Loading...
Specifications PATRIOT FIRE PROTECTION, INC. RECEIVED 4708 NE MINNEHAHA STREET VANCOUVER, WA 98 661 AUG 2 8 2009 CITY OF TIGARD BUILDING DIVISION HYDRAULIC CALCULATIONS FA5.2U0 Q' FOR ? v 'vvv / /3333 / 48 Pkwy TRIANGLE POINTE 13333 SW 68TH PKWY TIGARD, OREGON 97223 FILE: TRIANGLE POINTE.SDF DATE: 8/26/2009 - DESIGN DATA - OCCUPANCY CLASSIFICATION: LIGHT HAZARD DENSITY: .10 GPM AREA OF APPLICATION: 973 SQ. FT. MINIMUM COVERAGE PER SPRINKLER: 225 SQ. FT. MAXIMUM NUMBER OF SPRINKLERS CALCULATED: 12 SPRINKLERS • TOTAL SPRINKLER WATER FLOW REQUIRED: 217.3 GPM TOTAL WATER REQUIRED (including hose): 317.3 GPM FLOW AND PRESSURE (@ BOR): 217.3 GPM @ 83.7 PSI SPRINKLER ORIFICE SIZE: 1/2 INCH NAME OF CONTRACTOR: PATRIOT FIRE PROTECTION, INC. DESIGN /LAYOUT BY: JEFF COLLINS AUTHORITY HAVING JURISDICTION: CITY OF TIGARD CONTRACTOR CERTIFICATION NUMBER: 70822 CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 3808132120) HRS SYSTEMS, INC. ATLANTA, GA • SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 8/26/2009 C: \HASS FILES \TRIANGLE POINTE.SDF JOB TITLE: Triangle Pointe - Light Hazard - .10/973 Sq. Ft. WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) SOURCE 86.0 75.0 1313.0 85.2 317.3 80.3 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 317.3 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 217.3 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) SOURCE 0.0 SOURCE 80.3 217.3 101 11.0 K= 5.60 15.5 22.0 102 11.0 K= 5.60 11.9 19.3 103 11.0 K= 5.60 7.7 15.5 104 11.0 K= 5.60 7.4 15.2 105 11.0 K= 5.60 9.0 16.8 106 11.0 K= 5.60 8.9 16.7 107 11.0 K= 5.60 9.6 17.4 • 108 11.0 K= 5.60 9.3 17.1 109 11.0 K= 5.60 10.5 18.2 110 11.0 K= 5.60 11.4 18.9 111 11.0 K= 5.60 15.8 22.2 112 11.0 K= 5.60 10.3 18.0 1 11.0 - - - - 16.5 - - - 2 11.0 - - - - 12.7 - - - 3 11.0 - - - - 10.3 - - - 3A 11.0 - - - - 8.5 - - - 4 11.0 - - - - 9.9 - - - 5 11.0 - - - - 9.6 - - - 6 11.0 - - - - 9.6 - - - 8 11.0 - - - - 10.0 - - - 9 11.0 - - - - 11.3 - - - 10 11.0 - - - - 12.2 - - - 12 11.0 - - - - 39.5 - - - 13 11.0 - - - - 50.8 - - - TR -6.0 - - - - 76.4 - - - BF1 -9.0 - - - - 77.7 - - - BF2 -9.0 - - - - 83.7 - - - UG1 -11.0 - - - - 84.6 - - - SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 8/26/2009 C: \HASS FILES \TRIANGLE POINTE.SDF JOB TITLE: Triangle Pointe - Light Hazard - .10/973 Sq. Ft. . PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) Pipe: 1 -22.0 1.101 PL 1.00 PF 1.1 101 11.0 5.6 15.5 22.0 7.4 150 FTG TE PE 0.0 1 11.0 0.0 16.5 0.0 0.081 TL 13.00 PV Pipe: 2 -19.3 1.101 PL 1.00 PF 0.8 102 11.0 5.6 11.9 19.3 6.5 150 FTG TE PE 0.0 2 11.0 0.0 12.7 0.0 0.064 TL 13.00 PV Pipe: 3 -15.5 1.101 PL 5.50 PF 0.8 103 11.0 5.6 7.7 15.5 5.2 150 FTG 2E PE 0.0 3A 11.0 0.0 8.5 0.0 0.042 TL 19.50 PV Pipe: 4 -15.2 1.101 PL 7.50 PF 1.1 104 11.0 5.6 7.4 15.2 5.1 150 FTG T2E PE 0.0 3A 11.0 0.0 8.5 0.0 0.041 TL 26.50 PV Pipe: 5 -16.8 1.101 PL 1.00 PF 0.6 105 11.0 5.6 9.0 16.8 5.6 150 FTG TE PE 0.0 5 11.0 0.0 9.6 0.0 0.049 TL 13.00 PV Pipe: 6 -16.7 1.101 PL 1.00 PF 0.6 106 11.0 5.6 8.9 16.7 5.6 150 FTG TE PE 0.0 6 11.0 0.0 9.6 0.0 0.049 TL 13.00 PV Pipe: 7 -17.1 1.101 PL 1.50 PF 0.7 108 11.0 5.6 9.3 17.1 5.8 150 FTG TE PE 0.0 8 11.0 0.0 10.0 0.0 0.051 TL 13.50 PV Pipe: 8 -18.2 1.101 PL 1.50 PF 0.8 109 11.0 5.6 10.5 18.2 6.1 150 FTG TE PE 0.0 9 11.0 0.0 11.3 0.0 0.057 TL 13.50 PV Pipe: 9 -18.9 1.101 PL 1.50 PF 0.8 110 11.0 5.6 11.4 18.9 6.4 150 FTG TE PE 0.0 10 11.0 0.0 12.2 0.0 0.061 TL 13.50 PV Pipe: 10 114.0 1.598 PL 19.83 PF 23.0 12 11.0 0.0 39.5 0.0 18.2 150 FTG 7E PE 0.0 1 11.0 0.0 16.5 0.0 0.277 TL 82.83 PV Pipe: 11 92.0 1.598 PL 11.58 PF 3.8 1 11.0 0.0 16.5 0.0 14.7 150 FTG E PE 0.0 2 11.0 0.0 12.7 0.0 0.187 TL 20.58 PV Pipe: 12 72.7 1.598 PL 11.67 PF 2.4 2 11.0 0.0 12.7 0.0 11.6 150 FTG T PE 0.0 . 3 11.0 0.0 10.3 0.0 0.121 TL 19.67 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 8/26/2009 C: \HASS FILES \TRIANGLE POINTE.SDF JOB TITLE: Triangle Pointe - Light Hazard - .10/973 Sq. Ft. . PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) Pipe: 13 -30.7 1.101 PL 7.08 PF 1.8 3A 11.0 0.0 8.5 0.0 10.4 150 FTG T PE 0.0 3 11.0 0.0 10.3 0.0 0.151 TL 12.08 PV Pipe: 14 42.0 1.598 PL 0.50 PF 0.0 3 11.0 0.0 10.3 0.0 6.7 150 FTG - - -- PE 0.0 112 11.0 5.6 10.3 18.0 0.044 TL 0.50 PV Pipe: 14A 24.0 1.598 PL 17.00 PF 0.4 112 11.0 5.6 10.3 18.0 3.8 150 FTG T PE 0.0 4 11.0 0.0 9.9 0.0 0.016 TL 25.00 PV Pipe: 15 24.0 1.598 PL 19.17 PF 0.3 4 11.0 0.0 9.9 0.0 3.8 150 FTG - - -- PE 0.0 5 11.0 0.0 9.6 0.0 0.016 TL 19.17 PV Pipe: 16 7.2 1.598 PL 9.33 PF 0.0 5 11.0 0.0 9.6 0.0 1.2 150 FTG E PE 0.0 6 11.0 0.0 9.6 0.0 0.002 TL 18.33 PV Pipe: 17 -9.5 1.598 PL 9.25 PF 0.1 6 11.0 0.0 9.6 0.0 1.5 150 FTG E PE 0.0 107 11.0 5.6 9.6 17.4 0.003 TL 18.25 PV Pipe: 18 -26.9 1.598 PL 12.75 PF 0.4 107 11.0 5.6 9.6 17.4 4.3 150 FTG E PE 0.0 8 11.0 0.0 10.0 0.0 0.019 TL 21.75 PV Pipe: 19 -44.0 1.598 PL 9.17 PF 1.2 ' 8 11.0 0.0 10.0 0.0 7.0 150 FTG TE PE 0.0 9 11.0 0.0 11.3 0.0 0.048 TL 26.17 PV Pipe: 20 -62.1 1.598 PL 10.00 PF 0.9 9 11.0 0.0 11.3 0.0 9.9 150 FTG - - -- PE 0.0 10 11.0 0.0 12.2 0.0 0.090 TL 10.00 PV Pipe: 21 -81.0 1.598 PL 15.25 PF 3.6 10 11.0 0.0 12.2 0.0 13.0 150 FTG E PE 0.0 111 11.0 5.6 15.8 22.2 0.147 TL 24.25 PV Pipe: 22 -103.2 1.598 PL 30.83 PF 23.7 111 11.0 5.6 15.8 22.2 16.5 150 FTG BE PE 0.0 12 11.0 0.0 39.5 0.0 0.231 TL 102.83 PV Pipe: 23 -217.2 1.598 PL 3.33 PF 11.3 12 11.0 0.0 39.5 0.0 34.8 150 FTG E PE 0.0 13 11.0 0.0 50.8 0.0 0.915 TL 12.33 PV • Pipe: 24 -217.2 2.003 PL 17.00 PF 18.3 13 11.0 0.0 50.8 0.0 22.1 150 FTG T3E PE 7.4 TR -6.0 0.0 76.4 0.0 0.304 TL 60.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 8/26/2009 C: \HASS FILES \TRIANGLE POINTE.SDF JOB TITLE: Triangle Pointe - Light Hazard - .10/973 Sq. Ft. PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) Pipe: 25 -217.2 6.357 PL 3.00 PF 0.0 TR -6.0 0.0 76.4 0.0 2.2 120 FTG E PE 1.3 BF1 -9.0 0.0 77.7 0.0 0.002 TL 21.00 PV Pipe: 26 FIXED PRESSURE LOSS DEVICE BF2 -9.0 0.0 83.7 0.0 6.0 psi, 217.2 gpm BF1 -9.0 0.0 77.7 0.0 Pipe: 27 -217.2 6.357 PL 2.00 PF 0.0 BF2 -9.0 0.0 83.7 0.0 2.2 120 FTG E PE 0.9 UG1 -11.0 0.0 84.6 0.0 0.002 TL 20.00 PV Pipe: 28 -217.3 6.280 PL 200.00 PF 0.4 UG1 -11.0 0.0 84.6 0.0 2.3 140 FTG T2EB PE -4.8 SOURCE 0.0 SRCE 80.3 (N /A) 0.001 TL 307.00 PV NOTES (HASS): (1) Calculations were performed by the HASS 8.0 computer program under license no. 3808132120 granted by HRS Systems, Inc. 208 South Public Square Petersburg, TN 37144 (2) The system has been calculated to provide an average imbalance at each node of 0.007 gpm and a maximum imbalance at any node of 0.192 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 34.8 ft /sec at pipe 23. • • • v o > W WATER SUPPLY ANALYSIS .. y .. 100.0 Static: 86.00 psi Resid: 75.00 psi Flow: 1313.0 gpm y co LEGEND t r i rn Available pressure H 1 85.21 psi @ 317.3 gpm 11 0 � Required pressure N 2 80.29 psi @ 317.3 gpm A. Source Supply Curve G 80.0 B. System Demand Curve A ro m U o ro • 7J G • H rI z E m x P 60.0 _ r ( R 4 K E y S to pc 3 S w N X U a K M v R a W E 40.0 __ n c M H ( ▪ Y n p • z s 'o ro J H r i w r u rim ) 2 0.0 m U) 1-1 • y M H fr > • z 0 r rn 0.0 B o H z H ro W (I 0 -14.7 I I I I I I I { 400 600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM) SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 8/26/2009 C: \HASS FILES \TRIANGLE POINTE.SDF JOB TITLE: Triangle Pointe - Light Hazard - .10/973 Sq. Ft. . WATER SUPPLY CURVE 96+ • 88+ * \0 \ \\ \\\\\\ \\\\\\ 80+ X \\\\\\ \\\\\\ * < -75.0 psi @ 1313 gpm Flow Test Point 72+ P 64+ R 1 E 1 S I S 56+ U 1 R 1 E 1 48+ ( I P S 1 I 40+ ) I 32+ 24+ 16+ LEGEND I X = Required Water Supply 80.29 psi @ 317.3 gpm 8+ 1 0 = Available Water Supply " 1 85.21 psi @ 317.3 gpm 1 „ 0 + + - + - - -+ + + + + + + + 400 600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM) F-i° 206 9 - ovo June 5, 2009 Sprinkler 54a • NIKI1NG MIRAGE® STANDARD AND TECHNICAL DATA QR CONCEALED PENDENT SPRINKLER VK462 AND HP • SPRINKLER VK463 K5.6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269- 945 -9501 Technical Services 877 - 384 -5464 Fax: 269- 818 -1680 Email: techsvcs @vikingcorp.com 1. DESCRIPTION Viking Mirage® Standard and Quick Response Concealed Pendent Sprinkler VK462 and goo HP Sprinkler VK463 are thermosensitive glass -bulb spray sprinklers designed for installa- tion on concealed pipe systems where the appearance of a smooth ceiling is desired immaide The sprinkler is pre - assembled with a threaded adapter for installation with a low-profile ^�' ---=y- cover assembly that provides up to '' /2" (12.7 mm) of vertical adjustment The two -piece design allows installation and testing of the sprinkler prior to installation of the cover plate The "push -on ", "thread-off' design of the concealed cover plate assembly allows easy installation of the cover plate after the system has been tested and the ceiling finish has 4*41. been applied The cover assembly can be removed and reinstalled, allowing temporary • - removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler. 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV FM Approval: Class 2015 NYC Approved: MEA 89 -92 -E, Volume 32 VdS Approved: Certificate G4080021 LPC Approved: Ref. No 096e/12 CE Certified: Standard EN 12259 -1, EC- certificates of conformity 0832 -CPD -2032 and 0786 -CPD -40249 Refer to the Approval Chart on page 54c and Design Criteria on page 54d for cULus Listing requirements that must be followed 3. TECHNICAL DATA Specifications: Available since 2006. Minimum Operating Pressure 7 psi (0.5 bar)* Viking Technical Data may be found on Maximum Working Pressure: Sprinkler VK463 is rated for use with water working pressures ranging from the minimum 7 psi (0.5 bar) up to The Viking Corporation's Web site at 250 psi (17.2 bar) for high - pressure systems. High - pressure (HP) http: /lwww.vikinggroupinc.com. sprinklers can be identified by locating "250" stamped on the deflec- The Web site may include a more recent tor. Sprinkler VK462 is rated to a maximum 175 psi (12 bar) wwp. edition of this Technical Data Page. Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A Patent No 4,831,870 Thread size* 1/2" (15 mm) NPT Nominal K- Factor: 5.6 U.S. (80.6 metnct) Glass -bulb fluid temperature rated to -65 °F ( -55 °C) Patents Pending "cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0 35 bar) tMetnc K- factor measurement shown is when pressure is measured in Bar When pressure is measured in kPa, divide the metnc K- factor shown by 10 0 Material Standards: Sprinkler Body. Brass UNS- C84400 Deflector Copper UNS- C19500 for Sprinkler VK462 Phosphor Bronze UNS- C51000 for Sprinkler VK463 Deflector Pins. Stainless Steel Alloy Bulb Glass, nominal 3 mm diameter Pip Cap and Insert Assembly. Copper UNS- C11000 and Stainless Steel UNS- S30400 Button: Brass UNS- C36000 Screws* 18 -8 Stainless Steel Belleville Spring Sealing Assembly Nickel Alloy, coated on both sides with Teflon Tape Yoke* Phosphor Bronze UNS- C51000 Cover Adapter. Cold Rolled Steel UNS- G10080. Finish Clear Chromate over Zinc Plating Form No. F_103005 Replaces page 54a -e, dated Feb. 6, 2009 (Added CE Approval for Sprinkler 13503 with cover 13504). Sprinkler 54b June 5, 2009 MIRAGE® STANDARD AND QR CONCEALED PENDENT TECHNICAL DATA SPRINKLER VK462 AND HP • F SPRINKLER VK463 K5.6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269- 945 -9501 Technical Services 877 - 384 -5464 Fax: 269 - 818 -1680 Email: techsvcs @vikingcorp.com Cover Assembly Materials: Cover. Copper UNS- C11000 Base. Brass UNS-C26000 or UNS- C26800 Springs: Nickel Alloy Solder Eutectic Ordering Information: (Also refer to the current Viking price list.) Viking Mirage® Standard and Quick Response Concealed Pendent Sprinklers and Cover Plate Assemblies must be ordered separately: Sprinkler: Base Part No. 13503A, 14697A, or HP Base Part No. 13667A Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number Temperature Suffix ( °F / °C): 155 ° /68° = B, 175 ° /79° = D, 200 ° /93 = E For example, sprinkler VK463 with a 155 °F /68 °C temperature rating = 13667AB Cover Plate Assembly: Base Part No. 13504 (2 -3/4" diameter), Base Part No 13642 (3 -5/16" diameter), or Base Part No 15394 (square cover plate, 3 -5/16" diameter) Specify finish and temperature rating of the cover plate assembly by first adding the appropriate suffix for the finish and then the appropriate suffix for the cover temperature rating to the base part number Finish Suffix Polished Chrome = F, Painted White = M- /SW1004, Painted Ivory = M- /SW1634, Painted Black = M- /SW1007 Temperature Suffix ( °F / °C): 135 ° /57° UL (139 ° /59 FM) = A, 165 ° /74° = C For example, cover 13504 with a Polished Chrome finish and a 165 °F/74 °C temperature rating = 13504FC Note: Square cover plate 15394 cULus Listing is for the 135 °F (57 °C) temperature rated cover plate only. Refer to the Approval Chart. Available Finishes And Temperature Ratings: Refer to Table 1 Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book ) Sprinkler Wrenches": A Heavy Duty Wrench Part No 14047W/B (available since 2006), or B. Head Cabinet Wrench Part No. 14031 "° (available since 2006) C. Optional Concealed Cover Plate Installer Tool Part No 14412 for cover 13504, or Part No 14867 for the large diameter cover (available since 2007) "Requires a W ratchet (not available from Viking). "'Optional for removal of the protective cap Ideal for sprinkler cabinets • Sprinkler Cabinet: Part No. 01731A, Capacity' five (5) sprinklers (available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards 5. OPERATION During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches. Continued heating of the exposed sprinkler causes the heat - sensitive liquid in the glass bulb to expand and the bulb to shatter, releasing the yoke, pip -cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking Sprinklers VK462 and VK463 are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly • June 5, 2009 Sprinkler 54c MIRAGE® STANDARD AND NIKING TECHNICAL DATA QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 K5.6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269- 945 -9501 Technical Services 877- 384 -5464 Fax: 269- 818 -1680 Email: techsvcs@vikingcorp.com • Sprinkler NPT Nominal Maximum Overall Length Listings and Approvals` Base SIN Thread K- Factor Water Working (Sprinkler (Refer also to Design Criteria on page 54d.) Part No.' ®Z ® ® metre Pressure Inches mm cULus° FM NYC' VdS LPCB Standard Response Applications 13503A VK462 ® ®m 80 6 175 psi (12 bar) 2 -3/16" 56 -- -- AY1, CZ1 — — 14697A VK462 ®®E3 80.6 175 psi (12 bar) 2 -3/16" 56 — — -- — AV2, BW2 AV2, BW2' Quick Response Applications 13503A VK462 ® ®lan 80.6 175 psi (12 bar) 2 -3/16" 56 AV1, BX1 — AV1, BW1 — — AY2, CZ2 14697A VK462 ®® 5.6 80 6 175 psi (12 bar) 2 -3/16" 56 AV1, BX1 -- AV1, BW1 — — — 13667A VK463 ®®s] 80 6 250 psi (17 2 bar)' 2 -3/16" 56 AV1, BX1 -- AV1, BW1 -- -- -- Cover Plate Assembly Temperature Ratings° U - 135 °F (57 °C) cULus Listed cover 13504'. 13642' (large diameter), or 15394' (square cover plate) FM Approved as Sprinkler Temperature Ratings 139 °F (59 °C) A - 155 °F (68 ° C) V - 135 °F (57 °C) cULus Listed cover 13504' or 13642' (large Finishes of the Cover Plate Assembly'° B 175 °F (79 ° C) and 200 °F diameter) 1 - Polished Chrome. Painted White. Painted (93 °C) W - 165 °F (74 °C) cover 13504' or 13642' (large diameter) Ivory, or Painted Black C 200 °F (93 °C) X - 165 °F (74 °C) cover 13504'. 13642' (large diameter), or 2 - Polished Chrome, Painted White 15394' (square cover plate) Y - 135 'F (57 °C) cover 13504' Z - 165 °F (74 °C) cover 13504' Footnotes ' Part number shown is the base part number. For complete part number, refer to current Viking pnce list schedule 2 Metric K -factor measurement shown is when pressure is measured in Bar When pressure is measured in kPa. divide the metric K- factor shown by 10.0. 'The Water Working Pressure rating is stamped on the deflector " This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for an additional approvals. 5 Listed by Underwriter's Laboratories for use in the U S and Canada ° Accepted for use, City of New York Department of Buildings, MEA Number 89 -92 -E, Vol 32. ' CE Certified, Standard EN 12259 -1, EC- certificate of conformity 0832 -CPD -2032. ' CE Certified, Standard EN 12259 -1, EC- certificate of conformity 0786 -CPD -40249 ° The 135/139 °F cover has an orange label The 165 °F cover has a white label ' finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors Listings and approvals apply for any paint manufacturer. Contact Viking for additional information NOTE. Custom colors are indicated on a label inside the cover assembly Refer to Figure 1 TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES - -i t i 'Y ' )✓�l V'E I t "'( ri3 '>r H i a c of s • t F lw / 1 f�S Y ''�Q°Sr i 7 o T . : i - � : i � .., 4 `7� � Vl r i - Q raV.44b`k l ?� }k rJ ll1 a Ordinary 155 °F (68 °C) 100 °F (38 °C) 135 °F (57 °C) Red 139 °F (59 °C) ) FM FM Intermediate 175 °F (79 °C) 150 °F (65 °C) 165 °F (74 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) 165 °F (74 °C) Green Cover Plate Finishes: Polished Chrome, Painted White, Painted Ivory, or Painted Black Footnotes ' The sprinkler temperature rating is stamped on the sprinkler deflector Based on NFPA -13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction Refer to specific installation standards. Sprinkler 54d June 5, 2009 MIRAGE® STANDARD AND TECHNICAL DATA QR CONCEALED PENDENT SPRINKLER VK462 AND HP • SPRINKLER VK463 K5.6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269- 945 -9501 Technical Services 877 - 384 -5464 Fax: 269- 818 -1680 Email: techsvcs @vikingcorp.com cULus Listing Reauirements; Mirage Standard and Quick Response Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed for installation in accordance with the latest edition of NFPA 13 for standard coverage pendent spray sprinklers as indicated below • For hazard occupancies up to and including Ordinary Hazard, Group II • Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13 Maximum spacing allowed is 15 ft (4.6 m) • Minimum spacing allowed is 6 ft. (1 8 m) unless baffles are installed in accordance with NFPA 13 • Minimum distance from walls is 4 in. (102 mm). • Maximum distance from walls shall be no more than one -half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall • The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed NOTE: Concealed sprinklers must be installed In neutral or negative pressure plenums only. FM Approval Reauirements; Mirage Concealed Pendent Sprinkler VK462 is FM Approved as a standard response standard spray sprinkler as indicated in the Approval Chart for hazard occupancies up to and including Ordinary Hazard, Group II For installation in accordance with the latest applicable FM Loss Prevention Data Sheets (including 2 -8N) and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing. and deflector distance below the ceiling NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page SR1 -3 or QR1 -3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordi- nances, and standards, whenever applicable. Q� \co O UST k LJ t � DO NOT PAINT Q Q 9� (--) O v- �O VIKING Identification of' Custom Paint Color: I i All custom color painted cover plates will have an identifying label affixed to the inside of the cover that indicates custom 3 -5/16" (84.1 mm) color and will have a representative sample (a paint dot) of the paint on the label. Figure 1: Identification of Custom Paint Color for Concealed Covers Figure 2: Square Cover Assembly 15394 June 5, 2009 Sprinkler 54e • MIRAGE® STANDARD AND NiiuNG TECHNICAL DATA QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 K5.6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269- 945 -9501 Technical Services 877 - 384 -5464 Fax: 269- 818 -1680 Email: techsvcs @vikingcorp.com loom Sprinkler -moni► Wrench i.'�'=— Flat Sprinkler 11` alLlI Frame diameter opening Arms � 'l/1f, 2 -1/4' <57.2 mm) „ is required In � I - the ceiling. _ - Sprinkler and — a,___ — me _ Adapter Assembly �i.� (Protective Cap is removed for lal installation - -use Wrench 14031**) Mr11411:7 =.- NEVER install the sprinkler i by applying the installation Sprinkler wrench across the frame arms. Wrh (Part enc No. DO NOT overtighten. 14047W/B Us only the designated is shown) + sprinkler wrench, Viking Part I Number 14047W/B or 14031. _ *gA 1/2' ratchet is required (not 1 DO NOT apply more than r _ ;=; available from Viking). 25 ft. lbs. of torquie. A leak tight seal should be achieved Step 2. Carefully press the by turning the sprinkler Step 1: Carefully slide the wrench upward and turn slightly clockwise 1 to 1 -1/2 turns wrench sideways around to ensure engagement with the beyond finger tight. the deflector and pins. sprinkler wrench flats. Figure 3: Sprinkler Installation and Correct Use of Wrenches 1/2' (15 mm) — NPT 2 -3/4' �' _ _ 2 - 1/4' — �� t .-_-_._—. 2 - 3/16' Ulm lli (70 mm) (57.2 mm) �!j (56 mm) Maximum Minimum 1::::::15 2 -3/4' (70 mm) or 3 - 5/16' (84 1 mm) Note: Upon sprinkler activation, the deflector descends . to approximately 13/16' (20.6 mm) below the sprinkler body. Figure 4: Sprinkler Dimensions and Cover Installation Bulletin 154 Rev F co Reliabld Model G4A Quick Response Concealed A . Automatic Sprinkler . m The Concealer UL Quick Response •.E: FM Standard Response • • Concealed Sprinkler With a � • ' . 1/2" (13mm) or 11/2" (38mm) Adjustment = r • : i r • Features � . ..- r 0 1. Cover plate attachment with / (13mm) - ` " assembly adjustment. . `�~ 2. Smooth aesthetic ceiling profile. :: • 3. Factory installed protective cap. -< 4. Available in brass, chrome or black , , f • plated and white painted finishes. : `. 5. Ordinary temperature rating. -4. - , 6. Multiple orifices for design flexibility .: s Approvals & Listings ''.�' 1. Underwriters Labortories, Inc. (UL)- • .m...` _ Quick Response The Model G4A Concealer° is designed for use where 2. Underwriters Laboratories of Canada (ULC} aesthetic appearance is important. Offices, hospitals, motels Quick Response and restaurants are but a few of the applications where it can be 3. Factory Mutual Research Corp. (FM)- used It is available in different orifice sizes allowing the designer Standard Response to optimize system performance, thereby achieving a very • efficient installation. • Light Hazard Occupanicies- The Model G4A Concealer' is a UL listed Quick Response No Limitations Concealed sprinkler intended for use in accordance with NFPA • Ordinary Hazard Occupancies 13. FM Approves this sprinkler as a standard response Groups 1 & 2 Wet Systems Only concealed sprinkler intended for use in accordance with FM Loss Prevention Data Sheet 2 -8N 4. NYC MEA 258 -93-E - Quick Response Product Description The Reliable Model G4A Concealer''uses a proven quick re- U.S. Patent number 4,880,063. sponse fusible element in a standard style sprinkler frame with a drop -down deflector This assembly is recessed into the ceiling Application and concealed by a flat cover plate assembly. The threaded The Reliable Model G4A engagement provides " (13mm) of cover adjustment The flat cover plate is attached to the skirt using either 135 °F (57 °C) or Concealer is the most versatile 165 °F (74 °C) ordinary temperature classification solder quick response concealed sprin- When the ceiling temperature rises, the solder holding the flat kler available. It provides the best cover plate melts, the flat cover plate released thus exposing form of fire protection while - the sprinkler inside to the rising ambient temperature. offering an attractive appearance - The subsequent fusing of the element opens the waterway and 1/2" (13mm) of cover adjust- i - and causes the deflector to distribute the water. Any secure ment for ease of installation. The — .. „ engagement between the cover plate and cup will assure that small diameter cover plate as- the drop -down deflector is properly located below the ceiling. sembly is easily attached and blends into the ceiling, concealing . the most dependable fire protec- tion available, an automatic sprinkler system. The Reliable Automatic Sprinkler Co., Inc. , 103 Fairview Park Drive, Elmsford, New York 10523 Installation Ordering Information Do not install the G4A Concealer in ceilings which have 1 Sprinkler Model 1 .1t a • positive pressure in the space above. 2 Nominal Orifice • Cut a 2 inch (67mm) diameter hole is cut in the ceding, the 3 Flat Cover Plate /, t- �• sprinkler is easily installed with the Model G4 Wrench. The Assembly Finish wrench has drive tangs which insert into the cup slots. 4. Inlet Type t • .. When installing a sprinkler the wrench is first positioned into i the sprinkler /cup assembly until the wrench tangs engage the drive slots in the top of the cup (there are two sets of Cover Plate Finishes • ff drive slots in the cup). The sprinkler is then tightened into : °w the pipe fitting. When inserting or removing the wrench from Standard Finishes "g P P 9 9 the sprinkler /cup assembly, care should be taken to prevent Bronze jr damage to the sprinkler. DO NOT WRENCH ON ANY Chrome OTHER PART OF THE SPRINKLER/CUP ASSEMBLY. White Paint Model G4 Sprinkler Install the cover plate by hand turning the cover in the Wrench clockwise direction until it is tight against the ceiling. Special Application A protective cap is provided to protect the drop -down sprinkler Finishes deflector from damage which could occur during construction Bright Brass i UL Listing Category before the cover plate is installed. The cap is factory installed Black Plating Sprinklers, Automatic and inside the sprinkler cup Remove cap to install sprinkler, then Black Paint Open re- install cap until the cover plate is installed. on White Quick Response Sprinkler Maintenance Satin Chrome UL Guide Number The Model G4A Concealer should be inspected quarterly Other finishes and colors are VNIV and the sprinkler system maintained in accordance with NFPA available on special order 25. Do not clean sprinklers with soap and water, ammonia or any Co nsult factory for details other cleaning fluids. Remove any sprinkler that has been Temperature Rating painted (other than factory applied) or damaged in any way A g stock of spare sprinklers should be maintained to allow quick classification Sprinkler Cover Max. Ambient replacement of damaged or operated sprinklers. Prior to Plate Temp. installation, sprinklers should be maintained in the original Ordinary 165'F/74 °C 135'F/57°C loo °F /38 °c cartons and packaging to minimize the potential for damage to sprinklers that would cause improper operation or non-operation Intermediate 212°F/ 100 °c 165'F/74 °C 150'F/66°C Technical Data Sprinkler Inlet Total Nominal Nominal K Factor Thread Approvals IdentS Sprinkler Adjustment Orifice US Metric (SIN) Non Adjustable 1/2" (13mm) 1/2" (15mm) 5 6 80 1/2" NPT (RY) I 1,2.3,4 R5415 Non Adjustable Y2" (13mm) 4" (11mm) 4 2 60 h "NPT (R1/2) 1,2,4 R5413 Non Adjustable 1/2" (13mm) %" (10mm) 2 8 40 1/2 "NPT (R' /2) 1,2.3.4 R5411 I Adjustable 11/2" (38mm) h" (15mm) 5 6 80 1" NPT Male or Female I 1,2 4 R5418 Adjustable 1'/2 (38mm) %f' (11mm) 4.2 60 1" NPT Male or Female I 1,2.4 R5413 . Adjustable I 11/2" (38mm) 4 " (10mm) 2 8 40 1" NPT Male or Female I 1,2,4 R5412 J V3'.,:... 57V9. -' - ;i ll �___ /---- Ii( Z - Q.C•iY. i ^ Ili T — 1 IIIIf ) - L._._)- -- 1 I I i I — I I I' : If -! -_ -. -.+- p:P. I f I im-. ,- r _ L. ...ti -::,:. �La - .0t: s. :4 I � I ,'- i; %�' -' I OJ e_d 7 _ :: 6 - _,� - :. - °� � s W , _ I ifs �4 w : 1 . I ,..:.,.„. 4 i r. ' I D , 1 -.e I----, • C ... 1 . ..,.. -. .inn u. '.+�.... J .. FIg.1 -1" NPT Non - Adjustable Inlet Fig 2 - 1" NPT Male - Adjustable Inlet Fig 3 - 1" NPT Female- Adjustable Inlet The equipment presented in this bulletin is to be Installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicaoie Products manufactured and distributed by Reliable have been protecting life and property for over 80 years. and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout :he united States. Canada and foreign countries Manufactured by ® Recycled The Reliable Automatic Sprinkler Co., Inc. Reliabit (800) 431-1588 Sales Offices (800) 848 -6051 Sales Fax Revison lines indicate updated or new data (914) 829 -2042 Corporate Offices won reliablesprinkler com Internet Address EG P.in.ec in USA 4i07 P/N 9999970150 Bulletin 136 Rev O CO ® Model Fl FR Model F1FR Recessed 5" Quick Response Sprinklers o Model Fl FR Sprinkler Types Standard Upright Standard Pendent ." .."t Conventional ,o_ ` . 07''° Vertical Sidewall y.; i • „t Horizontal Sidewall - _ 1 s - HSW 1 Deflector ' A .c Model Fl FR Recessed Sprinkler Types y �`” Recessed Pendent Upright Pendent Recessed Horizontal Sidewall - HSW 1 Deflector - T Listings & Approvals �• ?1 , , : . 1. Listed by Underwriters Laboratories, Inc. (UL) • 2. Listed by Underwriters' Laboratories of Canada (ULC) . 3. Certified by FM Approvals _ h 4. Loss Prevention Council (LPC, UK) ti f ` ., 5. NYC BS&A No. 587 -75 -SA '•-'' 3 / tr?4 = 6. Meets MIL- S -901C and MIL -STD 167 -1 `. - ...—.f. 7. Verband der Schadenversicherer (VdS, Germany) ; - r 8. NYC MEA 258 -93 -E UL Listing Category Vertical Sidewall Conventional Sprinklers, Automatic & Open Quick Response Sprinkler UL Guide Number . VNIV Patents: US Patent No. 6,374,920 Applies to aT � . " a F �\ t Model Fl FR Vertical Sidewall Sprinklers. : •,. 7 - Product Description Horizontal Sidewall Recessed Pendent Reliable Models F1FR and F1FR Recessed Sprinklers are HSW 1 Deflector (Model FP Shown) quick response sprinklers which combine the durability of a pands, forcing the bubble smaller and smaller as the liquid standard sprinkler with the attractive low profile of a decorative pressure increases Continued heating forces the liquid to sprinkler. push out against the bulb, causing the glass to shatter, The Models F1FR and Fl FR Recessed automatic sprinklers opening the waterway and allowing the deflector to distnb- utilize a 3.0 mm frangible glass bulb. These sprinklers have ute the discharging water demonstrated response times in laboratory tests which are five to ten times faster than standard response sprinklers This Application quick response enables the Model F1FR and F1FR Recessed Quick response sprinklers are used in fixed fire protec- sprinklers to apply water to a fire much faster than standard Lion systems Wet, Dry, Deluge or Preaction Care must be sprinklers of the same temperature rating. exercised that the orifice size, temperature rating, deflector The glass bulb consists of an accurately controlled amount style and sprinkler type are in accordance with the latest of special fluid hermetically sealed inside a precisely manu- published standards of the National Fire Protection Asso- factured glass capsule. This glass bulb is specially con- ciation or the approving Authority Having Jurisdiction. structed to provide fast thermal response. The balance of Quick response sprinklers are intended for installation as parts are made of brass, copper and beryllium nickel specified in NFPA 13, FM Global Loss Prevention Data At normal temperatures, the glass bulb contains the fluid Sheet 2 -8N or other applicable standards Quick response in both the liquid and vapor phases. The vapor phase can sprinklers and standard response sprinklers should not be be seen as a small bubble. As heat is applied, the liquid ex- intermixed. The Reliable Automatic Sprinkler Co., Inc. 103 Fairview Park Drive, Elmsford, New York 10523 Model Fl FR Quick Response Upright, Pendent & Conventional Sprinklers Installation Wrench: Model D Sprinkler Wrench Installation Data: K Factor I I Sprinkler Identification Sprinkler Approval Nur__ IN S Sprinkler Type mbe (_) US Metric Height Organization SSU I SSP Standard - Upright (SSU) and Pendent (SSP) Deflectors Marked to Indicate Position }," (15mm) Standard Onfice with y," NPT (R7) Thread 5 6 80 2 2" (56mm) 1,2,3,4.5.6,7 R3625 R3615 1 / „' (20mm) Large Onfice with j;” NPT (R3 ) Thread 8 0 115 2 3" (58mm) I 12.3,4,7.8 R3622` I R3612 y„" (17mm) Small Orifice with y," NPT (RX) Thread 4 2 60 2 2" (56mm) I 1,2.8 i R3623"' R3613 %" (l Omm) Small Orifice with }," NPT (RX) Thread 2 8 40 2 2" (56mm) I 1,2,8 I R3621 R3611 10mm Orifice XLH with R Thread I 4 2 60 • 56mm i 4,6,7 R3624 R3614 Conventional- Install in Upright or Pendent Position 10mm Orrfice XLH with R% Thread 4 2 I 60 I 56mm — I R3674 15mm Standard Orifice with X" NPT (Ry) Thread 5 6 80 I 56mm 4,6,7 R3675 20mm Large Orifice with ?<' NPT (R3/4)Thread 8 0 115 I 58mm 4,7 R3672 (1) Polyester coated upright UL and ULC listed corrosion resistant r A! 01,74 ��i a'; Tt t' 9 r d � .Y • . ,- ` '''.ii' , Upright Pendent Conventional Model F1 FR Quick Response Recessed Pendent Sprinkler Installation Wrench: Model GFR1 Sprinkler Wrench Installation Data: Nominal Thread K Factor Sprinkler Approval Sprinkler Identification . Orifice Size US I Metric Height Organizations Number (SIN) I _.2 ° (15mm) X" NPT (R'h) 5 6 I 80 2 2' (56mm) I 1.2.3.4.5.7.8 I R3615 I ' 7 4 2 ' (20mm) 3/ NPT (R /) 8 0 I 115 2 3" (58mm) 1,2,3,8 R3612 7 (11mm) }2 " NPT (R1/2) 42 60 22" (56mm) 1,2,8 R3613 /" (10mm) 7" NPT (R1/2) 2 8 40 2 2" (56mm) 1,2,8 R3611 lomm R 4 2 60 56mm 4,7 R3614 (') Refer to escutcheon data table for approvals and dimensions 2 , /,' NOL[ Du I `— 2 5/6' Om [66 7mmj —� ' p i 2mm I-'O!- IN CEILING : 15/16' Du 2 5 /la' DO (55 7.,,.mi - [49 2mm) Cu? q _- - - - ___ L ,- - -- _ T Z , - / ; /2 6EDUCEP . T - TURV COLLAR — —r � r i/2 .EDUCE. ~ y uNBL PC.; Uu:S SPR:.V /LCO Q[.MCN BOSS ' w _ -'— I \ 1 / =_:_ 1 I L= J �•" '�r ' • : c l I AWU$ H �.�. I I r CC41.VL JIY[NSKiN C ILIA ./A ♦ � �. 1 _..1,,_ _ j' J TO FACE OF CEILING �, - Ill , 1 , I� - " 227 /32 - DLA I , D'UST ✓E!:i •_ ___� ' '722' ,I -----. , l ,_ 6F00[ 1 1 :JF I (I) REFER TO FI & F2 ESCUTCHEON NIA TABLE FOR APPROVALS AND D:YENYLNS (1) REFER 70 FP ESCUTC - EON DATA TABLE FOR A?P AND DI.UENSiONS 2. , . 4. Model Fl FR Quick Response Vertical Sidewall Sprinkler Installation Wrench: Model D Sprinkler Wrench ' Installation Position: Upright or Pendent Approval Type: Light Hazard Occupancy Installation Data: K Factor Sprinkler Nominal Thread Sprinkler Approval Orifice Size US Metric I Height Organizations Identification Number (SIN) ' /z" I ' /z" NPT (R1/2) 5 6 80 i 2 2" (56mm) 1 2, 3.6 .8 R3685 15mm 1/2" NPT (R'/) 5 6 80 1 2 2" (56mm) 4 In t" LPC Approval is for Pendent position only Deflector to Ceiling -• ; - . Orientation Dimension (Min. - Max.) . `, Upright 4" - 12" (102mm - 305mm) ` ' Pendent 6" - 12" (152rnm - 305mm) Vertical Sidewall US Patent No. 6,374,920 Model F1 FR Quick Response Horizontal Sidewall Sprinkler Deflector: HSW 1 Installation Wrench: Model D Sprinkler Wrench Installation Data: Approval Organizations 1 • K Factor and Type of Approval Sprinkler 1 Nominal Thread Sprinkler I Identification Orifice Size US Metric Length Light Ordinary Number (SIN) Hazard Hazard 1 X (15mm) }," NPT(R' /z) 5 6 80 2,63" (67mm) 1,2,3.5,8 1,2.5,8 I R3635 NOTE: UL. ULC and MEA Listing permits use with Fl or F2 recessed escutcheon FM Approvals do not permit recessed usage 4 `i1 ■ L r • . J (:,.A'.74;‘,.1;:-!.-1-. l r ck ,', 1 Horizontal Sidewall ; - . - - f : t;} , t : ;, . , _ . 1'ilv:,. _ / - _ r _ i :/ DE=EP TO _iC :J-C EON o .: i.:5:_ : F OR z..POVAL r.._ J' ,` 3. Installation Quick response sprinklers are intended for installation as tie vacuuming Remove any sprinkler which has been specified in NFPA 13, FM Global Loss Prevention Data Sheet painted (other than factory applied) or damaged in any • 2-8N or other applicable standards. Quick response sprin- way A stock of spare sprinklers should be maintained to klers and standard response sprinklers should not be inter- allow quick replacement of damaged or operated sprin- mixed. klers. Prior to installation, sprinklers should be maintained The Model F1FR Recessed Quick Response Spnnklers are to in the original cartons and packaging until used to mini - be installed as shown The Model Fl or F2 Escutcheons illus- mize the potential for damage to sprinklers that would trated are the only recessed escutcheons to be used with the cause improper operation or non - operation. Model Fl FR Sprinklers. The use of any other recessed escutch- Sprinkler T eon will void all approvals and negate all warranties. p Types When installing Model F1 FR Spnnklers, use the Model D Spnn- Standard Upright Her Wrench. When installing Model Fl FR Recessed Pendent or Standard Pendent Sidewall Sprinklers, use the Model GFR1 Sprinkler Wrench. Any Conventional other type of wrench may damage these sprinklers. Sidewall (Vertical, Horizontal HSW1) Glass bulb sprinklers have orange bulb protectors to minimize Recessed Pendent bulb damage during shipping, handling and installation RE- Recessed Horizontal Sidewall HSW1 MOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR ARE PROTECTION. Re- Finishes (2) moval of the protectors before this time may leave the bulb vul- Standard Finishes nerable to damage. FIASCO wrenches are designed to install Sprinkler I Escutcheon spnnklers when covers are in place. REMOVE PROTECTORS Bronze Brass BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS Chrome Plated Chrome Plated tat TO REMOVE THE PROTECTORS. White Polyester Coated White Painted tat Temperature Ratings Special Application Finishes Sprinkler Sprinkler Escutcheon Classification Temperature Max. Ambient Bulb Temp. Color Bright Brass Bright Brass °C °F Black Plated Black Plated Ordinary 57 135 100°F (38°C) Orange Ordinary 68 155 100°F (38 Red Black Paint Black Paint Intermediate 79 175 150°F (66'C) Yellow Off White Off White Intermediate 93 200 150°F(66'C) Green Satin Chrome Satin Chrome tit 1 41 2 86 225°F (107'C) Blue High (1) Other finishes and colors are available on special order (t) Not available for recessed sprinklers Consult the factory for details Escutcheon Data 121 FM Approvals is limited to bronze and brass, chrome or black plated finishes only raced Fdflr19 131 FP Push - on/Thread -off escutcheon Escutcheon Approvals Adjustnvant Dimension to Ceding or (4) UL and ULC listed corrosion resistance Mcdel VVall n SIN numbers R3621, R3622, R3623, R3625 Max Recess (38 1mm) MG.' ' Note: For %' orifice pendent FM approved white F1 1,2,4,8 Min Recess %" (5mm -24mm) polyester coated and UL approved white polyester • (19 1mm) corrosion resistant sprinklers refer to Bulletin 014. 1 / Max Recess (38 1mm) ?!e " - ' l;b " Ordering Information F2 1,2,3ft',4,5,7,8 Min Recess ' % (5mm -17mm) g Specify: (24mm) 1. Sprinkler Model FP 1 2 Max Re- ' A " 1 /2" ( 38 . 1mm) cessed (11mm) 2. Sprinkler Type Push-on" 6 3 Orifice Size Thread-off Min Recessed (24mm) m) 1" (25 4mm) 4 Deflector Type No Dimensional Figure for FP 5. Temperature Rating (1) Horizontal Sidewall is not FM approved in the reccesed configuration 6. Sprinkler Finish Maintenance 7. Escutcheon Type The Models F1FR and F1FR Recessed Sprinklers 8. Escutcheon Finish (where applicable) should be inspected quarterly and the sprinkler system maintained in accordance with NFPA 25 Do not clean Note: When Model F1FR Recessed sprinklers are sprinklers with soap and water, ammonia or any other ordered, the sprinklers and escutcheons are packaged cleaning fluids. Remove dust by using a soft brush or gen- separately Tne equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of me National Fire Protection Association. Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable Products manufactured and distributed by Reliable have been protecting life and property for over 80 years. and are installed and serviced by the most highly qualified and reputa- ble sprinkler contractors located throughout the United States, Canada and foreign countries Manufactured by • The Reliable Automatic Sprinkler Co., Inc. ® a yC! flI (800)831 -1088 Sales Offices (800)848 Sales Fax Corporate Offices Revision. Imes ndicate updated or nev+data (914)829 2042 - wmv rehaolospnnkier.com Internet Address EG Pnntea n u s 2 0609 PiN9999970027