Air and Dust Seal and continue around . INSTALLATION DIMENSIONS Dust retainer until the entire Air and Dust Seal is engaged. NOTE The Air and Dust Seal is only to be installed on the periphery of the Re- tainer. — - : FRAME r 7 : - I, _ � Step 8. Screw on the Cover Plate /Re- II � tainer Assembly until the Retainer - � � Figure 2 (or Air and Dust Seal - Figure ' S UPPORT - I - O; 5) contacts with the ceiling. Do not continue to screw on the Cover CUP 0 I A I Plate /Retainer Assembly such that it Willi L�1 1 1��0 ' lifts a ceiling panel out of its normal I■I / pA... • % � position. If the Cover Plate /Retainer ` Assembly cannot be engaged with the 0 Support Cup or the Cover Plate /Re- 7/8° (23 mm) tainer Assembly cannot be engaged SQUARE sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. ALIGN , J L. ARROWS WITH \� Care and FRAME ARMS 1 _ ■ di Maintenance ACCEPTS ' The Series RFII must be maintained 0 1/2° SOCKET and serviced in accordance with the DRIVE following instructions: NOTES FIGURE 3 Absence of the Cover Plate Assembly RFII SPRINKLER WRENCH may delay sprinkler operation in a fire situation. Page 4 of 4 TFP181 When properly installed, there is a SUPPORT SPRINKLER FACE OF ORIENT 1, nominal 3/32 inch (2,4 mm) air gap CUP / CEILING SEAL between the lip of the Cover Plate and / BEVELAS I the ceiling, as shown in Figure 2. This l =�` Th I.: SHOWN air gap is necessary for proper opera- PLATE A ,� �� tion of the sprinkler. If the ceiling is to Old ' RETAINER - be repainted after the installation of (ii If\ ASSEMBLY " " . ., the Sprinkler, care must be exercised to ensure that the new paint does NOT - ' A � � seal off any of the air gap. A � � A 4111V ROOM Factory painted Cover Plates MUST —� 1. NOT be repainted. They should be re – – LIP OF COVER SEAL placed, if necessary, by factory RETAINER PLATE painted units. FIGURE 5 Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504) the Enclosure. Separation may result. Before closing a fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT main control valve for maintenance local requirements and /or national SHALL TYCO FIRE PRODUCTS' LI- work on the fire protection system that codes. ABILITY EXCEED AN AMOUNT it controls, permission to shutdown the EQUAL TO THE SALES PRICE. affected fire protection system must be L imited THE FOREGOING WARRANTY IS obtained from the proper authorities MADE IN LIEU OF ANY AND ALL and all personnel who may be affected wa rranty OTHER WARRANTIES EXPRESS OR by this action must be notified. IMPLIED. INCLUDING WARRANTIES Sprinklers that are found to be leaking OF MERCHANTABILITY AND FIT - or exhibiting visible signs of corrosion Products manufactured by Tyco Fire NESS FOR A PARTICULAR PUR must be replaced. Products are warranted solely to the POSE. Automatic sprinklers must never be original Buyer for ten (10) years against defects in material and work- ' painted, plated, coated or otherwise manship when paid for and properly Ordering altered after leaving the factory. Modi- installed and maintained under normal fled sprinklers must be replaced. use and service. This warranty will ex- Procedure - Sprinklers that have been exposed to pire ten (10) years from date of ship - corrosive products of combustion, but have not operated, should be replaced ment by Tyco Fire Products. No war- When placing an order, indicate the full ▪ if they cannot be completely cleaned ranty is given for products or product name. Contact your local dis- components manufactured by compa- tributor for availability. by wiping the sprinkler with a cloth or nies not affiliated by ownership with ty by brushing it with a soft bristle brush. Tyco Fire Products or for products and Sprinkler Assembly: • Care must be exercised to avoid dam- components which have been subject rating) SeSi N) (specify temperature age to the sprinklers - before, during, to misuse, improper installation, corro- dent (specify). , P/N Sprinkler, y). and after installation. Sprinklers dam- sion, or which have not been installed, P aged by dropping, striking, wrench maintained, modified or repaired in ac 155E /sec 200F/93c twist/slippage, or the like, must be re- cordance with applicable Standards of Ty3551 51- 790 -1 -155 51- 790 -1 -200 placed. Also, replace any sprinkler that the National Fire Protection Associa- TY35o4 51- 796 -1 -155 51- 796 -1 -200 has a cracked bulb or that has lost tion, and /or the standards of any other TY3531 51- 792 -1 -155 51- 792 -1 -200 liquid from its bulb. (Ref. Installation Authorities Having Jurisdiction. Mate - TY3505 51- 797 -1 -155 51- 797 -1 -200 Section). rials found by Tyco Fire Products to be If a sprinkler must be removed, do not defective shall be either repaired or Separately Ordered Cover Plate: reinstall it or a replacement without replaced, at Tyco Fire Products' sole Specify: (specify temperature rating) reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate If a Cover Plate Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify). dislodged during service, replace it im- assume for it, any other obligation in mediately. connection with the sale of products or 135F/57C(a) 165Fn4C•(b) parts of products. Tyco Fire Products Brass 56- 792 -1 -135 56- 792 -1 -165 P P Y Bright Brass 56- 792 -2 -135 56- 792 -2 -165 The owner is responsible for the in- shall not be responsible for sprinkler Chrome 56- 792 -9 -135 56- 792 -9 -165 spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome - -8 -- -- protection system and de- incomplete information supplied by White 56 792 792 -0 -135 135 56 792 792 8 -0-165 165 their fire P y p pp y White (RAL9010)' 56- 792 -3 -135 56- 792 -3 -165 vices in compliance with this docu- Buyer or Buyer's representatives. Bright White 56- 792 -4 -135 56- 792 -4 -165 ment, as well as with the applicable IN NO EVENT SHALL TYCO FIRE Off White 56- 792 -5 -135 56- 792 -5 -165 • standards of the National Fire Protec- PRODUCTS BE LIABLE, IN CON- C 56- 792 -6-135 56- 792 -6-165 Custom 56- 792 -X -135 56- 792 -X -165 tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR addition to the standards of any other UNDER ANY OTHER LEGAL THE- (a) For use with 155E /93C sprinklers. jurisdiction. The in- (b) For use emi 200F/93C resales sprinklers. only. - authorities having 1 ORY, FOR INCIDENTAL, INDIRECT, • Eastern Hemisphere sales only. stalling contractor or sprinkler manu- SPECIAL OR CONSEQUENTIAL facturer should be contacted relative to DAMAGES, INCLUDING BUT NOT Sprinkler Wrench: any questions. LIMITED TO LABOR CHARGES, RE- Specify: RFII Sprinkler Wrench, It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56-000-1-075. sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal: tested, and maintained by a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal, P/N 56- 908 -1 -001. TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 t LICD Fire & Building Products Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series TY -FRB — 2.8, 4.2, 5.6, and 8,0 K- factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General mospheres. Although corrosion rests- tant coated sprinklers have passed the standard corrosion tests of the appli- —'' ' -- ,,•:,'' -. Description cable approval agencies, the testing is ,. , 4 not representative of all possible cor- �, ;. The Series TY -FRB, 2.8, 4.2, 5.6, and rosive atmospheres. Consequently, it I 8.0 K- factor, Upright and Pendent is recommended that the end user be rte► fiiii, Sprinklers described in this data sheet consulted with respect to the suitability P are quick response - standard cover- of these coatings for any given corro- ;j age, decorative 3 mm glass bulb type sive environment. The effects of ambi- .1 _ spray sprinklers designed for use in ent temperature, concentration of 16, light or ordinary hazard, commercial chemicals, and gas /chemical velocity, occupancies such as banks, hotels, should be considered, as a minimum, �ti_ shopping malls, etc. along with the corrosive nature of the , The recessed version of the Series chemical to which the sprinklers will be TY-FRB Pendent Sprinkler, where ap- exposed. '�� plicable, is intended for use in areas An intermediate level versions of the with a finished ceiling. It uses either a Series TY-FRB Pendent Sprinklers are -. „ two -piece Style 10 (1/2 inch NPT) or detailed in Technical Data Sheet Style 40 (3/4 inch NPT) Recessed Es- TFP356, and Sprinkler Guards are de - cutcheon with 1/2 inch (12,7 mm) of tailed in Technical Data Sheet TFP780 j - recessed adjustment or up to 3/4 inch / (19,1 mm) of total adjustment from the WARNINGS flush pendent position, or a two -piece The Series TY -FRB Sprinklers de- ' t e Style 20 (1/2 inch NPT) or Style 30 (3/4 scribed herein must be installed and '�� �' inch NPT) Recessed Escutcheon with maintained in compliance with this -.i' . .. - ..0 1/4 inch (6,4 mm) of recessed adjust- document, as well as with the applica- ' ment or up to 1/2 inch (12,7 mm) of ble standards of the National Fire Pro TY3231 - Pendent 5.6K, 1/2 "NPT total adjustment from the flush pen- tection Association, in addition to the TY4131 - Upright 8.0K, 3/4 "NPT dent position. The adjustment provided standards of any other authorities hay- TY4231 - Pendent 8.0K, 3/4 "NPT by the Recessed Escutcheon reduces ing jurisdiction. Failure to do so may the accuracy to which the fixed pipe impair the performance of these de- drops to the sprinklers must be cut. vices. Technical Corrosion resistant coatings, where The owner is responsible for maintain - applicable, are utilized to extend the ing their fire protection system and de- Data life of copper alloy sprinklers beyond vices in proper operating condition. that which would otherwise be ob- The installing contractor or sprinkler Approvals tained when exposed to corrosive at- manufacturer should be contacted UL and C -UL Listed. with any questions. FM, LPCB, and NYC Approved. (Refer to Table A for complete approval IMPORTANT information including corrosion resis- Always refer to Technical Data tant status.) Sheet TFP700 for the "INSTALLER Model /Sprinkler Maximum Working Pressure with respect that handl ing g a and instal- Identification 175 psi (12,1 bar) with re eco hnin d insta ' lation of sprinkler systems and com- Discharge Coefficient ponents. Improper handling and in- Numbers K = 2.8 GPM /psi (40,3 LPM /bar stallation can permanently damage K = 4.2 GPM /psi (60,5 LPM/bar"i a sprinkler system or its compo- TY1131 - Upright 2.8K, 1/2"NPT K = 5.6 GPM /psi (80,6 LPM /barli nents and cause the sprinkler to fail TY1231 - Pendent 2.8K, 1/2"NPT K = 8.0 GPM /psis / (115,2 LPM /barli to operate in a fire situation or cause TY2131 - Upright 4.2K, 1/2"NPT Temperature Ratings it to operate prematurely. TY2231 - Pendent 4.2K, 1/2 "NPT Refer to Table A and B TY3131 - Upright 5.6K, 1/2"NPT Page 1 of 8 JULY, 2004 TFP171 Page 2 of 8 TFP171 • ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 • PLATE SEATING * * NOMINAL RECESSED SURFACE 1/2 MAKE -IN ESCUTCHEON SSU NPT I DEFLECTOR 1 M _ IT r r Y I ri?T� al'f: 6 7/ 16" 1. 5 2 -1/4" f 'mr (11,1 mm) 1- 9/16" 4 (57,2 mm) = NOMINAL II I i 4)11 MAKE -IN 2 � � � 1 2 3/1 �7 3 I WRENC I (55,6 mm) $ � (39,7 mm) FLATS o � 1 Ill i�r �� irr �� 4=.11 SSP DEFLECTOR * — 2 -7/8" (73,0 mm) DIA. 1/2" NPT ** } 7 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 7/16° (11,1 mm) STYLE 10 or 20 PLATE SEATING „ * * NOMINAL RECESSED SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR 6 t ---.---- Intl r i 5 '■I_ 7/16° _ 2 3 /1 6° ,� } '!'� ( 11,1 mm (55,6 mm) I � �� �- l I NOMINAL i i 4 t M AKE -IN 11/2° I I/ r�� 1 2-3/16° 2 (38,1 mm) WRENCH — (55,6 mm) 0 y 3 1 10 II 111 FLAT SSP DEFLECTOR — 2 -7/8° (73,0 mm) DIA. 1/2° NPT I PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 2 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT m Finishes Bulb Glass 5) Sprinkler: Refer to Table A and B Compression Screw Bronze Operation Recessed Escutcheon: White Coated, Deflector ....... Copper /Bronze F- Chrome Plated, or Brass Plated Bushing (K =2.8) Bronze The glass Bulb contains a fluid which expands when exposed to heat. When y the rated temperature is reached, the 'rn Physical Characteristics fluid expands sufficiently to shatter the w cc Frame Bronze glass Bulb, allowing the sprinkler to = Button Brass /Copper activate and water to flow. 0 Sealing Assembly o Beryllium Nickel w/Teflont TFP171 Page 3 of 8 • ESCUTCHEON 7/16° (11,1 mm) STYLE 10 or 20 • PLATE SEATING *„ NOMINAL RECESSED SURFACE 1/2" T -I N ESCUTCHEON DEFLECTOR 6* i _ ---- rr= r r rMil 7/16° m m) 5 2- 3/16° � � lE � I (11,1 m i I (55,6 mm) ��� � �� �- NOMINAL ' 4 71� MAKIE -IN 1-11/2° qv M 1 2 3/16° r 2 (38,1 mm ) I WRENCH 1 (55,6 mm) PI FLATS _ I i 3 SSP DEFLECTOR * - 2-7/8" (73,0 mm) DIA. - 1 1/2° NPT f 1 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 1/2° (12,7 mm) STYLE 30 or 40 PLATE SEATING ** NOMINAL RECESSED * SURFACE NP NPT ESCUTCHEON T DEFLECTOR 6 1/2" ( 5 2 -5/16" �� �� (12,7 mm) �_._ IF (58,7 mm) 1 ��A � NOMINAL I 4 tIrrI I MAKE IN 1 -9/16° I 11Al...14 I� I 2 1/4° �' 2 (57 re (39,7 WR ENCH ,2 mm) 1 3 1 -- °•- --- _ -- • . -.. FLATS 1 Z 1 I 1 SSP DEFLECTOR * • 2 -7/8" (73,0 mm) DIA. 3/4° NPT 1 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 4 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT Listing is based on the requirements of Design NFPA 13, and FM Approval is based Installation C • on the requirements of FM's Loss Pre - riteria vention Data Sheets ). Only the Style The Series TY-FRB Sprinklers must be 10, 20, 30, or 40 Recessed Escutch- installed in accordance with the follow - The Series TY-FRB Pendent and Up- eon, as applicable, is to be used for ing instructions: right Sprinklers are intended for fire recessed pendent installations. protection systems designed in ac- NOTES cordance with the standard installation Do not install any bulb type sprinkler if rules recognized by the applicable the bulb is cracked or there is a loss of Listing or Approval agency (e.g., UL liquid from the bulb. With the sprinkler Page 4 of 8 TFP171 SPRINKLER FINISH (See Note 7) inch NPT sprinkler joint should be ob tained with a torque of 10 to 20 ft.lbs. K TYPE TEMP. BULB NATURAL CHROME WHITE*** (13,4 to 26,8 Nm). A maximum of 30 LIQUID BRASS PLATED POLYESTER ft.lbs. (40,7Nm) of torque is to be used to install sprinklers with 3/4 NPT con - 135°F/57°C Orange nections. Higher levels of torque may PENDENT 155 °F /68 °C Red distort the sprinkler inlet and cause (TY1231) 1, 2, 3, 5 leakage or impairment of the sprinkler. and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green Do not attempt to make -up for insuffi- (TY1131) cient adjustment in the escutcheon 2.8 286 °F /141 °C Blue plate by under- or over - tightening the 1/2" sprinkler. Readjust the position of the NPT 135 °F /57 °C Orange sprinkler fitting to suit. RECESSED PENDENT 155 °F /68 °C Red The Series TY -FRB Pendent and Up- (TY1231)• 175 °F /79 °C Yellow right Sprinklers must be installed in Figure 5 accordance with the following instruc- g ure 200 °F /93 °C Green 1, 2, 5 tions. 135 °F /57 °C Orange Step 1. Pendent sprinklers are to be RECESSED 155 °F /68 °C Red installed in the pendent position, and PENDENT upright sprinklers are to be installed in (TY1231)•• 175 °F /79 °C Yellow the upright position. Figure 6 200 °F /93 °C Green Step 2. With pipe thread sealant ap- 135 °F /57 °C Orange plied to the pipe threads, hand tighten PENDENT the sprinkler into the sprinkler fitting. (TY2231) 155 °F /68 °C Red Step 3. Tighten the sprinkler into the and 175 °F /79 °C Yellow sprinkler fitting using only the W -Type UPRIGHT 200 °F /93 °C Green 6 Sprinkler Wrench (Ref. Figure 13). (TY2131) With reference to Figures 1, 2, 3, and 4.2 286 °F /141 °C Blue 4, the W -Type 6 Sprinkler Wrench is to NPT 135 °F /57 °C Orange 1 2 be applied to the sprinkler wrench flats. RECESSED 155 °F /68 °C Red PENDENT (TY2231)• 175 °F /79 °C Yellow The Series TY -FRB Recessed Pen - Figure 7 200 °F /93 °C Green dent Sprinklers must be installed in accordance with the following instruc- - 135 °F /57 °C Orange tions. RECESSED 155 °F /68 °C Red Step A. After installing the Style 10. PENDENT 20, 30, or 40 Mounting Plate, as appli- (TY2231)*• 175 °F179 °C Yellow cable, over the sprinkler threads and Figure 8 200 °F /93 °C Green with pipe thread sealant applied to the pipe threads, hand tighten the sprin- NOTES: kler into the sprinkler fitting. 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. Step B. Tighten the sprinkler into the 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response sprinkler fitting using only the W P 9 9 Y YP e 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin Recessed Sprinkler Wrench (Ref. klers. Figure 14). With reference to Figure 1, 5. Approved by the City of New York under MEA 354 -01 -E. 2, 3, and 4, the W - Type 7 Recessed 7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- Sprinkler Wrench is to be applied to klers are UL and C -UL Listed as Corrosion Resistant Sprinklers. the sprinkler wrench flats. * Installed with Style 10 (1/2" NPT) or Style 40 (3/4° NPT) 3/4" Total Adjustment Step C. After the ceiling has been in- Recessed Escutcheon, as applicable. stalled or the finish coat has been a •' Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment P Recessed Escutcheon, as applicable. plied, slide on the Style 10, 20, 30, or • °' Frame and Deflector only. Listings and approvals apply to color (Special Order). 40 Closure over the Series TY N/A: Not Available Sprinkler and push the Closure over the Mounting Plate until its flange TABLE A comes in contact with the ceiling. LABORATORY LISTINGS AND APPROVALS 2.8 AND 4.2 K- FACTOR SPRINKLERS held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint should be present. The diameter of the should be obtained with a torque of 7 air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- , mm) for the 135 °F /57 °C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque inch (2,4 mm) for the 286 °F /141 °C may be used to install sprinklers with temperature ratings. 1/2 NPT connections. A leak tight 3/4 • • TFP171 Page 5of8 SPRINKLER FINISH (See Note 8) ° K TYPE TEMP. BULB NATURAL CHROME WHITE"' LEAD LIQUID BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 5.6 (TY3131) 286 °F /141 °C Blue 1/2" NPT 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 4, 5 N/A (TY3231)* ' 175 °F /79 °C Yellow Figure.9 200 °F /93 °C Green - 135 °F /57 °C Orange • RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A (T.Y3231)'• 175 °F /79 °C Yellow Figure 10 • 200 °F /93 °C Green • 135 °F /57 °C Orange ' PENDENT N) 155 °F /68 °C ' Red . and ' 175 °F /79 °C Yellow 1, 2, 5 1,2,3,4,5,6,7 • , UPRIGHT 200 °F /93 °C Green 8.0 (TY4131) 286 °F /141 °C Blue 3/4° NPT 135F/57°C Green RECESSED 155 °F /68 °C Orange PENDENT 1, 2, 4, 5 N/A (TY4231)* 175 °F /79 °C Red Figure 11 200 °F /93 °C Yellow' • 135 °F /57 °C Orange • • • , RECESSED 155 °F /68 °C ' Red . PENDENT 1,2,3,4,5 N/A (TY4231)• 175 °F /79 °C Yellow. Figure 12 200 °F /93 °C Green NOTES: - • 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers. 3. App 'roved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the LPCB does not rate the thermal sensitivity of recessed sprinklers. • 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31- 53- 428- 4444/Fax 31 -53 -428- 3377). 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a106) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion Resistant Sprinklers. Installed with Style 10 (1/2° NPT) or Style 40 (3/4° NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. °° Installed with Style 20 (1/2" NPT) or Style 30 (3/4° NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. °'° Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE B • LABORATORY LISTINGS AND APPROVALS 5.6 AND 8.0 K- FACTOR SPRINKLERS • Page 6 of 8 TFP171 • 2 -7/8' DIA _ 2 -7/8' DIA. 5/8x1/4" (73,0 mm) 3/4° (19,1 mm) (73,0 mm) • 1/2x1/8" 1/2° (12,7 mm) (15,9±6,4 mm) 2 -1/4° DIA 1 1/4° (6,4 mm) (12,7x3,2 mm) 2 -1/4' DIA. 1/4' (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) SPRINKLER PLATE SPRINKLER MOUNTING PLATE FITTING FITTING 1/8' I 1/8° A M •.' (3,2 mm) •� ( 3 ,2 mm) =AR r ---111 �� • l i Or, I , MOUNTING II, I' MOUNTING . SURFACE SURFACE --rms., • , CLOSURE SERIES 1 -5/16' (33,3 mm) CLOSURE SERIES 1.5/16° (33,3 mm) TY-FRB 13/16' (20,6 mm) TY -FRB 1 -1/16° (27,0 mm) FIGURE 5 FIGURE 6 SERIES TY -FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT 2 -7/8° DIA. - 2 -7/8' DIA. 5/8x1/4° (73,0 mm) 3/4' (19,1 mm) 1/2x1/8' (73,0 mm) 1/2' (12,7 mm) (15,9x6,4 mm) 2 -1/4' DIA. 1/4' (6,4 mm) (12,7x3,2 mm) 2 -1/4' DIA. 1/4' (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING • SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8° 1/8° (3,2 mm l ) M �l�lli N r (3'2 _ mm) I —� ���� MOUNTING MOUNTING . SURFACE . SURFACE --- - ---•• — �__ -- CLOSURE SERIES 1 -1/4° (31,8 mm) CLOSURE SERIES 1 -1/4° (31,8 mm) TY -FRB 3/4' (19,1 mm) TY -FRB 1° (25,4 mm) FIGURE 7 FIGURE 8 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT used to cover a clearance hole, may and after installation. Sprinklers dam - Care and delay the time to sprinkler operation in aged by dropping, striking, wrench a fire situation. twist/slippage, or the like, must be re- Maintenance Sprinklers that are found to be leaking has a cracked place oryt sprinkler has s lost The Series TY-FRB Sprinklers must be or exhibiting visible signs of corrosion liquid from its bulb. (Ref. Installation maintained and serviced in accord- must be replaced. Section). ance with the following instructions: Automatic sprinklers must never be Frequent visual inspections are rec- NOTES painted, plated, coated or otherwise altered after leaving the factory. I ommended to be initially performed for Before closing a fire protection system fled sprinklers must be replaced. placed. cad. corrosion resistant coated sprinklers, main control valve for maintenance Sprinklers that have been exposed to after the installation has been corn- work on the fire protection system that corrosive products of combustion, but pleted, to verify the integrity of the cor- it controls, permission to shut down the have not operated, should be replaced rosion resistant coating. Thereafter, affected fire protection system must be if they cannot be completely cleaned annual inspections per NFPA 25 obtained from the proper authorities by wiping the sprinkler with a cloth or should suffice; however, instead of in- and all personnel who maybe affected by brushing it with a soft bristle brush. specting from the floor level, a random by this action must be notified. sampling of close -up visual inspec- Care must be exercised to avoid dam- tions should be made, so as to better Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi- TFP1 71 Page 7 of 8 2 -7/8' DIA. _ 2 -7/8' DIA. • 5/8±1/4' ( mm) 3/4' (19,1 mm) (73,0 mm) (15,9±6,4 mm) 1/4' (6,4 mm) 1/231/8' 1/2' (12,7 mm) 2 -1/4' DIA. ( ) (12,733,2 mm) 2 -1/4' DIA. 1/4' (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8' 1/8' Walla (3 ' (3,2 mm) �� (3,2 mm) rj �, III } G MOUNTING SURFACE SURFACE � = MOUNTIN � CLOSURE SERIES 1 -1/4' (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm) TY -FRB 3/4' (19,1 mm) TY -FRB 1' (25,4 mm) FIGURE 9 FIGURE 10 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT 2 -7/8' DIA 2 -7/8' DIA. 5/831/4' ( mm) 3/4' (19,1 mm) 1/2x1/8, (73,0 mm) 1/2' (12,7 mm) (15,936,4 mm) 2 -1/4' DIA 1 1/4' (6,4 mm) (12,7x3,2 mm) 2 -1/4' DIA. 1/4' (6,4 mm) (57,2 mm) (57,2 mm FACE OF MOUNTING FACE OF mm) MOUNTING • SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8' 1/8' " (3,2 mm) r II I (3,2 mm) r�� 2.1 i Pr I f \ ' MOUNTING 1 • MOUNTING � SURFACE SURFACE 1 . CLOSURE SERIES 1 -5/16' (33,3 mm) CLOSURE SERIES 1 -5/16' (33,3 mm) TY -FRB 13/16' (20,6 mm) TY-FRB 1 -1/16' (27,0 mm) FIGURE 11 FIGURE 12 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT tion and the long term integrity of the corrosion resistant coating, as it may WRENCH be affected by the corrosive conditions � � RECESS present. WRENCH RECESS The owner is responsible for the in P (END °A° USED FOR spection, testing, and maintenance of 1/2° NPT MODELS) /\ their fire protection system and de- - `� vices in compliance with this docu- ` u ment, as well as with the applicable H RECESS . standards of the National Fire Protec- WRENCH USED FOR PUSH WRENCH tion Association (e.g., NFPA 25), in (END NPT MODELS) IN TO ENSURE addition to the standards of any other ENGAGEMENT . authorities having jurisdiction. The in- WITH SPRINKLER stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA facturer should be contacted relative to W -TYPE 6 SPRINKLER any questions. WRENCH It is recommended that automatic FIGURE 14 sprinkler systems be inspected, local requirements and /or national W TYPE7 RECESSED tested, and maintained by a qualified codes. SPRINKLER WRENCH Inspection Service in accordance with ,, Page 8 of 8 TFP171 P/N 57 -XXX -X- XXX I I TEMPERATURE MODEUSIN RATING SPRINKLER 330 2.8K UPRIGHT (1 /2 "NPT) TY1131 135 135 °F /57 °C 331 2 8K PENDENT (1 /2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C 340 4.2K UPRIGHT (1 /2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C 341 4.2K PENDENT (1 /2 "NPT) TY2231 3 WHITE (RAL9010)* 200 200 °F /93 °C 370 5.6K UPRIGHT (1 /2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C 371 5.6K PENDENT (1 /2 "NPT) TY3231 7 LEAD COATED 390 8.0K UPRIGHT (3 /4 "NPT) TY4131 391 8.0K PENDENT (3 /4 "NPT) TY4231 ' Eastern Hemisphere sales only. TABLE C PART NUMBER SELECTION SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS ORY, FOR INCIDENTAL, INDIRECT, Recessed Escutcheon: Limited SPECIAL OR CONSEQUENTIAL Specify: Style (specify) Recessed Es- DAMAGES, INCLUDING BUT NOT cutcheon with (specify finish), P/N Warranty LIMITED TO LABOR CHARGES, RE- (specify). ° GARDLESS OF WHETHER TYCO Products manufactured by Tyco Fire FIRE PRODUCTS WAS INFORMED 1/2° (15 mm) Products are warranted solely to the ABOUT THE POSSIBILITY OF SUCH Style 10 • original Buyer for ten (10) years DAMAGES, AND IN NO EVENT Chrome Plated P /N56- 701 -9 -010 against defects in material and work- SHALL TYCO FIRE PRODUCTS' LI- White Coated P/N 56- 701 -4 -010 when paid for and properly White RAL9010' P/N 56- 701 -3-010 manship P P P y ABILITY EXCEED AN AMOUNT Brass Plated P/N 56- 701 -2 -010 . installed and maintained under normal EQUAL TO THE SALES PRICE. use and service. This warranty will ex- THE FOREGOING WARRANTY IS 1/2" (15 mm) pire ten (10) years from date of ship- Style 20 ment by Tyco Fire Products. No war- • MADE IN LIEU OF ANY AND ALL, Chrome Plated P/N 56- 705 -9 -010 ranty is given for products or OTHER WARRANTIES EXPRESS OR White Coated .. P/N 56-705-4-010 components manufactured by compa IMPLIED. INCLUDING WARRANTIES White RAL9010' P/N 56- 705 -3 -010 Hies not affiliated by ownership with OF MERCHANTABILITY AND FIT- Brass Plated P/N 56- 705 -2 -010 Tyco Fire Products or for products and NESS FOR A PARTICULAR PUR- 3/4° (20 mm) components which have been subject POSE Style 30 to misuse, improper installation, corro- Chrome Plated ...... P/N 56- 705 -9 -011 sion, or which have not been installed, White Coated P/N 56- 705 -4 -011 maintained, modified or repaired in ac- White Plated o' P/N 56 -705 -3 -011 cordance with applicable Standards of r der�ng Brass Plated P/N 56- 705 -2 -011 the National Fire Protection Associa- Procedure 3/4° (20 mm) tion, and /or the standards of any other Style 40 Authorities Having Jurisdiction. Mate- esimtarabiligun Iracal distributor for avail- Chrome Plated .... . P/N 56- 700 -9 -010 rials found by Tyco Fire Products to be ability the White Coated P/N 56-700-4-010 defective shall be either repaired or ful rrproduct White RAL9010' P/N 56-700-3-010 replaced, at Tyco Fire Products' sole name. Refer to Brass Plated P/N 56- 700 -2 -010 option. Tyco Fire Products neither as- the complete List ti for o P y complete listing • Eastern Hemisphere sales only sumes, nor authorizes any person to of Part Numbers. assume for it, any other obligation In Sprinkler Wrench: connection with the sale of products or Sprinkler Assemblies with NPT Specify: W -Type 6 Sprinkler Wrench, parts of products. Tyco Fire Products Thread Connections: P/N 56- 000 -6 -387. shall not be responsible for sprinkler Specify: (Specify Model /SIN), Quick • system design errors or inaccurate or Response, (specify K- factor), (specify Specify: W -Type 7 Sprinkler Wrench, incomplete information supplied by temperature rating), Series TY-FRB P/N 56- 850 -4 -001. Buyer or Buyer's representatives. (specify Pendent or Upright) Sprinkler IN NO EVENT SHALL TYCO FIRE with (specify type of finish or coating), PRODUCTS BE LIABLE, IN CON P/N (specify from Table C). TRACT, TORT, STRICT LIABILITY OR UNDER ANY OTHER LEGAL THE - TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446