Specifications PATRIOT FIRE PROTECTION, INC. RECEIVED
4708 NE MINNEHAHA STREET
VANCOUVER, WA 98 661 AUG 2 8 2009
CITY OF TIGARD
BUILDING DIVISION
HYDRAULIC CALCULATIONS FA5.2U0 Q'
FOR ? v 'vvv /
/3333 / 48 Pkwy
TRIANGLE POINTE
13333 SW 68TH PKWY
TIGARD, OREGON 97223
FILE: TRIANGLE POINTE.SDF
DATE: 8/26/2009
- DESIGN DATA -
OCCUPANCY CLASSIFICATION: LIGHT HAZARD
DENSITY: .10 GPM
AREA OF APPLICATION: 973 SQ. FT. MINIMUM
COVERAGE PER SPRINKLER: 225 SQ. FT. MAXIMUM
NUMBER OF SPRINKLERS CALCULATED: 12 SPRINKLERS
•
TOTAL SPRINKLER WATER FLOW REQUIRED: 217.3 GPM
TOTAL WATER REQUIRED (including hose): 317.3 GPM
FLOW AND PRESSURE (@ BOR): 217.3 GPM @ 83.7 PSI
SPRINKLER ORIFICE SIZE: 1/2 INCH
NAME OF CONTRACTOR: PATRIOT FIRE PROTECTION, INC.
DESIGN /LAYOUT BY: JEFF COLLINS
AUTHORITY HAVING JURISDICTION: CITY OF TIGARD
CONTRACTOR CERTIFICATION NUMBER: 70822
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 3808132120)
HRS SYSTEMS, INC.
ATLANTA, GA
•
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 8/26/2009 C: \HASS FILES \TRIANGLE POINTE.SDF
JOB TITLE: Triangle Pointe - Light Hazard - .10/973 Sq. Ft.
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SOURCE 86.0 75.0 1313.0 85.2 317.3 80.3
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 317.3 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 217.3 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
SOURCE 0.0 SOURCE 80.3 217.3
101 11.0 K= 5.60 15.5 22.0
102 11.0 K= 5.60 11.9 19.3
103 11.0 K= 5.60 7.7 15.5
104 11.0 K= 5.60 7.4 15.2
105 11.0 K= 5.60 9.0 16.8
106 11.0 K= 5.60 8.9 16.7
107 11.0 K= 5.60 9.6 17.4
• 108 11.0 K= 5.60 9.3 17.1
109 11.0 K= 5.60 10.5 18.2
110 11.0 K= 5.60 11.4 18.9
111 11.0 K= 5.60 15.8 22.2
112 11.0 K= 5.60 10.3 18.0
1 11.0 - - - - 16.5 - - -
2 11.0 - - - - 12.7 - - -
3 11.0 - - - - 10.3 - - -
3A 11.0 - - - - 8.5 - - -
4 11.0 - - - - 9.9 - - -
5 11.0 - - - - 9.6 - - -
6 11.0 - - - - 9.6 - - -
8 11.0 - - - - 10.0 - - -
9 11.0 - - - - 11.3 - - -
10 11.0 - - - - 12.2 - - -
12 11.0 - - - - 39.5 - - -
13 11.0 - - - - 50.8 - - -
TR -6.0 - - - - 76.4 - - -
BF1 -9.0 - - - - 77.7 - - -
BF2 -9.0 - - - - 83.7 - - -
UG1 -11.0 - - - - 84.6 - - -
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 8/26/2009 C: \HASS FILES \TRIANGLE POINTE.SDF
JOB TITLE: Triangle Pointe - Light Hazard - .10/973 Sq. Ft.
. PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL /FT (PSI)
Pipe: 1 -22.0 1.101 PL 1.00 PF 1.1
101 11.0 5.6 15.5 22.0 7.4 150 FTG TE PE 0.0
1 11.0 0.0 16.5 0.0 0.081 TL 13.00 PV
Pipe: 2 -19.3 1.101 PL 1.00 PF 0.8
102 11.0 5.6 11.9 19.3 6.5 150 FTG TE PE 0.0
2 11.0 0.0 12.7 0.0 0.064 TL 13.00 PV
Pipe: 3 -15.5 1.101 PL 5.50 PF 0.8
103 11.0 5.6 7.7 15.5 5.2 150 FTG 2E PE 0.0
3A 11.0 0.0 8.5 0.0 0.042 TL 19.50 PV
Pipe: 4 -15.2 1.101 PL 7.50 PF 1.1
104 11.0 5.6 7.4 15.2 5.1 150 FTG T2E PE 0.0
3A 11.0 0.0 8.5 0.0 0.041 TL 26.50 PV
Pipe: 5 -16.8 1.101 PL 1.00 PF 0.6
105 11.0 5.6 9.0 16.8 5.6 150 FTG TE PE 0.0
5 11.0 0.0 9.6 0.0 0.049 TL 13.00 PV
Pipe: 6 -16.7 1.101 PL 1.00 PF 0.6
106 11.0 5.6 8.9 16.7 5.6 150 FTG TE PE 0.0
6 11.0 0.0 9.6 0.0 0.049 TL 13.00 PV
Pipe: 7 -17.1 1.101 PL 1.50 PF 0.7
108 11.0 5.6 9.3 17.1 5.8 150 FTG TE PE 0.0
8 11.0 0.0 10.0 0.0 0.051 TL 13.50 PV
Pipe: 8 -18.2 1.101 PL 1.50 PF 0.8
109 11.0 5.6 10.5 18.2 6.1 150 FTG TE PE 0.0
9 11.0 0.0 11.3 0.0 0.057 TL 13.50 PV
Pipe: 9 -18.9 1.101 PL 1.50 PF 0.8
110 11.0 5.6 11.4 18.9 6.4 150 FTG TE PE 0.0
10 11.0 0.0 12.2 0.0 0.061 TL 13.50 PV
Pipe: 10 114.0 1.598 PL 19.83 PF 23.0
12 11.0 0.0 39.5 0.0 18.2 150 FTG 7E PE 0.0
1 11.0 0.0 16.5 0.0 0.277 TL 82.83 PV
Pipe: 11 92.0 1.598 PL 11.58 PF 3.8
1 11.0 0.0 16.5 0.0 14.7 150 FTG E PE 0.0
2 11.0 0.0 12.7 0.0 0.187 TL 20.58 PV
Pipe: 12 72.7 1.598 PL 11.67 PF 2.4
2 11.0 0.0 12.7 0.0 11.6 150 FTG T PE 0.0
. 3 11.0 0.0 10.3 0.0 0.121 TL 19.67 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 8/26/2009 C: \HASS FILES \TRIANGLE POINTE.SDF
JOB TITLE: Triangle Pointe - Light Hazard - .10/973 Sq. Ft.
. PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL /FT (PSI)
Pipe: 13 -30.7 1.101 PL 7.08 PF 1.8
3A 11.0 0.0 8.5 0.0 10.4 150 FTG T PE 0.0
3 11.0 0.0 10.3 0.0 0.151 TL 12.08 PV
Pipe: 14 42.0 1.598 PL 0.50 PF 0.0
3 11.0 0.0 10.3 0.0 6.7 150 FTG - - -- PE 0.0
112 11.0 5.6 10.3 18.0 0.044 TL 0.50 PV
Pipe: 14A 24.0 1.598 PL 17.00 PF 0.4
112 11.0 5.6 10.3 18.0 3.8 150 FTG T PE 0.0
4 11.0 0.0 9.9 0.0 0.016 TL 25.00 PV
Pipe: 15 24.0 1.598 PL 19.17 PF 0.3
4 11.0 0.0 9.9 0.0 3.8 150 FTG - - -- PE 0.0
5 11.0 0.0 9.6 0.0 0.016 TL 19.17 PV
Pipe: 16 7.2 1.598 PL 9.33 PF 0.0
5 11.0 0.0 9.6 0.0 1.2 150 FTG E PE 0.0
6 11.0 0.0 9.6 0.0 0.002 TL 18.33 PV
Pipe: 17 -9.5 1.598 PL 9.25 PF 0.1
6 11.0 0.0 9.6 0.0 1.5 150 FTG E PE 0.0
107 11.0 5.6 9.6 17.4 0.003 TL 18.25 PV
Pipe: 18 -26.9 1.598 PL 12.75 PF 0.4
107 11.0 5.6 9.6 17.4 4.3 150 FTG E PE 0.0
8 11.0 0.0 10.0 0.0 0.019 TL 21.75 PV
Pipe: 19 -44.0 1.598 PL 9.17 PF 1.2
' 8 11.0 0.0 10.0 0.0 7.0 150 FTG TE PE 0.0
9 11.0 0.0 11.3 0.0 0.048 TL 26.17 PV
Pipe: 20 -62.1 1.598 PL 10.00 PF 0.9
9 11.0 0.0 11.3 0.0 9.9 150 FTG - - -- PE 0.0
10 11.0 0.0 12.2 0.0 0.090 TL 10.00 PV
Pipe: 21 -81.0 1.598 PL 15.25 PF 3.6
10 11.0 0.0 12.2 0.0 13.0 150 FTG E PE 0.0
111 11.0 5.6 15.8 22.2 0.147 TL 24.25 PV
Pipe: 22 -103.2 1.598 PL 30.83 PF 23.7
111 11.0 5.6 15.8 22.2 16.5 150 FTG BE PE 0.0
12 11.0 0.0 39.5 0.0 0.231 TL 102.83 PV
Pipe: 23 -217.2 1.598 PL 3.33 PF 11.3
12 11.0 0.0 39.5 0.0 34.8 150 FTG E PE 0.0
13 11.0 0.0 50.8 0.0 0.915 TL 12.33 PV
• Pipe: 24 -217.2 2.003 PL 17.00 PF 18.3
13 11.0 0.0 50.8 0.0 22.1 150 FTG T3E PE 7.4
TR -6.0 0.0 76.4 0.0 0.304 TL 60.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 8/26/2009 C: \HASS FILES \TRIANGLE POINTE.SDF
JOB TITLE: Triangle Pointe - Light Hazard - .10/973 Sq. Ft.
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL /FT (PSI)
Pipe: 25 -217.2 6.357 PL 3.00 PF 0.0
TR -6.0 0.0 76.4 0.0 2.2 120 FTG E PE 1.3
BF1 -9.0 0.0 77.7 0.0 0.002 TL 21.00 PV
Pipe: 26 FIXED PRESSURE LOSS DEVICE
BF2 -9.0 0.0 83.7 0.0 6.0 psi, 217.2 gpm
BF1 -9.0 0.0 77.7 0.0
Pipe: 27 -217.2 6.357 PL 2.00 PF 0.0
BF2 -9.0 0.0 83.7 0.0 2.2 120 FTG E PE 0.9
UG1 -11.0 0.0 84.6 0.0 0.002 TL 20.00 PV
Pipe: 28 -217.3 6.280 PL 200.00 PF 0.4
UG1 -11.0 0.0 84.6 0.0 2.3 140 FTG T2EB PE -4.8
SOURCE 0.0 SRCE 80.3 (N /A) 0.001 TL 307.00 PV
NOTES (HASS):
(1) Calculations were performed by the HASS 8.0 computer program
under license no. 3808132120 granted by
HRS Systems, Inc.
208 South Public Square
Petersburg, TN 37144
(2) The system has been calculated to provide an average
imbalance at each node of 0.007 gpm and a maximum
imbalance at any node of 0.192 gpm.
(3) Total pressure at each node is used in balancing the system.
Maximum water velocity is 34.8 ft /sec at pipe 23.
•
•
• v
o >
W
WATER SUPPLY ANALYSIS ..
y ..
100.0 Static: 86.00 psi Resid: 75.00 psi Flow: 1313.0 gpm y co
LEGEND t r i
rn
Available pressure
H
1 85.21 psi @ 317.3 gpm 11 0
� Required pressure N
2 80.29 psi @ 317.3 gpm
A. Source Supply Curve
G 80.0 B. System Demand Curve
A ro m
U o ro
•
7J
G • H
rI z
E m x
P 60.0 _ r (
R 4 K
E y
S to
pc 3
S w
N X
U a K
M v
R a W
E 40.0 __ n c
M H
( ▪ Y n
p • z
s 'o ro
J H r
i w r u
rim
) 2 0.0 m U) 1-1
• y
M H
fr >
• z
0
r
rn
0.0 B o
H
z
H ro
W
(I 0
-14.7 I I I I I I I {
400 600 800 1000 1200 1400 1600 1800 2000
FLOW (GPM)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7
DATE: 8/26/2009 C: \HASS FILES \TRIANGLE POINTE.SDF
JOB TITLE: Triangle Pointe - Light Hazard - .10/973 Sq. Ft.
. WATER SUPPLY CURVE
96+
•
88+
* \0 \ \\
\\\\\\
\\\\\\
80+ X \\\\\\
\\\\\\
* < -75.0 psi @ 1313 gpm
Flow Test Point
72+
P 64+
R 1
E 1
S I
S 56+
U 1
R 1
E 1
48+
( I
P
S 1
I 40+
) I
32+
24+
16+ LEGEND
I X = Required Water Supply
80.29 psi @ 317.3 gpm
8+
1 0 = Available Water Supply "
1 85.21 psi @ 317.3 gpm
1 „
0 + + - + - - -+ + + + + + + +
400 600 800 1000 1200 1400 1600 1800 2000
FLOW (GPM)
F-i° 206 9 - ovo
June 5, 2009 Sprinkler 54a
•
NIKI1NG MIRAGE® STANDARD AND
TECHNICAL DATA QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
• SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269- 945 -9501 Technical Services 877 - 384 -5464 Fax: 269- 818 -1680 Email: techsvcs @vikingcorp.com
1. DESCRIPTION
Viking Mirage® Standard and Quick Response Concealed Pendent Sprinkler VK462 and goo
HP Sprinkler VK463 are thermosensitive glass -bulb spray sprinklers designed for installa-
tion on concealed pipe systems where the appearance of a smooth ceiling is desired immaide
The sprinkler is pre - assembled with a threaded adapter for installation with a low-profile
^�' ---=y-
cover assembly that provides up to '' /2" (12.7 mm) of vertical adjustment The two -piece
design allows installation and testing of the sprinkler prior to installation of the cover plate
The "push -on ", "thread-off' design of the concealed cover plate assembly allows easy
installation of the cover plate after the system has been tested and the ceiling finish has 4*41.
been applied The cover assembly can be removed and reinstalled, allowing temporary • -
removal of ceiling panels without taking the sprinkler system out of service or removing
the sprinkler.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approval: Class 2015
NYC Approved: MEA 89 -92 -E, Volume 32
VdS Approved: Certificate G4080021
LPC Approved: Ref. No 096e/12
CE Certified: Standard EN 12259 -1, EC- certificates of conformity 0832 -CPD -2032 and 0786 -CPD -40249
Refer to the Approval Chart on page 54c and Design Criteria on page 54d for cULus Listing requirements that must be followed
3. TECHNICAL DATA
Specifications:
Available since 2006.
Minimum Operating Pressure 7 psi (0.5 bar)* Viking Technical Data may be found on
Maximum Working Pressure: Sprinkler VK463 is rated for use with water
working pressures ranging from the minimum 7 psi (0.5 bar) up to The Viking Corporation's Web site at
250 psi (17.2 bar) for high - pressure systems. High - pressure (HP) http: /lwww.vikinggroupinc.com.
sprinklers can be identified by locating "250" stamped on the deflec- The Web site may include a more recent
tor. Sprinkler VK462 is rated to a maximum 175 psi (12 bar) wwp. edition of this Technical Data Page.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A Patent No 4,831,870
Thread size* 1/2" (15 mm) NPT
Nominal K- Factor: 5.6 U.S. (80.6 metnct)
Glass -bulb fluid temperature rated to -65 °F ( -55 °C)
Patents Pending
"cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0 35 bar)
tMetnc K- factor measurement shown is when pressure is measured in Bar When pressure is measured in kPa, divide the metnc K- factor shown by 10 0
Material Standards:
Sprinkler Body. Brass UNS- C84400
Deflector Copper UNS- C19500 for Sprinkler VK462
Phosphor Bronze UNS- C51000 for Sprinkler VK463
Deflector Pins. Stainless Steel Alloy
Bulb Glass, nominal 3 mm diameter
Pip Cap and Insert Assembly. Copper UNS- C11000 and Stainless Steel UNS- S30400
Button: Brass UNS- C36000
Screws* 18 -8 Stainless Steel
Belleville Spring Sealing Assembly Nickel Alloy, coated on both sides with Teflon Tape
Yoke* Phosphor Bronze UNS- C51000
Cover Adapter. Cold Rolled Steel UNS- G10080. Finish Clear Chromate over Zinc Plating
Form No. F_103005 Replaces page 54a -e, dated Feb. 6, 2009 (Added CE
Approval for Sprinkler 13503 with cover 13504).
Sprinkler 54b June 5, 2009
MIRAGE® STANDARD AND
QR CONCEALED PENDENT
TECHNICAL DATA SPRINKLER VK462 AND HP
• F SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269- 945 -9501 Technical Services 877 - 384 -5464 Fax: 269 - 818 -1680 Email: techsvcs @vikingcorp.com
Cover Assembly Materials:
Cover. Copper UNS- C11000
Base. Brass UNS-C26000 or UNS- C26800
Springs: Nickel Alloy
Solder Eutectic
Ordering Information: (Also refer to the current Viking price list.)
Viking Mirage® Standard and Quick Response Concealed Pendent Sprinklers and Cover Plate Assemblies must be ordered separately:
Sprinkler: Base Part No. 13503A, 14697A, or HP Base Part No. 13667A
Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number
Temperature Suffix ( °F / °C): 155 ° /68° = B, 175 ° /79° = D, 200 ° /93 = E
For example, sprinkler VK463 with a 155 °F /68 °C temperature rating = 13667AB
Cover Plate Assembly: Base Part No. 13504 (2 -3/4" diameter), Base Part No 13642 (3 -5/16" diameter), or Base Part No
15394 (square cover plate, 3 -5/16" diameter)
Specify finish and temperature rating of the cover plate assembly by first adding the appropriate suffix for the finish and then the
appropriate suffix for the cover temperature rating to the base part number
Finish Suffix Polished Chrome = F, Painted White = M- /SW1004, Painted Ivory = M- /SW1634, Painted Black = M- /SW1007
Temperature Suffix ( °F / °C): 135 ° /57° UL (139 ° /59 FM) = A, 165 ° /74° = C
For example, cover 13504 with a Polished Chrome finish and a 165 °F/74 °C temperature rating = 13504FC
Note: Square cover plate 15394 cULus Listing is for the 135 °F (57 °C) temperature rated cover plate only. Refer to the Approval Chart.
Available Finishes And Temperature Ratings:
Refer to Table 1
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book )
Sprinkler Wrenches":
A Heavy Duty Wrench Part No 14047W/B (available since 2006), or
B. Head Cabinet Wrench Part No. 14031 "° (available since 2006)
C. Optional Concealed Cover Plate Installer Tool Part No 14412 for cover 13504, or Part No 14867 for the large diameter cover
(available since 2007)
"Requires a W ratchet (not available from Viking). "'Optional for removal of the protective cap Ideal for sprinkler cabinets
• Sprinkler Cabinet: Part No. 01731A, Capacity' five (5) sprinklers (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards
5. OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches.
Continued heating of the exposed sprinkler causes the heat - sensitive liquid in the glass bulb to expand and the bulb to shatter,
releasing the yoke, pip -cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector,
forming a uniform spray pattern to extinguish or control the fire
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinklers VK462 and VK463 are available through a network of domestic and international distributors See The Viking
Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly
•
June 5, 2009 Sprinkler 54c
MIRAGE® STANDARD AND
NIKING TECHNICAL DATA QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269- 945 -9501 Technical Services 877- 384 -5464 Fax: 269- 818 -1680 Email: techsvcs@vikingcorp.com
•
Sprinkler NPT Nominal Maximum Overall Length Listings and Approvals`
Base SIN Thread K- Factor Water Working (Sprinkler (Refer also to Design Criteria on page 54d.)
Part No.' ®Z ® ® metre Pressure Inches mm cULus° FM NYC' VdS LPCB
Standard Response Applications
13503A VK462 ® ®m 80 6 175 psi (12 bar) 2 -3/16" 56 -- -- AY1, CZ1 — —
14697A VK462 ®®E3 80.6 175 psi (12 bar) 2 -3/16" 56 — — -- — AV2, BW2 AV2, BW2'
Quick Response Applications
13503A VK462 ® ®lan 80.6 175 psi (12 bar) 2 -3/16" 56 AV1, BX1 — AV1, BW1 — — AY2, CZ2
14697A VK462 ®® 5.6 80 6 175 psi (12 bar) 2 -3/16" 56 AV1, BX1 -- AV1, BW1 — — —
13667A VK463 ®®s] 80 6 250 psi (17 2 bar)' 2 -3/16" 56 AV1, BX1 -- AV1, BW1 -- -- --
Cover Plate Assembly Temperature Ratings°
U - 135 °F (57 °C) cULus Listed cover 13504'. 13642' (large
diameter), or 15394' (square cover plate) FM Approved as
Sprinkler Temperature Ratings 139 °F (59 °C)
A - 155 °F (68 ° C) V - 135 °F (57 °C) cULus Listed cover 13504' or 13642' (large Finishes of the Cover Plate Assembly'°
B 175 °F (79 ° C) and 200 °F diameter) 1 - Polished Chrome. Painted White. Painted
(93 °C) W - 165 °F (74 °C) cover 13504' or 13642' (large diameter) Ivory, or Painted Black
C 200 °F (93 °C) X - 165 °F (74 °C) cover 13504'. 13642' (large diameter), or 2 - Polished Chrome, Painted White
15394' (square cover plate)
Y - 135 'F (57 °C) cover 13504'
Z - 165 °F (74 °C) cover 13504'
Footnotes
' Part number shown is the base part number. For complete part number, refer to current Viking pnce list schedule
2 Metric K -factor measurement shown is when pressure is measured in Bar When pressure is measured in kPa. divide the metric K- factor shown by 10.0.
'The Water Working Pressure rating is stamped on the deflector
" This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for an
additional approvals.
5 Listed by Underwriter's Laboratories for use in the U S and Canada
° Accepted for use, City of New York Department of Buildings, MEA Number 89 -92 -E, Vol 32.
' CE Certified, Standard EN 12259 -1, EC- certificate of conformity 0832 -CPD -2032.
' CE Certified, Standard EN 12259 -1, EC- certificate of conformity 0786 -CPD -40249
° The 135/139 °F cover has an orange label The 165 °F cover has a white label
' finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information
NOTE. Custom colors are indicated on a label inside the cover assembly Refer to Figure 1
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
- -i t i 'Y ' )✓�l V'E I t "'( ri3 '>r H i a c of s • t F lw / 1 f�S Y ''�Q°Sr i 7 o T .
: i - � : i � .., 4 `7� � Vl r i - Q raV.44b`k l ?� }k rJ ll1 a
Ordinary 155 °F (68 °C) 100 °F (38 °C) 135 °F (57 °C) Red
139 °F (59 °C) ) FM FM
Intermediate 175 °F (79 °C) 150 °F (65 °C) 165 °F (74 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) 165 °F (74 °C) Green
Cover Plate Finishes: Polished Chrome, Painted White, Painted Ivory, or Painted Black
Footnotes
' The sprinkler temperature rating is stamped on the sprinkler deflector
Based on NFPA -13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction Refer to specific installation standards.
Sprinkler 54d June 5, 2009
MIRAGE® STANDARD AND
TECHNICAL DATA QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
• SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269- 945 -9501 Technical Services 877 - 384 -5464 Fax: 269- 818 -1680 Email: techsvcs @vikingcorp.com
cULus Listing Reauirements;
Mirage Standard and Quick Response Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed for installation in accordance with the latest
edition of NFPA 13 for standard coverage pendent spray sprinklers as indicated below
• For hazard occupancies up to and including Ordinary Hazard, Group II
• Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13 Maximum spacing allowed is 15 ft (4.6 m)
• Minimum spacing allowed is 6 ft. (1 8 m) unless baffles are installed in accordance with NFPA 13
• Minimum distance from walls is 4 in. (102 mm).
• Maximum distance from walls shall be no more than one -half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall
• The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed
NOTE: Concealed sprinklers must be installed In neutral or negative pressure plenums only.
FM Approval Reauirements; Mirage Concealed Pendent Sprinkler VK462 is FM Approved as a standard response standard spray sprinkler as
indicated in the Approval Chart for hazard occupancies up to and including Ordinary Hazard, Group II For installation in accordance with the latest
applicable FM Loss Prevention Data Sheets (including 2 -8N) and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical
Advisory Bulletins contain guidelines relating to, but not limited to minimum water supply requirements, hydraulic design, ceiling slope and obstructions,
minimum and maximum allowable spacing. and deflector distance below the ceiling
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
SR1 -3 or QR1 -3 for general care, installation, and maintenance information. Viking sprinklers are to be installed
in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global,
LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordi-
nances, and standards, whenever applicable.
Q� \co O UST k LJ t �
DO NOT PAINT
Q Q 9�
(--)
O
v- �O
VIKING
Identification of' Custom Paint Color: I i
All custom color painted cover plates will
have an identifying label affixed to the
inside of the cover that indicates custom 3 -5/16" (84.1 mm)
color and will have a representative sample
(a paint dot) of the paint on the label.
Figure 1: Identification of Custom Paint Color for Concealed Covers Figure 2: Square Cover Assembly 15394
June 5, 2009 Sprinkler 54e
• MIRAGE® STANDARD AND NiiuNG
TECHNICAL DATA QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269- 945 -9501 Technical Services 877 - 384 -5464 Fax: 269- 818 -1680 Email: techsvcs @vikingcorp.com
loom Sprinkler
-moni► Wrench
i.'�'=— Flat
Sprinkler 11` alLlI
Frame
diameter opening Arms � 'l/1f,
2 -1/4' <57.2 mm)
„
is required In � I - the ceiling. _ - Sprinkler and — a,___ — me
_ Adapter Assembly
�i.� (Protective Cap
is removed for lal
installation - -use
Wrench 14031**) Mr11411:7 =.-
NEVER install the sprinkler
i by applying the installation
Sprinkler wrench across the frame arms.
Wrh
(Part enc No. DO NOT overtighten.
14047W/B Us only the designated
is shown) + sprinkler wrench, Viking Part
I Number 14047W/B or 14031.
_ *gA 1/2' ratchet
is required (not 1 DO NOT apply more than
r _ ;=; available from Viking). 25 ft. lbs. of torquie. A leak
tight seal should be achieved
Step 2. Carefully press the by turning the sprinkler
Step 1: Carefully slide the wrench upward and turn slightly clockwise 1 to 1 -1/2 turns
wrench sideways around to ensure engagement with the beyond finger tight.
the deflector and pins. sprinkler wrench flats.
Figure 3: Sprinkler Installation and Correct Use of Wrenches
1/2'
(15 mm) —
NPT
2 -3/4' �' _ _ 2 - 1/4' — ��
t .-_-_._—.
2 - 3/16' Ulm lli (70 mm) (57.2 mm) �!j
(56 mm) Maximum Minimum
1::::::15 2 -3/4' (70 mm) or
3 - 5/16' (84 1 mm)
Note: Upon sprinkler activation, the deflector descends
. to approximately 13/16' (20.6 mm) below the sprinkler body.
Figure 4: Sprinkler Dimensions and Cover Installation
Bulletin 154 Rev F
co
Reliabld Model G4A
Quick Response
Concealed A
. Automatic Sprinkler .
m
The Concealer
UL Quick Response •.E:
FM Standard Response •
• Concealed Sprinkler With a � • ' .
1/2" (13mm) or 11/2" (38mm) Adjustment = r •
: i r
•
Features � . ..- r 0
1. Cover plate attachment with / (13mm) - ` "
assembly adjustment. . `�~
2. Smooth aesthetic ceiling profile. :: •
3. Factory installed protective cap. -<
4. Available in brass, chrome or black , , f •
plated and white painted finishes. : `.
5. Ordinary temperature rating. -4. - ,
6. Multiple orifices for design flexibility .: s
Approvals & Listings ''.�'
1. Underwriters Labortories, Inc. (UL)- • .m...` _
Quick Response The Model G4A Concealer° is designed for use where
2. Underwriters Laboratories of Canada (ULC} aesthetic appearance is important. Offices, hospitals, motels
Quick Response and restaurants are but a few of the applications where it can be
3. Factory Mutual Research Corp. (FM)- used It is available in different orifice sizes allowing the designer
Standard Response to optimize system performance, thereby achieving a very
• efficient installation.
• Light Hazard Occupanicies- The Model G4A Concealer' is a UL listed Quick Response
No Limitations Concealed sprinkler intended for use in accordance with NFPA
• Ordinary Hazard Occupancies 13. FM Approves this sprinkler as a standard response
Groups 1 & 2 Wet Systems Only concealed sprinkler intended for use in accordance with FM
Loss Prevention Data Sheet 2 -8N
4. NYC MEA 258 -93-E - Quick Response
Product Description
The Reliable Model G4A Concealer''uses a proven quick re-
U.S. Patent number 4,880,063. sponse fusible element in a standard style sprinkler frame with a
drop -down deflector This assembly is recessed into the ceiling
Application and concealed by a flat cover plate assembly. The threaded
The Reliable Model G4A engagement provides " (13mm) of cover adjustment The flat
cover plate is attached to the skirt using either 135 °F (57 °C) or
Concealer is the most versatile 165 °F (74 °C) ordinary temperature classification solder
quick response concealed sprin- When the ceiling temperature rises, the solder holding the flat
kler available. It provides the best cover plate melts, the flat cover plate released thus exposing
form of fire protection while - the sprinkler inside to the rising ambient temperature.
offering an attractive appearance - The subsequent fusing of the element opens the waterway
and 1/2" (13mm) of cover adjust- i - and causes the deflector to distribute the water. Any secure
ment for ease of installation. The — .. „ engagement between the cover plate and cup will assure that
small diameter cover plate as- the drop -down deflector is properly located below the ceiling.
sembly is easily attached and
blends into the ceiling, concealing
. the most dependable fire protec-
tion available, an automatic
sprinkler system.
The Reliable Automatic Sprinkler Co., Inc. , 103 Fairview Park Drive, Elmsford, New York 10523
Installation Ordering Information
Do not install the G4A Concealer in ceilings which have 1 Sprinkler Model 1 .1t a
• positive pressure in the space above. 2 Nominal Orifice
• Cut a 2 inch (67mm) diameter hole is cut in the ceding, the 3 Flat Cover Plate /, t- �•
sprinkler is easily installed with the Model G4 Wrench. The Assembly Finish
wrench has drive tangs which insert into the cup slots. 4. Inlet Type t • .. When installing a sprinkler the wrench is first positioned into i
the sprinkler /cup assembly until the wrench tangs engage
the drive slots in the top of the cup (there are two sets of Cover Plate Finishes • ff
drive slots in the cup). The sprinkler is then tightened into : °w
the pipe fitting. When inserting or removing the wrench from Standard Finishes "g
P P 9 9
the sprinkler /cup assembly, care should be taken to prevent Bronze jr
damage to the sprinkler. DO NOT WRENCH ON ANY Chrome
OTHER PART OF THE SPRINKLER/CUP ASSEMBLY. White Paint Model G4 Sprinkler
Install the cover plate by hand turning the cover in the Wrench
clockwise direction until it is tight against the ceiling. Special Application
A protective cap is provided to protect the drop -down sprinkler Finishes
deflector from damage which could occur during construction Bright Brass i UL Listing Category
before the cover plate is installed. The cap is factory installed Black Plating Sprinklers, Automatic and
inside the sprinkler cup Remove cap to install sprinkler, then Black Paint Open
re- install cap until the cover plate is installed. on White Quick Response Sprinkler
Maintenance Satin Chrome UL Guide Number
The Model G4A Concealer should be inspected quarterly Other finishes and colors are VNIV
and the sprinkler system maintained in accordance with NFPA available on special order
25. Do not clean sprinklers with soap and water, ammonia or any Co nsult factory for details
other cleaning fluids. Remove any sprinkler that has been Temperature Rating
painted (other than factory applied) or damaged in any way A g
stock of spare sprinklers should be maintained to allow quick classification Sprinkler Cover Max. Ambient
replacement of damaged or operated sprinklers. Prior to Plate Temp.
installation, sprinklers should be maintained in the original Ordinary 165'F/74 °C 135'F/57°C loo °F /38 °c
cartons and packaging to minimize the potential for damage to
sprinklers that would cause improper operation or non-operation Intermediate 212°F/ 100 °c 165'F/74 °C 150'F/66°C
Technical Data
Sprinkler Inlet Total Nominal Nominal K Factor Thread Approvals IdentS Sprinkler
Adjustment Orifice US Metric (SIN)
Non Adjustable 1/2" (13mm) 1/2" (15mm) 5 6 80 1/2" NPT (RY) I 1,2.3,4 R5415
Non Adjustable Y2" (13mm) 4" (11mm) 4 2 60 h "NPT (R1/2) 1,2,4 R5413
Non Adjustable 1/2" (13mm) %" (10mm) 2 8 40 1/2 "NPT (R' /2) 1,2.3.4 R5411 I
Adjustable 11/2" (38mm) h" (15mm) 5 6 80 1" NPT Male or Female I 1,2 4 R5418
Adjustable 1'/2 (38mm) %f' (11mm) 4.2 60 1" NPT Male or Female I 1,2.4 R5413
. Adjustable I 11/2" (38mm) 4 " (10mm) 2 8 40 1" NPT Male or Female I 1,2,4 R5412 J
V3'.,:... 57V9.
-' - ;i ll �___
/---- Ii( Z
- Q.C•iY. i ^ Ili T — 1 IIIIf ) - L._._)-
--
1 I I i I — I I I' :
If -! -_ -.
-.+-
p:P. I f I im-. ,-
r _ L. ...ti -::,:.
�La - .0t: s. :4 I � I ,'- i; %�' -' I
OJ e_d 7
_ :: 6 - _,� - :. - °� �
s W , _ I ifs �4 w
: 1 . I
,..:.,.„. 4 i r. ' I D , 1
-.e I----, • C ... 1 .
..,.. -. .inn u.
'.+�.... J ..
FIg.1 -1" NPT Non - Adjustable Inlet Fig 2 - 1" NPT Male - Adjustable Inlet Fig 3 - 1" NPT Female- Adjustable Inlet
The equipment presented in this bulletin is to be Installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicaoie
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years. and are installed and serviced by the most highly qualified
and reputable sprinkler contractors located throughout :he united States. Canada and foreign countries
Manufactured by ® Recycled
The Reliable Automatic Sprinkler Co., Inc.
Reliabit (800) 431-1588 Sales Offices
(800) 848 -6051 Sales Fax Revison lines indicate updated or new data
(914) 829 -2042 Corporate Offices
won reliablesprinkler com Internet Address EG P.in.ec in USA 4i07 P/N 9999970150
Bulletin 136 Rev O CO
® Model Fl FR
Model F1FR Recessed 5"
Quick Response
Sprinklers o
Model Fl FR Sprinkler Types
Standard Upright
Standard Pendent ." .."t
Conventional ,o_ ` . 07''°
Vertical Sidewall y.;
i • „t
Horizontal Sidewall - _ 1 s
- HSW 1 Deflector ' A .c
Model Fl FR Recessed Sprinkler Types y �`”
Recessed Pendent Upright Pendent
Recessed Horizontal Sidewall
- HSW 1 Deflector - T
Listings & Approvals �• ?1 , , : .
1. Listed by Underwriters Laboratories, Inc. (UL)
• 2. Listed by Underwriters' Laboratories of Canada (ULC) .
3. Certified by FM Approvals _ h
4. Loss Prevention Council (LPC, UK) ti f ` .,
5. NYC BS&A No. 587 -75 -SA '•-'' 3 / tr?4 =
6. Meets MIL- S -901C and MIL -STD 167 -1 `. - ...—.f.
7. Verband der Schadenversicherer (VdS, Germany) ; - r
8. NYC MEA 258 -93 -E
UL Listing Category Vertical Sidewall Conventional
Sprinklers, Automatic & Open
Quick Response Sprinkler
UL Guide Number .
VNIV
Patents: US Patent No. 6,374,920 Applies to aT � . " a F �\ t
Model Fl FR Vertical Sidewall Sprinklers. : •,. 7 -
Product Description Horizontal Sidewall Recessed Pendent
Reliable Models F1FR and F1FR Recessed Sprinklers are HSW 1 Deflector (Model FP Shown)
quick response sprinklers which combine the durability of a pands, forcing the bubble smaller and smaller as the liquid
standard sprinkler with the attractive low profile of a decorative pressure increases Continued heating forces the liquid to
sprinkler. push out against the bulb, causing the glass to shatter,
The Models F1FR and Fl FR Recessed automatic sprinklers opening the waterway and allowing the deflector to distnb-
utilize a 3.0 mm frangible glass bulb. These sprinklers have ute the discharging water
demonstrated response times in laboratory tests which are
five to ten times faster than standard response sprinklers This Application
quick response enables the Model F1FR and F1FR Recessed Quick response sprinklers are used in fixed fire protec-
sprinklers to apply water to a fire much faster than standard Lion systems Wet, Dry, Deluge or Preaction Care must be
sprinklers of the same temperature rating. exercised that the orifice size, temperature rating, deflector
The glass bulb consists of an accurately controlled amount style and sprinkler type are in accordance with the latest
of special fluid hermetically sealed inside a precisely manu- published standards of the National Fire Protection Asso-
factured glass capsule. This glass bulb is specially con- ciation or the approving Authority Having Jurisdiction.
structed to provide fast thermal response. The balance of Quick response sprinklers are intended for installation as
parts are made of brass, copper and beryllium nickel specified in NFPA 13, FM Global Loss Prevention Data
At normal temperatures, the glass bulb contains the fluid Sheet 2 -8N or other applicable standards Quick response
in both the liquid and vapor phases. The vapor phase can sprinklers and standard response sprinklers should not be
be seen as a small bubble. As heat is applied, the liquid ex- intermixed.
The Reliable Automatic Sprinkler Co., Inc. 103 Fairview Park Drive, Elmsford, New York 10523
Model Fl FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
K Factor I I Sprinkler Identification
Sprinkler Approval Nur__ IN S
Sprinkler Type mbe (_)
US Metric Height Organization
SSU I SSP
Standard - Upright (SSU) and Pendent (SSP) Deflectors Marked to Indicate Position
}," (15mm) Standard Onfice with y," NPT (R7) Thread 5 6 80 2 2" (56mm) 1,2,3,4.5.6,7 R3625 R3615 1
/ „' (20mm) Large Onfice with j;” NPT (R3 ) Thread 8 0 115 2 3" (58mm) I 12.3,4,7.8 R3622` I R3612
y„" (17mm) Small Orifice with y," NPT (RX) Thread 4 2 60 2 2" (56mm) I 1,2.8 i R3623"' R3613
%" (l Omm) Small Orifice with }," NPT (RX) Thread 2 8 40 2 2" (56mm) I 1,2,8 I R3621 R3611
10mm Orifice XLH with R Thread I 4 2 60 • 56mm i 4,6,7 R3624 R3614
Conventional- Install in Upright or Pendent Position
10mm Orrfice XLH with R% Thread 4 2 I 60 I 56mm — I R3674
15mm Standard Orifice with X" NPT (Ry) Thread 5 6 80 I 56mm 4,6,7 R3675
20mm Large Orifice with ?<' NPT (R3/4)Thread 8 0 115 I 58mm 4,7 R3672
(1) Polyester coated upright UL and ULC listed corrosion resistant
r A! 01,74 ��i
a'; Tt t'
9 r d � .Y • . ,- ` '''.ii'
,
Upright Pendent Conventional
Model F1 FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model GFR1 Sprinkler Wrench
Installation Data:
Nominal Thread K Factor Sprinkler Approval Sprinkler Identification
. Orifice Size US I Metric Height Organizations Number (SIN) I
_.2 ° (15mm) X" NPT (R'h) 5 6 I 80 2 2' (56mm) I 1.2.3.4.5.7.8 I R3615 I
' 7 4 2 ' (20mm) 3/ NPT (R /) 8 0 I 115 2 3" (58mm) 1,2,3,8 R3612
7 (11mm) }2 " NPT (R1/2) 42 60 22" (56mm) 1,2,8 R3613
/" (10mm) 7" NPT (R1/2) 2 8 40 2 2" (56mm) 1,2,8 R3611
lomm R 4 2 60 56mm 4,7 R3614
(') Refer to escutcheon data table for approvals and dimensions
2 , /,' NOL[ Du I `— 2 5/6' Om [66 7mmj —�
' p i 2mm I-'O!- IN CEILING
: 15/16' Du 2 5 /la' DO (55 7.,,.mi -
[49 2mm) Cu?
q _- - - - ___ L ,- - -- _ T Z
, - / ; /2 6EDUCEP .
T -
TURV COLLAR — —r � r i/2 .EDUCE.
~ y
uNBL PC.; Uu:S SPR:.V /LCO
Q[.MCN BOSS '
w
_ -'— I \ 1 / =_:_ 1
I
L= J
�•" '�r ' • : c l I
AWU$ H �.�. I I r CC41.VL JIY[NSKiN C ILIA ./A
♦ � �. 1 _..1,,_ _ j' J TO FACE OF CEILING �, - Ill , 1 , I�
- " 227 /32 - DLA I , D'UST ✓E!:i •_ ___�
' '722' ,I -----. , l ,_
6F00[ 1 1 :JF
I
(I) REFER TO FI & F2 ESCUTCHEON NIA TABLE FOR APPROVALS AND D:YENYLNS (1) REFER 70 FP ESCUTC - EON DATA TABLE FOR A?P AND DI.UENSiONS
2.
, .
4.
Model Fl FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
' Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
K Factor Sprinkler
Nominal Thread Sprinkler Approval
Orifice Size US Metric I Height Organizations Identification
Number (SIN)
' /z" I ' /z" NPT (R1/2) 5 6 80 i 2 2" (56mm) 1 2, 3.6 .8
R3685
15mm 1/2" NPT (R'/) 5 6 80 1 2 2" (56mm) 4 In
t" LPC Approval is for Pendent position only
Deflector to Ceiling
-• ; - . Orientation Dimension (Min. - Max.)
.
`, Upright 4" - 12" (102mm - 305mm)
` ' Pendent 6" - 12" (152rnm - 305mm)
Vertical Sidewall
US Patent No. 6,374,920
Model F1 FR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Approval Organizations 1
• K Factor and Type of Approval Sprinkler 1
Nominal Thread Sprinkler I Identification
Orifice Size US Metric Length Light Ordinary Number (SIN)
Hazard Hazard 1
X (15mm) }," NPT(R' /z) 5 6 80 2,63" (67mm) 1,2,3.5,8 1,2.5,8 I R3635
NOTE: UL. ULC and MEA Listing permits use with Fl or F2 recessed escutcheon FM Approvals do not permit recessed usage
4 `i1 ■
L
r •
.
J (:,.A'.74;‘,.1;:-!.-1-. l r ck ,',
1
Horizontal Sidewall ; - . - - f : t;} , t : ;, . , _
. 1'ilv:,. _ /
- _ r _
i :/ DE=EP TO _iC :J-C EON o .: i.:5:_ : F OR z..POVAL r.._ J' ,`
3.
Installation
Quick response sprinklers are intended for installation as tie vacuuming Remove any sprinkler which has been
specified in NFPA 13, FM Global Loss Prevention Data Sheet painted (other than factory applied) or damaged in any
• 2-8N or other applicable standards. Quick response sprin- way A stock of spare sprinklers should be maintained to
klers and standard response sprinklers should not be inter- allow quick replacement of damaged or operated sprin-
mixed. klers. Prior to installation, sprinklers should be maintained
The Model F1FR Recessed Quick Response Spnnklers are to in the original cartons and packaging until used to mini -
be installed as shown The Model Fl or F2 Escutcheons illus- mize the potential for damage to sprinklers that would
trated are the only recessed escutcheons to be used with the cause improper operation or non - operation.
Model Fl FR Sprinklers. The use of any other recessed escutch- Sprinkler T
eon will void all approvals and negate all warranties. p Types
When installing Model F1 FR Spnnklers, use the Model D Spnn- Standard Upright
Her Wrench. When installing Model Fl FR Recessed Pendent or Standard Pendent
Sidewall Sprinklers, use the Model GFR1 Sprinkler Wrench. Any Conventional
other type of wrench may damage these sprinklers. Sidewall (Vertical, Horizontal HSW1)
Glass bulb sprinklers have orange bulb protectors to minimize Recessed Pendent
bulb damage during shipping, handling and installation RE- Recessed Horizontal Sidewall HSW1
MOVE THIS PROTECTION AT THE TIME THE SPRINKLER
SYSTEM IS PLACED IN SERVICE FOR ARE PROTECTION. Re- Finishes (2)
moval of the protectors before this time may leave the bulb vul- Standard Finishes
nerable to damage. FIASCO wrenches are designed to install Sprinkler I Escutcheon
spnnklers when covers are in place. REMOVE PROTECTORS Bronze Brass
BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS Chrome Plated Chrome Plated tat
TO REMOVE THE PROTECTORS. White Polyester Coated White Painted tat
Temperature Ratings Special Application Finishes
Sprinkler Sprinkler Escutcheon
Classification Temperature Max. Ambient Bulb
Temp. Color Bright Brass Bright Brass
°C °F
Black Plated Black Plated
Ordinary 57 135 100°F (38°C) Orange
Ordinary 68 155 100°F (38 Red Black Paint Black Paint
Intermediate 79 175 150°F (66'C) Yellow Off White Off White
Intermediate 93 200 150°F(66'C) Green Satin Chrome Satin Chrome
tit 1 41 2 86 225°F (107'C) Blue
High (1) Other finishes and colors are available on special order
(t) Not available for recessed sprinklers Consult the factory for details
Escutcheon Data 121 FM Approvals is limited to bronze and brass, chrome or black
plated finishes only
raced Fdflr19 131 FP Push - on/Thread -off escutcheon
Escutcheon
Approvals Adjustnvant Dimension to Ceding or (4) UL and ULC listed corrosion resistance
Mcdel VVall n SIN numbers R3621, R3622, R3623, R3625
Max Recess (38 1mm) MG.' ' Note: For %' orifice pendent FM approved white
F1 1,2,4,8 Min Recess %" (5mm -24mm) polyester coated and UL approved white polyester
• (19 1mm) corrosion resistant sprinklers refer to Bulletin 014.
1 /
Max Recess (38 1mm) ?!e " - ' l;b " Ordering Information
F2 1,2,3ft',4,5,7,8 Min Recess ' % (5mm -17mm) g
Specify:
(24mm) 1. Sprinkler Model
FP 1 2 Max Re- ' A " 1 /2" ( 38 . 1mm)
cessed (11mm) 2. Sprinkler Type
Push-on" 6 3 Orifice Size
Thread-off Min Recessed (24mm) m) 1" (25 4mm)
4 Deflector Type
No Dimensional Figure for FP 5. Temperature Rating
(1) Horizontal Sidewall is not FM approved in the reccesed configuration 6. Sprinkler Finish
Maintenance 7. Escutcheon Type
The Models F1FR and F1FR Recessed Sprinklers 8. Escutcheon Finish (where applicable)
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25 Do not clean Note: When Model F1FR Recessed sprinklers are
sprinklers with soap and water, ammonia or any other ordered, the sprinklers and escutcheons are packaged
cleaning fluids. Remove dust by using a soft brush or gen- separately
Tne equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of me National Fire Protection Association. Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years. and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throughout the United States, Canada and foreign countries