Plans v Bulletin 136 Rev.L
lite
�• ® Model F1 FR c
Model F1FR Recessed
Imumilmommommininumo Quick Response
Sprinklers
I Model Fl FR Sprinlder Types
Standard Upright
Standard Pendent
Conventional a 11 , Z =
Vertical Sidewall o ° ir',p
Horizontal Sidewall z`
- HSW 1 r r o..""
1
Def lector L1J 0
V j , :
� � •4
Model Fl FR Recessed •, 'n :. ; ,
Recessed Pendent Ts
Recessed Horizontal Sided r
- HSW 1 Deflector
Upright Pendent
Listings & Approvals
1. Listed by Underwriters Laboratories, Inc. (UL)
2. Listed by Underwriters' Laboratories of Canada (ULC) ' _'`
3. Certified by FM Approvals
provals , > —
4. Loss Prevention Council (LPC, UK)
\
5. NYC BS&A No. 587 -75 -SA r y'
6. Meets MIL- S -901C and MIL -STD 167 -1
7. Verband der Schadenversicherer (VdS Germ . � ..7.
t - - ?
8. NYC MEA 258 -93-E
UL Listing Category - f : • ,
Sprinklers, Automatic & Open
Quick Response Sprinkler
UL Guide Number Vertical Sidewall Conventional
I VNIV
•
Product Description
Reliable Models F1FR and F1FR Recessed Sprinklers are
quick response sprinklers which combine the durability of a " • standard sprinkler with the attractive low profile of a decorative l�ii �' "' . -f
sprinkler. �} v � !' a - z '
•
The Models Fl FR and Fl FR Recessed l� i= �..
utilize a 3.0 mm frangible glass bulb. Theses p �be er rs have
demonstrated response times in laboratory tests which are five
to ten times faster than standard response sprinklers. This
quick response enables the Model F1FR and F1FR Recessed Horizontal Deflector �� HSW 1 Deflector Recessed Pendent
sprinklers to
apply water to a fire much faster than standard
sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount Application
os
pecial fluid hermetically sealed inside a precisely manufac- Quick response sprinklers are used in fixed ar us t be
tured glass tion systems: Wet, D mt
g capsule. This glass bulb is specially constructed to exercised that the orifice size, temperature rating, deflector
provide fast thermal response. The balance of parts are made
•' of brass, copper and beryllium nickel. style and sprinkler type are in accordance with the latest
At normal temperatures, the glass bulb contains the fluid published standards of the National Fire Protection Asso-
in both the liquid and vapor phases. The vapor phase can ciation or the approving Authority Having Jurisdiction.
be seen as a small bubble. As heat is applied, the liquid ex- Quick response sprinklers are intended for installation as
pands, forcing the bubble smaller and smaller as the liquid specified in NFPA 13. Quick response sprinklers and stan-
pressure increases. Continued heating forces the liquid to card response sprinklers should not be intermixed.
push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
The temperature rating of the sprinkler is identified by the
color of the glass bulb.
The Reliable Automatic Sprinkler Co., Inc. 525 North MacQuesten Parkway, Mount Vernon, New York 10552
Model Fl FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench .
Installation Data:
Standard - Upri (SSU) an Pendent (SSP) K Factor Sprinkler Approval Sprinkler
Deflectors Marked to Indicate Position US Metric Height Organization SSU SSP
y" (15mm) Standard Orifice with y" NPT R Thread 5.6 80 2.2" (56rrvn) 12,3,4,5,6,7 R3625 R3615
, 4 8.0 115 2.3" (58, nu) 1,2,3,4,7,8 R3622 R3612
4.2 60 2.54 "(65mm) 1,2,8 R3623 R3613
tom_ \-• - - AI Illiiiiiiiimms 2.8 40 2.54 "(65mm) 1,2,8 R3621 R3611
4.2 60 56.1mm 4,6,7 R3624 R3614
Conventional - Install in Upright or Pendent Position
10mm Orifice XLH with R% Thread 4.2 60 56.1 mm — R3674
15mm Standard Orifice with y" NPT (Ry) Thread 5.6 80 56.1mm 4,6,7 R3675
20mm Large Orifice with 3 A" NPT (R 8.0 115 _ 58.4mm 4,7 R3672
t
A s 1 . . .. X -. l't
[ lip, i'
�� l C i i a 1 ' �
Upright Pendent Upright Conventional
Model Fl FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model RC1 Sprinkler Wrench
Installation Data:
Sprinkler Nominal Thread
K Factor P Approval Sprinkler Identification
Orifice Size US Metric Height Organizations Number (SIN)
. Yz" (15mm) y" NPT (R') 5.6 80 2.2" (56mrn) 1,2,3,4,5,7,8 R3615
Mk. , -T 8.0 115 2.3" (58mm) 1,2,3 R3612
......, 1 . 1 1 11 11Piiiii. 4.2 60 2.54" (65mm) 1,2,8 R3613
2.8 40 2.54" (65mm) 1,2,8 R3611
10mm RY 4.2 60 56.1mm 4,7 R3614
(1) Refer to escutcheon data table for approvals and dimensions.
�_ 2 ,/4 ( Ot
(57.2 r4
-..— , 10/r6 Du
(4tlmm(
r �a
,- It 1 /2 - INDUCER
- -
maw COUNT
win non
I I
Ui
�, 1 r
r i I L.1 14L, Oa Or ma 1Rr'�
iliidni r A co,.. O. } 1
J »n, - Ot
(72.24144 - 126,1;010
(,) TOTER TO 1SCV,CTOON TLTA TABLE MR APPROVALS AND m msaa.
2.
Model Fl FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
. 1 Approval Type: Light Hazard Occupancy
Installation Data:
Nominal Orifice Thread Size K Factor
+ US Metric Sprinkler Height Organizations Sprl Number (SIN) lion
• 1/2" '/z" NPT (R'/s) 5.6 80 2.2" (56mm) 1, 2, 3, 6, 8
15mm Y2" NPT (R1/2) 5.6 80 (1) R3685
2.2" (56mm) 4
(1) LPC Approval is for Pendent position only.
Orientation Deflector to Ceiling
' ., Dimension (Min. - Max.)
1 ' ` .: Upright -
4" - 12" (102mm - 305mm)
t q Pendent 6" - 12" (152mm - 305mm)
il
jtl• ,.- r-.i
4 --;
Vertical Sidewall
Model Fl FR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
K Factor Approval Sprinkler
and
TYPe at
Organizations
Nominal Thread -� Sprinkler A'pro Identification
• Orifice Size US Metric Length Light Ordinary Number
Hazard Hazard (SIN) -
I y" (15mm) y" NPT(R' /z) 5.6 80 I 2.63^ (67mm) 1,2,3,5,8 1,2,5,8 _ R3635
NOTE: UL and ULC Listing permits use with F1 or F2 recessed escutcheon.
-•
f
\ Z
Horizontal Sidewall
3.
Installation Sprinkler Types
Quick response sprinklers are intended for installation Standard Upright
as specified in NFPA 13. Quick response sprinklers and Standard Pendent
standard response sprinklers should not be intermixed.
' I The Model Fl FR Recessed Quick Response Sprinklers Conventional
_ are to be installed as shown. The Model Fl or F2 Escutch- Sidewall (Vertical, Horizontal HSW1)
eons illustrated are the only recessed escutcheons to be Recessed Pendent
' used with the Model Fl FR Sprinklers. The use of any other Recessed Horizontal Sidewall HSW1
• recessed escutcheon will void all approvals and negate all
warranties.
When installing Model Fl FR Sprinklers, use the Model D
Sprinkler Wrench. When installing Model F1FR Recessed Finishes ( ' ) (4
Sidewall Sprinklers, use the Model GFR1 Sprinkler Standard Finishes
Wrench. Use the Model RC1 Wrench for installing F1FR
Sprinlder Escutcheon
Recessed Pendent Sprinklers. Any other type of wrench
may damage these sprinklers. Bronze Brass
Chrome Plated Chrome Plated (3)
White Polyester Coated White Painted (3)
Temperature Ratings Special Application Finishes
Sprinkler Escutcheon Max. Ambient Bulb Sprinlder Escutcheon Temperature Temp Color Bright Brass Bright Brass
°C °F Plated Black Plated
57 135 100°F (39°C) Orange Black Paint Black Paint
Ordinary 68 155 100°F (38°C) Red
79 175 150°F (66°C) Yellow Off White Off White
93 200 15�F(66°C) Green Satin Chrome Satin Chrome
141 286 225°F (107°C)
Blue I (t) Other finishes and colors are available on special order.
(1) Not available for recessed sprinklers. Consult the factory for details.
( FM Approvals is limited to bronze and brass, chrome or black
Escutcheon Data plated finishes only.
( FP Push- on/Thread -off escutcheon I
Esartcheon Model Approvals Musa l Dimension b Ceiling or
Wall Dimension
F1 1.2,4 X" %" X6"-,(6- Ordering Information
(19mm) (19mm) (5mm - 24mm) Specify:
F2 1,2,3,4,5,7,8 (13mm) (25mm) (5rmt- 17mrn) 1. Sprinkler Model
X6" 2. Sprinkler Type
FP 1,2 Full y Recessed (11mm) 3. Orifice Size
Push -on/
Thread -oft 1,2 Fully Retracted 'V6" 4. Deflector Type
(24mm) 5. Temperature Rating
Maintenance 6. Sprinkler Finish
' • The Models F1FR and F1FR Recessed Sprinklers 7. Escutcheon Type
• should be inspected quarterly and the sprinkler system 8. Escutcheon Finish (where applicable)
maintained in accordance with NFPA 25. Do not clean
' sprinklers with soap and water, ammonia or any other Note: When Model F1FR Recessed sprinklers are
cleaning fluids. Remove dust by using a soft brush or gen- ordered, the sprinklers and escutcheons are packaged
tie vacuuming. Remove any sprinkler which has been separately.
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
- allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
I in the original cartons and packaging until used to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non - operation.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throughout the United States, Canada and foreign countries
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. ® Recycled
'a (800)431 -1588 Sales Offices Pa
(800)848-6051 Sales Fax
(914)668 - 3470 Corporate Offices Revision lines indicate updated or new data