Specifications • FP52Q ? -0 37 r z& 7o se...,) * - - S T A N D B Y BATTERY WORKSHEE o n,J "'ACTION ... PROJECT NAME: TECHNOLOGY SYS I L MS j ,i z Apex Industries 835 SE 17TH AVENUE LL' ° 12670 SW Hall PORTLAND OREGON 97214 m Tigard Oregon 97223 (503) 231 -1992 Device Quantity of Standby mA Alarm mA Total Device Total Device Description Devices Per Device Per Device Standby mA Alarm mA DMP XR5 Fire Control Panel 1 50 50 50 50 DMP 630F Annunciator 1 63 92 63 92 Bosch F220 -P Smoke Detector 1 12 20 12 20 0 0 0 0 0 Total System Current 125 162 Auxilliary Devices (list all) 4 -wire duct detector 0 0 0 4 -wire beam detector 0 0 0 door holder 0 N/A * 0 0 EOL relay 0 0 0 Other 0 0 0 Auxilliary Device Totals 1Amp Unfiltered Aux Pwr 0 0 0 Notification Appliances (list all) Wheelock AS- 24MCWR 110cd 1 N/A 173 N/A 173 Wheelock AS- WPMCCH FR 115cd 1 N/A 300 N/A 300 0 N/A 0 N/A 0 0 N/A 0 N/A 0 Aux relays 0 N/A 0 N/A 0 • Other 0 — — N/A 0 N/A 0 Notification Appliance Totals 2 N/A 473 (2NAC circuits at 2.5A limited to 4 Amps Total) Summary Section Standby Hrs. Required 24 Alarm Sounding Minutes 5 Total System Standby mA 125 Total System Alarm mA 635 _ Total System Standby A/H 3.00 Total System Alarm A/H 0.05 Min. A/H Battery Required 3.05 Recommended A/H Battery ** , 7.00 , Use next size battery with capacity greater than required,but not to exceed 40 A/H. • F/ 2c i — crx,c) 3 PE S E SIGNALING NYC U(. MEA I �) LISTED _ i Economical, reliable performance for small commercial applications ••i.,x 4erCer,r•ssaiss s�ss I li i • XR5 commercial fire and slave communicators from DMP are perfect for small commercial installations that require reliable, cost - effective monitoring. • Built -in 2 -line dialer • 500mA auxiliary power • One Class A (Style D) zone for sprinkler supervision • Four Class B (Style A) smoke - detector zones • Four Class B (Style A) expansion zones Rely on DMP to increase the value of your next fire alarm installation. High- quality DMP panels and network monitoring technologies have led the industry for decades and significantly reduce the cost of monitoring communications. XRS --- 9 ZONE SYSTEM FEATURES • One Class A (Style D) waterflow zone • DMP Serial 1 or Contact ID communication formats • Four Class B (Style A) 2 -wire smoke detector zones • Compatible with the iCOMsL for network /Internet reporting • Four Class B (Style A) expansion zones using 714 or 715 • Programmable reporting to one or two central stations • 100mA 12 VDC switched 4 -wire smoke power (XR5FC) • Remote upload /download with Remote Link' • Two Form C relay outputs optional • Built -in plain English programming from any keypad • Four open collector outputs for annunciation • Individual zone programming for fire, fire verification, • Built -in dual phone line module with line monitoring retard delay, cross - zoning, and fire supervisory • Built -in bell circuit trouble monitor, connects to Model 865 • Compatible with 630F and 692F keypads or 866 Notification Circuit Modules • Fire Drill feature for practice evacuations • 600mA alarm bell output (XR5FC) • Swinger bypass option on all zones • 500mA auxiliary output • Inherent power limited circuits • Operates on 16 VAC power • Automatic recall test reporting • 4 -wire keypad and annunciator circuit • One -man Walk Test -_ • 16 event history can be viewed from 630F keypad • Automatic standby battery test —^--^ D.gi[.:N Mao torn, Pr hats COMMUNICATION POWERFUL FALSE ALARM BUILT -IN PROGRAMMER Each XR5 panel contains a built -in dual REDUCTION FEATURES An internal English text Programmer phone line module with line supervision The built -in false alarm reduction enables technicians to easily program that can communicate to one or two features include cross zoning, fire and test the panel from any keypad. remote receivers using DMP Serial 1 verification, fire retard, and CleanMe " A lockout code restricts access to only digital dialer or Contact ID (CID) formats. reporting. authorized persons. You can also selectively enable alarm, Cross zoning allows multiple zones to supervisory/trouble, backup, and recall REMOTE PROGRAMMING be cross zoned and reports alarms only test reporting to either of the two when two or more zones fault within a Remotely program XR5 panels using receivers. programmable time of 4 to 250 seconds. Remote Link'"' programming software from Should just one zone trip, only a zone DMP. You can upload panel programming, NETWORK MONITORING make the necessary programming An iCOMst Network Alarm Communicator fault report is sent to the central changes, and then download the revised connects to the XR5 to provide Internet/ station. programming into the panel. LAN /WAN communications to the panel. Fire verification provides a 120 - second Expand Remote Link /System Link When used in this manner or as a slave window during which a smoke detector functionality with Advanced Reporting, or stand -alone network communicator, can trip, be automatically reset, and Alarm Monitoring, Command Center, or the iCOMsL reduces or eliminates costly then must trip a second time before an Link Server packages. telephone lines and communicates to the alarm is indicated. A single trip on the central station via high -speed network zone sends only a zone fault report to 630F FIRE COMMAND CENTER connections. the central station. KEYPAD OPERATION ONE - MAN WALK TEST Fire retard allows a programmable time For system annunciation, include the Conduct one-man tests of the system of up to 250 seconds for waterflow DMP 630F Fire Command keypad in your and all connected devices using the Walk detection. This eliminates the need installation. This 20 -key, 32- character LCD Test feature. Simply enter an access for additional mechanical delays at the annunciator provides full -text displays code into the keypad and XR5 panels flowswitch. of system events and menu prompts. It can be used for system operation, automatically enter test mode. Each time ANNUNCIATOR OUTPUTS annunciation, and programming. The a zone trips during the test, the bell rings Four open collector outputs can be 630F is protected by either a keyswitch for two seconds and a Sensor Reset is used for a variety of remote control and or code. The keyswitch enables the four automatically performed to reset latched annunciation applications. Each output is function buttons: Silence, Reset, Test, detectors. When the test is completed, rated for 50mA maximum. Add the Model and Fire Drill. Install the 630F using the the results display at the keypad and can 860 Relay Output module to provide four included backbox and trim frame for be sent to the central station, form C relay contacts. Each Model 305 flush -mount applications and the 635 -R 1 ZONE EXPANDER relay is rated at 42mA and the module backbox for surface mount applications. The 714 provides four inputs and is easily mounts inside the XR5 enclosure. The 630F has the ability to annunciate suitable for use with normally open and all on -board and expansion zones on TROUBLE ANNUNCIATOR the XR5. normally closed fire devices. 714 inputs MODULE are supervised and can be programmed For slave communicator applications, 692F FIRE COMMAND LED for any zone type. The 714 connects to the XR5SL provides an enclosure door- KEYPAD the keypad bus. mounted Model 377 Trouble Annunciator The 692F Fire Command LED Keypad I S ZONE EXPANDER Module. The Model 377 offers Trouble offers 5 sets of highly visible LED The 715 expander provides four Class B and System OK LEDs with audible alert annunciation of alarm and trouble powered inputs and is suitable for use and a Silence button for acknowledging conditions. It provides individual zone with the 2-wire conventional smoke trouble conditions. alarm and trouble LEDs for zones one to detectors. 715 inputs are supervised and five only. Also, system LEDs, an internal can be programmed for any zone type. sounder, 2-button Fire alarm initiation, The 715 connects to the keypad bus. and only Silence, Reset, and Fire Drill functions are provided. The 692F is used in applications where only the panel's five on -board zones are used. : _ Model 377 Trouble Sikrce/Reset Panel Annunciator 10•1 Mod //u\�le Silence /Reset 13 1=1 CJ 0 0 _ Silence/Reset 0 /i :: Telephone • Belt L / • t t)j !la }'R+ ,, 1� y "F' n m°61:° 4 S Y lj ", l I tT Fl • Relay Sockets for Opbo l Direct connect a I F orm C Outputs on ]ll „nswndned 120 VAC 60 NZ "— r. n L __,- l C AC +B -B BELL See RED SEE GRN BLS Z1A +27A- Z1B+Z1B- Z2+ 12- 23+ Z3- Z4+ Z4- 15+ 05- i a3 A a1a 7!e ► 3, eof e e 04 0 Ee , 1�1 uQ O e�� 1Q - ", c :' Model3p � �' L•1 . , ® ® ® ® ®� ® {i , �� G Q 7 ` nC .' - ; � � C ® � .. r r: 1. l .�.�, wire-. transformer 1 1 t R1 I • fiR ©ii1•i�� er�i1 a 16.5 VAC 40VA i © © 0 © © © © © Ices S Output Header J12 © 0 3.3k Ohm F O Open CoMcbe Header J12 Secondary 12 Power Supple 1 1 2 Reaictor © © © f ,, , ,e 5wA e Model 300 Harness 12 VDC X81 0 Si II II Model 309 Output 1 Output 2 1 2 Amp$ Max . o WRMt GROUND — . Output Header J11 C Waler Ppe —' Z*A l © ©© Two Form C {SPOT) °+0 I EaM Ground U0 lo 500mA Our Mary Wrrenl al 12 VDC from bmWW 7 MO III III ZerM3 Zeno3 Z one 3.3UOhn 3.3k pen 3.3k0o. Keypad Model 630F °....■ 4... 63mA al 8.5 to 14 VDC BHP 10 1 00 , I- ® © ©© • ®• Supervised Circuit it CDC) oa \ l Keypad L Model 692F 30mA al 8 to 16 VDC mm =ireie (=)1=)m 5 Zone LED Keypads XR5FC System Configuration Diagram .. sop ...., Digital Monitoring Products • FIRE COMMAND KEYPADS POWER SUPPLIES ACCESSORIES 630F Remote Fire Command 504 -24 Provides 4 Amps @ 24 VDC 300 Plug -in Harness • 32- character LCD 504-24LX Provides 4 Amps @ 24 VDC 305 Plug -in Relay Output 635 -R Keypad Conduit Backbox 505-12 Provides 5 Amps @ 12 VDC 306 Harness Connection 692F Fire Command' Keypad 505-12L Provides 5 Amps @ 12 VDC 318 Dual Battery Harness AUXILIARY MODULES 505 -12LX Provides 5 Amps @ 12 VDC 320 40 VA Wire -in Transformer 377 Trouble Annunciator Module 367 12 VDC 7.7 Ah battery (included with XR5SL) COMPUTER SOFTWARE 860 Relay Module Remote Link Upload /Download Programming 370RJ Lightning Suppressor with Software Two RJ Jacks 865 Style W/X Notification Circuit System Link End -User Management Software Module Advanced Reporting Module 866 Style W Notification Circuit Module Alarm Monitoring Module iCOMR. Network Alarm Communicator Command Center Module LXPANSION MODULES Link Server Application 714 4 -zone Class -B Expansion DETECTORS 715 4 -zone 2 -wire smoke Expansion SLR -8358 Photoelectric Smoke 521B /BXT Addressable Smoke, CleanMe" U — – 1 _ _ -- 1 SPECIFICATIONS LISTINGS AND APPROVALS Primary Power 16.5 VAC 40VA transformer (Model 320) Refer to the XR5 Installation Guide (LT- 0229), XR5 Programming Guide Secondary Power 12 VDC 7.7Ah battery (Model 367) (LT -0312) and specific compliance listings for installation and Out uts programming requirements necessary to meet a particular p approval. Auxiliary 500mA @ 12 VDC e Annunciator 50mA each (switched ground) California State Fire Marshal (CSFM) $ XR5FC Outputs FCC Part 15 i c Alarm 600mA @ 12 VDC FCC Part 68 ° Smoke 100mA @ 12 VDC New York City (MEA) i Enclosure Red (Models 340FC or 340SL) Underwriters Laboratories (UL) Listed o Dimensions 12.5" x 9.5" x 3.75" ANSI /UL 864 Control Units for Fire - Protective Signaling Systems § NMI Material 20 -gauge cold - rolled steel For additional information, access www.dmp.com and select Compliance. m ' _No 800- 641 -4282 INTRUSION • FIRE • ACCESS • NETWORKS ' www.dmp.com 2500 North Partnership Boulevard . Digital Monitoring Product. Made in the USA Springfield, Missouri 65803 -8877 ill:. P'E ET• SIGNALING NYC ; `� M E A te , LISTED l� _ Fire annunciation solutions — 1 • • - ' v =• = DMP Fire Command Keypads provide a variety ` + f of fire annunciation solutions for residential and commercial fire applications. ._a The 630F provides 32- character full text - LCD display of system events and menu prompts for efficient, easy use. • The keypads offer simple, one - button access to common features, including: • Silence alarms • Reset sensors • Test the system • Perform a fire drill The 692F includes a highly visible LED annunciator. 630F AND 692F DMP FIRE COMMAND KEYPADS FIRE COMMAND FEATURES 692E FEATURES • Simple harness connection to 4 -wire keypad bus • Three status LEDs: Silenced, Trouble, and Power • At- a- glance system status • 10 zone LEDs: 5 Trouble LEDs and 5 Alarm LEDs • Powered from panel or auxiliary power supply • No addressing required - use as many as you need • Optional backboxes for conduit or wall mount applications • Zone monitoring feature for all zones • Attractive non - obtrusive designs • Four short tones indicate an unsuccessful keypad operation • 2- button Panic keys • Quick key on keypad for changing user code N3 . FEATURES • Audible tone on each key press 32-character FEATURES LCD display • Zone LEDs: Normal, Trouble, • • Flush or Surface mount Bypassed, and Alarm conditions • Keyswitch enables single button operation • Full operation with authorized code •, Built -in diagnostics 0C Power, Trouble, Alarm LED • Compatible with XRSFCIXRSSL, XR100 /XR500 Series, or MD. " "` XR2500F 1�-- • S stem events dis•la to 'lain E •hsh , D,jt-0 Monitornj Pt ocWote 1 ' r 3 OF REMOTE ANNUNCIATOR SUPERVISED AND STATUS LEDS The 630F Fire Command Center offers UNSUPERVISED OPERATION The Green Power LED lights when primary a 32- character full text LCD readout that The 630F keypad can be programmed AC or DC power to the panel is at an - displays system events and menu prompts, for supervised or unsupervised operation acceptable level and flashes when its making it efficient and easy -to -use. The on the keypad data bus, increasing the battery is low or missing. backbox and trim frame provide an attractive overall number of keypads you can install A Yellow Trouble LED turns on when either installation. The keypad can either be flush- to provide maximum flexibility. When the panel has failed to communicate mounted or surface - mounted. supervised, the keypad occupies its own with the central station receiver or when address. Unsupervised operation allows phone line 1 or 2 is in a bad condition. you to install multiple keypads on the bus The 692F also uses a Yellow Silenced LED with the same address. The 692F is always to indicate when the panel Bell Output :VD set as unsupervised. has been silenced. !v ( los on an 692F FIRE COMMAND KEYPAD ZONE LEDS tip, kin go The 692F Fire Command Keypad offers Zone LEDs indicate the status of the first • 4 t`,, wiz highly visible LED annunciation of alarm five zones. Each zone has a trouble and and trouble conditions on DMP XR5FC alarm LED to indicate at -a- glance zone and XR5SL Commercial Fire Panels. status. It provides individual zone alarm and KEYPAD FUNCTION KEYS 630F Keypad trouble LEDs, status LEDs, an internal There are four clearly labeled function buzzer, 2- button functions. keys on the 692F keypad. The SILENCE, SINGLE BUTTON OPERATION The 692F is cased in a durable Red plastic RESET, TEST, and CODE function keys The 630F Fire Command Center has a factory housing with a removable base for easy allow the user to press one key to initiate installed keyswitch that enables the four installation. operations. As an added security measure, function buttons —Alarm Silence, System the user must enter a valid security code Reset, System Test, and Fire Drill. The after pressing one of the function keys. user can also access these four functions and many more through the User Menu by �r r Cp entering a valid user code. — -- " BUILT - IN DIAGNOSTICS two An internal diagnostics program lets 112 ei.2 En ma installers and service technicians test the operation of the keypad at any time 1 without disabling the system. 692F Keypad Fire Keyboard Operating Current Display Panic User Operating p g Command Zones Type Keys Compatible Panels Red in Brightness Voltage Model Alarm Standby (92m Alarm 630E None LCD Yes XR5FC /XR5SL, XR100 /XR500 Series, No Yes 12 VDC 63mA A XR2500F 692F None LED Yes XR5FC /XR5SL (First five zones only) No Yes 12 VDC 30mA 70mA 630F SPECIFICATIONS KEYPAD ACCESSORIES Operating Voltage 8.5 to 15 VDC 635 1.75" 630F Keypad Conduit Backbox Current Draw 63mA standby, 92mA maximum 635F 2.5" 630F Keypad Conduit Backbox Trim Frame Dimensions 10.4" W x 7.0" H x 1.7" D 695 1.5" Keypad Conduit Backbox j Backbox Dimensions 8.75" W x 6.375" H x 2.5" D 696 1/2" Keypad Backbox Panel Compatibility XR500 Series, XR100 Series, 699 Keypad Deskstand XR2500F 300 4 -wire Replacement Harness S 692F SPECIFICATIONS LED Keypad Housing { Operating Voltage 8.5 to 15 VDC LISTINGS AND APPROVALS = Current Draw 30mA standby, 70mA maximum California State Fire Marshal (CSFM) B Dimensions 6.8" W x 5.0" H x 1.1" D FCC Part 15 Panel Compatibility XR5FC and XR5SL Underwriters Laboratories (UL) Listed ANSI /UL 864 Control Units for Fire Protective Signaling ANSI /UL 985 Household Fire Warning For additional information, access www.dmp.com and select Compliance. A E _ o - 800 - 641 - 428 2 INTRUSION • FIRE • ACCESS • NETWORKS � ° www.dmp.com 2500 North Partnership Boulevard Digital Monitoring Product. Made in the USA Springfield, Missouri 65803-8877 i iii . / COOPER Wheelock Weatherproof Appliances - Series AH Audibles, AS Audible Strobes, MT Multitone Strobes, RSS Strobes and ET70 Speaker Strobes and Weatherproof Mounting Accessories I ,. , i N in ,,„:, F Description: Designed for life safety, performance and reliability, Cooper When used in conjunction with Wheelock PS- 24 -8MC Power Wheelock's cost effective weatherpoof notification appliances Supplies or SM /DSM Sync Modules, the Wheelock weatherproof include: appliances can be synchronized to meet NFPA 72 synchronization Weatherproof Appliances Series requirements. The horn output of horn strobes can be independently controlled on 2 -wire circuits using the Wheelock patented sync Strobes RSSWP protocol. MTWP horn strobe models are 4 -wire appliances; the Horn Strobes ASWP strobes can be synchronized while the audible can be connected Horns AH -24WP, AH -12WP to a coded fire alarm system or can be set to produce any of eight Multitone Horn Strobes MTWP selectable tones. Multitone Horns MT Speaker Strobes ET7OWP Speakers ET -1010 Features: All strobe models are UL dual listed - meeting both UL1638 Approvals include: UL Standards 1971, 1638, 464 and 1480 and UL1971 requirements. As dual listed appliances, these California State Fire Marshal (CSFM) and New York City weatherproof strobes, horn strobes and speaker strobes are listed (MEA), Factory Mutual (FM) and Chicago (BFP) . See for outdoor applications under UL 1638 as well as under UL 1971, the Standard for Safety Signaling Devices for Hearing Impaired. agency approvals by model number on page two of this • With an extended temperature range of —31 °F to 150 °F ( -40 °C document to 66 °C), Wheelock weatherproof appliances meet or exceed UL • Compliance with the following requirements: NFPA, UFC, outdoor test requirements for rain, humidity and corrosion resistance ANSI 117.1, OSHA Part 29, 1910.165,ADA while providing multiple strobe intensity options, including the highest strobe ratings available for area coverage per NFPA 72 • Weatherproof with extended temperature range of —31 °F to strobe spacing tables (up to 185 candela for wall mounting and 177 150 °F ( -35 °C to 66 °C) candela for ceiling mounting). • Dual Listed strobe models (UL 1638 and UL 1971) To enable weatherproof mounting, Cooper - Wheelock provides the • Industry's highest strobe candela options industry's widest choice of mounting options for surface or unique semi -flush installation. Models are available for surface mounting • Synchronization capability using Series SM, DSM Synch to Wheelock weatherproof backboxes on walls or ceilings. The Modules (MTWP and MT -12/24 audible is non -sync) optional WP -KIT allows the weatherproof backboxes (IOB, WPBB or • Models with field selectable tone, dBA and candela settings WPSBB) to be mounted to a recessed electrical box for concealed conduit installation. For semi -flush installation, the WPA and Wall or ceiling mounting options WFPA kits allow a customer to mount the weatherproof appliances • Surface of semi -flush mounting to a recessed electrical box without the need for an external IN /OUT wiring termination accepting two #12 -18 AWG wires • weatherproof backbox. See the Backboxes, Plates and Gaskets at each terminal Table on page three of this document for a summarization of these mounting options and the required accessories. e "::off ) 11> M EA APPROVED E5946 151 -92 -E 7125 -0785:131 (ASWP) S5391 7125 -0785.146 (ET701A/P) S2652 7125 -0785156 (MTWP) 7300 -0785.154 (RSSWP) NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU • AND /OR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their UL Listed Regulated Voltage Range. • All candela ratings represent minimum effective Strobe intensity based on UL Standards 1971 and 1638 as indicated in candela ratings table. Wall Mount Ceiling Mount Wall or Ceiling Mount 'E / R E L Et low. RSSWP MTWP . °. RSSWP MTWP MT AH FIRE Iliti l a ASWP ET7OWP ASWP ET7OWP ET -1010 Strobe Order Code Strobe Order Code Audible Order Code RSSWP- 2475W -FR Red 9013 RSSWP- 2475C -FR Red 4338 AH- 24WP -R Red 7416 RSSWP - 2475W -FW White 3034 RSSWP - 2475C -FW White 4446 AH- 12WP -R Red 7415 RSSWP- 24MCWH -FR Red 5161 RSSWP - 24MCCH -FR Red 5167 RSSWP- 24MCWH -FW White 5165 RSSWP - 24MCCH- FWWhite 5187 Horn MT- 12/24 -R Red 5023 Audible Strobe Audible Strobe ASWP - 2475W -FR Red 9012 ASWP- 2475C -FR Red 4251 Speaker ASWP- 24MCHW -FR Red 5137 ASWP- 2475C -FW White 4502 ET- 1010 -R Red 3135 ASWP- 24MCWH -FW White 5140 ASWP - 24MCCH -FR Red 5149 ET- 1010 -W White 3137 Multi -tone Strobe ASWP - 24MCCH -FW White 5157 MTWP- 2475W -FR Red 8420 Multi -tone Strobe UL Max. Current AH MTWP - 2475W -FW White 3112 MTWP- 2475C -FR Red 4457 24 VDC 12 VDC MTWP- 24MCWH -FR Red 5132 MTWP - 2475C -FW White 4478 High (99) dBA 0.080 0.192 MTWP- 24MCWH -FW White 5134 MTWP - 24MCCH -FR Red 5102 Med (95) dBA 0.043 0.108 Speaker Strobe MTWP- 24MCCH -FW White 5122 Low (90) dBA 0.021 0.058 • ET7OWP- 2475W -FR Red 9077 Speaker Strobe ET70WP- 2475W -FW White 3179 ET70WP- 2475C -FR Red 4452 UL Reverberant dBA © 10 Feet ET7OWP- 24185W -FR Red 4885 ET70WP- 2475C -FW White 4454 Watts 1/8 1/4 1/2 1 2 4 8 ET70WP- 24185W -FW White 4891 ET70WP- 24177C -FR Red 4845 • ET70WP- 24177C -FW White 4859 ET -1010 77 80 83 86 87 92 94 ET70WP 78 81 84 87 90 93 95 I Candela Ratings UL 1638 UL 1638 RSS, ET70WP and ASWP • Series UL 1971 MTWP UL Max Current © 77 °F -31°F (Strobe Only) High Med Low Model Number Agency Approvals 2475 30 180 75 0.138 0.168 0.155 0.150 Strobe UL MEA CSFM FM BFP 135 135 56 0.300 0.355 0.340 0.335 MCWH RSSWP -2475 X X X X 185 185 77 I • II 0.480 0.465 0.460 RSSWP- 24MCWH X • 115 115 47 0.300 0.355 0.340 0.335 RSSWP - 24MCCH X • • MCCH Audible Strobe 177 177 73 0. 0 0.480 0.465 0.460 ASWP -2475 X X X X X 24185 185 185 77 0.420 "'Wall mount rating only ASWP -MCWH x • 24177 177 177 73 0.420 ASWP -MCCH X • Multitone Strobe MTWP -2475 X X X X • UL Max. Current MTWP /MT MT MTWP -MCWH X • • (Audible) 24 VDC 12 VDC MTWP -MCCH X • dBA HI STD HI STD Horns /Audibles Horn 0.108 0.044 0.177 0.034 AH -24WP X X X - X - AH -12WP X X X - X Bell 0.053 0.024 0.095 0.020 AH -12/24 X X X X X (March Time 0.104 0.038 0.142 0.034 Code 3 Horn 0.091 0.035 0.142 0.034 Speaker Strobe .Code 3 Tone 0.075 0.035 0.105 0.021 ET70WP -2475 X X X • • ET70WP -185 X Slow Whoop 0.098 0.037 0.142 0.035 ET70WP -185 X • Siren 0.104 0.036 0.152 0.030 - Hi /Lo 0.057 0.025 0.114 0.026 'Pending . / COOPER Wheelock Series AS Audible Strobe Appliances and Series AH Auddibles SERIES AS SERIES AH Description Features The Wheelock patented 2 -wire Series AS Audible Strobe • Approvals include: UL Standard 1971, UL Standard 464 Appliances and Series AH Audibles offer more features with New York City (MEA), California State Fire Marshal (CSFM), low current draw. Factory Mutual (FM), and Chicago (BFP). See approvals by model in Specifications and Ordering Information Strobe options for wall mount models include 1575cd or the Wheelock patented MCW multi - candela wall strobes with field • ADA/NFPA/UFC /ANSI Compliant selectable candela settings of 15/30/75/110cd, or the high • Wall mount models are available with Field Selectable intensity MCWH strobe with field selectable 135/185cd. Candela Settings of 15/30/75/110cd or 135/185cd (Multi - Ceiling mount models incorporate Wheelock's patented MCC Candela models) or 1575cd (single candela model) multi - candela ceiling strobe with field selectable intensities of • Ceiling mount models are available with field selectable 15/30/75/95cd or the high intensity MCCH strobe with field candela settings of 15/30/75/95cd or 115/177cd (multi - candela selectable 115/177cd. ceiling models) The audible provides a selectable choice of either a • Selectable Continuous Horn or Temporal (Code 3). continuous horn or temporal pattern (Code 3) when • 3 Selectable dBA settings (99, 95 and 90 dBA) in both tones constant voltage from a Fire Alarm Panel (FACP) is Patented 2 -Wire Audible Strobe Appliance. • applied. Each tone has 3 dBA settings to choose from. • Patented Universal Mounting Plate When used with the Wheelock Series SM or DSM Sync Module • or Wheelock PS- 24 -8MC Power Supplies with Patented • Weatherproof models are available for outdoor use Sync Protocol, synchronization of the continuous horn tone • Strobes produce 1 flash per second over the regulated provides the temporal (code 3) tone (mandated by NFPA 72) voltage range simultaneously for all audible appliances. This ensures a distinct temporal (code 3) pattern when 2 or more audibles • 12 and 24 VDC models with wide UL "Regulated Voltage are within hearing distance. If not synchronized the temporal Range" using filtered DC or unfiltered FWR input voltage sound could overlap and not be distinctive. At the same time • The strobes can be synchronized using Wheelock's sync the strobes will be synchronized. This provides the ability to modules or power supplies with built in sync protocol comply with ADA guidelines concerning photosensitive epilepsy Fast installation with IN /OUT screw terminals using • and the NFPA standards when installing 2 or more visual #12 to #18 AWG wires appliances within the field of view all of this plus the ability to silence the audible is achieved by using only 2 wire. For Weatherproof Series AS, See Datasheet S9004 410 w n (41: iell MEA APPROVED E5946 151 -92 -E 7125 -0785:131 85391 NOTE: AILCAUTIONS and WARNINGS are Identified by the symbol A. All warnings are printed in bold capital letters. n WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.000PERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAWL1RE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. . General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range ". Note that NFPA -72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 °F to 120 °F (0 °C to 49 °C) and maximum humidity of 93% (t 2 %). • Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology "Listed Voltage Range ". Table 1: Ratings Per UL 1971 Table 2: dBA Ratings for 12 VDC and 24 VDC Series Input Regulated AS /AH 12 and 24 VDC Audible Model Strobe Reverberant Number Voltage Voltage Range Candela (cd) dBA Anechoic VDC VDC /FWR Description Volume dBA PerrUL464 @10 ft. AS -24MCW 24 16.0 - 33.0 15/30/75/110 10 ft. AS- 24MCCH 24 16.0 - 33.0 115/177 High 91 99 Continuous Medium 88 95 AS- 241575W 24 16.0 - 33.0 15 (75 on Axis) Horn AS- 121575W 12 8.0 - 17.5 15 (75 on Axis) Low 83 90 AS -24MCC 24 16.0 - 33.0 15/30/75/95 High 87 99 AS- 24MCWH 24 16.0 - 33.0 135/185 Code 3 Horn Medium 84 95 ASWP -2475W 24 16.0 - 33.0 75 @ -31 °F Low 79 90 Table 3: Average RMS Current Audible Wall Mount Audible Strobe Models Ceiling Mount Audible Strobe Models 24 VDC Models AH -24 AS- 241575W AS -24MCW AS- 24MCWH AS -24MCC AS- 24MCCH 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd High (99) 24 vdc 0.062 0.100 0.080 0.102 0.150 0.194 0.250 0.320 0.088 0.114 0.165 0.205 0.250 0.320 dBA UL max' 0.080 0.121 0.088 0.125 0.200 ".2fij 0.355 0.480 0.095 0.138 0.221 0.285 0.355 0.480 Med (95) 24 vdc 0.033 0.080 0.060 0.084 0.132 /0 0.230 0.305 0.066 0.092 0.145 0.186 0.230 0.305 dBA UL max' 0.043 0.107 0.074 0.110 0.190 0.253 73 0.340 0.465 0.080 0.122 0.201 0.269 0.340 0.465 Low (90) 24 vdc 0.017 0.072 0.052 0.076 0.121 0.158 0.220 0.295 0.056 0.082 0.132 0.173 0.220 0.295 dBA UL max' 0.021 0.100 0.068 0.105 0.182 0.245 0.335 0.460 0.074 0.113 0.198 0.263 0.335 0.460 Wall Mount Audible Audible 12 VDC Models Strobe Table 4: Average Current* (AMPS) For Series ASWP" High dBA Medium dBA Low dBA AH - 12 AS 121575W Voltage Setting Setting Setting 12 vdc 0.163 0 .260 (99) dBA (95) dBA (90) dBA High (99) 24.0 VDC 0.128 0.105 0.098 dBA UL max* 0.192 0.320 UL Max' 0.168 0.155 0.150 Med (95) 12 vdc 0.076 0.195 dBA UL max* 0.108 0.275 • RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16 -33v Low (90) 12 vdc 0.039 0.175 for 24v units). For strobes the UL max current is usually at the minimum dBA uL max' 0.058 0.265 listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. re Alarm Systems I F22O Photoelectric Smoke Detectors s{ . ,. ' t ,... ` '; • ,',: BOSCH t"" 3! Invented for life F220 Photoelectric Smoke Detectors • Two -wire or four -wire bases • • 30 ft (9 m) spacing between detectors • Optional CO- sensor, heat - sensor enhanced detection .4 /1141.,. chamber • Clean chamber without removal or disassembly • CleanMe"" signaling capability . • Sensitivity readout on detector 0 1 • Detector chamber compensates for dust build-up • Tamper protection I nii i mss • Dual -color LED . Vii' The F220 Photoelectric Smoke Detectors are UL Listed, • F220 -B6PS 12/24 VDC Four -wire Addressable Base open-area photoelectric smoke detectors. Use them with Monitoring the Detection Chamber commercial fire protective signaling systems and household These detectors have several features that work together to fire warning systems (see NFPA 72, the National Fire Alarm maximize the performance of the optical chamber: Code). These smoke detectors scatter light using a pulsed • Compensation: The detector monitors the chamber for infrared source operating with a gated, high-speed, the effects of dust build -up within the chamber and photodiode infrared sensor. The symmetry of the optical automatically compensates for these effects. If the chamber allows 360° uniform smoke entry, but minimizes chamber becomes contaminated beyond its ability to external light entry. The detectors use low current compensate, the green LED flashes every 4 sec to electronic circuitry, so they can connect to 12 VDC nominal indicate trouble. • Chamber Checke Self- diagnostics: The detector or 24 VDC nominal power source circuits. automatically indicates visually if the calibration is out of the factory-listed range. This meets NFPA guidelines for sensitivity testing, because you can visually inspect the detector and check the flash rate of the LED. If the Functions calibration is out of range, the green LED on the Compatible Bases detector flashes once every 4 sec. This indicates that Configure the detectors into two -wire or four -wire versions the detector must be cleaned following the instructions provided with the detector. by selecting the appropriate mounting base. These • CleanMe Mode: Indicates if the calibration is out of the detectors are compatible with any of the F220-B6 bases: factory-listed range by sending a trouble signal to the • F220-B6 12/24 VDC Two -wire Mounting Base CleanMe - compatible control panel, if so programmed. • F220-B6R Standard 12/24 VDC Four -wire Mounting • Chambermaid": The detector has a unique cleaning Base mechanism. Use the valve on the back of the detector • F220-B6RS 24 VDC Four -wire Mounting Base with to insert the nozzle of a can of clean, dry compressed Sounder air. Clean the chamber with a short (1 to 2 sec) blast of • F220-B6C 12/24 VDC Four -wire Mounting Base with air. Auxiliary Relay • F220-B6E 12/24 VDC Four-wire Power Supervision . Mounting Base • F220 -B6PM 24 VDC Four -wire Addressable Master Base www.boschsecurity.com I / F220 Photoelectric Smoke Detectors Heat and Carbon Monoxide Enhancements Certifications and Approvals The detectors are available with an optional fixed - temperature heat sensor, a carbon monoxide (CO) sensor, All F220 Smoke Heads and Detector Bases or a combination of heat and CO sensors. These optional Listings and UL UROX: Smoke - Automatic Fire Detectors (UL268) sensors enhance the operation of the smoke detector by Approvals: UL UROX7: Smoke - Automatic Fire Detectorscertified reducing false alarms. forCanada(ULC- S529 -02) • Carbon Monoxide: Without the presence of CO, a Factory Mutual Research normal byproduct of combustion, the detection Hong Kong Fire Services Department chamber is half as sensitive to smoke as a standard commercial photoelectric smoke chamber. This NYC /MEA (117-05-E) reduces false alarms. When the sensor detects CO, the F220 P /PTHSmoke Heads detection chamber's sensitivity to smoke increases so it equals or exceeds that of a standard commercial Listings and CSFM 7272-1615: 106 photoelectric smoke chamber. Approvals: CE Note The F220 -PTHC detects carbon monoxide (CO) F220- PTHCSmoke Head as a component of a fire. It is not a CO detector Listings and CSFM 7272-1615: 107 and cannot activate an alarm in the presence Approvals: CE of CO only. F220-B6/B6C/B6E/B6R Detector Bases • Heat: When the heat sensor detects a temperature rise, Listings and CSFM 7300-1615: 105 the photoelectric chamber becomes more smoke Approvals: sensitive. The heat sensor initiates an alarm if the F220- B6PM /PS Detector Bases ambient temperature exceeds +135 °F ( +57 °C). Listings and CSFM 73001615: 215 Dual -color LED Approvals: A dual -color LED indicator flashes green every 8 sec when the detector has power and the smoke sampling circuitry is working. If CleanMe is enabled, the green LED double Installation /Configuration Notes flashes (two flashes a half second apart) every 8 sec to indicate normal operation. The LED turns red if an alarm is Compatible Control Panels sent. After the alarm condition clears, reset the detector by Addressable Systems: compatible with addressable interrupting its power. If the chamber becomes systems controlled by D9412GV2, D7412GV2, D9412G, or contaminated beyond its ability to compensate, the green D7412G Control Panels or the D9124 Fire Alarm Control LED flashes every 4 sec to indicate trouble. Panel when used with the F220 -B6PM or F220-B6PS Addressable Detector Bases. Test Functions The F220 Photoelectric Smoke Detectors feature a unique Two wire: Bosch Security Systems, Inc. makes no claim • magnet operation and sensitivity test function. Test the written, oral, or implied that the F220 Photoelectric Smoke detector's operation by placing the magnet next to the Detectors work with any two -wire control panels except detector's LED for three consecutive flashes. This causes those specified in the Control Panel Compatibility chart in the detector to send an alarm. Placing a magnet next to the the Technical Service Note (P /N: 4998148185). detector's LED for at least one red flash but less than three Four -wire: compatible with all UL Listed four -wire control flashes activates the detector's sensitivity mode. panels. Refer to the control panel's installation instructions Tamper Detection for proper end -of -line (EOL) resistor selection. When detector heads are correctly installed in any of the Mounting the Bases F220-B6 bases, the positive power line provides tamper Note Consult NFPA -72 for proper detector detection. The control panel initiates a trouble signal if a placement. detector is removed from its base. A mechanical tamper lock comes with each base to prevent unauthorized head Depending on local regulations, the bases can be surface removal. mounted directly on four -inch square or octagonal electrical boxes and single -gang switch boxes. Note The volume of any electrical box used should be large enough to accommodate the number and size of conductors as specified by the National Electrical Code or any local • authorities having jurisdiction (AHJ). F220 Photoelectric Smoke Detectors I 3 Loop Supervision Ordering Information Loop supervision requires one D275 or F220-B6E per loop F220 PTHC Photoelectric Smoke Detector F220 -PTHC when using F220-B6R /B6C bases and is supervised by the with +135 °F( +57 ° Heat and Carbon control panel. Monoxide Sensors .......... Wiring the Bases F220-PTH Photoelectric Smoke Detector F220 -PTH Refer to the F220 Series Detectors with F220.86 /C /E /R Bases with +135 °F ( +57°C) Heat Sensor Installation Instructions (P /N: 4998138694), the F220 Series F220 -P Photoelectric Smoke Detector F220 -P Detectors with F220 -B6RS Bases Installation Instructions (P/ N: F01UO29847), or the F220- B6PS /M Installation Accessories Instructions (P /N: 4998149982) for detailed wiring D275 Power Supervision Module D275 instructions. DRA -5 Remote Annunciator (5 VDC) DRA -5 DT -2 Detector Removal Tool DT -2 F220•B612/24 VDC Two-wire Base F220 -B6 Technical Specifications F220 -B6R Standard 12/24 VDC Four -wire F220 -B6R Environmental Considerations Base Relative Humidity: 0% to 95% non-condensing; 15 0 /0to 95% non- F220-B6RS 24 VDC Four-wire Detector F220 B6RS condensing for CO sensing model Base with Sounder Temperature +32 °F to +100 °F (0 °C to +38 °C) F220 -B6C 12/24 VDC Four-wire Base with F220-66C (normal operating): Auxiliary Form C Relay Mechanical Properties F220-B6E 12 /24VDC Four -wire Power F220-B6E Supervision Base with End-of-line Power Color: White Monitoring Relay Dimensions (diameter x H): 6.75 in. x 2.25 in. (17.1 cm x 6.4 cm) F220-B6PM 24 VDC Four -wire Addressable F220 -B6PM Power Requirements Master Base F220-B6PS 12/24 VDC Four -wire F220-B6PS Current (alarm): 20 mA minimum at 8.5 VDC; Addressable Base (detector head only) 35 mA maximum at 32 VDC Current (start-Up): 0.12 mA maximum at 32 VDC Maximum RMS Ripple: 25% of DC input Power -up Time: 22 seconds maximum Voltage (standby) F220-86: 8.5 VDC to 32.0 VDC • F220-B6C /-B6R /•86E: 10.0 VDC to 30.0 VDC F220 -B6RS: 16.0 VDC to 30.0 VDC F220 -B6PM: with D299: 18.9 VDC to 28.0 VDC without D299: 9.6 VDC to 28.0 VDC F220- B6PS: 18.9 VDC to 28.0 VDC Trademarks Chamber Checkl is a registered trademark of Bosch Security Systems in the United States. Chambermaid'" Is a trademark of Bosch Security Systems in the United States. CleanMe°L isa registered trademark of GE Interlogixin the United States and /or other countries. Europe, Middle East, Africa: Americas: Asia - Pacific: Represented by Bosch Security Systems B.V. Bosch Security Systems. Inc. Bosch Security Systems Pte Ltd • P O. Box 80002 130 Perrnton Parkway 38C Jalan Pemimpin 5600 JB Eindhoven. The Netherlands Fairport, New York, 14450, USA Singapore 577180 Phone • 31 40 2577 284 Phone. • 1 800 289 0096 Phone: .65 6319 3450 Fat .31 40 2577 330 Fax. •1 585 223 9180 Fax- .65 6319 3499 emea.secur.tysystems@bosch corn security.sales ®us.bosch coin apr.securitysystemseebosch.corn • www boschsecurity corn www.boschsecurity.us www boschsecurity corn C Bosch Security Systems, Inc. 2007 1 Data subject to change without notice F11163957871 Cur: en-US, V5, 13 Mar 2007