Plans .A4ec2,0iI- cco 3S' 2B'0 5 sw 77+ii p CLASSIFICATION REPORT INTERTEK TESTING SERVICES NA INC. 3933 US RT 11, CORTLAND, NY 13045 607- 753 -6711 FAX 607 - 756 -9891 Job No. 98250 -208 .Page 1 of 4 Date: June 15, 1998 Revised: January 8, 2007 CLASSIFICATION REPORT NO. 550000 INSPECTION, TESTS, AND EVALUATION OF A SPRAY BOOTH RENDERED TO Nova Verta, USA Spokane, WA GENERAL: This report gives the results of the evaluation of spray booth for conformance with the requirements of the Standard for Spray Application Using Flammable and Combustible Materials, ANSUNFPA 33, 2003 Edition and Certification Requirements for Paint Spraybooths and Drying Ovens, CGA CR90 -003. Compliance was determined with UFC 4502.5.2 on May 15, 1997. These products were also evaluated with considerations for UL 795 (Commercial Heating Equipment) and CGA -3.2 (Industrial and Commercial Gas - Fired Package Furnaces), however, no listing is being carried .for these standards. The sample was provided by the client and tested in the field. The evaluation commenced on April 12, 1995 and concluded on July 11, 1995. An additional specimen for CTOF and a Double booth was evaluated on February 5, 2002 in Lubbock, TX. Testing for additional heaters was performed in August 2004. An additional investigation to the report into compliance with NFPA33 -2003 was performed on January 8, 2007. CLASSIFICATION REPORT Spray Application Using Flammable and Combustible Materials ANSI/NFPA 33, 2003 Edition Certification Requirements for Paint Spraybooths and Drying Ovens CGA CR90 -003 Participant: Nova Verta, USA 16311 East Euclid Avenue, Suite H Spokane, WA 99216 -1670 Cort /Safe /Eng /LetngRprt /12Dec97 An independent organization testing for safety, performance, and certification All services undertaken subject to the following general policy: Reports are submitted for exclusive use of the clients to whom they are addressed. Their significance is subject to the adequacy and representative character of the samples and to the comprehensiveness of the tests, examinations or surveys made. No quotations from reports or use of lTS's name is permitted except as expressly authorized by ITS in writing. Intertek Testing Services NA Inc. Nova Verta, USA Report Number: 550000 Page 2 of 4 Issued: 06/15/98 Revised: 3/25/05 CONSTRUCTION PRODUCT COVERED: Spray Booth, Model K40: Super Prestige, Prestige, Super Conquer, Conquer, Raptor, Empress, Excel and Maxi- range 30 -60. Model 3000 and 4000 Series. PRODUCT DESCRIPTION: The product covered by this report is fully automated spray booth with forced air filtration system and a paint cure cycle. It is erected on site, ground supported and permanently connected to the supply sources. An indirect -fired make -up air heater pre- conditions the air used for ventilation and curing, where supplied, and is connected to the booth through permanently installed ducts and dampers. Listed direct fired burners are also approved with airflow consistency maintained per model design. Direct fired capability is not permitted in any instance where any recirculated air is present in CTOF booths for curing (high heat). MODEL SIMILARITY: Super Prestige contains 80 -100 ca. 4' florescent light tubes with external dimensions of 26',28', or 30'8" long x 14'8" wide x 11'2" high. Prestige contains 80 ea. 4' fluorescent light tubes, with external dimensions of 24' or 26' long x13'5" wide x10'2" high. Super Conquer contains 56 ea. 4' florescent light tubes, with external dimensions of 24'4" or 26'4" long x13'5" wide x10'2" high. Conquer contains 40 ea. 4' florescent light tubes, with external dimensions of 24'4" or 26'4" long x13'5" wide x102" high. Raptor contains 40 ea. 4' florescent light tubes, with external dimensions of 24'4 ", 26'4" 30'8 "long x13'5" wide x10'2" high. Excel contains 40 ea. 4' florescent light tubes, with external dimensions of 24' or 26' long x145" wide x10'2" high. Empress construction is identical to the Excel, except for the installation of one or more double - insulated sidewalls. Super Prestige models are same construction as Prestige other than the larger make up air of the M l .5 on 26', 28' and 30' dry exhaust models. M2 with 2 WW arc used on the 28' and 30' wet exhaust models. Maxi Range models 30' -80' in length and vary in height outside of 16' -20' and 16.5' -20' in width. The Maxi Range models have the ability to sub divide into 2 separate booths to be operated independently or simultaneously and may have 1 to 3 electric roll up doors. Door motor has been tested to comply for its location to be located within the 3' rule. 3000 and 4000 Series CTOF (Closed Top Open Front) and Double Booths are alike in all aspects other than lights in hip run front -to- back in 3000 Series, and side -to -side in 4000 Series. Booth volumes for these two series shall be limited to 7500 cubic feet, with no areas that permit dead air space. CTOF booths have no fixed doors, and rely on curtains classified as noncombustible or limited • combustible as defined in NFPA 220 or Method 2 of NFPA 701. Double booths have door frontals and exits complying with NFPA 101. The booth ventilation system cannot be isolated for operation of a single side. RATINGS: ELECTRICAL: PRODUCT VOLTAGE AMPERAGE FREQUENCY Model K40 208/240/480 V, 3 phase or single phase 125 A fuse max. 60 Hz 208/240/480 V, 3 phase or single phase 60 A fuse max. 60 Hz 120 V, single phase 60 A fuse max. 60 Hz Maxi Range Models, 3000 And 4000 Series 208/240/480 V, 3 phase 400 A fuse max. 60 Hz 208/240/480 V, 3 phase 200 A fuse max. 60 Hz 4 '• Due to the nature of the electrical service available, some units require a separate disconnect for the booth lighting circuits. BURNER: Fuel Type Capacity Natural Gas, Liquid Propane Ml, M I R - 800,000 Btu/hr max. or Oil M1.5, M 1.5 R - 1,500,000 Btu/hr max M2, M2R - 1,500,000 Btu/hr max. Natural Gas LMUI — 1,000,000 Btu/hr max. LMU1.5 — 1,200,000 Btu/hr max. tort /Safe /Eng /LetngRprt /12Dee97 Intertek Testing Services NA Inc. Nova Verta, USA Report Number: 550000 Page 3 of 4 Issued: 06/15/98 Revised: 3/25/05 TEST PERFORMANCE A representative sample of the product was tested in accordance with the Standard for Spray Application Using Flammable and Combustible Materials, ANSI/NFPA 33, 2000 Edition. Results of these tests also indicate compliance with CSA CR90 -003. The following tests were performed: Tests Airflow Door Closing Force Combustion Test Temperature Test Combustible Mixture Test Proximity of Electric Roll Up Door Motor at Top of Door The following testing was performed for CTOF /Double Booth: Tests Airflow Overspray Capture — Panel Spray Overspray Capture — Direct Spray Results of the tests indicate the specimens conform to applicable test criteria. Cort /Safe /Eng/LntngRprt /12Dec97 Intertek Testing Services NA Inc. Nova Verta, USA Report Number: 550000 Page 4 of 4 Issued: 06/15/98 Revised: 3/25/05 CONCLUSION A representative sample of the product covered by this report has been evaluated and found to comply with the applicable requirements of the Standard for Spray Application Using Flammable and Combustible Materials, ANSI/NFPA 33, 2000 Edition, and Certification Requirements for Paint Spraybooths and Drying Ovens, CGA CR90 -003. Reported by: Report Reviewed by: [signature on file] (N Brian Berlin Dale W. Soos Project Engineer Sr. Project Engineer Cort /Safe /Eng /LatngRprt /12Doc97 LISTING REPORT INTERTEK TESTING SERVICES NA INC. 3933 US RT 11, CORTLAND, NY 13045 607 -753 -6711 FAX 607 - 756 -9891 REVISIONS TO LISTING REPORT NO. 550000 INSPECTION, TESTS, AND EVALUATION OF SPRAY BOOTH RENDERED TO Nova Verta, USA Spokane, WA, 99212 The following revisions have been made to Listing Report: Date Approval Page Item Description of Change 9/22/99 D Soos 1 Participant Changed participants address Job No.J97022950 2 Product Covered Added Models Super Prestige, Raptor, Maxi Range 30 -60. 2 Product Descript. Added, "Listed direct fired burners arc also approved with airflow consistency maintained per model design ". 2 Model Similarity Description added. 2 Ratings: Added the Maxi Range models. Electrical: 208/240/480V, 3 phase or single phase, 400 A fuse max., 60 Hertz. 208/240/480V, 3 phase or single phase, 200 A fuse max., 60 Hertz 2 Burner: Added Fuel Type, Natural gas, Liquid Propane gas or Oil. Added Capacity, M 1, M I R - 800,000 Btu/hr max., M1.5, M1.5R - 1,500,000 Btu/hr max., M2, M2R — 1,500,000 Btu/hr max. 3 Tests Added, "Proximity of Electric Roll Up Door Motor at Top of Door ". 2/26/02 Soos All Updated std date to 2000. 3008277 1 Added CTOF/Double Booth info, changed address 2, 3 Added CTOF /Double Booth 4/16/02 Soos 2 Corrected cure and DF information 3008277 3/25/05 Soos All Added new std — CR90 -003 and other Canadian std refs 3063219 1 Revised format to identify classification and standards 2 Burner Added LMU 1 and LMU 1.5 1/8/07 Soos/Ncaglc Cover Updated report to NFPA 33 -2003 3107926 • Cort /Safe /Rng /LatngRprt /12Dec97 • Date Approval Page Item Description of Change • mm/dd /YY Initials of Engineer Job. No. Name Cort /safe /Eng /LatngRprt /12Dec97 CLASSIFICATION REPORT INTERTEK TESTING SERVICES NA INC. 3933 US ROUTE 11 CORTLAND, NY 13045 Job No. 3008277 Issued: September 11, 2001 REPORT NO. 3008277 -001 INSPECTION, TESTS AND EVALUATION OF A PAINT MIXING ROOM RENDERED TO NOVA VERTA USA SPOKANE, WASHINGTON GENERAL: This Report gives the results of the inspection, tests and evaluation of a Paint Mix Room for compliance with applicable requirements of the Standard for Spray Application Using Flammable or Combustible Materials, ANSUNFPA 33 -2000. A representative drawing of the Mix Room was provided by the client on and evaluated at ITS' Cortland, NY facility. • CLASSIFICATION ANSUNFPA 33 Participant: Manufacturer; NOVA VERTA USA Same as Participant 16311 Suite H Spokane, WA 99216 -1670 Contact: Mr. Brad Kennison Contact: Phone: 509 444 7910 800 668 2921 Phone: l ., sj ,. Fax: 509 444 3699 Fax: An independent organization testing for safety, performance, and certification. All services undertaken are subject to the following general policy: Reports are submitted for exclusive use of the clients to whom they are addressed Their significance is subject to the adequacy and representative character of the samples and to the comprehensiveness of the tests, examinations or surveys made. This document may not be reproduced except in its entirety without written permission from ITS. Cortland \ Form V.rrunggeport124Feb00 Intertek Testing Services NA Inc. Report No. 3008277 -001 Page 1 Issued: 09/11/01 Nova Verta USA PRODUCT DESCRIPTION PRODUCT COVERED Paint Mix Room, Model MR- (Followed by dimension size, for example, MR -916 is a 9'x16' room). PRODUCT DESCRIPTION The product covered by this report is a paint mixing mom for use in conjunction with a Classified Paint Spray Booth. The booth may or may not be attached to the mixing room. A door is provided for personnel access. A continuously operating spark -proof blower is provided for evacuation of volatiles. The mixing room is a freestanding structure and is provided with a fire rated air damper, lighting fixtures, and is permanently connected to the electrical supply MODEL SIMILARITY • All models are identical except for dimensions. Some may incorporate an external electrical control panel with switching capability for lighting and mixing banks. CLASSIFICATION LIMITATIONS Maximum mixing room footprint to be 150 square feet Fire suppression systems to be installed per applicable NFPA Standards, by others. Door opening force must be less than 30 lbf. All electrical wiring and components must be installed per the applicable clauses of NFPA 70, and NFPA 33, for Hazardous areas. Installation must be completed per NFPA 33, all joints shall be caulked or otherwise made air tight. Ventilation fan must be non - sparking and maintained in continuous operation. Portable fire extinguishers must be located per NFPA 10, by others. All flammable and combustible liquids shall be stored, handled, and mixed per the applicable requirements of NFPA 30. Aluminum shall not be used to complete any enclosure, or for ducting. ELECTRICAL RATINGS Product Voltage Amperage Frequency MR- (Followed by dimension size) 120 40 60 CoNmxtFomALLsdnetepa t24Fe600 Intertek Testing Services NA Inc. Report No. 3008277 -001 Page 2 Issued: 09/11/01 Nova Verta USA Revised: 04 /16/02 TEST PERFORMANCE A representative sample of the product was tested in accordance with the Standard for Spray Application Using Flammable or Combustible Materials, NFPA 33. The following tests were performed: Test Description None ( i Results of the tests indicate the specimens conform to applicable test criteria. CadarchFamHimogRepoM'./Feb00 1 Intertek Testing Services NA Inc. Report No. 3008277 -001 Page 3 Issued: 09/11/01 Nova Verta USA ' CONCLUSION A representative sample of the product covered by this report has been evaluated and found to comply with the applicable requirements of the Standard for Spray Application for Flammable and Combustible Materials, NFPA 33. 1 f: C Report approved by: 4q,if4r, , Dale W. Soos Kevin J. Wolf Sr. Project Engineer Engineering Manager - I-IVAC Cmtl®dtPonnU.ist ngRepvtt24Few . 1 1 Intertek Testing Services NA Inc. r0 . Report No. 3008277 -001 Page 4 Issued: 09/11/01 Nova Verta USA GENERAL INFORMATION The Applicant and Manufacturer have agreed to produce, test and label ETL Listed products in accordance with the requirements of this Report. The Manufacturer has also agreed to notify ITS and to request authorization prior to using alternate parts, components or materials. COMPONENTS Components used shall be those listed in the ITS report covering the products specified m the index including any amendments and/or revisions. LISTING MARK The ETL listing mark applied to the products shall either be separable in form, such as labels purchased from ITS, or on a product nameplate or other media only as specifically authorized by ITS. Use of the listing mark is subject to the control of ITS. MANUFACTURING AND PRODUCTION TESTS Manufacturing and Production Tests shall be performed as required in this Report. FOLLOW -UP SERVICE Periodic unannounced audits of the manufacturing facility shall be scheduled by ITS. An audit report shall be issued after each visit. In addition to the audit of the manufacturing facility, one annual audit of the listed apparatus at a field installation will be conducted as described below under "MELD INSTALLATION AUDIT ". Special attention will be given to the following: 1. Conformance of the manufactured product to the descriptions in this Report 2. Conformance of the use of the ETL mark with the requirements of this Report and. the Listing, Labeling, and Follow -up Service Agreement. 3. In -plant quality control procedures and personnel. 4. Manufacturing changes. 5. Performance of specified Manufacturing and Production Tests. In the event that the ITS representative identifies non-conformance(s) to any provision of this Report, the Applicant shall take one or more of the following actions: 1. Correct the non- conformance. 2. Remove the ETL Listing Mark from non - conforming product 3: - Contact -the- issuing - product safety evaluation center for- instructions.- ......- - -- -... . _.._ ......... _- • . . . .. ............... _. FIELD INSTALLATION AUDIT (For Spray Booths Only) 1. During the manufacturing facility audit, the listee must produce records of recent installations which indicate what was installed and when and where each installation took place. 2. The ETL representative will make this list available to Follow Up Services in Cortland where the Certification Manager will select several potential sites for the field audit. 3. Based on the site information submitted to the listee by the Certification Manager, the listee will identify, in a letter to the Certification Manager, one or more sites where the annual field installation audit may take place. 4. The Certification Manager will advise the listee of the final selection and a scheduled date for the audit. 5. The areas for examination for the field installation include: Nameplate/Markings Lighting Explosion Relief Venting Cotda itFanaistingRepatl:4Fcb00 8 I 7 I 6 I 5 ,, 4 I 3 I 2 I 1 205' -7 ' 0. Q Li , l 8' 48' -9' 26' -101-le 27' -Oft i 51' -2-1 , 16' -I0' L7' 11 D IL 5b I • 22' 25' D M�� 1� 1— ALUMINIUM ROOM U I R CON AMP «C 1 >:J'�1. "� RAMP ° PARTS PREP AREA 1,� 1 1 1 E •n , 1[2•40.1=1.11 �e1l� uui I I p . ESTIMATING / DAMAGE ANALYSIS I 41110 _ — — — — — 1 I \ U . R STORAGE ROOM � � E 1 ___71,,,i. rh .y " — in in I I �____�� ;, 1 1 II • =-4.- . _ , ily _ REST ROOM _ 1 — — — — — _ — — c:=1) �� I ` b 16' - •--- -i 3 , - I I L . 10 ._2. I 16 ._ I . 1 16 . I. 12 U. - 2' S• 4' . 1 2 '-2' ' 8 '.Q;. II .� C,1 8• 10 . R'-T u,•21. 12 . _ 2 . 17._ - If ` I I I I. J2'_2 I q'-8• 12'-2' I 7. 2 ,_ l i. I ,�12' -Y 15. fi 1. IZ '-Y II•. I• • I I I' -2� - t ' 6 � -02 2 11/ � I I [ , � Z � l� / \I 't 9 YI� � t 104 `a0' . 205 _, • 510' -5i' • Is re ( -ARTI STIC AUTOBODY . , ILI0P1 1- FLOOR RAN SCALE: 5/32".P-E ;; -i - '1S } , 5 / ` 1 e I; 7' 1� . . , !' ` . . ■ Li . ' - . •:. W: z:' ' e s.• :-... — •,... , j".: '• -. ,k,. \ • ,.... _ t V ��% 1 I � r • w....,_, ,.. ,, , I +.. ; .► f , B 1v� ,� I ' ti> 4 i i L . • 4 ' j . e,„.,. • i r 1 m °- r �� s . y _ y ,ft I I .� .3 ' y 5 ` q� \ BOOTH EXHAUST BOX e . _ - A - : t { " I i 't � J* � . � � ; I 1 . - 'sue?. 1 r d f .'' �_ e • i. 5 4 ti '. ■ r ", N. . Y k` ' 6 F3 II� �,I��t� i , A 800 1 668 -2921 WWW.NOVAVERTAUSA.COM PREP EXHAUST BOX MUM PA! ARTISTIC AUTOBODY C 0 NORTHWEST COLLISION EQUIP. AA-020911 -11 mrc 9032' -1'-0' .' M.POORE 13C Al 8 7 6 5 4 3 2 1 [Page Too Large for OCR Processing] [Page Too Large for OCR Processing] [Page Too Large for OCR Processing] [Page Too Large for OCR Processing]