Specifications FPS2. .01 cro o99 tqcn 'Ffre & Building R E C E I V E D SE P . / Products 1 4 201 • Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 CITY OF TIGARD BUILDING DIVISION Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K- factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage tained when exposed to corrosive at- General mospheres. Although corrosion resis- tant coated sprinklers have passed the ,,. Description standard corrosion tests of the appli -_ . ' ' cable approval agencies, the testing is - The Tyco® Series TY -FRB, 2.8, 4.2, not representative of all possible cor- 5.6, and 8.0 K- factor, Upright and Pen- rosive atmospheres. Consequently, it T IR i dent Sprinklers described in this data is recommended that the end user be I sheet are quick response - standard consulted with respect to the suitability coverage, decorative 3 mm glass bulb of these coatings for any given corro- '. _ • type spray sprinklers designed for use sive environment. The effects of ambi- in light or ordinary hazard, commercial ent temperature, concentration of — . .. � occupancies such as banks, hotels, chemicals, and gas /chemical velocity, `' shopping malls, etc. should be considered, as a minimum, The recessed version of the Series along with the corrosive nature of the TY -FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be exposed. �_,�� \ plicable, is intended for use in areas p with a finished ceiling. It uses either a An intermediate level versions of the r ' two -piece Style 10 (1/2 inch NPT) or Series TY -FRB Pendent Sprinklers — ' . � N Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet r /.,�" cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de- recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780 (19,1 mm) of total adjustment from the - flush pendent position, or a two-piece WARNINGS e . . Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY - FRB Sprinklers de ' 0 inch NPT) Recessed Escutcheon with scribed herein must be installed and --+"r .. 1/4 inch (6,4 mm) of recessed adjust maintained in compliance with this ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica- total adjustment from the flush pen ble standards of the National Fire Pro - dent position. The adjustment pro tection Association, in addition to the vided by the Recessed Escutcheon re - standards of any other authorities hav- Model /Sprinkler duces the accuracy to which the fixed ing jurisdiction. Failure to do so may pipe drops to the sprinklers must be impair the performance of these de- Identification cut. vices. Corrosion resistant coatings, where The owner is responsible for maintain- Numbers applicable, are utilized to extend the ing their fire protection system and de- life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2 "NPT that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2 "NPT manufacturer should be contacted TY2131 - Upright 4.2K, 1/2 "NPT with any questions. TY2231 - Pendent 4.2K, 1/2 "NPT IMPORTANT TY3131 - Upright 5.6K, 1/2 "NPT Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2 "NPT Sheet TFP700 for the "INSTALLER TY4131 - Upright 8.0K, 3/4 "NPT WARNING" that provides cautions TY4231 - Pendent 8.0K, 314 "NPT with respect to handling and instal- TY4831 Upright 8.0K, 1/2 "NPT lation of sprinkler systems and corn- TY4931 Pendent 8.0K, 1/2 "NPT ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail . to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 AUGUST, 2007 TFP171 1 Page 2 of 10 TFP1 71 ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING NOMINAL RECESSED - SURFACE 1/2" MAKE -IN ESCUTCHEON SSU PT DEFLECTOR i _ 6 1 11'1 - '1'11'1 1 r"'T�j � 7/16" '� 2 -1/4" } i ��li _ =, i t 4 (57,2 mm) 1 =A OM (11,1 mm) NOMINAL I I MAKE -IN I 2 1-9/16" I 011 �r 2-3/16" t ili � 3 (39,7 mm) WRENCH 1 (55,6 mm) FLATS =_ 1 ■ i 1 SSP DEFLECTOR * -- •' - 2 -7/8" (73,0 mm) DIA. � 1/2" NPT f 7 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. . Screw FIGURE 1 QUICK RESPONSE SERIES TY -FRB UPRIGHT (171131) AND PENDENT (TY1231) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT • ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING NOMINAL RECESSED SURFACE 1/2" AKE -IN ESCUTCHEON DEFLECTOR 13• 7/16" '�' 5 2 -3/16" '!� (11,1 mm) t (55,6 mm) =A ,A�— I NOMINAL I MAKE -IN 1 -1/2" I ��� i 2 3/16" 'da 2 (38,1 mm) I 110 WRENCH (55,6 mm) 4 y . II FLATS ----1-----4-- 0,0 3 1 i i 6 i SSP DEFLECTOR * -- •• - 2 -7/8" (73,0 mm) DIA. 1/2" NPT f 1 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw FIGURE 2 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT il TFP171 Page 3 of 10 ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING NOMINAL RECESSED ' SURFACE 1/2" FT MAKE -IN ESCUTCHEON DEFLECTOR F— —_________.. — � c ! .= , 5 2-3/16" �� ' —� 7/1m - -- — I (11,1 mm) I (55,6 mm) 1 1 ■ � 7.— 4 NOMINAL MAK -IN , I 1-1/2" I 41111-111 I `� , 2 -3/16" ... 4 2 ____i_ ( 38,1 mm) WRENCH (55,6 mm) 3 1 • �,�r -• • -:���r FLATS I 0 To i SSP DEFLECTOR 2 -7/8" (73,0 mm) DIA. I 1/2" NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION • 1 - Frame 3 - Sealing 4-Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw • FIGURE 3 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40 PLATE SEATING NOMINAL RECESSED SURFACE NP MAKE -IN ESCUTCHEON T DEFLECTOR 6 * 1 /2" Imil 5 2- 5/16" `� � � ( 12 ,7 mm) i (58,7 mm) 11111=1111 ,� 1- - I NOMINAL 4 l L "-IN M AKE -IN , li 1-9/16" I I (5 -1 /4" 1 v f 2 (39,7 WRENCH l �i 9 1 • - --- • FLATS 1 Lf 3 SSP DEFLECTOR * 2 -7/8" (73,0 mm) DIA. 3/4" NPT 1 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4-Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw FIGURE 4 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT • Page 4 of 10 TFP171 7/16" (11,1 mm) 1/2" NOMINAL SSU NPT MAKE -IN DEFLECTOR *6 I ° rrrr - � '�n, tfr1 *l�' e Y 1 !g 5 2 -1/4" 2 -3/16" I (57,2 mm) =�1 I (55,6 mm) I ' 4 19/16" I WR r V __ L � (39,7 mm) FLT SSP 1 DEFLECTOR CROSS PENDENT UPRIGHT SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw FIGURE 5 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS 8.0 K- FACTOR, 1/2 INCH NPT Technical Operation Data The glass Bulb contains a fluid which . - expands when exposed to heat. When Approvals the rated temperature is reached, the UL and C -UL Listed. fluid expands sufficiently to shatter the FM, LPCB, and NYC Approved. glass Bulb, allowing the sprinkler to . (Refer to Table A and B for complete activate and water to flow. approval information including corro- sion resistant status.) Design • Maximum Working Pressure Refer to Table C. Criteria Discharge Coefficient K = 2.8 GPM /psi / (40,3 LPM /bar1/2) The Series TY -FRB Pendent and Up- K = 4.2 GPM /psi / (60,5 LPM /bar1 /2) right Sprinklers are intended for fire K = 5.6 GPM /psi / (80,6 LPM /bar1/2) protection systems designed in ac- K = 8.0 GPM /psi / (115,2 LPM /bar1 /) cordance with the standard installation rules recognized by the applicable Temperature Ratings Listing or Approval agency (e.g., UL Refer to Table A and B Listing is based on the requirements of Finishes NFPA 13, and FM Approval is based Sprinkler: Refer to Table A and B. on the requirements of FM's Loss Pre - Recessed Escutcheon: White Coated, vention Data Sheets ). Only the Style • Chrome Plated, or Brass Plated. 10, 20, 30, or 40 Recessed Escutch- eon, as applicable, is to be used for recessed pendent installations. Physical Characteristics Frame Bronze E Button Brass /Copper Sealing Assembly 2 Beryllium Nickel w /Teflont a Bulb Glass 2 - Compression Screw Bronze N Deflector Copper /Bronze 0 Bushing (K =2.8) Bronze • 0 0 0 TFP171 Page 5 of 10 SPRINKLER FINISH (See Note 7) K TYPE TEMP. BULB NATURAL CHROME WHITE"** LIQUID BRASS PLATED POLYESTER 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY1231) 1 2 3 5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 2.8 (TY1131) 286"F/141°C Blue 1/2" NPT 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT (TY1231)* 175 °F /79 °C Yellow Figure 6 200 °F /93 °C Green 1, 2, 5 • 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT (TY1231)** 175 °F /79 °C Yellow Figure 7 200 °F /93 °C Green 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY2231) and 175 °Ff79 °C Yellow UPRIGHT 200 °F /93 °C Green (TY2131) 4.2 4.2 286 °F /141 °C Blue 1 2 1/2" NPT 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT (TY2231)* 175 °F /79 °C Yellow Figure 8 200"F/93°C Green 135"F/57°C Orange • RECESSED 155 °F /68 °C Red PENDENT (TY2231) ** 175 °Ff79 °C Yellow • Figure 9 200 °F /93 °C Green NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Re- sponse Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin- klers. 5. Approved by the City of New York under MEA 354 -01 -E. 7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- klers are UL and C -UL Listed as Corrosion Resistant Sprinklers. * Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. ** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. * ** Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE A LABORATORY LISTINGS AND APPROVALS 2.8 AND 4.2 K- FACTOR SPRINKLERS • • Page 6 of 10 TFP171 • SPRINKLER FINISH (See Note 8) K TYPE TEMP. BULB NATURAL CHROME WHITE*" LEAD LIQUID BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange PENDENT 155"F/68°C Red (TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 5.6 (TY3131) 286 °F /141 °C Blue 1/2" NPT 135 °F /57 °C Orange RECESSED 155"F/68°C Red PENDENT 1, 2, 4, 5 N/A (TY3231)* 175 °F /79 °C Yellow Figure 10 200 °F /93 °C Green 135"F/57°C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 (TY3231)" 175 °F /79 °C Yellow N/A Figure 11 200 °F /93 °C Green 135 °F /57 °C Orange PENDENT 155"F/68°C Red (TY4231) and 175 °F /79 °C Yellow 1, 2, 5 1, 2, 3, 4, 5, 6, 7 UPRIGHT 200"F/93°C Green 8.0 (TY4131) 286 °F /141 °C Blue 3/4" NPT 135 °F /57 °C Green RECESSED 155 °F /68 °C Orange PENDENT 1, 2, 4, 5 N/A (TY4231)* 175 °F /79 °C Red Figure 12 200"F/93°C Yellow • 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 N/A (TY4231)" 175"F/79°C Yellow Figure 13 200 °F /93 °C Green 135"F/57°C Orange PENDENT 155 °F /68 °C Red 8.0 (TY4931) 1/2" and 175 °F /79 °C Yellow 1, 2, 5 1,2,4,5,6 NPT UPRIGHT 200"F/93°C Green (TY4831) 286"F/141°C Blue NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428 - 3377). 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion Resistant Sprinklers. • Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. " Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. ▪ Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE B • LABORATORY LISTINGS AND APPROVALS 5.6 AND 8.0 K- FACTOR SPRINKLERS TFP171 Page 7 of 10 SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD BRASS PLATED POLYESTER COATED PENDENT (TY3231) and 2 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A 1/2" RECESSED PENDENT NPT (TY323) PENDENT (TY4231) and 4 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A 3/4" RECESSED PENDENT NPT (TY4231) •• PENDENT (TY3231) and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR) 5.6 UPRIGHT (TY3131) OR 1/2" RECESSED PENDENT 175 PSI (12,1 BAR) NPT (TY3231) N/A (SEE NOTE 1) PENDENT (TY4231) and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR) 8 UPRIGHT (TY4131) 3/4" RECESSED PENDENT NPT (TY4231) N/A 8.0 PENDENT (TY4931) 1/2" and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR) NPT UPRIGHT (TY4831) NOTES: 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C -UL); and , the Approval by the City of New York. • TABLE C, MAXIMUM WORKING PRESSURE tained with a torque of 10 to 20 ft.lbs. the sprinkler into the sprinkler fitting. Installation (13,4 to 26,8 Nm). A maximum of 30 Step 3. Tighten the sprinkler into the ft.lbs. (40,7Nm) of torque is to be used p T W - the using only ler e y he he y The Series TY -FRB Sprinklers must to install sprinklers with 3/4 NPT con- sprinkler ft Wrench (Rey f. Figure W- W-Type be installed in accordance with the fol- nections. Higher levels of torque may With reference to .(Re 2, 3, 4, lowing instructions: distort the sprinkler inlet and cause and 5, the W-Type 6 Sprinkler Wrench NOTES leakage or impairment of the sprinkler. is to be applied to the sprinkler wrench • Do not install any bulb type sprinkler if Do not attempt to make -up for insuffi- flats. the bulb is cracked or there is a loss of cient adjustment in the escutcheon The Series TY - FRB Recessed Pen- liquid from the bulb. With the sprinkler plate by under- or over - tightening the dent Sprinklers must be installed in held horizontally, a small air bubble sprinkler. Readjust the position of the accordance with the following instruc- should be present. The diameter of the sprinkler fitting to suit. tions. air bubble is approximately 1/16 inch The Series TY - FRB Pendent and Up - Step A. After installing the Style 10. (1,6 mm) for the 135 °F /57 °C to 3/32 right Sprinklers must be installed in 20, 30, or 40 Mounting Plate, as appli- inch (2,4 mm) for the 286 °F /141 °C accordance with the following instruc- cable, over the sprinkler threads and temperature ratings. tions. with pipe thread sealant applied to the A leak tight 1/2 inch NPT sprinklerjoint Step 1. Pendent sprinklers are to be pipe threads, hand tighten the sprin- should be obtained with a torque of 7 installed in the pendent position, and kler into the sprinkler fitting. to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- upright sprinklers are to be installed in Step B. Tighten the sprinkler into the mum of21 ft. lbs. (28,5 Nm) of torque the upright position. sprinkler fitting using only the W -Type may be used to install sprinklers with 7 Recessed Sprinkler Wrench (Ref. • 1/2 NPT connections. A leak tight 3/4 Step 2. With pipe thread sealant ap- Figure 15). With reference to Figure 1, inch NPT sprinkler joint should be ob- plied to the pipe threads, hand tighten 2, 3, and 4, the W -Type 7 Recessed Page 8 of 10 TFP171 2 -7/8" DIA. 2 -7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/211/8" (73,0 mm) 1/2" (12,7 mm) • (15,9±6,4 mm) 1/4" (6,4 mm) (12,7±3,2 mm) 2 -1l4' DIA. 2 -1/4° DIA. 1/4 "(6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8' 1/8" • ?, (3,2 mm) •� ( 3,2 m m) �.L / c ice° la , MOUNTING �1I' MOUNTING A SURFAC . SURFACE . v Are-re-c., i CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1 -5/16" (33,3 mm) TY -FRB 13/16" (20,6 mm) TY -FRB 1 -1/16" (27,0 mm) FIGURE 6 FIGURE 7 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA. 2 -7/8° DIA. (73,0 mm) 3/4" (19,1 mm) (73,0 mm) 5/8±1/4" 112±1/8" 1/2" (12,7 mm) (15,916,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8° 1/8" M NW 1 (3 mm) (3,2 °1��11) X1811; . __ �� il r f , MOUNTING 1,l' I . SURFACE MOUNTING , . SURFACE - - - - - -- CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm) TY -FRB 3/4" (19,1 mm) TY-FRB 1° (25,4 mm) FIGURE 8 FIGURE 9 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT Sprinkler Wrench is to be applied to work on the fire protection system that altered after leaving the factory. Modi- the sprinkler wrench flats. it controls, permission to shut down the fied sprinklers must be replaced. Step C. After the e ceiling has been in- affected fire protection system must be Sprinklers that have been exposed to stalled the finish coat has been n- obtained from the proper authorities corrosive products of combustion, but s s slide on in the Style 10, 20, been p- and all personnel who maybe affected have not operated, should be replaced or 40 Closure over the Series TY -FRB by this action must be notified if they cannot be completely cleaned Sprinkler and push the Closure over The owner must assure that the sprin by wiping the sprinkler with a cloth or the Mounting Plate until its flange klers are not used for hanging of any by brushing it with a soft bristle brush. comes in contact with the ceiling. objects; otherwise, non - operation in Care must be exercised to avoid dam - and the event ofa fire or inadvertent opera age to the sprinklers - before, during, are ani� Lion may result. and after installation. Sprinklers dam - Absence of an escutcheon, which is aged by dropping, striking, wrench used to cover a clearance hole, may twist/slippage, or the like, must be re- Maintenance delay the time to sprinkler operation in placed. Also, replace any sprinkle The Series TY -FRB Sprinklers must a fire situation. that has a cracked bulb or that has lost p liquid from its bulb. (Ref. Installation be maintained and serviced in accord- Sprinklers that are found to be leaking Section). ance with the following instructions: or exhibiting visible signs of corrosion • must be replaced. Frequent visual inspections are rec- NOTES ommended to be initially performed for • Before closing a fire protection system Automatic sprinklers must never be corrosion resistant coated sprinklers, main control valve for maintenance painted, plated, coated or otherwise after the installation has been com- TFP171 Page 9 of 10 2 -7/8" DIA. 2 -7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) (73,0 mm) 1/2±1/8" 1/2" (12,7 mm) • (15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm 2 -1/4" DIA. --.. II 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" = �l�l�i ( mm) = �1. I (3,2 mm) %//' 4 ,■ � � , , 1 } \ - ' MOUNTING 1111 MOUNTING SURFAC SURFACE _= ' � r CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm) TY -FRB 3/4" (19,1 mm) TY -FRB 1' (25,4 mm) FIGURE 10 FIGURE 11 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT 2 -7/8' DIA. 2 -7/8" DIA. 5/8±1/4" (73.0 mm) 3/4" (19,1 mm) 1/2 ±1/8" (73,0 mm) 1/2" (12,7 mm) (15.9±6,4 mm) 2 -1/4' DIA. 1 1/4' (6.4 mm) (12,7±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (57,2 mm) FACE OF MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" I 1/8" (3,2 mm) (3,2 mm) mill (3,2 r rlll �� I — I� MOUNTING � I MOUNTING � I SURFACE l • SURFACE ir CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1 -5/16" (33,3 mm) TY -FRB 13/16" (20,6 mm) TY -FRB 1 -1/16" (27,0 mm) FIGURE 12 FIGURE 13 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT pleted, to verify the integrity of the cor- e WRENCH rosion resistant coating. Thereafter, RECESS annual inspections per NFPA 25 should suffice; however, instead of.in- WRENCH RECESS I��0 specting from the floor level, a random (END "A" USED FOR sampling of close -up visual inspec- 1/2" NPT MODELS) tions should be made, so as to better - determine the exact sprinkler condi- tion and the long term integrity of the ..,., corrosion resistant coating, as it may WRENCH RECESS be affected by the corrosive conditions (END "B" USED FOR PUSH WRENCH IN TO ENSURE present. 3/4" NPT MODELS ENGAGEMENT The owner is responsible for the in- FIGURE 14 WITH SPRINKLER WRENCHING AREA spection, testing, and maintenance of W -TYPE 6 SPRINKLER their fire protection system and de- WRENCH FIGURE 15 vices in compliance with this docu- W -TYPE 7 RECESSED • ment, as well as with the applicable SPRINKLER WRENCH facturer should be contacted relative standards of the National Fire Protec- to any questions. tion Association (e.g., NFPA 25), in Inspection Service in accordance with addition to the standards of any other It is recommended that automatic local requirements and /or national authorities having jurisdiction. The in- sprinkler systems be inspected, codes. stalling contractor or sprinkler manu- tested, and maintained by a qualified . Page 10 of 10 TFP171 P/N 57 - XXX - X - XXX I I TEMPERATURE MODEUSIN RATING • SPRINKLER 330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135 °F /57 °C 331 2.8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C 340 4.2K UPRIGHT (1/2 "NPT) . TY2131 4 WHITE POLYESTER 175 175 °F /79 °C 341 4.2K PENDENT (1/2 "NPT) TY2231 3 WHITE (RAL9010)* 200 200 °F /93 °C 370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C 371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED 390 8.0K UPRIGHT (3/4 "NPT) TY4131 391 8.0K PENDENT (3/4 "NPT) TY4231 • Eastern Hemisphere sales only. 360 8.0K UPRIGHT (1/2 "NPT) TY4831' 361 8.0K PENDENT (1/2 "NPT) TY4931' TABLE D PART NUMBER SELECTION SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS In no event shall TFBP be liable, in Limited contract, tort, strict liability or under Ordering Warranty any other legal theory, for incidental, indirect, special or consequential dam- Procedure ages, including but not limited to labor Products manufactured by Tyco Fire & charges, regardless of whether TFBP When placing an order, indicate the Building Products (TFBP) are war- was informed about the possibility of full product name. Refer to the Price ranted solely to the original Buyer for such damages, and in no event shall List for complete listing of Part Num- ten (10) years against defects in mate- TFBP's liability exceed an amount bers. rial and workmanship when paid for equal to the sales price. Contact your local distributor for avail - and properly installed and maintained under normal use and service. This The foregoing warranty is made in lieu ability. warranty will expire ten (10) years of any and all other warranties. ex- from date of shipment by TFBP. No press or implied including warranties Sprinkler Assemblies with NPT warranty is given for products or corn- of merchantability and fitness for a par- Thread Connections: ponents manufactured by companies tjcular purpose. Specify: (Specify Model /SIN), Quick Response, (specify K- factor), (specify not affiliated by ownership with TFBP This limited warranty sets forth the ex- temperature rating), Series TY -FRB or for products and components which clusive remedy for claims based on (specify Pendent or Upright) Sprinkler have been subject to misuse, improper failure of or defect in products, materi- with (specify type of finish or coating), installation, corrosion, or which have als or components, whether the claim P/N (specify from Table D). not been installed, maintained, modi- is made in contract, tort, strict liability tied or repaired in accordance with ap- or any other legal theory. Recessed Escutcheon: plicable Standards of the National Fire Protection Association, and /or the This warranty will apply to the full ex- Specify: Style (10, 20, 30, or 40) Re- standards of any other. Authorities tent permitted by law. The invalidity, in cessed Escutcheon with (specify *) fin - Having Jurisdiction. Materials found whole or part, of any portion of this ish, P/N (specify*). by TFBP to be defective shall be either warranty will not affect the remainder. repaired or replaced, at TFBP's sole Refer to Technical Data Sheet TFP770. option. TFBP neither assumes, nor Sprinkler Wrench: authorizes any person to assume for it, Specify: W -Type 6 Sprinkler Wrench, any other obligation in connection with P/N 56- 000 -6 -387. the sale of products or parts of prod- ucts. TFBP shall not be responsible for Specify: W -Type 7 Sprinkler Wrench, sprinkler system design errors or inac- P/N 56- 850 -4 -001. curate or incomplete information sup - plied by Buyer or Buyer's repre- sentatives. TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 .. Vico Fire & Building . . Products ' Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series RFII — 5.6 K- factor "Royal Flush II" Pendent Concealed Sprinklers Quick & Standard Response, Standard Coverage General Cap. The Protective Cap is temporarily removed for installation, and then it can be replaced to help protect the allik Description sprinkler while the ceiling is being in- stalled or finished. The tip of the Pro - The Series RFII Quick Response tective Cap can also be used to mark (3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas- _ mm bulb), 5.6 K- Factor, "Royal Flush ter board, ceiling tiles, etc. by gently .; J II" Concealed Pendent Sprinklers are pushing ceiling product against - -- P pushin the ceilin roduct a ainst the _ L decorative sprinklers featuring a flat Protective Cap. When the ceiling in- cover plate designed to conceal the stallation is complete the Protective sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate tecturally sensitive areas such as hotel Assembly installed. lobbies, office buildings, churches, and restaurants. As an option, the Series RFII Standard • Response (5 mm bulb) "Royal Flush II" Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be sembly that conceals the sprinkler op- fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175 erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM. The separable two -piece design of the intended for sensitive areas where it is Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical blies allows installation of the sprin- through the cover plate from the area klers and pressure testing of the fire above the ceiling. Data • protection system prior to installation WARNINGS of a suspended ceiling or application The Series RFII Concealed Pendent Approvals for Series RFII of the finish coating to a fixed ceiling. PP They also permit removal of sus Sprinklers described herein must be UL and C -UL Listed. FM Approved. • pended ceiling panels for access to installed and maintained in compli NYC under MEA 353 -01 -E. LPCB (Ref. building service equipment without ance with this document, as well as No. 094a/09 for TY3551 & 094a/10 for having to first shut down the fire pro wi the applicable standards of the TY3531) Approved. tection system and remove sprinklers. Nat Fire Protection Association The approvals apply only to the serv- rwo pig in addition to the standards of any ice conditions indicated in the Design Also, the separable two-piece design f the the Sprinkler other authorities having jurisdiction. . Criteria section and maximum pres- inch (12,7 mm) of vertical p provides i two-piece s for ign for 1/2 Failure to do so may impair the per- sure ratings indicated in the formance of these devices. Model/Sprinkler Identification Num- to reduce the accuracy to which the P length of fixed pipe drops to the sprin The owner is responsible for maintain tiers section. klers must be cut. mg their fire protection system and de Approvals for Air & Dust Seal vices in proper operating condition. (Part #10908100) The Series RFII Sprinklers are The installing contractor or sprinkler g p RFII and C-UL Listed for use with the shipped with a Disposable Protective manufacturer should be contacted RFII (TY3551 & TY3504) Standard Re- with any questions: sponse Concealed Sprinkler. IMPORTANT Temperature Ratings Always refer to Technical Data Model /Sprinkler 155F/68C Sprinkler - 135F/57C Plate Sheet TFP700 for the `INSTALLER 200F/93C Sprinkler - 165F/74C Plate WARNING" that provides cautions Identification Discharge Coefficient 1i2 with respect to handling and instal- K = 5.6 GPM /psi / (80,6 LPM/bar ) lation of sprinkler systems and com- Numbers Adjustment ponents. Improper handling and in- 1/2 inch (12,7 mm) stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm Finishes a sprinkler system or its compo bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass nents and cause the sprinkler to fail UL, C -UL, FM, LPCB and NYC. Plated, or White Painted (Custom paint to operate in a fire situation or cause TY3504 (5 mm bulb) & TY3505 (3 mm matches and colors other than white it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by are available on request.) Page 1 of 4 JULY, 2004 TFP181 Page 2 of 4 TFP181 Physical Characteristics 1/2• NPT r Frame Bronze ; ASSEMBLY . Support Cup . Chrome Plated Steel Guide Pins Stainless Steel 11, ` � Deflector Bronze FRAME , ,1 � Compression Screw Brass i � 1n % Ito e CAP • Bulb Glass i �- Cap Bronze or Copper SUPPORT t Sealing Assembly CUP WITH BULB Beryllium Nickel w/Teflon' ROLL FORMED ) MIMI ; Cover Plate Brass THREADS ; _ �I' Retainer Brass Ejection Spring . . . . Stainless Steel / !Air Alar77( ,, A,,'1 COMPRESSION GUIDE \ I � SCREW Patents PINS 2 U.S.A. 4,014,388 (2) I I .___ _ 1 DEFLECTOR i , (DROPPED Op eration DEFLECTOR ; -i_ _____1;_,,; ' POSITION) When exposed to heat from a fire, the I SPRINKLER/SUPPORTCUP Cover Plate, which is normally sol- I ASSEMBLY dered to the Retainer at three points, falls away to expose the Sprinkler As- THREAD INTO I RETAINER sembly. At this point the Deflector sup- SUPPORT CUP • I` WITH THREAD y p p UNTIL MOUNTING O • O ) DIMPLES ported by the Guide Pins drops down SURFACE IS to its operational position. FLUSH WITH EJECTION The glass Bulb contains a fluid that CEILING SPRING expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the r � glass Bulb, activating the sprinkler and allowing water to flow. SOLDER COVER TABS (3) COVER PLATE/RETAINER PLATE ASSEMBLY . Design FIGURE 1 Criteria SERIES RFII CONCEALED SPRINKLER ASSEMBLY . The RFII (TY3551 & TY3504), 5 mm Bulb Type, Concealed Pendent Sprin- Step 1. The sprinkler must only be klers are UL and C -UL Listed as stand- Installation installed in the pendent position and and response - standard spray sprin- with the centerline of the sprinkler per - klers for use in accordance with the The Series RFII must be installed in pendicular to the mounting surface. current NFPA standard. They are FM accordance with the following instruc- Step 2. Remove the Protective Cap. Approved as standard response - tions: standard spray sprinklers for use in • Step 3. With pipe thread sealant ap- accordance with the current FM Loss NOTES plied to the pipe threads, hand tighten Prevention Data Sheets. Do not install any bulb type sprinkler if the sprinkler into the sprinkler fitting. The RFII (TY3531 & TY3505) 3 mm the bulb is cracked or there is a loss of Step 4. Wrench tighten the sprinkler liquid from the bulb. With the sprinkler usin only the RFII Sp Sprinkler Wrench Bulb Type, Concealed Pendent Sprin- held horizontally, a small air bubble g y (Ref. Figure 3). The RFII Sprinkler klers are UL and C - Listed as quick should be present. The diameter of the response - standard spray sprinklers air bubble is approximately 1/16 inch W rench i s to be applied to the Sprin for use in accordance with the current (1,6 mm) for the 155 °F /68 °C and 3/32 kler as shown in Figure 3. NFPA standard. They are FM Ap- inch (2,4 mm) for the 200 °F /93 °C tern Step 5. Replace the Protective Cap proved as standard response - stand- perature ratings. (Ref. Figure 4) by pushing it upwards and spray sprinklers for use in accord- until it bottoms out against the Support ante with the current FM Loss A leak tight 1/2 inch NPT sprinklerjoint Cup. The Protective Cap helps prevent Prevention Data Sheets. should be obtained with a torque o 7 damage to the Deflector and Arms dur- The Series RFII Concealed Pendent to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi ing ceiling installation and /or during S i Seri s are C listed and a mum of 21 ft.lbs. (28,5 Nm) of torque application of the finish coating of the p y p - is to be used to install sprinklers. proved with the Series RFII Concealed Higher levels of torque may distort the ceiling. It may also be used to locate Cover Plates having a metallic or white sprinkler inlet with consequent leak the center of the clearance hole by painted finish. age or impairment of the sprinkler. gently pushing the ceiling material up The Series RFII must not be used in against the center point of the Protec- Do not attempt to compensate for in- five Cap. applications where the air pressure sufficient adjustment in the Sprinkler above the ceiling is greater than that Assembly by under or over - tightening NOTE below. Down drafts through the Sup the Sprinkler /Support Cup Assembly. A.s long as the Protective Cap remains ' port Cup could delay sprinkler opera Readjust the position of the sprinkler in place, the system is considered to tion in a fire situation. fitting to suit. be "Out of Service ". Registered Trademark of DuPont • , TFP181 Page 3 of 4 FACE OF CLEARANCE HOLE CLEARANCE — SPRINKLER DIAMETER - HOLE . FITTING I DIMENSION C \ rya SPRINKLER SUPPORT CUP \ r A _ , w 1/2° (12,7 mm) MI THUEN D ADJUSTMENT FACE OF CEILING, RETAINING RING I FIGURE 4 MOUNTING D ISPOSABLE PROTECTIVE CAP SURFACE �/ d=,, \ / / \ / Step 6. After the ceiling has been com- pleted with the 2-1/2 inch (63,5 mm) m� I I - 11� diameter clearance hole and in prepa- ration for installing the Cover Plate As- �_� �_ _ ��_� sembly, remove and discard the Pro - -1-- tective Cap, and verify that the 3/16° to 11/16" MANUFACTURER DEFLECTOR COVER PLATE Deflector moves up and down freely. If (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER the Sprinkler has been damaged and REFERENCE 3/32° (2,4 mm) POSITION ASSEMBLY the Deflector does not move up and down freely, replace the entire Sprin- COVER PLATE COVER PLATE kler assembly. Do not attempt to mod- - PROFILE DEPTH DIAMETER - ify or repair a damaged sprinkler. DIMENSION B DIMENSION A Step 7. When installing an Air and Dust Seal, refer to Figure 5, otherwise proceed to Step 8. To attach the Air and A: 3 -1/4" (82,6 mm) C: 2 -3/8" to 2 -5/8° (60,3 to 66,7 mm) Dust Seal, verify the angle of the out - B: 3/16" (4,8 mm) D: 1 -3/4" to 2 -1/4° (44,5 to 57,2 mm) side edge of the seal is oriented ac- cording to Figure 5. Start the edge of • FIGURE 2 the Retainer in the grooved slot of the SERIES RFII CONCEALED SPRINKLER Air and Dust Seal and continue around INSTALLATION DIMENSIONS the retainer until the entire Air and Dust Seal is engaged. NOTE The Air and Dust Seal is only to be installed on the periphery of the Re- .___ '--- — . '. ° tamer. ► = FRAME – � ARM � Step 8. Screw on the Cover Plate /Re- '— tamer Assembly until the Retainer - I J _ . J I � Figure 2 (or Air and Dust Seal - Figure SUPPORT - – 5) contacts with the ceiling. Do not - i CUP I I continue to screw on the Cover Plate /Retainer Assembly such that it WW1 I lifts a ceiling panel out of its normal EMI ,.,^��� position. If the Cover Plate /Retainer Assembly cannot be engaged with the O Support Cup or the Cover Plate /Re- 7/8" (23 mm) tainer Assembly cannot be engaged SQUARE sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. ALIGN J L. ARROWS WITH --, ' Care and FRAME ARMS (� Maintenance ACCEPTS \ ' The Series RFII must be maintained 0 1/2° SOCKET and serviced in accordance with the • DRIVE following instructions: NOTES FIGURE 3 Absence of the Cover Plate Assembly RFII SPRINKLER WRENCH may delay sprinkler operation in a fire situation. Page 4 of 4 TFP181 When properly installed, there is a SUPPORT SPRINKLER FACE OF ORIENT nominal 3/32 inch (2,4 mm) air gap CUP CEILING SEAL between the lip of the Cover Plate and _ , =�` I . A , G ��� , BEVEL As • the ceiling, as shown in Figure 2. This --- � SHOWN air gap is necessary for proper opera- I PLATE lion of the sprinkler. If the ceiling is to . ` + ) RETA INER - El • be repainted after the installation of )) i '`' ASSEMBLY m. � the Sprinkler, care must be exercised " ' pi - - 7 • to ensure that the new paint does NOT A I ; 1 seal off any of the air gap. l ; EAN Factory painted Cover Plates MUST /� ) �I��� _ "''- ROOM r NOT be repainted. They should be re- � LIP OF COVER SEAL placed, if necessary, by factory RETAINER PLATE painted units. FIGURE 5 Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504) the Enclosure. Separation may result. Before closinga fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT main control valve for maintenance local requirements and /or national SHALL TYCO FIRE PRODUCTS' LI- work on the fire protection system that codes. ABILITY EXCEED AN AMOUNT it controls, permission to shutdown the EQUAL TO THE SALES PRICE. affected fire protection system must be THE FOREGOJNG WARRANTY IS obtained from the proper authorities Limited THE IN LIEU OF ANY AND AL and all personnel who may be OTHER WARRANTIES EXPRESS OR by this action must be notified. arranty IMPLIED. INCLUDING WARRANTIES Sprinklers that are found to be leaking Products manufactured by Tyco Fire OF MERCHANTABILITY AND FIT - or exhibiting visible signs of corrosion Y y /NESS FOR A PARTICULAR PUR- must be replaced. Products are warranted solely to the original Buyer for ten (10) years Automatic sprinklers must never be POSE against defects in material and work - painted, plated, coated or otherwise manship when paid for and properly Ordering altered after leaving the factory. Modi- installed and maintained under normal fied sprinklers must be replaced. use and service. This warranty will ex- Procedure Sprinklers that have been exposed to ire ten corrosive products of combustion, but P ( 10 )Years from date of ship - co not operated should be replaced ment by Tyco Fire Products. No war- When placing an order, indicate the full • if they cannot be completely cleaned ranty is given for products or product name. Contact your local dis- by wiping the sprinkler with a cloth or components manufactured by compa- tributor for availability. by brushing it with a soft bristle brush. Hies not affiliated by ownership with Sprinkler Assembly: Tyco Fire Products or for products and age be e avoid m components which have been subject rating) ng) Semi s � RFIeConcealed Pen - 9 to the sprinklers nklers before, during, 9, to misuse, improper installation, corro- dent Sprinkler, P/N (specify). and after installation. Sprinklers dam- sion, or which have not been installed, P (P fy). aged by dropping, striking, wrench maintained, modified or repaired in ac 199E /6ac 200F/93c twist/slippage, or the like, must be re- cordance with applicable Standards of Ty3551 51- 790 -1 -155 51- 790 -1 -200 placed. Also, replace any sprinkler that the National Fire Protection Associa- TY3504 51- 796 -1 -155 51 -796 -1 -200 has a cracked bulb or that has lost tion, and /or the standards of any other TY3531 51 -792 -1 -155 51- 792 -1 -200 liquid from its bulb. (Ref. Installation Authorities Having Jurisdiction. Mate - TY3505 51-797 -1 -155 51- 797 -1 -200 Section). rials found by Tyco Fire Products to be If a sprinkler must be removed, do not defective shall be either repaired or Separately Ordered Cover Plate: reinstall it or a replacement without replaced, at Tyco Fire Products' sole Specify: (specify temperature rating) reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate If a Cover Plate Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify). dislodged during service, replace it im- assume for it, any other obligation in mediately. connection with the sale of products or 135F/57C(a) 165F/74C•(b) parts of products. Tyco Fire Products Brass 56 -792 -1 -135 56- 792 -1 -165 P P Y Bright Brass 56- 792 -2 -135 56- 792 -2 -165 The owner is responsible for the in- shall not be responsible for sprinkler Chrome 56- 792 -9 -135 56- 792 -9-165 spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome 56- --- - protection system and de- incomplete information supplied by White 56- 792 792 6 -3-135 135 56 56792 -792 -3-165 6 -165 their fire P Y P PP Y White (RAL9010)' 56- 792 -3-135 56- 792 -3 -165 vices in compliance with this docu- Buyer or Buyer's representatives. Bright White 56- 792 -4 -135 56 -792 -4 -165 ment, as well as with the applicable IN NO EVENT SHALL TYCO FIRE Off W hite 56- 792 -5 -135 56- 792 -5-165 standards of the National Fire Protec- PRODUCTS BE LIABLE, IN CON- Clack 56- 792 -6-135 56 -792 -6-165 Custom 56- 792 -X -135 56- 792 -X -165 tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR (a) For use with 200F/93C 00F/93C sprinklers. addition to the standards of any other UNDER ANY OTHER LEGAL THE- jurisdiction. The in- (b) For use with hresales sprinklers. authorities having 1 ORY, FOR INCIDENTAL, INDIRECT, • Eastern Hemisphere sales only. • stalling contractor or sprinkler manu SPECIAL OR CONSEQUENTIAL facturer should be contacted relative to DAMAGES, INCLUDING BUT NOT Sprinkler Wrench: any questions. LIMITED TO LABOR CHARGES, RE- Specify: RFII Sprinkler Wrench, It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56- 000 -1 -075. - sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal: tested, and maintained by a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal, P/N 56- 908 -1 -001. TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 • • c 3 -1/14" > , 371/4" A 4 / 7 ---..(.... I( _ N M � / • V J V • 171C401 FRICTION ADJUSTABLE CANOPY 2" to 3" adjustable depth 3 -1/4" diameter coverage (In Extended Position In Closed Position) Minimum Order (See front page) Maximum shipping charge per order (See front page) PRICES F.O.B. our Factory. Write for extra catalogs. 3/4" and 1" I.P.S. Hole furnished at 5 each extra charge. • • • PAGE 5 [Page Too Large for OCR Processing]