Specifications /qEd.,2010- 060 33 TRANE° Submittal /02( Stki Ci -cap. > z Sa • Prepared For: Date: January 18, 2010 Customer P.O. Number: Customer Project Number: Sold To: Job Number: Job Name: Lincoln Tower VAV Boxes Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval. • Product Summary Qty Product 1 Variable Air Volume Single Duct Terminal Units 1 Variable Air Volume Fan Powered Terminal Units The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval. • David Havelick Trane 7257 SW Kable Lane Portland, OR 97224 -7181 • Phone: (503) 620 -8031 • Fax: (503) 639 -1454 • • J: IJOBSI 124142128121SUB. doc Table Of Contents Product Summary 1 Variable Air Volume Single Duct Terminal Units (Item Al) Tag Data 3 Product Data 3 Performance Data 3 Mechanical Specifications 4 Unit Dimensions 5 Accessory 6 Variable Air Volume Fan Powered Terminal Units (Item B1) Tag Data 7 Product Data 7 Performance Data 7 Mechanical Specifications 8 Unit Dimensions 10 Accessory 11 Field Wiring 13 • • , Lincoln Tower VAV Boxes January 18, 2010 Tag Data - Variable Air Volume Single Duct Terminal Units (Qty: 1) Item Tag(s) • Qty Description Model Number Al VAV 1 Variable Air Volume Single Duct Terminal VCCF08 Product Data - Variable Air Volume Single Duct Terminal Units Item: Al Qty: 1 Tag(s): VAV Single duct cooling only terminal 8" inlet size, 900 cfm (203mm inlet, 425 Us) Matte faced insulation - 1/2" (13 mm) Normally open, 3000 series pneu vol reg, r.a. stat Standard actuator Left hand & /or same side connection (control & /or hot water coil) Performance Data - Variable Air Volume Single Duct Terminal Units Tags VAV Design cooling airflow (cfm) 700 Min cooling airflow (cfm) 140 Valve heating airflow (cfm) 140 Cooling inlet diameter 8" Cooling inlet velocity (ft/min) 2005 APD @ cooling airflow (in H2O) 0.050 Operating weight (lb) 16.0 Room heating setpoint (F) 68.00 Primary EDB (F) 55.00 Unit LAT (F) 55.00 Electric heat kW (kW) 0.00 Less Or Provided By Others: Disconnect, transformer, re heat, pneumatic pipe /piping or accessories unless specifically called out, pneumatic thermostat (Not available factory option), sound attenuators, external vibration isolation, external seismic restraints or calculations, air balance, testing /balancing, start up, Owner training, and labor warranty. • FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13 Others Lincoln Tower VAV Boxes January 18, 2010 Mechanical Specifications - Variable Air Volume Single Duct Terminal Units Item: Al Qty: 1 Tag(s): VAV General Unit Information The unit casing is comprised of 22 gauge galvanized steel. Outlet connection is slip and drive. Agency Listing - The unit is UL and Canadian UL listed as a room air terminal unit. UL Control # 9N65. All Trane terminal units are ARI 880. - 98 certified. General Unit Clearance Allow adequate clearance to meet NEC on control box side of unit to meet NEC. A minimum of one and one half duct diameters of straight duct work, upstream of the air inlet connection, should be present for optimum airflow measurement performance. Upstream duct work should be the same diameter as the primary inlet connection. 1/2" Matte - Faced Insulation The interior surface of the unit casing is acoustically and thermally lined with 1/2" 1.50 lb.cu. ft. [24.00 kg. /cu. m.] composite density glass fiber with 4.0 lb. cu.ft. [64 kg. /cu. m.] high density facing. The insulation is UL listed and meets NFPA -90A and UL 181 standards. The insulation R -value is 1.9. All cut edges of insulation are completely encapsulated in metal to prevent erosion. Air Valve Round The air inlet connection is an 18 gauge galvanized steel cylinder sized to fit standard round duct. A multiple point, averaging flow sensing ring is provided with balancing taps for measuring within +/- 5% of unit cataloged airflow. An airflow versus pressure differential calibration chart is provided. The damper blade is constructed of a closed cell foam seal mechanically locked between two 22 gauge galvanized steel disks. The damper blade assembly is connected to a cast zinc shaft supported by self lubricating bearings. The shaft is cast with a damper position indicator. The valve assembly includes a mechanical stop to prevent over stroking. At 4.0" w.g. air valve leakage does not exceed 1% of cataloged airflow. Air Valve Size - 08 Air Valve is 900.0 cfm 8" inlet. Slip 8 Drive Connection A slip and drive connection has two straight flanges on the top and bottom, and two drive connections on the left and right sides. This is a standard option on all VAV single duct terminal units. • Normally Open Pneumatic Actuator Normally open pneumatic actuator with 3.00 psi to 8.00 psi spring range. Pneumatic Volume Regulator - 3011 PVR The regulator is a thermostat reset velocity controller which provides consistent air delivery within 5% of cataloged flow down to 18% of unit cataloged CFM, independent of changes in system static pressure. Factory calibrated, field adjustable set points for minimum and maximum flows. Average total unit bleed rate, excluding thermostat, is 28.8 scim at 20.00 psi 7.87m1 /min @ supply. Pneumatic Controls Option PNO5 Normally Open Valve Actuator, 3011 Pneumatic Volume Regulator, (for use with Reverse Acting Thermostat) With an increase in room temperature, the thermostat pressure is decreased. This signal is input to the volume • regulator, which also receives the inputs of primary inlet total and static pressure from the flow ring. The volume regulator outputs a signal compensated for changing duct pressures to the valve actuator to open the damper and increase primary cooling flow to the space. With a decrease in room temperature, the opposite action occurs. Minimum and maximum primary airflow settings are maintained by the volume regulator. When the system is designed with reheat, heating stages are energized at the appropriate pressure settings. • FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 4 of 13 Others' • Lincoln Tower VAV Boxes January 18, 2010 •• Unit Dimensions - Variable Air Volume Single Duct Terminal Units Item: Al Qty: 1 Tag(s): VAV F— 5 12 21/4' < X 8' 7. II VALVE IR 4' MOIL '�! „11 FLOW L ACTUATOR 1 %r / � �� ;:i 0 0 0 7 < , ‘ \ ''', . SLIP & DRIVE 12' I • CONNECTION TOP VIEW 121/7 > 1/2” ► 11" A Customer Notes 1. Air Inlet is centered in unit front panel. i 2. Slip & Drive discharge outlet standard. 3. Minimum of 1.5 duct diameters of straight duct required at inlet for proper flow reading. 10' 11 12' ` 4. Allow 12" on control side for servicing. 5. Unit is fieldconvertable from a left -hand I connection (shown) to a right -hand by rotating unit. ■ CONTROLLER V Approximate Dry Weight 16.0lb BACK VIEW Weights reflected may vary ±5.0 lb based upon options selected. FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 5 of 13 Others Lincoln Tower VAV Boxes January 18, ?.010 Accessory - Variable Air Volume Single Duct Terminal Units Item: Al Qty: 1 Tag(s): VAV s `� 51 `(201 ` • r 1 . L - - -- Two Pipe I Remote Mounted I T -Stat I / L (Reverse Acting) I M Volume O Regulator I I I / ' S \ r — — , Restrictor I One Pipe I 137.9 / Tee I Remote Mounted I \ (20) , — i r — — — 1 T -Stat I L (Reverse Acting) J T -Stat Branch Pressure (kPa) / Restricted Leg S v ‘ 137.9 / N I n ° \ ( 20) / I I I One Pipe Inset 1o0 loo Max m U CFM ��,(jo LPS a 0 0 Min Min CFM LPS I 1 1 1 1 1 I 1 1 I I I I 1 I 3 8 15 Customer Notes: T -Stat Branch Pressure (PSI) . 1. Factory installed. • — — — — — — Optional or installed by others. FLD = Fumished by Trane U.S. Inc. / Installed by Equipment Submittal Page 6 of 13 Others Lincoln Tower VAV Boxes January 18, 2010 Tag Data - Variable Air Volume Fan Powered Terminal Units Qty: 1) I Item Tag(s) Qty Description Model Number B1 FPVAV 1 VAV Fan Powered Terminal Units VPEF0803SQ Product Data - Variable Air Volume Fan Powered Terminal Units Item: B1 Qty: 1 Tag(s): FPVAV Parallel with electric heat 8" (203 mm) 03 super quiet fan 1/2" [13mm] matte faced insulation Slip and drive connection 277/60/1 motor voltage Single speed motor w/ SCR Pneumatic normally open w/3011 pneumatic volume regulator Left hand connection Power fuse 480 volt, 3 phase 2 stages of heat - equal increments 3.5 kilowatt P.E. w /magnetic contactors Disconnect switch Electric heater air flow switch Performance Data - Variable Air Volume Fan Powered Terminal Units Tags FPVAV Design cooling airflow (cfm) 700 Min cooling airflow (cfm) 140 Valve heating airflow (cfm) 140 Cooling inlet diameter (in) 8.000 Cooling inlet velocity (ft/min) 2005 APD @ cooling airflow (in H2O) 0.125 Fan airflow (cfm) 350 Downstream SP (in H2O) 0.250 Fan TSP (in H2O) 0.254 % of fan range ( %) 11.00 Fan power (hp) 0.333 Plenum EAT (F) 85.00 Primary EDB (F) 55.00 Operating weight (lb) 112.0 Unit heating airflow (cfm) 490 Coil heating capacity (MBh) 11.95. Room heat loss (MBh) 16.43 Room heating setpoint (F) 68.00 Coil EAT (F) 76.43 Unit LAT (F) 98.91 Coil LAT (F) 98.91 Full load amps (A) 5.81 Min circuit ampacity (A) 7.26 Max overcurrent protection (A) 15.00 Electric heater kW (kW) 3.50 Less Or Provided By Others: Pneumatic pipe /piping or accessories unless specifically called out, pneumatic thermostat (Not available factory option), sound attenuators, external vibration isolation, external seismic restraints or calculations, air balance, testing /balancing, start up, Owner training, and labor warranty. • FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 7 of 13 Others Lincoln Tower VAV Boxes January 18, ?010 Mechanical Specifications - Variable Air Volume Fan Powered Terminal Units Item: B1 Qty: 1 Tag(s): FPVAV General Unit Information Casing - The unit casing is 22 gauge galvanized steel. Outlet duct connection is flanged. Total metal encapsulation of all insulation edges. Hanger Brackets provided. Side access is provided. Filter - A filter is provided on the plenum inlet. Agency Listing - UL and Canadian UL listed as environmental air terminal unit. UL Control #9N65. All Trane terminal units are ARI 880 -98 certified. General Unit Clearance Leave a minimum of 36" on control box side of unit for adequate service access. Allow at least 12" on remaining sides for unit clearance. A minimum of one and one half duct diameters of straight duct work, upstream of the air inlet connection, should be present for optimum airflow measurement performance. Upstream duct work should be the same diameter as the primary inlet connection. 1/2" Matte - Faced Insulation The interior surface of the unit casing is acoustically and thermally lined with 1/2 ", 1.8 lb /cu. ft composite density glass fiber with high density facing. The insulation is UL listed and meets NFPA -90A and UL 181 standards. All insulation options will meet the 25/50 smoke developed and flame spread rating (per ASTM E 84 and UL 723 and CAN /ULC S102 -M88) Meets NFPA- 90B. The insulation R -value is 1.9. All cut edges of insulation are completely encapsulated in metal to prevent erosion. • Air Valve & Fan Description (Parallel) (Series) The air inlet connection is an 18 gauge galvanized steel cylinder sized to fit standard round duct. A multiple point, averaging flow sensing ring is provided with balancing taps for measuring airflow within +/- 5% of unit cataloged airflow. Also provided with each unit is a calibration chart indicating airflow versus flow sensor pressure differential. The damper blade is constructed of a closed cell foam seal mechanically locked between two 22 gauge galvanized steel disks. The damper blade assembly is connected to a cast zinc shaft which rotates in a self lubricating bearing. The shaft is cast with a damper position indicator. The valve assembly includes a mechanical stop to prevent over stroking. Air valve leakage <1% at 4 ". 0803SQ Air Valve /Fan Combination Size (Parallel) 8" Inlet designed for up to 900.0 cfm. Fan is 1100.0 cfm for Std Motor and 1085.0 cfm for ECM Motor. Motor Single Speed, direct drive induction, permanent split capacitor type. Thermal overload protection provided. Motors will be designed specifically for use with an open SCR which is standard. Motors will accommodate anti - backward rotation at start up. Motor and Fan assembly are isolated from terminal unit. Fuse Any electric heat unit with a calculated MCA greater or equal to 30 will have a fan fuse provided. SCR- Variable Fan Speed Control Switch The SCR speed control device allows the operator infinite fan speed adjustment so the fan output may be modified to achieve•exact CFM requirements. Electric Heat Coil Factory provided and mounted. UL recognized, resistance open -type heater, a disc -type automatic thermal primary safety device and manual reset load thermal secondary device. Heater element material is nickel- chromium. The heater terminal box is provided with 7/8" knockouts for customer power supply. Terminal connections are plated steel with ceramic or phenolic insulators. All fan - powered units with electric reheat are single -point power connections. For 480 volt 3 phase and 575 volt 3 phase heaters a 4 wire (includes neutral) power supply is required. Electric Heat Coil Factory provided and mounted. Resistance open -type heater, a disc -type automatic thermal primary safety device and manual reset load thermal secondary device. Heater element material is nickel- chromium. The heater terminal box is provided with knockouts for customer power supply. Terminal connections are plated steel with ceramic or phenolic FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 8 of 13 Others . Lincoln Tower VAV Boxes January 18, 2010 insulators. All fan - powered units with electric reheat are single -point power connections. For 480 volt 3 phase and 575 volt 3 phase heaters a 4 wire (includes neutral) power supply is required. P.E. Switch with Magnetic Contactor This switch and magnetic contact is for the use with an electric heater with Pneumatic VAV Controls. Power Disconnect Switch (for VSEF & VPEF) A factory provided interlocking door disconnect switch located on the electric heater control panel. • Airflow Switch An air pressure device designed to disable the heater when the unit fan is off. Power Fuse A safety fuse located in the electric heater's line of power to prevent power surge damage to the electric heater. Pneumatic Actuator A normally open or normally closed pneumatic actuator operates over a 3.00 psi to 8.00 psi spring range. Slip & Drive Connection A slip and drive connection has two straight flanges on the top and bottom, and two drive connections on the left and right sides. The drive sides are straight flanges which form a "U" shape. The mating ductwork has a similar setup. The two top and bottom pieces are shaped like a compressed "S" with sealant in the hollow of the "S ". These pieces will slide over the top and bottom straight flanges. The top and bottom flanges of the mating ductwork will slide into the otherside of these pieces. The two side pieces are shaped like a "C" and are called "Drives ". These pieces will slide over the "U" shaped flanges so the connection can not be pulled apart. These pieces are usually hammered into place. No screws are required, and by removing the drives, the ducts may be disconnected. Pneumatic Volume Regulator- 3011 Series The regulator is a thermostat reset velocity controller which provides consistent air delivery within 5% of normal flow down to 18% of unit cataloged CFM, independent of changes in system static pressure. Factory calibrated, field adjustable set points for minimum and maximum flows. Average total unit bleed rate, excluding thermostat, is 28.8 scim at 20 psig (7.87 I /min @ 138 kpa) supply. Pneumatic Controls Option PNO5 Normally Open Valve actuator, 3011 Pneumatic Volume Regulator, (Reverse Acting Thermostat) With an increase in room temperature, the thermostat pressure is decreased. This signal is input to the volume regulator, • which also receives the inputs of primary inlet total and static pressure from the flow ring. The volume regulator outputs a signal compensated for changing duct pressures to the valve actuator to open the damper and increase primary cooling flow to the space. With a decrease in room temperature, the opposite action occurs. Minimum and maximum primary airflow settings are maintained by the volume regulator. When the system is designed with reheat, heating stages are energized at the appropriate pressure settings. • FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 9 of 13 Others Lincoln Tower VAV Boxes January 18, 2Q10 Unit Dimensions - Variable Air Volume Fan Powered Terminal Units Item: B1 Qty: 1 Tag(s): FPVAV . Unit Size VPEF0803SO • Nominal $' Dia. x 4' Depth Valve Size 8 Depth Nominal 0350 Fan Fan Size \ &;<:�.� ��:.�,_ Filter Size 16'a 20'x 1 - (OTY 1) `\`�`�� � \�`��\� . AO • TOP VIEW . Y0' . • ••›‹:1-8^—cl t s- p NOTES: Z AIRFLOW 16.50 X 11.30 A 1. Allow a minimum 6' plenum inlet clearance ( � \I for un -ducted installations. . L 2. Filter is secured in filter frame located in unit inlet. I 0 . . 32 112• 3. For Motor access, remove bottom screws on hanger brackets to slide panel as shown in drawing. 4. See Installation Documents for exact hanger bracket location. 22• 5. Air valve centered between top & bottom panel. • * 6. Healing coil un -insulated. External insulation may HEATER be field supplied and installed as required. ;.1 6- 7. All high & low voltage controls have same -side NEC jumpback clearance. ' PANEL SLIDES FOR MOTOR ACCESS 8. Allow 48' of straight duct downstream of AIRFLOW unit before first runout and inside of the duct should DISCHARGE OUTLET . be equal discharge size. 9. Terminal box access door is side hinged. Allow for dearance. r 10. A 4 wire power supply required for 48013 & 57513 5' 40' 1 single point connection units. T u 1 16' 17 1/2' Approximate 112.0 lb v l Dry Weight 160.0 lb Weights reflected may vary 20" ±5.0 lb based upon options DISCHARGE VIEW selected. FLO = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 10 of 13 Others ;•Lincoln Tower VAV Boxes January 18, 2010 Accessory - Variable Air Volume Fan Powered Terminal Units Item: B1 Qty: 1 Tag(s): FPVAV 62.06 kPa (9 PSI) Fan P.E. •031' ,31 Electric Heater Switch X15 k 201 Terminal Box (N.O.) Tee I L J I LJ I r L - - -- Two Pipe 1 Remote Mounted 1 I T -Stat • (Reverse Acting) I T • Tee M Volume • Regulator r - Restrictor I One Pipe Tee I Remote Mounted I T-Stat • L (Reverse Acting) I • 1 • / J Restricted Leg S © \ 137.9 137.9 \ ( (20) One Pipe Inset T-Stat Pressure (kPa) • N N � CD OD N • Fan On 100 100 MAX MAX CFM Pe4, 3rd LPS • 3 2 ` 2nd MIN MIN CFM 111111=1 LPS 3 8 9 10 12 14 Stages of Heat T •Stat Branch Pressure (PSI) • • Customer Notes: • • 1. Factory installed. — — — — — — Optional or installed by others. • FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 11 of 13 Others • • • Lincoln Tower VAV Boxes January 18, 2010 Accessory - Variable Air Volume Fan Powered Terminal Units • Item: B1 Qty: 1 Tag(s): FPVAV Notes: 1. When attenuator is required, add inlet attenuator pressure to discharge static pressure for final fan performance. VPCF and VPEF maximum Minimum 1 -row coil maximum - •- .- . -• -•- 2 -row coil maximum Pe In. wg Parallel Fan Size 03SQ —PSC 199 0.80 - 174 0.70 150 0.60 • • 4 .1 . •\ • to 125 0.50 E m E � � a co • \ \ i 100 0.40 = \ 5%5\ cn 0 75 0.30 ' • t - u p • 50 0.20 . 25 0.10 200 300 400 500 600 700 800 900 1000 1100 1200 1300 Cirri 94 • 142 189 236 283 330 378 425 472 519 566 614 Us Airflow • • • FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 12 of 13 Others ,,.Lincoln Tower VAV Boxes January 18, 2010 •� Field Wiring - Variable Air Volume Fan Powered Terminal Units' Item: B1 Qty: 1 Tag(s): FPVAV • 480 Volt. 3 Phase, 4 wire L3 L2 L1 N • I I I I I I I I I I I �— • N Heater Control Wiring • • Lt. WARNING HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH A\ CAUTION USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED Customer Notes: TO ACCEPT OTHER TYPES OF 1. Factory installed. CONDUCTORS. • • FAILURE TO DO SO MAY CAUSE — — — — Optional or installed by others. DAMAGE TO THE EQUIPMENT. • FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 13 of 13 Others [Page Too Large for OCR Processing] [Page Too Large for OCR Processing]