Loading...
Specifications NAC EOL VOLTAGE CALCULATION - P52 v7 —o 2/3 • CAPITOL ELECTRIC CO., INC. 7632 s vv l- urk &wv Ro{ (503) 255 -9488 Office (503) 255 -1966 Fax 4 Job Name: SW CENTER OFFICE BUILDING Job Address: 7632 SW DURHAM ROAD Job Number: RECEIVED Prepared By: Dan Wilson APR 13 2009 Date: 4/7/2009 CITY OF TIGARD BUILDING DIVISION Panel Description: Silent Knight 5495 NAC Power Supply Panel No.: NAC 1.1 ALARM OUTPUT TOTALS OUTPUT 1 0.755 AMPS OUTPUT 2 1.735 AMPS OUTPUT 3 1.434 AMPS OUTPUT 4 0.870 AMPS TOTAL 4.7941 AMPS WIRE LENGTH TOTALS OUTPUT # I WIRE LENGTH 1 GAUGE OUTPUT 1 413 14 OUTPUT 2 663 14 OUTPUT 3 741 14 OUTPUT 4 391 14 TOTAL 22081 FEET NAC 1.1 EOLv Calc.xls JOB INF SHEET NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. ▪ (503) 255 -9488 Office . - (503) 255 -1966 Fax • Job Name: SW CENTER OFFICE BUILDING • Job Address: 7632 SW DURHAM ROAD Job Number: Conductor Wire Guage I 14 I Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F) I 3.07 I Date: 4/7/2009 Cable Length In Feet (source to end of line) 741 I Total Circuit Current I 1.434 I Nominal System Voltage I 20.4 Panel Description: Silent Knight 5495 NAC Power Supply Minimum Device Voltage I 16 I Panel No.: NAC 1.1 Output No.: 3 Point To Point Method EOLv I 17.73 I Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv I 13.88 I Circuit Within Limits ? NO Load Centering Method EOLv I 17.14 Circuit Within Limits ? YES • Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet ) 1 FLOOR 2, ALLSTATE AS- 24MCW -FW (75) H/S WHT -H 75 Cd 0.200 86 19.64 2 FLOOR 2, ALLSTATE RSS- 24MCW -FW (30) STB WHT 30 Cd 0.092 29 19.42 3 FLOOR 2, ALLSTATE AS- 24MCW -FW (15) H/S WHT -H 15 Cd 0.088 18 19.30 4 FLOOR 2, ALLSTATE AS- 24MCW -FW (110)H /S WHT -H 110 Cd 0.267 30 19.10 5 FLOOR 2, ALLSTATE RSS - 24MCW -FW (15) STB WHT 15 Cd 0.060 30 18.96 6 FLOOR 2, ALLSTATE RSS - 24MCW -FW (15) STB WHT 15 Cd 0.060 20 18.87 7 FLOOR 2, ALLSTATE AS- 24MCW -FW (75) H/S WHT -H 75 Cd 0.200 60 18.62 8 FLOOR 2, ALLSTATE AS- 24MCW -FW (75) H/S WHT -H 75 Cd 0.200 101 18.33 9 FLOOR 2, ALLSTATE AS- 24MCW -FW (110)H /S WHT -H 110 Cd 0.267 367 17.73 10 17.73 11 17.73 12 17.73 13 17.73 14 17.73 15 17.73 16 17.73 17 17.73 18 17.73 19 17.73 20 _ 17.73 NAC 1.1 EOLv Calc.xls OUTPUT 3 NAC EOL VOLTAGE CALCULATION ' CAPITOL ELECTRIC CO., INC. • (503) 255 -9488 Office • (503) 255 -1966 Fax • Job Name: SW CENTER OFFICE BUILDING Job Address: 7632 SW DURHAM ROAD Job Number: Conductor Wire Guage I 14 I Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F) ( 3.07 Date: 4/7/2009 Cable Length In Feet (source to end of line) I 391 I Total Circuit Current I 0.87 I Nominal System Voltage I 20.4 Panel Description: Silent Knight 5495 NAC Power Supply Minimum Device Voltage I 16 I Panel No.: NAC 1.1 Output No.: 4 Point To Point Method EOLv I 18.65 I Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv I 18.31 I Circuit Within Limits ? YES Load Centering Method EOLv I 19.36 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet ) 1 FLOOR 2, ALLSTATE AS- 24MCW -FW (30) H/S WHT -H 30 Cd 0.125 207 19.29 2 FLOOR 2, ALLSTATE RSS- 24MCW -FW (15) STB WHT 15 Cd 0.060 65 19.00 3 FLOOR 2, ALLSTATE AS- 24MCC -FW (177) H/S WHT -M 177 Cd 0.305 41 18.82 4 FLOOR 2, ALLSTATE AS- 24MCW -FW (75) H/S WHT -M 75 Cd 0.190 71 18.66 5 FLOOR 2, ALLSTATE AS- 24MCW -FW (75) H/S WHT -M 75 Cd 0.190 7 18.65 6 18.65 7 18.65 8 18.65 9 18.65 10 18.65 11 18.65 12 18.65 13 18.65 14 18.65 15 18.65 16 18.65 17 18.65 18 18.65 19 18.65 20 18.65 NAC 1.1 EOLv Calc.xls OUTPUT 4 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503) 255 -9488 Office, (503) 255 -1966 Fax JOB NAME: SW CENTER OFFICE BUILDING • ADDRESS: 7632 SW DURHAM ROAD TIGARD, OR 97223 DATE: 4/7/09 PANEL DESCRIPTION: NAC 1.1 PREPARED BY: Dan Wilson DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT NAC EXTENDER Silent Knight 5495 NAC Panel 1 0.075 0.075 0.175 0.175 CIRCUIT # 1 Floor 1, Allstate • 0.000 Wheelock AS- 24MCW -FW 110 Cd HIS (H) 1 _.. - -_ - 0.267 0.267 Wheelock AS- 24MCW -FW 75 Cd HIS (H) 2 0.200 0.400 Wheelock AS- 24MCW -FW 30 Cd H/S (H) 0.125 0.000 Wheelock AS- 24MCW -FW 15 Cd H/S (H) 1 0.088 0.088 0.000 0.000 0.000 0.000 TOTAL 0.755 CIRCUIT # 2 Floor 1, Allstate, UHC -130 0.000 Wheelock AS- 24MCW -FW 110 Cd HIS (H) 1 0.267 0.267 Wheelock AS- 24MCW -FW 75 Cd HIS (H) 3 0.200 0.600 • Wheelock AS- 24MCW -FW 30 Cd H/S (H) 0.125 0.000 Wheelock AS- 24MCW -FW 15 Cd H/S (H) 1 0.088 0.088 Wheelock AS- 24MCW -FW 75 Cd H/S (M) 2 0.190 0.380 Wheelock AS- 24MCW -FW 30 Cd HIS (M) 2 0.110 0.220 Wheelock RSS- 24MCW -FW 15 Cd Strobe 3 0.060 0.180 0.000 TOTAL 1.735 CIRCUIT # 3 Floor 2, Allstate 0.000 Wheelock AS- 24MCW -FW 110 Cd H/S (H) 2 0.267 0.534 Wheelock AS- 24MCW -FW 75 Cd H/S (H) 3 0.200 0.600 Wheelock AS- 24MCW -FW 30 Cd H/S (H) 0.125 0.000 Wheelock AS- 24MCW -FW 15 Cd HIS (H) 1 0.088 0.088 Wheelock RSS - 24MCW -FW 30 Cd Strobe 1 0.092 0.092 Wheelock RSS - 24MCW -FW 15 Cd Strobe 2 0.060 0.120 0.000 0.000 TOTAL 1.434 CIRCUIT # 4 Floor 2, Allstate 0.000 Wheelock AS- 24MCW -FW 75 Cd H/S (M) 2 0.190 0.380 Wheelock AS- 24MCW -FW 30 Cd HIS (H) 1 0.125 0.125 Wheelock RSS - 24MCW -FW 15 Cd Strobe 1 0.060 0.060 Wheelock AS- 24MCC -FW 177 Cd H/S (M) 1 • 0.305 0.305 0.000 0.000 0.000 0.000 TOTAL 0.870 NAC 1.1 Batt Calc.xls Page 1 of 2 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., - __ (503) 255 -9488 Office, (503) 255 -1966 Fax JOB NAME: SW CENTER OFFICE BUILDING ADDRESS: 7632 SW DURHAM ROAD TIGARD, OR 97223 DATE: 4/7/2009 PANEL DESCRIPTION: NAC 1.1 PREPARED BY: Dan Wilson DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT AUXILIARY DEVICES : 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.000 STANDBY TOTAL CURRENT: I 0.075 I STANDBY HOURS: 24 STANDBY AMP HOURS: 1.800 NAC DEVICE CURRENT I 4.794 ALARM TOTAL CURRENT: I 4.969 ALARM MINUTES: 5 ALARM AMP HOURS: 0.414 TOTAL CALCULATED AMP HOURS 2.214 APPLIED SAFETY FACTOR 1.15 MINIMUM AMP HOURS REQURED 2.546 SELECTED BATTERY SIZE I 2 EACH 12 VOLT, 7 AMP HOUR BATTERIES NAC 1.1 Batt Calc.xls Page 2 of 2 J • ; i:_ / /, 1 �:x '� 1 U f . vF � e.te� i ` A p A _ a� "all I, • d J � ® - r .Zt. , UWll 1_r�._E4,5 ` u . ____ .. Helping People Take Actions" SERIES AS SINGLE & MULTI - CANDELA AUDIBLE STROBE APPLIANCES SERIES AH AUDIBLES - . 'f F s Description _ =-_= = = R L=�-1 -,. _ Wheelock's patented 2 -wire Serie AS Audible Strobe E ' . -� Appliances and Series AH Audibles offer more features �' with low current draw. Strobe options for wall mount models include 1575cd or SERIES AS SERIES AH Wheelock's patented MCW multi - candela wall strobes with field selectable candela settings of 15/30/75/110cd, ,; d ,� = or the high intensity MCWH strobe with field selectable �T _ ' '— - -- = _ '1 a 135/185cd. 15 a 30 ` = Mt � s r �,foi Ceiling mount models incorporate Wheelock patented MCC multi - candela ceiling strobe with field selectable Multi-Candela Indicator . intensities of 15/30/75/95cd or the high intensity MCCH M u bottom la lens) strobe with field selectable 115/177cd. The audible provides a selectable choice of either a Features continuous horn or temporal pattern (Code 3) when • Approvals include: UL Standard 1971, UL Standard 464 constant voltage from a Fire Alarm Panel (FACP) is New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM), and Chicago (BFP). See approvals by applied. Each tone has 3 dBA settings to choose from. model in Specifications and Ordering Information. When used with the Wheelock Series SM or DSM Sync • ADA/NFPA/UFC /ANSI Compliant Module or Wheelock PS - 12/24 - 8CP and PS - 12/24 - 8MP • Wall mount models are available with Field Selectable Candela Settings of 15/30/75/110cd or 135/185cd Power Supplies with Patented Sync Protocol, (Multi Candela models) or 1575cd (single candela synchronization of the continuous horn tone provides the model) temporal (code 3) tone (mandated by NFPA 72) Ceiling mount models are available with field selectable • simultaneously for all audible appliances. This ensures a candela settings of 15/30/75/95cd or 115/177cd distinct temporal (code 3) pattern when 2 or more audibles (multi - candela ceiling models) are within hearing distance. If not synchronized the • Selectable Continuous Horn or Temporal (Code 3). temporal sound could overlap and not be distinctive. At • 3 Selectable dBA settings (99, 95 and 90 dBA) in both the same time the strobes will be synchronized. This tones provides the ability to comply with ADA guidelines • Patented 2 - Wire Audible Strobe Appliance. Patented Universal Mounting Plate concerning photosensitive epilepsy and the NFPA • Weatherproof models are available for outdoor use standards when installing 2 or more visual appliances Strobes produce 1 flash per second over the regulated within the field of view all of this plus the ability to silence voltage range the audible is achieved by using only 2 wire. • 12 and 24 VDC models with wide UL "Regulated Voltage Range" using filtered DC or unfiltered FWR input voltage • • The strobes can be synchronized using Wheelock's sync modules or power supplies with built in sync protocol • Fast installation with IN /OUT screw terminals using For Weatherproof Series AS, See Datasheet S9004 #12 to #18 AWG wires Copyright 2004 Wheelock Inc. All rights reserved. . L NOTE: All CAUTIONS and WARNINGS are identified by the symbol A . All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION; WHICH COULD RESULT IN PROPERTY • DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. General Notes • Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Note that NFPA -72 (1999) specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971: • Series AS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32° F to 120° F (0° C to 49° C) and maximum humidity of 93% (± 2 %). Series AH -24 horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). • Series AH -24WP audible appliances are listed under UL Standard 464 for indoor /outdoor use with a temperature range of -31 °F to 150 °F ( -35 °C to 66 °C) and.maximum humidity of 95 %. • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change, UL used the terminology "Listed Voltage Range ". Table 1: Ratings Per UL 1971 Regulated Modal Input Voltage VDC Range VDCIFWR voltage Strobe Candela (cd) AS -24MCW 24 16.0 - 33.0 15/30/75/110 AS- 24MCCH 24 16.0 - 33.0 115/177 AS- 241575W 24 16.0 - 33.0 15 (75 on Axis) AS- 121575W 12 8.0 - 17.5 15 (75 on Axis) AS -24MCC 24 16.0 -33.0 15/30/75/95 AS- 24MCWH 24 16.0 - 33.0 135/185 ASWP -2475W 24 16.0 - 33.0 75 © -31 ° F Table 2: dBA Ratings for 12 VDC and 24 VDC Series AS /AH 12 and 24 VDC Audible Description Volume Reverberant dBA Anecholc Per UL 464 @ 10 ft. dBA ©10 fL High 91 99 Continuous Horn Medium 88 95 Low 83 90 High 87 99 Code 3 Horn Medium 84 95 Low 79 90 Table 3: Average RMS Current Audible Wall Mount Audible Strobe Models Ceiling Mount Audible Strobe Models 24 VDC Models AH -24 AS- 241575W AS -24MCW AS- 24MCWH AS -24MCC AS- 24MCCH 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.062 0.100 0.080 0.102 0.150 0.194 0.250 0.320 0.088 0.114 0.165 0.205 0.250 0.320 High (99) dBA UL max' 0.080 0.121 0.088 0.125 0.200 0.267 0.355 0.480 0.095 0.138 0.221 0.285 0.355 0.480 24 vdc 0.033 0.080 0.060 0.084 0.132 0.173 0.230 0.305 0.066 0.092 0.145 0.186 0.230 0.305 Med (95) dBA UL max' 0.043 0.107 0.074 0.110 0.190 0.253 0.340 0.465 0.080 0.122 0.201 0.269 0.340 0.465 1 24 vdc 0.017 0.072 0.052 0.076 0.121 0.158 0.220 0.295 0.056 0.082 0.132 0.173 0.220 0.295 Low (90) dBA UL max' I 0.021 0.100 0.068 0.105 0.182 0.245 0.335 0.460 0.074 0.113 0.198 0.263 0.335 0.460 • Audible Wall Mount 12 VDC Models Audible Strobe AH - 12 AS 121575W • RMS current ratings are per UL average RMS method. UL max current • - 12 vdc 0.163 0.260 rating is the maximum RMS current within the listed voltage range (16- High (99) dBA UL max' 0.192 0.320 33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current 12 vdc 0.076 0.195 is usually at the maximum listed voltage (33v for 24v units). For unfiltered Med (95) dBA FWR ratings, see installation instructions. UL max' 0.108 0.275 12 vdc 0.039 0.175 Low (90) dBA UL max' 0.058 0.265 • fr �f c ; ii � : 4 : � is : 4 ' L7 I J Helping People Take Actions" SERIES RSS & RSSP SINGLE & MULTI - CANDELA STROBES & STROBE PLATES DESCRIPTIO ,f , >Y Wheelock's patented Series RSS Strobe Appliances and w"• � � , , Series RSSP Strobe Plates have lower current draw while s: , lqF'�,. : -�:>.; ' F ; _ ::....n / maintaining outstanding performance, reliability and cost f , i effectiveness. These versatile appliances will satisfy F _ -- // virtually all requirements for indoor, wall or ceiling mount Series RSS RSS Round applications. Series RSSP Strobe options for wall mount models include 1575 or `_ <�_; Wheelock's Patented MCW multi - candela strobe with field — • . selectable candela settings of 15/30/75/110cd or the high . .. • �� • o _ intensity MCWH strobe with field selectable 135/185cd. R . 75 f �' j to • ` Ceiling mount models include the patented MCC multi- 1� candela ceiling strobe with field selectable intensities of Multi - Candela Indicator ' 15/30/75/95cd or the high intensity MCCH strobe with (bottom of Strobe Lens) • field selectable 115/177cd. Features ' All models may be synchronized using the Wheelock • Approvals include: UL Standard 1971, New York City SM, DSM Sync Modules or the PS- 12/24 -8CP and (MEA), California State Fire Marshal (CSFM), Factory PS- 12/24 -8MP Power Supplies with Wheelock's Patented Mutual (FM), and Chicago (BFP) See approvals by Sync Protocol. Synchronized strobes can eliminate model in Specifications and Ordering Information possible restrictions on the number of strobes in the field • ADA/NFPA/UFC /ANSI compliant. Meets OSHA 29 of view. Wheelock's synchronized strobes offer an easy Part 1910.165 way to comply with ADA recommendations concerning • Wall mount Multi - Candela models are available photosensitive epilepsy as well as meeting the with Field Selectable Candela Settings of 15/30/ requirements of NFPA 72. 75/110cd or 135/185cd. Single Candela models are available in 1575cd Wheelock's Series RSS Strobes employ a Patented • Ceiling mount Multi- Candela models are Integral Strobe Mounting Plate that can be mounted to a available with field selectable candela settings of • single gang, double gang, 4" square, 100mm European 15/30/75/95cd or 115/177cd. (Round or Square) backboxes or the SHBB surface backbox. If the flush • Strobes produce 1 flash per second over the backbox has side or top space between it and the finished regulated voltage range wall, the NATP (Notification Appliance Trimplate) may be • 12 and 24 VDC models with wide UL "Regulated used. It provides an additional .65" of trim for the Appliance. Voltage" using filtered (DC) or unfiltered VRMS input An attractive cover plate is provided for a clean, finished voltage appearance on all models. • Synchronize using Wheelock's sync modules or power supplies with built -in sync protocol - The Series RSSP Multi- Candela Strobe Plates are a cost • Fast installation with IN /OUT screw terminals using effective way to retrofit required wall strobe appliances to #12 to #18 AWG wire bells, horns, chimes, multitones or speakers and easily mounts to standard 4" backboxes or for surface mount use with Wheelock's SBL2 surface backbox. For Weatherproof Series RSS See Datatsheet S9004 Copyright 2004 Wheelock, Inc. All rights reserved. 1' NOTE: All CAUTIONS and WARNINGS are identified by the symbol O. All warnings are printed in bold capital letters. • A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN • IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. • • • General Notes • Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Note that NFPA -72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. - . • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series RSS & RSSP Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32° F to 120° F (0° C to 49° C) and maximum humidity of 93% (± 2%). • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change, UL used the terminology "Listed Voltage Range ". Table 1: Average RMS Current* RSS /RSSP -Wall Mount RSS - Ceiling Mount RSS /RSSP 24VDC 241575W 24MCW 24MCWH 24MCC 24MCCH Models 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270 UL max` 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420 RSS /RSSP RSS/RSSP * RMS current ratings are per UL average RMS method. UL max current 24VDC Wall Mount rating is the maximum RMS current within the listed voltage range (16 -33v Models 121575W for 24v units). For strobes the UL max current is usually at the minimum 12 vdc 0.152 listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, UL max` 0.255 see installation instructions. Table 2: Audibles /Speakers for RSSP Strobe Plate Product Series Multitone Appliances AMT, MT Horns AH, NH, HS Motor Bells MB- G6/G10 Speakers ET- 1010/1080, E70, ET70 Chimes CH70 A WARNING: CONTACT WHEELOCK FOR THE CURRENT "INSTALLATION INSTRUCTIONS" AND "GENERAL INFORMATION" SHEET (P82380) ON THESE PRODUCTS. THESE DOCUMENTS UNDERGO PERIODIC CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING: • TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. • FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS. • ADDING, REPLACING OR CHANGING APPLIANCES OR CHANGING CANDELA SETTINGS WILL AFFECT CURRENT DRAW. RECALCULATE CURRENT DRAW TO INSURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY ALL APPLIANCES DO NOT EXCEED THE RATED CAPACITY OF THE POWER SOURCE OR FUSES. • COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW. • • THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR "REGULATED VOLTAGE RANGE ". • INSTALLATION OF 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS. • INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES. • USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBES ON CODED OR • • INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBES MAY NOT FLASH. • FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER INSTALLATION, APPLICATION, AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. • CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS.