NAC EOL VOLTAGE CALCULATION
•
FP 52011 o ,, s1# RF1 VD
CAPITOL ELECTRIC CO., INC. 1212_3 S (Q/`J
(503) 255 -9488 Office DEC 1 4 2011
(503) 255 -1966 Fax
CITY OF TIGARD
Job Name: Tigard Corporate Center Building -A
BUILDING DIVISION
Job Address: 12123 SW 69th Ave Tigard, OR 97223
Job Number: Conductor Wire Guage I 14
Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F) I 3.07
Date: 12/13/2011
Cable Length In Feet (source to end of line) I 529
Total Circuit Current I 2.002
Nominal System Voltage I 20.4
Panel Description: Silent Knight 5495 -5 Power Supply Minimum Device Voltage I 16
Panel No.: NAC 1
Output No.: 3 Point To Point Method EOLv ( 16.41
Circuit Within Limits ? YES
NAC Devices Mfg By: Wheelock
I I
Load Centering Method EOLv 17.15
Circuit Within Limits ? YES
Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At
No. Rating Current Previous Device Device
( Feet )
•
1 Floor 2 Electrical Room DSM- 12/24 -R (1 CKT ONLY) NA 0.0275 2 20.38
2 Floor 1 RSS- 24MCW -FW (75) STB WHT 75 Cd 0.165 86 19.33
3 Floor 1 STW (15) Strobe -Wall, White 15 Cd 0.057 26 19.04
4 Floor 1 AS- 24MCW -FW (110)H /S WHT -M 110 Cd 0.253 80 18.18
5 Floor 1 AS- 24MCW- FW,(110)H /S WHT -M 110 Cd 0.253 80 17.45,
6 Floor 1 RSS - 24MCW -FW (75) STB WHT 75 Cd 0.165 3 17.42
7 Floor 1 RSS - 24MCW -FW (75) STB WHT 75 Cd 0.165 49 17.10
8 Floor 1 AS- 24MCW -FW (75) H/S WHT -M 75 Cd 0.190 38 16.89
9 Floor 1 AS- 24MCW -FW (110)H /S WHT -M 110 Cd 0.253 45 16.68
10 Floor 1 RSS - 24MCW -FW (110) STB WHT 110 Cd 0.220 69 16.48
11 Floor 1 AS- 24MCW -FW (110)H /S WHT -M 110 Cd 0.253 51 16.41
12 16.41
13 16.41
14 16.41
15 16.41
16 16.41
17 16.41
.18 16.41
19 16.41
20 _ 16.41
TCC -A NAC Panel 1 EOLv Calc.xls OUTPUT 3
• NAC EXTENDER BATTERY CALCULATIONS
CAPITOL ELECTRIC CO., INC.
(503) 255 -9488 Office, (503) 255 -1966 Fax
JOB NAME: Tigard Corporate Center Building -A
ADDRESS: 12123 SW 69th Ave. Tigard, OR 97223 DATE: 12/13/11
PANEL DESCRIPTION: NAC 1 PREPARED BY: Dan Wilson
DEVICE TOTAL DEVICE TOTAL
STANDBY STANDBY ALARM ALARM
DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT
NAC EXTENDER
Silent Knight 5495 -5 NAC Panel 1 0.075 0.075 0.175 0.175
CIRCUIT # 1 Floor -1
0.000
Wheelock DSM- 12/24 -R Synch Module (1/2) 1 0.0275 0.028
Wheelock AS- 24MCW -FW 110 Cd H/S (M) 3 0.253 0.759
Wheelock AS- 24MCW -FW 75 Cd H/S (M) 1 0.190 0.190
Wheelock RSS- 24MCW -FW 110 Cd Strobe 1 0.220 0.220
Wheelock RSS - 24MCW -FW 75 Cd Strobe 4 0.165 0.660
Wheelock RSS - 24MCW -FW 15 Cd Strobe 0.060 0.000
0.000
0.000
TOTAL 1.857
CIRCUIT # 2 Floor -1
0.000
Wheelock DSM- 12/24 -R Synch Module (1/2) 1 0.0275 0.028
Wheelock AS- 24MCW -FW 110 Cd H/S (M) 1 0.253 0.253
Wheelock AS- 24MCW -FW 75 Cd H/S (M) 4 0.190 0.760
Wheelock RSS - 24MCW -FW 110 Cd Strobe 0.220 0.000
Wheelock RSS - 24MCW -FW 75 Cd Strobe 6 0.165 0.990
Wheelock RSS - 24MCW -FW 15 Cd Strobe 0.060 0.000
0.000
0.000
TOTAL 2.031
CIRCUIT # 3 Floor -1
0.000
Wheelock DSM- 12/24 -R Synch Module ( 1/2) 1 0.0275 0.028
Wheelock AS- 24MCW -FW 110 Cd H/S (M) 4 0.253 1.012
Wheelock AS- 24MCW -FW 75 Cd H/S (M) 1 0.190 0.190
Wheelock RSS - 24MCW -FW 110 Cd Strobe 1 0.220 0.220
Wheelock RSS - 24MCW -FW 75 Cd Strobe 3 0.165 0.495
Wheelock RSS - 24MCW -FW 15 Cd Strobe 0.060 0.000
Whlk STW 15 Cd Strobe -Wall 1 0.057 0.057
0.000
TOTAL 2.002
CIRCUIT # 4 Floor -1
0.000
Wheelock DSM- 12/24 -R Synch Module (1/2) 1 0.0275 0.028
Wheelock AS- 24MCW -FW 110 Cd H/S (M) 1 0.253 0.253
Wheelock AS- 24MCW -FW 75 Cd H/S (M) 2 0.190 0.380
Wheelock RSS - 24MCW -FW 110 Cd Strobe 0.220 0.000
Wheelock RSS - 24MCW -FW 75 Cd Strobe 4 0.165 0.660
• Wheelock RSS - 24MCW -FW 15 Cd Strobe 2 0.060 0.120
0.000
0.000
TOTAL 1.441
TCC -A NAC Panel 1 Batt Calc.xls Page 1 of 2
NAC EXTENDER BATTERY CALCULATIONS
CAPITOL ELECTRIC CO. INC.
(503) 255 -9488 Office, (503) 255 -1966 Fax
JOB NAME: Tigard Corporate Center Building -A
ADDRESS: 12123 SW 69th Ave. Tigard, OR 97223 DATE: 12/13/11
PANEL DESCRIPTION: NAC 1 PREPARED BY: Dan Wilson
DEVICE TOTAL DEVICE TOTAL
STANDBY STANDBY ALARM ALARM
DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT
AUXILIARY DEVICES _ .
0.000 0.000
0.000 0.000
0.000 0.000 •
TOTAL 0.000
STANDBY TOTAL CURRENT: I 0.075 I
STANDBY HOURS: 24
STANDBY AMP HOURS: 1.800 NAC DEVICE CURRENT I 7.329
ALARM TOTAL CURRENT: I 7.504
ALARM MINUTES: 5
ALARM AMP HOURS: 0.625
TOTAL CALCULATED AMP HOURS 2.425
APPLIED SAFETY FACTOR 1.20
MINIMUM AMP HOURS REQURED 2.910
SELECTED BATTERY SIZE I 2 EACH 12 VOLT, 7 AMP HOUR BATTERIES
TCC -A NAC Panel 1 Batt Calc.xls Page 2 of 2
Wheelock° ExcederTM Series
COOPER Notification
EDP Finally, Design and Safety Meet...
Ceiling Wall
Description:
The Wheelock ExcederTM Series of notification appliances feature
a sleek modern design that will please building owners with reduced - Save up to 48% in current draw*
total cost of ownership. Installers will benefit from its comprehensive
feature list, including the most candela options in one appliance,
low current draw, no tools needed for setting changes, voltage test - Up to 9 models now in 1 appliance
points, 12/24 VDC operation, universal mounting base and multiple
mounting options for both new and retrofit construction. up 14% installation**
- Save u to cost of installation
The Wheelock® ExcederTM Series incorporates high reliability and
high efficiency optics to minimize current draw allowing for a greater
number of appliances on the notification appliance circuit. All strobe �,���
models feature an industry first of 8 candela settings on a single ��J Sleek Modern Aesthetics
appliance. Models with an audible feature 3 sound settings (90, 95,
99 dB). All switches to change settings, can be set without the use
of a tool and are located behind the appliance to prevent tampering. F Slide Switches
Wall models feature voltage test points to take readings with a •
voltage meter for troubleshooting and AHJ inspection.
The Wheelock® ExcederTm Series of wall and ceiling notification Voltage Test Points
appliances feature a Universal Mounting Base (UMB) designed
to simplify the installation and testing of horns, strobes, and
combination horn strobes. The separate universal mounting tr4 Multiple Voltages
base can be pre -wired to allow full testing of circuit wiring before
the appliance is installed and the surface is finished. It comes
complete with a Contact Cover for protection against dirt, dust, paint Audible Settings
and damage to the contacts. The Contact Cover also acts as a so, ss, 99 dB
shunting device to allow pre -wire testing for common wiring issues.
The Contact Cover is polarized to prevent it from being installed
incorrectly and prevents the appliance from being installed while A., 8 Candela Settings "'
it is on the UMB. When the Contact Cover is removed the circuit Wall - 15/1575/30/75/95 /110/135/185
will show an open until the appliance is installed. The UMB allows Ceiling - 15/30/60/75/95/115 /150/177
for consistent installation and easy replacement of appliances if
required. Wall models provide an optional locking screw for extra _.v� Universal Mounting Base "'
secure installation, while the ceiling models provide a captivated v Ceiling and Wall
Mounts to 5 Backbox Types
screw to prevent the screw from falling during installation.
Environmentally Friendly
Low Current Draw
Compatibility and Requirements
- Synchronize using the Wheelock Sync Modules or panels with built -in Wheelock Patented Sync Protocol
- Compatible with UL "Regulated Voltage" using filtered VDC or unfiltered VRMS input voltage
- Strobes produce 1 flash per second over the "Regulated Voltage" range
• Compared to competitive models "' Patented
▪ Compared to previous models
NOTE: All CAUTIONS and WARNINGS are identified by the symbol a. All warnings are printed in bold capital letters.
A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING
• OR APPLYING THIS PRODUCT. VISIT WWW.000PERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION
INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND
SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS.
' General Notes:
General Notes:
• Strobes are designed to flash at 1 flash per second minimum over their 'Regulated Voltage Range°.
• All candela ratings represent minimum effective strobe intensity based on UL Standard 1971.
• Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32 °F to 120 °F (0°C to 49 °C) and
maximum humidity of 93% (± 2 %) UL 464 (85% UL 1971).
• Series Exceder horns are under UL Standard 464 for audible signal appliances (Indoor use only).
Low Current Draw = Fewer Power Supplies
Strobe Ratings per UL Standard 1971
UL Max Current*
24 VDC / 24 FWR 12 VDC
Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
Range VDC
ST 8.0 -33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140
STC 8.0 -33.0 0.061 0.085 0.103 0.135 0.163 0.182 0.205 0.253 0.110
Horn Strobe Ratings per UL 1971 & UL 464 at 24 VDC
UL Max Current* at 99 dBA
24 VDC 12 VDC
Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
Range VDC
HS 8.0 -33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159
HSC 8.0 -33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 0.125
UL Max Current* at 95 dBA
24 VDC 12 VDC
Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
Range VDC
HS 8.0 -33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153
HSC 8.0 -33.0 0.073 0.087 0.128 0.139 0.163 0.186 0.230 0.272 0.122
UL Max Current* at 90 dBA
24 VDC 12 VDC
Model Reg Voltaae 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
Range VDC
HS 8.0 -33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148
HSC 8.0 -33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120
Horn Ratings per UL 464 t +' _ " x .
Model Regulated Voltage 99 dB 95 dB 90 d6�:p. ap .'.::__ ,:-' : , '
Range VDC �. x. , ,
HN 16 -33.0 0.064 0.044 0.022 _.
HNC 16 -33.0 0.084 0.044 0.022 `•
HN 8.0 -17.5 0.047 0.026 0.017 4l i 0 • • °
HNC 8.0 -17.5 0.047 0.026 0.017 : •YM1' • s w3
UL max current rating is the maximum RMS current within the listed voltage range (16 -33 VDC for 24 VDC units). For strobes the
UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the
maximum listed voltage (33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions.
• I
SERIES AS
SINGLE & MULTI - CANDELA
AUDIBLE STROBE APPLIANCES
SERIES AH AUDIBLES
Description i = =
Wheelock's patented 2 -wire Series AS Audible Strobe
Appliances and Series AH Audibles offer more features • ;= ; _ =_
•
with low current draw.
Strobe options for wall mount models include 1575cd or SERIES AS SERIES AH
Wheelock's patented MCW multi - candela wall strobes
with field selectable candela settings of 15/30/75/110cd,
or the high intensity MCWH strobe with field selectable
•
135/185cd -t-'�- ----
try
Ceiling mount models incorporate Wheelock's patented 1= — " itrt :
MCC multi - candela ceiling strobe with field selectable ® "'— rasa
intensities of 15/30/75/95cd or the high intensity MCCH Multi - Candela Indicator
strobe with field selectable 115/177cd. (bottom of lens)
The audible provides a selectable choice of either a Features
continuous horn or temporal pattern (Code 3) when • Approvals include: UL Standard 1971, UL Standard 464
constant voltage from a Fire Alarm Panel (FACP) is New York City (MEA), California State Fire Marshal (CSFM),
applied. Each tone has 3 dBA settings to choose from. Factory Mutual (FM), and Chicago (BFP). See approvals by
model in Specifications and Ordering Information.
When used with the Wheelock Series SM or DSM Sync • ADA/NFPA/UFC /ANSI Compliant
Module or Wheelock PS - 12/24 - 8CP and PS - 12/24 - 8MP • Wall mount models are available with Field Selectable
Power Supplies with Patented Sync Protocol, Candela Settings of 15/30/75/110cd or 135/185cd
synchronization of the continuous horn tone provides the (Multi Candela models) or 1575cd (single candela
temporal (code 3) tone (mandated by NFPA 72) model)
•
simultaneously for all audible appliances. This ensures a Ceiling mount models are available with field selectable
candela settings of 15/30/75/95cd or 115/177cd
distinct temporal (code 3) pattern when 2 or more audibles (multi - candela ceiling models)
are within hearing distance. If not synchronized the • Selectable Continuous Horn or Temporal (Code 3).
temporal sound could overlap and not be distinctive. At • 3 Selectable dBA settings (99, 95 and 90 dBA) in both
the same time the strobes will be synchronized. This tones
provides the ability to comply with ADA guidelines • Patented 2 -Wire Audible Strobe Appliance.
concerning photosensitive epilepsy and the NFPA • Patented Universal Mounting Plate
standards when installing 2 or more visual appliances • Weatherproof models are available for outdoor use
•
within the field of view all of this plus the ability to silence Strobes produce 1 flash per second over the regulated
the audible is achieved by using only 2 wire. voltage range • 12 and 24 VDC models with wide UL "Regulated
• Voltage Range" using filtered DC or unfiltered FWR input
voltage
• The strobes can be synchronized using Wheelock's sync
modules or power supplies with built in sync protocol
• Fast installation with IN /OUT screw terminals using
For Weatherproof Series AS, See Datasheet S9004 #12 to #18 AWG wires
Copyright 2004 Wheelock Inc. All rights reserved.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A . All warnings are printed in bold capital letters.
A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR
•
APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER
APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY
DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS.
• General Notes
• Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Note that NFPA -72 (1999) specifies a flash
rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
• All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
• Series AS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32° F to 120° F (0° C to 49° C) and
maximum humidity of 93% (± 2 %).
• Series AH -24 horns are listed under UL Standard 464 for audible signal appliances (Indoor use only).
• Series AH -24WP audible appliances are listed under UL Standard 464 for indoor /outdoor use with a temperature range of -31 °F to 150 °F
( -35 °C to 66 °C) and maximum humidity of 95 %.
• "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change, UL
used the terminology "Listed Voltage Range ".
Table 1: Ratings Per UL 1971
Model Input Voltage VOC Regulated Voltage Strobe Candela (cd)
Range VDCIFWR
AS -24MCW 24 16.0 - 33.0 15/30/75/110
AS- 24MCCH 24 16.0 - 33.0 115/177
AS- 241575W 24 16.0 - 33.0 15 (75 on Ads)
AS- 121575W 12 8.0 - 17.5 15 (75 on Ads)
A5-24MCC 24 16.0 - 33.0 15/30/75/95
AS- 24MCWH 24 16.0 - 33.0 135/185
AS WP -2475W 24 16.0 - 33.0 75 Q -31'F
Table 2: dBA Ratings for 12 VDC and 24 VDC Series AS /AH 12 and 24 VDC Audible
Description Volume Reverberant dBA Anechoic
Per UL 464 Q 10H. dBAQ 10H.
High 91 99
Continuous Horn Medium 88 95
Low 83 90
High 87 99
Code 3 Horn Medium 84 95
Low 79 90
Table 3: Average RMS Current
Audible Wall Mount Audible Strobe Models Ceiling Mount Audible Strobe Models
24 VDC Models AH -24 AS- 241575W AS -24MCW AS- 24MCWH AS -24MCC AS- 24MCCH
1575cd 75cd 30cd 75cd 110cd 135cd 185cd 75cd 30cd 75cd 95cd 115cd 177cd
24 vdc 0.062 0.100 0.080 0.102 0.150 0.194 0.250 0.320 0.088 0.114 0.165 0.205 0.250 0.320
High (99) dBA
UL max' 0.080 0.121 0.088 0.125 0.200 0.267 0.355 0.480 0.095 0.138 0.221 0.285 0.355 0.480
24 vdc 0.033 0.080 0.060 0.084 0.132 0.173 0.230 0.305 0.066 0.092 0.145 0.186 0.230 0.305
Med (95) dBA
UL max' 0.043 0.107 0.074 0.110 0.190 0.253 0.340 0.465 0.080 0.122 0.201 0.269 0.340 0.465
24 vdc 0.017 0.072 0.052 0.076 0.121 0.158 0.220 0.295 0.056 0.082 0.132 0.173 0.220 0.295
Low (90) dBA
UL max' 0.021 0.100 0.068 0.105 0.182 0.245 0.335 0.460 0.074 0.113 0.198 0.263 0.335 0.460
Audible Wall Mount
12 VDC Models Audible Strobe
AH - 12 AS 121575W • RMS current ratings are per UL average RMS method. UL max current
12 vdc 0.163 0.260 rating is the maximum RMS current within the listed voltage range (16-
High (99) dBA 3 3v for 24v units). For strobes the UL max current is usually at the
UL max' 0.192 0.320 ) Y
minimum listed voltage (16v for 24v units). For audibles the max current
•
12 vdc 0.076 0.195 is usually at the maximum listed voltage (33v for 24v units). For unfiltered
Med (95) dBA FWR ratings, see installation instructions.
UL max' 0.108 0.275
12 vdc 0.039 0.175
Low (90) dBA
UL max* 0.058 0.265
•
i •
SERIES RSS & RSSP SINGLE
& MULTI - CANDELA STROBES
& STROBE PLATES
DESCRIPTION 1 - ---.: 6 .__ -A
Wheelock's patented Series RSS Strobe Appliances and L'
Series RSSP Strobe Plates have lower current draw while , . • . ,_ Y ; _ r
maintaining outstanding performance, reliability and cost •
effectiveness. These versatile appliances will satisfy
virtually all requirements for indoor, wall or ceiling mount Series RSS RSS Round
applications. Series RSSP
Strobe options for wall mount models include 1575 or _ , :,___._
Wheelock's Patented MCW multi - candela strobe with field - - - - -'
selectable candela settings of 15/30/75/110cd or the high u; —=°— 3 4 .
intensity MCWH strobe with field selectable 135/185cd. =-1 1J 15 j r sa 1;l}
EELiaZial Ceiling mount models include the patented MCC multi
-
- = = - - =_= ` —
• candela ceiling strobe with field selectable intensities of Multi - Candela Indicator
15/30/75/95cd or the high intensity MCCH strobe with (bottom of Strobe Lens)
field selectable 115/177cd.
. Features
All models may be synchronized using the Wheelock • Approvals include: UL Standard 1971, New York City
SM, DSM Sync Modules or the PS- 12/24 -8CP and (MEA), California State Fire Marshal (CSFM), Factory
PS- 12/24 -8MP Power Supplies with Wheelock's Patented Mutual (FM), and Chicago (BFP) See approvals by
Sync Protocol. Synchronized strobes can eliminate model in Specifications and Ordering Information
possible restrictions on the number of strobes in the field • ADA/NFPA/UFC /ANSI compliant. Meets OSHA 29
of view. Wheelock's synchronized strobes offer an easy Part 1910.165
way to comply with ADA recommendations concerning • Wall mount Multi - Candela models are available
photosensitive epilepsy as well as meeting the with Field Selectable Candela Settings of 15/30/
requirements of NFPA 72. 75/110cd or 135/185cd. Single Candela models
are available in 1575cd
Wheelock's Series RSS Strobes employ a Patented • Ceiling mount Multi - Candela models are
Integral Strobe Mounting Plate that can be mounted to a available with field selectable candela settings of
single gang, double gang, 4" square, 100mm European 15/30/75/95cd or 115/177cd. (Round or Square)
backboxes or the SHBB surface backbox. If the flush • Strobes produce 1 flash per second over the
backbox has side or top space between it and the finished regulated voltage range
wall, the NATP (Notification Appliance Trimplate) may be • 12 and 24 VDC models with wide UL "Regulated
used. It provides an additional .65" of trim for the Appliance. Voltage" using filtered (DC) or unfiltered VRMS input
An attractive cover plate is provided for a clean, finished voltage
appearance on all models. • Synchronize using Wheelock's sync modules or power
supplies with built -in sync protocol
• The Series RSSP Multi - Candela Strobe Plates are a cost • Fast installation with IN /OUT screw terminals using
effective way to retrofit required wall strobe appliances to #12 to #18 AWG wire
bells, horns, chimes, multitones or speakers and easily
mounts to standard 4" backboxes or for surface mount
use with Wheelock's SBL2 surface backbox.
For Weatherproof Series RSS See Datatsheet S9004
Copyright 2004 Wheelock, Inc. All rights reserved.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, •
SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN
. IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN
PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS.
General Notes
• Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Note that NFPA -72 specifies a flash rate of
1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
• All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
• Series RSS & RSSP Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32° F to 120° F (0 C to
49° C) and maximum humidity of 93% (± 2 %).
• "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change, UL used the
terminology "Listed Voltage Range ".
Table 1: Average RMS Current*
RSSIRSSP RSSIRSSP - Wall Mount RSS - Ceiling Mount
• 24VDC 241575W 24MCW 24MCWH 24MCC 24MCCH
Models
1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd
24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270
UL max* 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420
RSS /RSSP RSS /RSSP * RMS current ratings are per UL average RMS method. UL max current
24VDC Wall Mount rating is the maximum RMS current within the listed voltage range (16 -33v
Models 121575W for 24v units). For strobes the UL max current is usually at the minimum
12 vdc 0.152 listed voltage (16v for 24v units). For audibles the max current is usually at
the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings,
UL max* 0.255 see installation instructions.
Table 2: Audibles /Speakers for RSSP Strobe Plate
Product Series
•
Multitone Appliances AMT, MT
Horns AH, NH, HS
•
Motor Bells MB- G6 /G10
Speakers ET- 1010/1080, E70, E170
Chimes CH70
Lj WARNING: CONTACT WHEELOCK FOR THE CURRENT "INSTALLATION INSTRUCTIONS" AND "GENERAL INFORMATION" SHEET (P82380) ON THESE
PRODUCTS. THESE DOCUMENTS UNDERGO PERIODIC CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS.
THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING:
• TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES.
• FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS.
• ADDING, REPLACING OR CHANGING APPLIANCES OR CHANGING CANDELA SETTINGS WILL AFFECT CURRENT DRAW. RECALCULATE CURRENT
DRAW TO INSURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY ALL APPLIANCES DO NOT EXCEED THE RATED CAPACITY
OF THE POWER SOURCE OR FUSES.
• COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW.
• THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR "REGULATED VOLTAGE RANGE ".
. • INSTALLATION OF 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS.
• INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES.
•
• USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBES ON CODED OR
INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBES MAY NOT FLASH.
• FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER
INSTALLATION, APPLICATION, AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY
DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS.
• CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE
PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS.