Specifications NAC EOL VOLTAGE CALCULATION
. FPS 2.06 9- o-0-0zq REC E D
CAPITOL ELECTRIC CO., INC. 147- 32o MAY 112009
(503) 255 -9488 Office pgT1GP►�
(503) 255 -1966 Fax BUILD 0OWISIpN
Job Name: 2 Lincoln Center
Job Address: 10220 SW Greenburg Road Tigard, OR 97223
Job Number: Conductor Wire Guage I 14 I
Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F) I 3.07 I
Date: 5/7/2009
Cable Length In Feet (source to end of line) I 298 I
Total Circuit Current I 0.607 I
Nominal System Voltage I 20.4 I
Panel Description: Silent Knight 5395 Power Supply Minimum Device Voltage I 16 I
Panel No.: NAC 1.1
Output No.: 1 Point To Point Method EOLv I 19.67
Circuit Within Limits ? YES
NAC Devices Mfg By: Wheelock
End Of Line Method EOLv I 19.29 I
Circuit Within Limits ? I l YES
Load Centering Method EOLv ( 19.85
Circuit Within Limits ? YES
' Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At
No. Rating Current Previous Device Device
( Feet )
•
1 Floor 1 Electrical Room DSM- 12/24 -R (1 CKT ONLY) NA 0.0275 3 20.39
2 Suite 320 AS- 24MCC -FW (75) H/S WHT -M 75 Cd 0.201 135 19.91
3 Suite 320 RSS - 24MCW -FW (15) STB WHT _ 15 Cd 0.060 22 19.86
4 Suite 320 AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 43 19.77
5 Suite 320 RSS - 24MCW -FW (15) STB WHT 15 Cd 0.060 31 19.73
6 Suite 320 AS- 24MCW -FW (15) H/S WHT -M 15 Cd 0.074 30 19.69
7 Suite 320 AS- 24MCW -FW (30) H/S WHT -M 30 Cd 0.110 34 19.67
8 19.67
9 19.67
10 19.67
11 19.67
12 19.67
13 19.67
. 14 19.67
15 19.67
16 19.67
17 19.67
18 19.67
19 19.67
20 19.67
2Lincoln NAC 1.1 EOLv Calc OUTPUT 1
NAC EXTENDER BATTERY CALCULATIONS
CAPITOL ELECTRIC CO., INC.
(503) 255 -9488 Office, (503) 255 -1966 Fax
JOB NAME: 2 Lincoln Center
ADDRESS: 10220 SW Greenburg Rd. Tigard, OR 97223 DATE: 5/7/09
PANEL DESCRIPTION: NAC 1.1 PREPARED BY: Dan Wilson
DEVICE TOTAL DEVICE TOTAL
STANDBY STANDBY ALARM ALARM
DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT
MAC EXTENDER
Silent Knight 5395 NAC Panel 1 0.075 0.075 1.000 1.000
CIRCUIT # 1 Suite 320
0.000
Wheelock DSM- 12/24 -R Synch Module (1/2) 1 0.0275 0.028
Wheelock AS- 24MCW -FW 30 Cd H/S (M) 1 0.110 0.110
Wheelock AS- 24MCW -FW 15 Cd H/S (M) 2 0.074 0.148
Wheelock RSS- 24MCW -FW 15 Cd Strobe 2 0.060 0.120
Wheelock AS- 24MCC -FW 75 Cd H/S (M) 1 0.201 0.201
0.000
0.000
0.000
TOTAL 0.607
CIRCUIT # 2 Building Alarm Bells
0.000
Maximum Circuit Current 1 1.500 1.500
0.000
0.000
0.000
0.000
•
0.000
• 0.000
0.000
TOTAL 1.500
CIRCUIT # 3
0.000
0.000
• 0.000
0.000
0.000
0.000
0.000
• . 0.000
• 0.000
• - • - TOTAL 0.000
CIRCUIT # 4
0.000
0.000
0.000
0.000
0.000
0.000
•
• . . • 0.000
•
0.000
0.000
TOTAL 0.000
2Lincoln NAC 1.1 Batt Calc Page 1 of 2
NAC EXTENDER BATTERY CALCULATIONS
CAPITOL ELECTRIC CO•, INC.
(503) 255 -9488 Office, (503) 255 -1966 Fax
JOB NAME: 2 Lincoln Center
ADDRESS: 10220 SW Greenburg Rd. Tigard, OR 97223 DATE: 5/7/09
PANEL DESCRIPTION: NAC 1.1 PREPARED BY: Dan Wilson
DEVICE TOTAL DEVICE TOTAL
STANDBY STANDBY ALARM ALARM
DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT
AUXILIARY DEVICES i
0.000 0.000
0.000 0.000
0.000 0.000
TOTAL 0.000
STANDBY TOTAL CURRENT: I 0.075 I
STANDBY HOURS: 24
STANDBY AMP HOURS: 1.800 NAC DEVICE CURRENT ( 2.107
ALARM TOTAL CURRENT: I 3.107
ALARM MINUTES: 5
ALARM AMP HOURS: 0.259
TOTAL CALCULATED AMP HOURS 2.059
APPLIED SAFETY FACTOR 1.15
MINIMUM AMP HOURS REQURED 2.368
SELECTED BATTERY SIZE I 2 EACH 12 VOLT, 7 AMP HOUR BATTERIES
2Lincoln NAC 1.1 Batt Calc Page 2 of 2
,r i :T'
. I ■ II I • . Cc: /r..../":71 / S ' P r.i . s i 1 i ti;;;I g:■, 1 . U r li 11 I.' ' ‘. '; lOgi*)/ ' L It-ii j % 1 0 (.7. ,, ir . 1 i ," . -- - .
I AD A ,: `_,., \,,� rif :J • . • l , _ ,. _ r\'�_.� . , —�__,
Helping People Take Actions''
SERIES AS
SINGLE & MULTI - CANDELA
AUDIBLE STROBE APPLIANCES
SERIES AH AUDIBLES
1 .k.,-:•-'• ,b, -
Description r
Wheelock's patented 2 -wire Series AS Audible Strobe R T r� = -r
Appliances and Series AH Audibles offer more features -
with low current draw.
Strobe options for wall mount models include 1575cd or SERIES AS SERIES AH
Wheelock's patented MCW multi - candela wall strobes
with field selectable candela settings of 15/30/75/110cd,_ , e.,� _ •
or the high intensity MCWH strobe with field selectable E -- __ __ _�
135/185cd. ,. .- l51
Ceiling mount models incorporate Wheelock's patented ; — - iFO i
MC C multi - candela ceiling strobe with field selectable Multi-Candela
Indicator
intensities of 15/30/75/95cd or the high intensity MCCH (bottom la lens)
strobe with field selectable 115/177cd.
The audible provides a selectable choice of either a Features
continuous horn or temporal pattern (Code 3) when • Approvals include: UL Standard 1971, UL Standard 464
constant voltage from a Fire Alarm Panel (FACP) is New York City (MEA), California State Fire Marshal (CSFM),
Factory Mutual (FM), and Chicago (BFP). See approvals by
applied. Each tone has 3 dBA settings to choose from. model in Specifications and Ordering Information.
When used with the Wheelock Series SM or DSM Sync • W A /NFPNUFC /A I rCompliant
lab available with Field Selectable
Module or Wheelock PS 12/24 - 8CP and PS 12/24 - 8MP • Call mount
Settings models are av /30/7 able with h 13d/18 Selectable
Power Supplies with Patented Sync Protocol, (Multi - Candela models) or 1575cd (single candela
synchronization of the continuous horn tone provides the model)
temporal (code 3) tone (mandated by NFPA 72) Ceiling mount models are available with field selectable
• simultaneously for all audible appliances. This ensures a candela settings of 15/30/75/95cd or 115/177cd
distinct temporal (code 3) pattern when 2 or more audibles (multi - candela ceiling models)
are within hearing distance. If not synchronized the • Selectable Continuous Horn or Temporal (Code 3).
temporal sound could overlap and not be distinctive. At • 3 Selectable dBA settings (99, 95 and 90 dBA) in both
the same time the strobes will be synchronized. This tones
provides the ability to comply with ADA guidelines • Patented 2 - Wire Audible Strobe Appliance.
Patented Universal Mounting Plate
concerning photosensitive epilepsy and the NFPA •
Weatherproof models are available for outdoor use
standards when installing 2 or more visual appliances Strobes produce 1 flash per second over the regulated
• within the field of view all of this plus the ability to silence voltage range
• the audible i s achieved by using only 2 wire. • 12 and 24 VDC models with wide UL "Regulated
Voltage Range" using filtered DC or unfiltered FWR input
voltage
• The strobes can be synchronized using Wheelock's sync
modules or power supplies with built in sync protocol
• Fast installation with IN /OUT screw terminals using
For Weatherproof Series AS, See Datasheet S9004 #12 to #18 AWG wires
Copyright 2004 Wheelock Inc. Al! rights reserved.
d
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A . All warnings are printed In bold capital letters. THESE SPECIFICATIONS APPLY
APPLYING TH S PRODUCT. AL URE TO COMP Y WITTH ANY AND ASSOCIATED OF T ESE INSTRUCTIONS, CAUTIONS OR WARNINGS COU D BEFORE USING,
RESULT IN IMPROPER
OR
APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION; WHICH COULD RESULT IN PROPERTY
DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS.
` General Notes
• Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Note that NFPA -72 (1999) specifies a flash
rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
• All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
• Series AS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32° F to 120° F (0° C to 49° C) and
maximum humidity of 93% (t 2 %).
• Series AH -24 horns are listed under UL Standard 464 for audible signal appliances (Indoor use only).
• Series AH -24WP audible appliances are listed under UL Standard 464 for indoor /outdoor use with a temperature range of -31 °F to 150 °F
( -35 °C to 66 °C) and.maximum humidity of 95 %.
• "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change, UL
used the terminology "Listed Voltage Range ".
Table 1: Ratings Per UL 1971
Regulated Vo
Model Input Voltage VDC Range VDCIFWR ltage Strobe Candela (cd)
A5-24MCW 24 16.0 - 33.0 15/30/75/110
AS- 24MCCH 24 16.0 - 33.0 115/177
AS- 241575W 24 16.0 - 33.0 15 (75 on Pods)
AS- 121575W 12 8.0 - 17.5 15 (75 on Axis)
AS -24MCC 24 16.0 - 33.0 15130/75/95
AS- 24MCWH 24 16.0 - 33.0 135/185
ASWP -2475W 24 16.0 - 33.0 75 @ -31 °F
Table 2: dBA Ratings for 12 VDC and 24 VDC Series ASIAN 12 and 24 VDC Audible
Description Volume Reverberant dBA Anechoic
Per UL 464 @ 10 ft. dBA @ 10 ft.
High 91 99
Continuous Horn Medium 68 95
Low 83 90
High 87 99
Code 3 Horn Medium 84 95
Low 79 90
Table 3: Average RMS Current
Audible Wall Mount Audible Strobe Models Ceiling Mount Audible Strobe Models
24 VDC Models AH - 24 AS 241575W AS - 24MCW AS 24MCWH AS - 24MCC AS 24MCCH
1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd
24 vdc 0.062 0.100 0.080 0.102 0.150 0.194 0.250 0.320 0.088 0.114 0.165 0.205 0.250 0.320
High (99) dBA
UL max' 0.080 0.121 0.088 0.125 0.200 0.267 0.355 0.480 0.095 0.138 0.221 0.285 0.355 0.480
24 vdc 0.033 0.080 0.060 0.084 0.132 0.173 0.230 0.305 0.066 0.092 0.145 0.186 0.230 0.305
Med (95) dBA
UL max' 0.043 0.107 0.074 0.110 0.190 0.253 0.340 0.465 0.080 0.122 0.201 0.269 0.340 0.465
24 vdc 0.017 0.072 0.052 0.076 0.121 1 0.158 0.220 0.295 0.056 0.082 0.132 0.173 0.220 0.295
Low (90) dBA I UL max' I 0.021 0.100 0.068 0.105 0.182 0.245 0.335 0.460 0.074 0.113 0.198 0.263 0.335 0.460
Audible Wall Mount
12 VDC Models Audible Strobe
AH -12 AS- 121575W • RMS current ratings are per UL average RMS method. UL max current
12 vdc 0.163 0.260 rating is the maximum RMS current within the listed voltage range (16-
High (99) dBA UL max' 0.192 0.320 33v for 24v units). For strobes the UL max current is usually at the
minimum listed voltage (16v for 24v units). For audibles the max current
12 vdc 0.076 0.195 ,. is usually at the maximum listed voltage (33v for 24v units). For unfiltered
Med (95) dBA FWR ratings, see installation instructions.
UL max' 0.108 0.275
12 vdc 0.039 0.175
•
Low (90) dBA UL max' 0.058 0.265
k u,,hf..elocat i , / • , [ _ ; . , e.:ij �.r : t F _;, , i, 7 ,, : S t. 3.�: -�� i - - . -
. _' r / , J tj
ti L ADP, s A ......‹N- ® Gn L . . N �1 ' t`.� " F,• : ` _�
-' �Y'�7 r'.:: is '�
Helping People Take Actions"
SERIES RSS & RSSP SINGLE
& MULTI - CANDELA STROBES
& STROBE PLATES
ali
DESCRIPTION = =` , -; Mr
• Wheelock's patented Series RSS Strobe Appliances and ' = ,` . `'e_ ',
Series RSSP Strobe Plates have lower current draw while 7C`k 1: F � - '�' _
maintaining outstanding performance, reliability and cost { `a I /
effectiveness. These versatile appliances will satisfy F , i
virtually all requirements for indoor, wall or ceiling mount Series RSS RSS Round
applications. Series RSSP
Strobe options for wall mount models include 1575 or ` _ fi r -: . -..
Whe Patented MCW multi - candela strobe with field •- -
selectable candela settings of 15/30/75/110cd or the high - _
intensity MCWH strobe with field selectable 135/185cd. 175 . �
Ceiling mount models include the patented MCC multi- �� =
candela ceiling strobe with field selectable intensities of Multi - Candela Indicator
- 15/30/75/95cd or the high intensity MCCH strobe with (bottom of Strobe Lens)
field selectable 115/177cd. Features
All models may be synchronized using the Wheelock • Approvals include: UL Standard 1971, New York City
SM, DSM Sync Modules or the PS- 12/24 -8CP and (MEA), California State Fire Marshal (CSFM), Factory
PS- 12/24 -8MP Power Supplies with Wheelock's Patented Mutual (FM), and Chicago (BFP) See approvals by
Sync Protocol. Synchronized strobes can eliminate model in Specifications and Ordering Information
possible restrictions on the number of strobes in the field • ADA/NFPA/UFC /ANSI compliant. Meets OSHA 29
of view. Wheelock's synchronized strobes offer an easy Part 1910.165
way to comply with ADA recommendations concerning • Wall mount Multi- Candela models are available
photosensitive epilepsy as well as meeting the with Field Selectable Candela Settings of 15/30/
requirements of NFPA72. 75/110cd or 135/185cd. Single Candela models
are available in 1575cd
Wheelock's Series RSS Strobes employ a Patented • Ceiling mount Multi - Candela models are
Integral Strobe Mounting Plate that can be mounted to a available with field selectable candela settings of
single gang, double gang, 4" square, 100mm European 15/30/75/95cd or 115/177cd. (Round or Square)
backboxes or the SHBB surface backbox. If the flush • Strobes produce 1 flash per second over the
backbox has side or top space between it and the finished regulated voltage range
wall, the NATP (Notification Appliance Trimplate) may be • 12 and 24 VDC models with wide UL "Regulated
used. It provides an additional .65" of trim for the Appliance. Voltage" using filtered (DC) or unfiltered VRMS input
An attractive cover plate is provided for a clean, finished voltage
appearance on all models. • Synchronize using Wheelock's sync modules or power
supplies with built -in sync protocol
The Series RSSP Multi - Candela Strobe Plates are a cost • Fast installation with IN /OUT screw terminals using
effective way to retrofit required wall strobe appliances to #12 to #18 AWG wire
bells, horns, chimes, multitones or speakers and easily
mounts to standard 4" backboxes or for surface mount
use with Wheelock's SBL2 surface backbox.
For Weatherproof Series RSS See Datatsheet S9004
Copyright 2004 Wheelock, Inc. All rights reserved.
• NOTE: All CAUTIONS and WARNINGS are identified by the symbol O. All warnings are printed in bold capital letters.
Q WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,
SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN
IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN
PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS.
•
General Notes
• Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Note that NFPA -72 specifies a flash rate of
1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. •
• All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
• Series RSS & RSSP Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32° F to 120° F (0° C to
49° C) and maximum humidity of 93% (t 2 %).
• "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change, UL used the
terminology "Listed Voltage Range ".
Table 1: Average RMS Current'
RSSIRSSP - Wall Mount RSS - Ceiling Mount
RSS /RSSP
24VDC 241575W 24MCW 24MCWH 24MCC 24MCCH
Models 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd
24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270
UL max' 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420
RSS/RSSP RSSIRSSP • RMS current ratings are per UL average RMS method. UL max current
24VDC Wall Mount rating is the maximum RMS current within the listed voltage range (16 -33v
Models 121575W for 24v units). For strobes the UL max current is usually at the minimum
12 vdc 0.152 listed voltage (16v for 24v units). For audibles the max current is usually at
the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings,
UL max' 0.255 see installation instructions.
Table 2: Audibles /Speakers for RSSP Strobe Plate
Product Series
Multitone Appliances AMT, MT
Horns AH, NH, HS
Motor Bells MB- G6 /G10
Speakers ET- 1010/1080, E70, E170
Chimes CH70
A WARNING: CONTACT WHEELOCK FOR THE CURRENT "INSTALLATION INSTRUCTIONS" AND "GENERAL INFORMATION" SHEET (P82380) ON THESE
PRODUCTS. THESE DOCUMENTS UNDERGO PERIODIC CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS.
THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING:
• TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES.
• FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS.
• ADDING, REPLACING OR CHANGING APPLIANCES OR CHANGING CANDELA SETTINGS WILL AFFECT CURRENT DRAW. RECALCULATE CURRENT
DRAW TO INSURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY ALL APPLIANCES DO NOT EXCEED THE RATED CAPACITY
OF THE POWER SOURCE OR FUSES.
• COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW.
• THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR "REGULATED VOLTAGE RANGE ".
• INSTALLATION OF 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS.
• INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES.
• USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBES ON CODED OR
• INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBES MAY NOT FLASH.
• FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER
INSTALLATION, APPLICATION, AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY
DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS.
• CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE
PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS.
' ; � = '�� •
,Y , 1005
Helping People Take Actions'
• SERIES SM AND DSM
SYNC MODULES
Description
Wheelock's Series SM and DSM Sync Modules are 1 ` A'',
utilized with the Series AS /AH, Series NS /NS4 /NH, Series - 4 s
• RSS, Series RSSP, Series SLM and selected strobe' 4 •
applications with other Wheelock combination appliances. ,� . ` �� Y°
:' s •
When used with Series AS Audible Strobes and /or Series ,- try
`
NS Horn Strobes, the SM and DSM Sync Modules provide ! f f - ^ 73
independent operation of synchronized temporal pattern Series SM or DSM
(code 3) horn and synchronized strobe flash, as well as
the ability to silence the horn while maintaining the strobe
flash. while using only a single pair of wires. The sync
modules are available in two versions; the SM -12/24 for
control of a Class B NAC circuit; and a dual output version,
the DSM -12/24 for control of either a Class A or two (2)
Class B NAC circuits.
Features Specifications and Ordering Information
• Approvals include: UL Standard 1971, ULC, New York In ut Average
•
City (MEA), California State Fire Marshal (CSFM) and Model Order voltage Current UL Mounting
Chicago (BFP). Code VDC
VDC
@ 24 Max' Options"
• Uniquely designed to accept an independent strobe
and audible input from the FACP and convert to a SM-12/24-R 6369 12 0.017 0.023 W
single output that connects to Wheelock's Series AS 24 0.028 0.038 W
or Series NS family of audible strobes. DsM- 12/24 -R••• 6374 12 0.020 0.026 W
• Series SM and DSM Sync Modules can also be used 24 0.035 0.055 W
to synchronize Wheelock's Series RSS, RSSP and
SLM Sync Strobes. R = Red
• 3 ampere per circuit current handling at 12 or 24 VDC. • RMS current ratings are per UL average RMS method. UL max
• Low operating current draw. current rating is the maximum RMS current within the listed voltage
• Compatible with all standard fire alarm control panels. range (16 -33v for 24v units). For strobes the UL max current is
• Meets the NFPA -72 requirement for Temporal usually at the minimum listed voltage (16v for 24v units). For audibles
Pattern when used with the Series AS /AH and /or the max current is usually at the maximum listed voltage (33v for
Series NS /NS4 /NH. 24v units). For unfiltered FWR ratings, see installation instructions.
'• Refer to Data sheet # S7000 for Mounting Options.
• 3 year warranty. •.• The maximum number of interconnected DSM modules is
twenty (20).
The total distance from the first to the last DSM shall not
exceed 1,000 feet of #18 AWG wire. Use only #18 AWG wire.
• POWERPATH AS /AH, NS, HS4 /HS
FIRE ALARM POWERPATHMP NH, RSS, RSSP,
CONTROL PANEL OR SM OR DSM E w /STB, ET w /STB,
(FACP) OTHER POWER CH w /STB
BOOSTERS APPLIANCES
SM or DSM Connection Diagram with Power Booster
Copyright 2004 Wheelock, Inc. All rights reserved.