Specifications rp5a o -o oC(
I 7ay.o( ✓e
D E PORTLAND, OR 97224
PHONE 503 - 620 -4020 RECEIVED
FIRE, I N C/ FAX 503 - 620 -1058
• CCB# 64174
OCT 14 2009
CITY OF TIGARD
BUILDING DIVISION
Oregon Business Park III
CIDA Inc
DATA SUBMITTAL
FOR
FIRE PROTECTION SYSTEM
October 13, 2009
09 -4391
FIRE PROTECTION CONTRACTORS
Oregon Business Park III — CIDA, Inc.
October 13, 2009
Page 2 of 2
TABLE OF CONTENTS
Pipe & Fittings
Pipe
CIS Fittings
Victaulic Mechanical Tee Style #920/921
Victaulic Firelock Outlet Tee Style #922
Hangers
Tolco Pipe Ring Fig. #200
Tolco C -Type Beam Clamp Fig. #65
Tolco Retainer Strap Fig. #69
Sammy Super Screws Fig. #XP -20
Sprinkler Heads
Reliable Model Fl ' /2" 155 Degree Chrome Pendent
FIRE PROTECTION CONTRACTORS
a a
INUC NUCN
-- - I -' Pipe and Supply Corp.
Pipe Specification A135
Specification A135 NPS 1/4 -- 30 ", Schedules 10, 40 and XL THD, Lightwall
Scope Covers two grades of electric resistance welded steel pipe. Grade A is adapted for flanging and bending and is suitable for
welding. Purpose for which pipe is intended should be stated on order.
Kinds of Steel Permitted Open -hearth Basic - oxygen
For Pipe Material Electric- furnace
Permissible Variations The minimum wall thickness at any point shall not be more than 12.5% under the nominal wall thickness specified.
in Wall Thickness Threadable, lightwall (XL) must meet manufacturers minimums.
Chemical C max % Mn max °/u P max % S max "/o
Requirements Seamless or ERW
Grade A 0.25 0.95 0.05 0.06
Grade B 0.30 1.20 0.05 0.06
Tensile Grade A Grade B
Requirements Tensile Strength, min., psi 48,000 60,000
Yield Strength, min., psi 30,000 35,000
NDE & Hydrostatic inspection test pressures for plain end and threaded are specified. Hydrostatic pressure shall be maintained
Hydrostatic for not less than 5 seconds for all sizes of electric resistance weld pipe. Non - destructive electric test should be in accordance
Testing with practices E213, method E227 or practice E213.
Permissible Variations Plus or Minus 10% schedule 10
in Weights per Foot Plus 10% minus 3 1/2% schedule 40
Permissible Variations Plus or minus 1%
in Outside Diameter
Mechanical Tests Tensile Test -- Transverse returned on pipe NPS 8 and larger.
Specified Flattening test -- Three steps required with weld located 0° or 90° from the line of direction of force required.
Number of Flattening and tensile on one length of pipe from each lot of 400 lengths or less of a style.
Tests Required
Lengths Pipe shall be furnished in 38' with a minimum of 20 ft. Pipe furnished to schedule 10 shall be in a specified length between
16 and 22 ft.
Required Markings Rolled, Stamped or Stenciled (Mfgrs. Option)
on Each Length Name or brand of manufacturer.
(On Tags attached to Kind of pipe, that is, electric- resistance welded A, electric welded B, same schedule wall thickness, schedule 10 or 40, NL
each Bundle in case ASTM A135
of Bundled Pipe) Length of pipe.
General End finish may be plain end beveled or plain end square cut.
Information
Standards and Specifications
( __ � � AIMV
1L'
INTfNN•T10NAl. INC.
Ill .
Dimensions Material Galvanizing Thread Pressure Federal/Other
! Rating
1 .Mi. Fittings .
! Class 150 /PN 20 ASME 816.3• ASTM A -197 ASTM A -153 ASME 81 20.1+ ASME 8163• ASME 816.3"
l r Class 300 /PN 50 ASME 816.3• ASTM A -197 ASTM A -153 ASME 8120.1+ ASME 816.3•
i M.I. Unions
Class 150 /PN 20 ASME 816.39• ASTM A -197 ASTM A -153 ASME 8120.1+ ASME 816.39• ASME 816.39'
Class 250 ASME B16.39• ASTM A -197 ASTM A -153 ASME 8120.1+ ASME 816.39•
Class 300 /PN 50 ASME 816.39• ASTM A -197 ASTM A -153 ASME 8120.1+ ASME 816.39•
Cast Iron Threaded Fittings
1 Class 125 ASME 816.4• ASTM A -126 (A) ASTM A -153 ASME 81.20.1+ ASME 816.4• ASME 816.4111
Class 250 ASME 816.4• ASTM A -126 (A) ASTM A -153 ASME 81.20.1+ ASME 816.4• ASME 816.4•
C. 1. Plugs and Bushings
ASME 816.14• ASTM A -126 (A) l ASTM A -153 ( ASME 81.20.1+ ASME B16.14• WW -P-471
C. 1. Drainage Threaded Fittings
ASME 816.12• ASTM A -126 (A) ASTM A -153 ASME 81.20.1+ ASME 816.12•
4 C. 1. Flanges and Flanged Fittings
Class 125 (1' -12') ASME 816.1• ASTM A- 126 (A) or (B) ASTM A -153 ASME 81.20.1+ ASME B16.1 ASME 816.1•
Class 125 (14•-up) ASME 816.1• ASTM A -126 (8) ASTM A -153 ASME 81.20.1+ ASME 316.1 ASME 816.1•
-
Class 250 (1 t -12') ASME 816.1• ASTM A- 126 (A) or (8) ASTM A -153 ASME 81.20.1+ ASME 316.1 ASME 316.1.
Class 250 (14' -up) ASME 816.1• ASTM A -126 (B) _ ASTM A -153 ASME 81.20.1+ ASME 816.1 ASME 816.1•
Forged Steel Threaded Fittings
Class 2000. 3000. ASTM A105.
6000 ASME 816.11• ASTM A182, ASME81.20.1+ ASME 81611•
ASTM A350
Pipe Nipples
Steel Pipe ASTM A733 ASTM A53 ASME 81.201+ WWN 351
- Welded Type F or Type E
Steel Pipe
- Seamless ASTM A733 ASTM A106 Gr. B ASME 81.20.1+ WWN 351
(High Temp.)
Brass ASTM 843 ASME B1.20.1+ YAWN 351
•The standard
•an American National standard (ANSI)
+ASME 81.20.1 was ANSI 32.1
•Formerly WW-P -501
•'Formerly WW-P -521
• • •Formerly WW -U -531
•
•
PF - 149 1
IPS CARBON STEEL PIPE — HOLE CUT PRODUCTS 11.02
VICTAULIC" IS AN ISO 9001 CERTIFIED COMPANY
Styles 920 and 920N Mechanical -T® Bolted Branch Outlets
PRODUCT DESCRIPTION
Victaulic Mechanical -P Outlet provides a direct branch connection at any location a hole can be cut in
pipe. The hole is cut oversize to receive a "holefinder" locating collar which secures the outlet in position
permanently A pressure responsive gasket seals on the pipe O.D.
, ' Cross -type connections can be achieved by utilizing two upper housings of the same style and size, with
the same or differing branch size connections. NOTE Style 920 and Style 920N housings cannot be
mated to achieve a cross connection.
Style 920 and Style 920N Mechanical -T outlets are available with grooved or female threaded outlet.
Specify choice on order. Units are supplied painted with plated bolts. Galvanized housings are available,
supplied with plated bolts.
Styles 920 and 920N All sizes of Style 920 and 920N are rated at 500 psi (3450 kPa) working pressure on Schedule 10 and 40
carbon steel pipe. They may also be used on high density polyethylene or polybutylene (HDPE) pipe.
' VA Pressure ratings on HDPE are dependent on the pipe rating. Contact Victaulic for ratings on other pipe.
Style 920 and 920N are not recommended for use on PVC plastic pipe.
Standard piping practices dictate that the Mechanical -T Styles 920 and 920N must be installed so that
the main and branch connections are a true 90° angle when permanently attached to the pipeline surface.
Style 920 Cross
VS ®
See Victaulic
publication 10.01
for details.
See chart on page 5
for pressure ratings.
MATERIAL SPECIFICATIONS
Housing/Coating. Ductile iron conforming to ASTM A -536, grade 65- 45 -12, with orange enamel coating.
Ductile iron conforming to ASTM A -395, grade 65- 45 -15, is available upon special request.
• Optional: Hot dipped galvanized
Gasket: (Specify choice)
• Grade "E" EPDM
EPDM (Green color code). Temperature range -30 °F to +230 °F ( -34 °C to +110 °C). Recommended for
cold and hot water service within the specified temperature range plus a variety of dilute acids, oil -free
air and many chemical services. UL Classified in accordance with ANSI /NSF 61 for cold +86 °F
( +30 °C) and hot +180 °F ( +82 °C) NOT RECOMMENDED FOR PETROLEUM SERVICES.
• Grade "T" nitrile
Nitrile (Orange color code). Temperature range -20 °F to +180 °F ( -29 °C to +82°C) Recommended for
petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature
range. Not recommended for hot water services over +150 °F ( +66 °C) or for hot dry air over +140 °F
( +60 °C).
'Services listed are General Service Recommendations only. It should be noted that there are services for
which these gaskets are not recommended. Reference should always be made to the latest Victaulic
Gasket Selection Guide for specific gasket service recommendations and for a listing of services which
are not recommended.
Bolts/Nuts: Heat - treated plated carbon steel, trackhead meeting the physical and chemical
requirements of ASTM A -449 and physical requirements of ASTM A -183.
REGISTERED TRADEMARK OF VICTAULIC - 0 COPYRIGHT 2004 VICTAULIC - PRINTED IN U.S.A. - SKU OWCAS-67BNLV 1480 REV G
United States • Phone: 1 -800- PICK -VIC (1 -800 -742- 5842) • Fax: 610- 250 -8817 • e -mail: pickvic @victaulic.com
Canada • Phone: 905- 884 -7444 • Fax: 905 -884 -9774 • e -mail: viccanada @victaulic.com
Europe • Phone:32 -9- 381.1500 • Fax: 32 -9 -380 -4438 • e -mail: viceuro @victaulic.be , �� �', �®
Central and South America • Phone: 610. 559 -3300 • Fax: 610. 559.3608 • e -mail: viral @victaulic.com
Australasia • Phone: 86-21-58855151 • Fax: 86.21- 58851298 • e -mail: vicap@victaulic.com
11.02
DIMENSIONS
=
y =� Max. Dimensions - Inches/millimeters Aprx.
SIZE Work. Hole Fem. Wgt. Each
^, I Run X Branch Press. Dia. Thd. Grv. Lbs/kg
V �� N ominal Inches Style PSI +0.13 V V Fern.
/1-r ^ r-'■ i i mm No. kPa -0.00 T" t 4 t W V Z Thd. Grv.
■ - 2 X 500 1.50 2.00 2.53 - 1.61 5.35 2.75 3.1
-
-
� W `+ 2 X t5 920N
3450 38.1 51 64 41 136 70 1,5
+ Alt X V4 (a) 920N 500 1.50 1.97 2.53 1.61 5.35 2.75 3.1 -
Styles 920 and 920N X 20 3450 38.1 50 64 41 136 70 1,5 -
w /Grooved Outlet X 1 (a) 920N 500 1.50 1.85 2.53 - 1.61 5.35 2.75 3.0 -
X 25 3450 38,1 47 64 - 41 136 70 1,4 -
X 1 (a) t 920N 500 1.75 2.05 2.75 3.00 1.61 5.35 3.00 3.5 3.2
X 32 3450 44.5 52 70 76 41 136 76 1,7 1.5
v T z -1 X "3 (a) 1 920N 500 1.75 2.03 2.75 3.12 1.61 5.35 3.25 3.6 3.2
i I X 40 3450 41,5 52 70 79 41 136 83 1,7 1.5 Poll 1
2V2 X 1 /2 (a) 500 1.50 2.21 2.74 - 1.86 5.64 275 3.0 -
.41 sic T r-r 65 X 15 920N 3450 38.1 56 70 47 143 70 1.1 k� I ` / X �/' (a) 920N 500 1.50 2.18 2.74 1 86 5.64 2.75 3.0
-
X 3450 38,1 55 70 47 143 70 1,4
X 500 -
Styles 920 and d 920N X 1 ( 25 920N 3 3� 0 2 2 1 1.86 143 2 70 1,4
w/Female Threaded Outlet X 1'/4 t (a) 920N 500 1.75 2.30 3.00 3.25 1.86 6.29 3.00 3.5 3.2
X 32 3450 44,5 58 76 83 47 160 76 1,7 1.5
X 1 t (a) 920N 500 2.00 2.28 3.00 3.25 1.86 6.26 3.25 3.6 3.3
X 40 3450 50.8 58 76 83 47 159 83 1,7 1.6
NOTE: Style 920 and Style 76.1 mm X 1 /2 (a) 300 1.50 2.22 2.75 - 1.88 6.46 3.16 3.9 -
920N housings cannot be X 15 920 2065 38,1 56 70 - 48 164 80 1.8 -
mated to achieve cross X 3 /4 (a) 920 300 1.50 2.19 2.75 - 1.88 6.46 3.16 3.9 -
connections. X 2 2065 38,1 56 70 - 48 164 80 1,8 -
X 1 (a) 300 1.50 2.07 2.75 - 1.88 6.46 3.16 3.8 -
These new size Style X 25 920 2065 38,1 53 70 - 48 164 80 1.7 -
NEW 920N products require a
HOLE SIZE different hole size than X 1 /4 (a) T 920N 500 1.75 2.30 3.00 3.31 1.92 6.29 3.00 3.5 3.2
the Style 920 it replaces. X 32 3450 44.5 58 76 84 49 160 76 1.6 1.5
for proper installation. X 1 (a) 500 2.00 2.28 3.00 3.31 1.92 6.29 3.25 3.5 3.3
Use caution Co assure X 40 920N 3450 50,8 58 76 84 49 160 83 1.6 1.5
the proper size hole is
prepared for the specific 3 X 1 /3 (a) 920N 500 1.50 2.52 3.05 - 2.28 6.15 2.75 3.4 -
size and style used. 80 X 15 3450 38,1 64 78 - 58 156 70 1.6 -
Failure to use the proper X 3 14 (a) 500 1.50 2.49 3.05 - 2.28 6.15 2.75 3.4
hole size could result in X 920N 3450 38,1 63 78 58 156 70 1,6
joint leakage and -
property damage. X 1 (a) 920N 500 1 50 2.38 3.06 - 2.28 6.15 2.75 3.3 -
X 25 3450 38.1 61 78 - 58 156 70 1,6 -
X 1'/4 (a) t 920N 500 1.75 2.55 3.25 3.56 2.28 6.15 3.00 3.8 3.7
X 32 (b) 3450 44,5 65 83 90 58 156 76 1.8 1.8
X 1 (a) t 920N 500 2.00 2.78 3.50 3.56 2.28 6.15 3.25 4.1 3.8
X 40 (b) 3450 50.8 71 89 90 58 156 83 1.9 1.8
X 2 (a) 920N 500 2.50 2.75 3.50 3.56 2.28 6.75 3.88 4.9 4.6
X 50 3450 63.5 70 89 90 58 172 99 2.3 2,1
3 X 2 920N 500 2.50 - 3.75 2.44 6.72 3.88 - 3.8
90 X 50 3450 63.5 - 95 62 171 99 - 1.8
4 X 1 12 (a) 920N 500 1.50 3.03 3.56 - 2.69 7.01 2.75 3.7 -
100 X 15 3450 38,1 77 90 - 68 178 70 1,8 -
X 3 /4 (a) 920N 500 1.50 3.00 3.56 - 2.69 7.01 2.75 3.7 -
X 20 345C 38,1 76 90 - 68 178 70 1,8 -
X 1 (a) 920N 500 1.50 2.88 3.56 - 2.69 7.01 2.75 3.6 -
X 25 345C 38,1 73 90 - 68 178 70 1,8 -
X 1' /4 (a) t 920N 500 1.75 3.08 3.78 4.00 2.69 7.01 3.00 4.0 3.6
X 32 (b) 3450 44,5 78 96 102 68 178 76 1,9 1,8
X 1 (a) 1 920N 500 2.00 3.28 4.00 4.00 2.69 7.01 3.25 4.2 3.9
X 40 (b) 3450 50,8 83 102 102 68 178 83 2,0 1,9
X 2 (a) t 920N 500 2.50 3.25 4.00 4.00 2.69 7.01 3.88 5.0 4.6
X 50 3450 63.5 83 102 102 68 178 99 2,3 2,1
X 2 (a) 1 500 2.75 2.88 4.00 4.00 2.69 7.34 4.63 5.8 5.0
X 65 920 3450 69.9 73 102 102 68 186 118 2.6 2,3
X 76,1 mm 920 500 2.75 - - 4.00 2.69 7.34 4.63 - 6.4
3450 69,9 - - 102 68 186 118 - 2.9
X 3 (a) t 500 3.50 3.31 4.50 4.12 2.69 7.73 5.12 8.4 6.4
X 80 920 3450 88.9 84 114 105 68 196 130 3,8 2,9
108,0 mm X 1 (a) 920N 500 1.75 3.08 3 78 - 2.63 7.64 3.05 5.0 -
•
X 32 3450 44,5 78 96 - 67 194 78 2.3 -
X 1 /2 (a) 920N 500 2.00 3.28 4.00 - 2.63 7.64 3.25 5.0 -
X 40 3450 50.8 83 102 - 67 194 83 _ 2.3 -
Table continued on page 3. See notes on page 4.
2 Styles 920 and 920N Mechanical -T'' Bolted Branch Outlets
11.02
DIMENSIONS
Y 2 SIZE Max. Hole Dimensions - Inches /millimeters Aprx. Wgt. Ea
I Run X Branch Work. Dia. Fern. l bsJkg
- 1 y ! Nominal Inches Style Press. +0,13 Thd. Grv. Fern.
L � _ v ; 108.0 mm mm No. PSUkPa -0.00 7** V** V # W Y Z Thd. Gm
' �4' X 2 (a) 500 2.50 3.25 4.00 - 2.63 7.64 4.00 4.00 5.6
j x 920N 3450 63.5 83 102 67 194 102 2.5 so 1 ■ � � i w 76,1 mm 920 500 2.75 2.88 4.00 4.00 2.63 7.64 4.29 8.00
4 3450 69.9 73 102 102 67 194 109 203.20
Styles 920 and 920N X 3 (a) 500 3.50 3.31 4.50 4.00 2.63 7.63 4.88 - 6.5
w/Grooved Outlet X 80 920 3450 88,9 84 114 102 67 '194 124 - 3.0
5 X 1 /2 500 2.00 4.22 4.75 3.16 9.70 3.69
125 X 15 920 3450 50,8 107 121 80 246 94
X 1 (a) • 500 2.00 4.03 4.75 4.75 3.16 9.70 3.69 7.4 7.6
X 40 920 3450 50.8 102 121 121 80 246 94 3.4 3,4
X 2 (a) T
X 50 920 500 2.50 4.00 4.75 4.75 3.16 9.70 4.38 8.2 8.0
f � - � 3450 63.5 102 121 121 80 246 111 3.7 3.6
rte. ^ �•r, T \ mil X 2' /z (a) 1. 920 500 2.75 3.63 4.75 4.75 3.16 9.70 4.63 8.3 7.9
i S 4 f i X 65 3450 69.9 92 121 121 80 246 118 3.8 3.6
W X 3 (a)1 920 500 3.50 3.81 5.00 4.63 3.16 9.70 5.31 8.4 8.8
y II X 80 3450 88.9 97 127 118 80 246 135 3.8 4,0
Styles 920 and 920N 133.0 mm X 2 920N 500 2.50 3.75 4.50 3.17 8.00 3.88
w /Female Threaded Outlet X 50 3450 63.5 95 114 81 203 99
X 3 500 3.50 3.81 5.00 3.00 9.46 5.31
X 80 920 3450 88.9 97 127 76 240 135
139,7 mm X 1'6 t 920N 500 2.00 3.78 4.50 - 3.30 8.23 3.25
X 40 3450 50,8 96 114 - 84 209 83
NOTE: Style 920 and Style X 2 t 500 2.50 3.75 4.50 - 3.30 8.23 3.88
920N housings cannot be X 50 920N 3450 63,5 95 114 - 84 209 99
mated to achieve cross X 76,1 mm (a)(b) 920 500 2.75 3.63 4.75 - 3.13 9.85 4.63 - 8.8
connections. 3450 69,9 92 121 - 80 250 118 - 4,0
here new size Style X 76.1 mm 920 500 3.50 - - 4.63 3.16 9.70 5.31 11.0 -
NEW 320N products require a 3450 88,9 118 - 80 246 135 5.0
HOLE SIZE different hole size than X 3 500 3.50 3.81 5.00 4.63 3.16 9.85 5.38 14.0
the Style 920 it replaces, X 88,9 920 3450 88,9 96.80 127 118 80 250 137 6,4
for proper installation. 6 X 1 500 1.75 4.43 5.13 5.13 3.79 9.15 3.25 4.8
Use caution to assure 920N
the proper size hole is 150 X 32 (b) 3450 44.5 112 130 130 96 232 83 - 2.2
prepared for the specific X 1 (a) t 500 2.00 4.40 5.12 5.13 3.79 9.15 3.25 5.4 5.1
size and style used. X 40 (b) 920N 3450 50,8 112 130 130 96 232 83 2.4 2,3
Failure to use the proper
hole size could result in X 2 (a) T 920N 500 2.50 4.38 5.13 5.13 3.79 9.15 3.88 6.0 5.6
joint leakage and X 50 3450 63,5 111 130 130 96 232 99 2.7 2.5
property damage. X 2 (a) T 920 500 2.75 4.01 5.13 5.12 3.69 10.51 4.63 8.3 7.6
X 65 3450 69.9 110 130 130 94 267 118 3,8 3.4
X 76,1 mm (a)(b) 920 500 2.75 - - 5.21 3.69 10.51 4.63 - 8.4
3450 69,9 - - 132 94 267 118 - 3,8
X 3 (a) t 500 3.50 4.31 5.50 5.13 3.69 10.51 5.31 9.9 8.4
•
X 80 920 3450 88.9 110 140 130 94 267 135 4,5 3.8
X 4 (a) t 920 500 4.50 3.81 5.75 5.38 3.69 10.51 6.25 10.1 10.1
X 100 3450 114.3 97 146 137 94 267 159 4,6 4,6
159,0 mm X 11/4 920N 500 1.75 4.43 5.13 3.63 9.40 3.25
X 32 3450 44,5 113 130 92 239 83
X 1'/2 (a) 920N 500 2.00 4.41 5.13 - 3.63 9.40 3.25 7.8 -
X 40 3450 50.8 112 130 - 92 239 83 3,5 -
X 2 (a) 920N 500 2.50 4.38 5.13 - 3.63 9.40 3.88 8.0 -
X 50 3450 63.5 111 130 - 92 239 99 3,6 -
X 76.1 mm 920 500 2.75 4.38 5.50 5.13 3.63 9.40 4.63
3450 69,9 111 140 130 92 239 118
X 3 500 3.50 4.31 5.50 5.13 3.63 9.40 5.31 8.10
X 80 920 3450 88,9 110 140 130 92 239 135 205.74
X 108,0 mm 920 500 4.50 - - 5.38 3.63 9.40 6.12 - 10.0
3450 114.3 - - 137 92 239 155 - 4,5
X 114,3 mm 920 500 4 50 3.81 5.75 - 3.63 9.40 6.25 18.0 -
3450 114,3 96.80 146 - 92 239 159 8,2 -
165,1 mm X 1 920N 500 1.50 3.88 4.56 3.79 9.34 2.75
X 25 3450 38,1 99 116 96 237 70
X 11/. 920N 500 1.75 4.43 5.13 3.79 9.34 3.25
X 32 3450 44,5 113 130 96 237 83
X 1 (a) I 920N 500 2.00 4.41 5.13 3.79 9.34 3.25
X 40 3450 50,8 112 130 96 237 83
X 2 (a) 1 920N 500 2.50 4.38 5.13 3.79 9.34 3.88
• X 50 3450 63,5 111 130 96 237 99
X 2 t 920 500 2.75 4.01 5.13 - 3.63 10.51 4.63 8.6 7.6
X 65 3450 69.9 110 130 - 92 267 118 3,9 3,4
Table continued on page 4. See notes on page 4
Styles 920 and 920N Mechanical -T' Bolted Branch Outlets 3
11.02
DIMENSIONS
- =_ = � SIZE Max. Hole Dimensions - Incheslmillimeters
Run X Branch Work. Dia.
t Nominal Inches Style Press. *0.13 Apnt. Wgt. Ea
V mm No. PSUkPa -0.00 LbsAtg
sir ^ r�r \Ifi�� 165,1 mm 920 500 2.75 4.01 5.13 5.21 3.63 10.51 4.63 8.6 7.6
X 76,1 mm (ow
_ i1 3450 69,9 110 130 132 92 267 118 3.9 3.4
X 3 (a) t 920 500 3.50 4.31 5.50 5.13 3.63 10.51 5.31 10.2 8.4
+ IVI X 80 3450 88.9 110 140 130 92 267 135 4.6 3,8
Styles 920 and 920N X 4 (a) t 920 500 4.50 3.81 5.75 5.38 3.63 10.51 6.25 10.5 8.4
y X 100 3450 114,3 97 146 137 92 267 159 4.8 3,8
w /Grooved Outlet 8 X 2 (a) 500 2.75 5.44 6.19 - 4.81 12.42 4.50 11.6 -
200 X 50 920 3450 69.9 138 157 - 122 316 114 5.3 -
X 2'/2 (a) t 500 2.75 5.07 6.19 6.19 4.81 12.42 4.50 11.6 11.6
X 65 920 3450 69.9 129 157 157 122 316 114 5.3 5,3
+ Y 7 _� X 3 ( t 920 3450 88.9 5.31 6.50 6.50 4.81 2 12.42 135 12.6 11.6
80 V 7 161 T r � � X 4 (a) t 920 500 4.50 4.81 6.75 6.38 4.81 12.42 6.25 15.3 12.5
X 100 3450 114.3 122 171 162 122 316 159 6.9 5,7
- + M
Styles 920 and 920N
w /Female Threaded Outlet
NOTE: Style 920 and Style
920N housings cannot be
mated to achieve cross
connections.
These new size Style
NEW 920N products require a
HOLE SIZE different hole size than
the Style 920 it replaces,
for proper installation.
Use caution to assure
the proper size hole is
prepared for the specific
size and style used.
Failure to use the proper
hole size could result in
joint leakage and
property damage.
NOTES
"Center of run to engaged pipe end,
female threaded outlet only (Dimen-
sions approximate).
Available with grooved or female
threaded outlet. Specify choice on
order.
# Center of run to end of fitting.
# Female threaded outlets are avail-
able to NPT and BSPT specifications.
(a) British Standard female pipe
threaded outlet is available as listed.
Specify "BSPT" clearly on order.
(b) For 76,1 mm threaded outlet. spec
ify 2' /i BSPT clearly on order.
4 Styles 920 and 920N Mechanical -T'"' Bolted Branch Outlets
11.02
FLOW DATA
OUTLET SIZE Equivalent Length OUTLET SIZE Equivalent Length
Feet/meter of Pipe Feet/meter of Pipe
Nominal Actual Nominal Actual
Diameter Ouut. . Di a. Female Diameter Out. Die. Female
• 1.61 InJmm InJmm Grooved Threaded In /mm InJmm Grooved Threaded
0.840 2.0 2 2.375 9.0 10.5
ail 15 21.3 - 0.6 50 60,3 2.7 3.2
0 ilEi MIN 3 /4 1.050 - 4.0 2 2.875 11.0 12.5
20 26,7 1,2 65 73,0 3,4 3.8
1 1.315 5.0 3 3.500 13.5 15.5
Exaggerated for Clarity 25 33,7 1.5 80 88,9 4,1 4.7
114 1.660 5.5 6.0 4 4.500 20.0 22.0
Flow test data has shown that 32 42.4 1,7 1,8 100 114.3 6.1 6.7
the total head loss between 1 1.900 7.0 8.0
point (1) and (2) for the Style 40 48,3 2.1 2.4
920, 900N and 929
Mechanical -T fittings can Formulas for CV Values:
best be expressed in terms of
the pressure difference across ,AP _ Where:
the inlet and branch. The
pressure difference can be C .. Q = Flow (GPM) Cv = Flow Coefficient
obtained from the relationship Q = C,, x AP = Pressure Drop (PSI)
to the right.
Cv Values Pipe Size Pipe Size Pipe Size
Values for flow of water at Actual Actual Actual
+16 °C are shown i n Nominal Outside Nominal Outside Nominal Outside
+60 °F
(+16°C) Diameter Diameter Cv Diameter Diameter Cv Diameter Diameter Cv
the table at right. Inches/mm Inches/mm Values Inches/mm Inches/mm Values Inches/mm Inches/mm Values
72 0.840 144 1.660 2'/2 2.875 135
15 21,3 32 42,4 65 73,0
3 /4 1.050 1 1.900 3 3.500
20 26,7 2 40 48.3 80 88,9 200
1 1.315 2 2.375 4.500
?5 33? 25 50 603 114.3 400
APPROVED PRESSURE RATINGS
The information provided below is based on the latest listing and approval data at the time of publication.
Listings/Approvals are subject to change and /or additions by the approvals agencies. Contact Victaulic
for performance on other pipe and the latest listings and approvals.
Rated Working Pressures
Run Slim PSUkPa
Actual
Nominal Outside
Diameter Diameter Outlet Size Pipe
Inches/aim Inches/mm Inches/mm Schedul UL ULC FM
2 - 6 2.875 - 6.625 All 10, 40 400 400 400
65 - 150 73.0 - 168.3 2755 2755 2755
2 - 4 2.875 - 4.500 300 300 300
65 - 100 73,0 - 114.3 All DF 2065 2065 2065
2 - 4 2.875 - 4.500 All SF 300 300 300
65 - 100 73.0 - 114,3 2065 2065 2065
6 6.625 300 300 250
150 168.3 3. 4 10 2065 2065 1724
6 6.625 300 300 300
150 168.3 3,4 30, 40 2065 2065 2065
200 219,1 21/2 10, 40 2 55 - -
8 8.625 300 - 250
200 219.1 3.4 10 2065 - 1724
8 8.625 300 - 300
200 219,1 3,4 30. 40 2065 - 2065
NOTES: 10 refers to Listed /Approved Schedule 10 steel sprinkler pipe.
40 refers to Listed /Approved Schedule 40 steel sprinkler pipe.
DF refers to Listed/Approved Dyna -Flow steel sprinkler pipe manufactured by American Tube Company.
• SF refers to Listed /Approved Super -Flo steel sprinkler pipe manufactured by Allied Tube and Conduit Corporation.
. This product shall be manufactured by Victaulic Company. All products to be installed in accordance with current Victaulic installation /assembly instructions.
Victaulic reserves the right to change product specifications. designs and standard equipment without notice and without incurring obligations.
Styles 920 and 920N Mechanical -T Bolted Branch Outlets 5
IRS CARBON StEEL PIPE - HOLE CUT PRODUCTS 1 0.52
FireLock® Outlet T
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
•
STYLE 922
The Style 922 Outlet -T provides a convenient method of incorporating Ifz, 1/4, and 1715, 20
and 25 mm outlets for directly connecting sprinklers, drop nipples, sprigs, gauges, drains and
other outlet products. Available for 1 through 76.1 mm /32 to 76.1 mm piping systems, Style
• 922 outlets are UL /ULC Listed, LPC, Vds /FM approved for branch connections on wet and dry
systems.
The locating collar engages into the hole prepared in the pipe. When tightened, the assembly
IP a
compresses the gasket onto the OD of the pipe. The Style 922 Outlet -T is UL /FM rated up
to 300 psi /2068 kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire
protection systems.
Style 922 is suitable for use on standard, lightwall, Schedule 5 and other specialty pipes.* It is
supplied with a clear, rust inhibitive coating. Contact Victaulic for other optional coatings.
*Consult Section 10.01 for specific listings /approvals.
MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A -536, grade 65- 45 -12. Ductile iron conforming to ASTM
A -395, grade 65- 45 -15, is available upon special request.
Gasket:
• Grade "E" EPDM - Type A
(Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and
Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services up to the
rated working pressure using the Grade "E" Type A Gasket System.
Bolts/Nuts: Heat - treated plated carbon steel, trackhead meeting the physical and chemical require-
ments of ASTM A -449 and physical requirements of ASTM A -183.
JOB/OWNER CONTRACTOR ENGINEER
System No. Submitted By Spec Sect Para
Location Date Approved
Date
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. 1Ctaul.0
REVD 10.52 1
IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS 10.52
FireLock® Outlet T ®O e ca 01
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
STYLE 922
6
DIMENSIONS Nominal Size Hole A
pprox.
inches /mm Diameter Dimensions - inches /millimeters Weight Ea,. I'
Run X Branch +0.061 +1.5
y Z FPT* - 0.0010.0 P V W Y Z Ihs/kg
r ____ I
1 !/a X 1/2 114. 1.30 1.83 1.10 3.87 2.56 L0
� 32 15 30.2 33.0 46.5 27.9 98.3 65.0 0.45
T 14 194 1.28 1.83 1.10 3.87 2.56 1.1
.� / ` �. f \D".4( 20 30.2 32.5 46.5 27.9 98.3 ' 65.0 0.50
IMI .,�/ 1 1 V. 152 2.18 1.10 3.87 256 1.2
�� irk 25 30.2 38.6 55.4 27.9 98.3 65.0 0.54
1 h 1/2 194 1.42 1.95 1.22 4.08 2.56 1.2
40 X 15 30.2 36.1 49.5 31.0 103.6 65.0 0.54
14 1 94 1.40 1.95 1.22 4.08 2.56 1.2
20 30.2 35.6 _ 49.5 31.0 103.6 65.0 0.54
1 194 1.64 2.30 1.22 4.08 2.56 1.3
25 30.2 41.7 58.4 31.0 103.6 65.0 0.59
2 y 134 1.66 2.19 1.46 4.60 256 13
50 X 15 30.2 42.2 55.6 37.1 116.8 65.0 0.59 _
14 1 95. 1.64 2.19 1.46 4.60 256 1.4
20 30.2 41.7 55.6 37.1 116. 65.0 0.64
1 1'15. 1. 234 1.46 4.60 236 15
25 30.2 47.8 64.5 ■ 37.1 116.8 65.0 0.68
21/2 Yz 135. 1.91 2.44 T 1.71 5.40 256 1.6
65 X 15 30.2 48.5 62.0 43.4 137.2 65.0 0.73
14 1 Via 1.89 2.44 1.71 5.40 256 1.6
20 30.2 48.0 62.0 43.4 137 65.0 0.73 _
1 135. 2.13 2.79 1.71 5.40 2.56 1.6
25 30.2 54.1 70.9 43. 137,2 65.0 0.73
76.1 mm X Yz 195. 1.91 2.44 1.71 530 256 1.6
15 30.2 48.5 62.0 43.4 139.7 65.0 0.73
34 195. 1.89 2.44 1.71 530 256 1.6
20 30.2 48.0 62.0 43.4 139.7 65.0 0.73
1 194 2.13 2.79 1.71 5.50 2.56 1.7
25 30.2 54.1 70.9 1 43.4 139.7 65.0 0.80
t Victaulic female threaded products are designed to accommodate standard NPT or BSPT (optional)
male pipe threads only. Use of male threaded products with special features, such as probes, dry pen-
dent sprinklers, etc., should be verified as suitable for use with this Victaulic product. Failure to verify
suitability in advance may result in assembly problems or leakage.
"Center of run to engaged pipe end for NPT threads (dimensions are approximate).
www.victaulic.com ✓ctauIic'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY ® 2006 VICTAULIC COMPANY ALL RIGHTS RESERVED. PRINTED IN THE USA
10.52_2 REVD
IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS 10.52
Fi reLock ® Outlet -T SEE VICTAULIC Q ICPUBLICATION1 0 . 0.01 FOR DETAILS
•
STYLE 922
4
PERFORMANCE
Equivalent Length of
Nominal Size 1" Pipe
Inches/mm Feet /meters
114 X 1 8.5
32 25 2.6
1'V 1 8.5
40 25 2.6
2 1 — — 8.5
50 X 25 2.6
2' a I 8.5
65 X 25 2.6
761 mm X — 8.5
25 2.6
•
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. ® 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA jCtaullC'
REVD 10.32 3
IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS 10.52
R UL FY U C 1
FireLock® Outlet -T SEE VICTAULIC PUBLICATION ®1FO�TAILS
STYLE 922
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be
installed in accordance with current Victaulic installation /assembly instructions. Victaulic reserves the
right to change product specifications, designs and standard equipment without notice and without
incurring obligations.
US & WORLD HEADQUARTERS CANADA CENTRAL AND SOUTH AMERICA
P.O. Box 31 905 - 884 -7444 1- 610- 559 -3300
Easton, PA 18044 -0031 USA 905 - 884 -9774 (fax) 1- 610 - 559 -3608 (fax)
4901 Kesslersville Road viccanada @victaulic.com vical @victaulic.com
Easton, PA 18040 USA EUROPE ASIA PACIFIC
1 -800- PICK -VIC (1- 800 - 742 -5842) 32- 9- 381 -15 -00 86- 21- 54253300
1- 610 - 559 -3300 32 -9- 380 -44 -38 (fax) 86 -21- 54253671 (fax)
1- 610 - 250 -8817 (fax) viceuro @victaulic.be vicap @victaulic.com
pickvic @victaulic.com
UNITED KINGDOM MIDDLE EAST
www.victaulic.com
44 (0) 1438741100 971 -4- 883 -88 -70 1111111111111111111 11111 III 111
44 (0) 1438313883 (fax) 971 -4- 883 -88 -60 (fax) WCAS- 6QKGYH
viceuro @victaulic.be
UPDATED 8/2006
10.52 3355 REVD /Ct9UI,C'
VICTAULIC iS A REGISTERED TRADEMARK OF VICTAULIC COMPANY ® 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
10.52
® TOLCO www.tolco.com
.. : NIBCO Revision 5/24/2001
- Fig. 200 - "Trimline" Adjustable Band Hanger 0 US LEHI
Size Range — 1/2" thru 8" pipe
• Material — Carbon Steel, Mil. Galvanized to G90 .,.
specifications
Function — For fire sprinkler and other general piping
purposes. Knurled swivel nut design permits hanger
adjustment after installation. `
Features — .„...< • (1/2" thru 2 ") Flared edges ease installation for
all pipe types and protect CPVC plastic pipe from
i
abrasion. Captured design keeps adjusting nut i e
from separating with hanger. Hanger is easily B
installed around pipe.
• (21/2" thru 8" Spring tension on nut holds it A A
securely in hanger before installation. Adjusting
nut is easily removed.
Approvals — Underwriters' Laboratories listed (1/2"
thru 8 ") in the USA (UL) and Canada (cUL) for steel
and CPVC plastic pipe and Factory Mutual Engineering
Approved (3/4" thru 8 "). Conforms to Federal 1/2 THRU 2 INCH PIPE 2 112 THRU 8 INCH PIPE
Specifications WW -H -171 E, Type 10 and Manufacturers
Standardization Society SP -69, Type 10. w
Maximum Temperature — 650 °F
Finish — Mil. Galvanized. For Stainless Steel materi-
als, order TOLCOTM' Fig. 200WON.
/ „„,,-------,.
Order By — Figure number and pipe size ■
• i \ i •�
) \\, __________)
.... j
Dimensions • Weights
Pipe Rod Size Max. Rec. Approx.
Size Inch Metric A B Load Lbs. Length
1/2 3/8 8mm or 10mm 3% 2% 400 11
3/4 3/8 8mm or 10mm 31/4 21/2 400 11
1 3/8 8mm or 10mm 3% 24 400 12
11/4 3/8 8mm or 10mm 3 21/2 400 13
1 3/8 8mm or 10mm 31 21 400 14
2 3/8 8mm or 10mm 41/2 3 400 15
21/2 3/8 10mm 5% 41 600 27
3 3/8 10mm 5 4 600 29
31/2 3/8 10mm 7% 51/4 600 34
4 3/8 10mm 7% 5 1000 35
• 5 1/2 12mm 91/2 6 1250 66
6 1/2 12mm 101 6% 1250 73
8 1/2 12mm 13 8% 1250 136
® OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH 951.737.5599 • FAX: 951 137 0330
CUSTOMER SERVICE • 800 786.5266
wwwtolco.cam
• ® TDLCD www.tolco.com
.:,rand NIBCO Revision 9/22/2001
Fig. 65 and Fig. 66
Reversible C -Type Beam Clamps 3/4" and 1 Throat Openings
Size Range — (Fig. 65 and Fig. 66) 3/8 ", 1/2" and 5/8" rod Component of State of
California OSHPD Approved
Material — Carbon Steel with hardened cup point set screw and Seismic Restraints System
jam nut ® C V)
Function — Recommended for hanging from steel beam where flange
thickness does not exceed 3/4" (Fig. 65) or 1'/4" (Fig. 66).
Features — All steel construction eliminates structural deficiencies
associated with casting type beam clamps. May be used on top or bot- B
torn flange of the beam. (Beveled lip allows hanging from top flange ,
where clearance is limited.) May be installed with set screw in up or D
down position. Offset design permits unlimited rod adjustment by E
allowing the rod to be threaded completely through the clamp. Open ,
design permits inspection of thread engagement. I Oa C
Approvals — Underwriters' Laboratories Listed in the USA (UL) and °� � •
Canada ( Factory Mutual Engineering approved. Conforms to
Federal Specification WW -H -171 E, Type 23 and Manufacturers F
Standardization Society SP -69, Type 19. Exceeds requirements of the �r =�'
National Fire Protection Association (NFPA), Pamphlet 13, 3/8" rod will
support 1/2" thru 4" pipe, 1/2" rod will support 1/2" thru 8" pipe. ,� A
Included in our Seismic Restraints Catalog approved by the State of 1��
California Office of Statewide Health Planning and Development
(OSHPD). For additional load, spacing and placement relating to J
OSHPD projects, please refer to the TOLCO Seismic Restraint
Systems Guidelines.
Finish — Plain
Note — Available in Electro- Galvanized and HDG finish.
• Order By — Figure number, rod size and finish
Fig. 65 Patent #4,570,885 B
Fig. 65
Dimensions • Weights % r , / C
Rod Size Max. Rec. Approx. S
A B C D E F Load Lbs.* Wt. /100
3/8 1/.. , 3/4 1 7/16 1 610 28
F
1/2 11, 3/4 1 9/16 1' /4 1130 55
5/8 1' /: 3/4 1 9/16 114 1130 55
* Max. loads for clamp with set screw in up or down position. �v'
Fig. �•� A
g66 ,
Dimensions • Weights 4 =_ ,
Rod Size Max. Rec. Approx.
A B C D E F Load Lbs.* Wt. /100
3/8 1 114 1 7/16 1 610 28
1/2 17. 1 /1 1 9/16 1' /4 1130 55
5/8 11 1 L 1 9/16 174 1130 55
* Max. loads for clamp with set screw in up or down position.
® OFFICE /MANUFACTURING FACILITY • .AMPSON AVE • CORONA. CA 92879 • PH: 951 737 5599 • FAX: 951 737.0330
CUSTOMER SERVICE • 800 786 5266
wwwtoko.com
® TOLCO www,tolco,
NIBCO Revision 8/13/2001
Fig. 69 - Beam Clamp Retaining Strap Oc0
Size Range — 3/8" thru 7/8" rod by 4" thru 16" length.*
Function — To offer more secure fastening of various types
of beam clamps to beam where danger of movement might be
expected. NFPA 13 requires the use of retaining straps with
all beam clamps installed in earthquake areas. Satisfies
requirements of NFPA 13 (1999) 6- 4.7.1.
Important Note — Good installation practice of a retaining
strap requires that the strap be held tightly and securely to all
component parts of the assembly. Therefore a locking mecha-
nism of some kind such as a hex nut or the beveled locking
slot on the TOLCOTM Fig. 69R will provide a more secure
reliable installation.
Approvals — Underwriters' Laboratories listed in the
USA (UL) and Canada (cUL). Approved for use with any
listed beam clamp. Included in our Seismic Restraints
Catalog approved by the State of California Office of
Statewide Health Planning and Development (OSHPD).
Finish — Pre - Galvanized
Order By — Figure number, type, length "B" and rod size
being used with beam clamp
Note — Minimum return on Strap: 1".
Dimensions • Weights
U..
Type Rod Size A Hole Size B r' - IA
1 3/8 7/16 Specify
1/2
1/2 9116 Specify = ups
2 5/8 11/16 Specify = -7
3/4 13/16 Specify
3 3/8 - 7/8 Specify Specify
Longer lengths are available, consult factory.
�
//4 WA rit
Office /Manufacturing Facility • 1375 Sampson Ave. • Corona. CA 92879 • Ph 909.737.5599 • Fax: 909 737.0330
Customer Service • 300 786 5266
www.tolco.com
SIDEWINDERS
HORIZONTAL MOUNT
lo od
Nut Driver 1/4" 8018957 4016 SWG 100 1/4 X 1 25 9.38 125
Use #taSW Nut Oriver 1/4" 8019957 300 SWG 200 1/4 X 2 25 10.00 125
for Sidewinders and
1/2 Sammys 3/8" 8020957 18 SWG 10 1/4 X 1 25 7.50 125
4 S 1 . 3/8" 8021957 19 SWG 20 1/4 X 2 25 8.75 125
Q 3/8" 8022925 26 SWG 25 -380 3/8 X 2 -112 25 12.81 125
3/8" 8023925 25 SWG 30 1/4 X 3 25 10.63 125
3/8" 8050957 39 SWD 10 1/4 -14 X 1 25 7.50 125
3/8" 8051957 40 SWD 15 1/4-14 X 1 -1/2 25 9.38 125 -1 •[—
Iteel
Part #8114910
3/8" 8052957 41 SWD 20 1/4-14 X 2 25 8 13 125
Item # 101
3/8" 8053957 42 SWD 516 5/16 -18 X 1 -1/4 25 8.75 125
Q 3/8" 8054957 46 SWDR 1 -1/2" 1/4 -20 X 1 -1/2 25 9.06 125
Q• 3/8' 8055957 43 SWDR 1" 1/4-20 X 1 25 8.75 125 ii
3/8" 8056957 44 SWDR 516 5/16 -18 X 1 -1/4 25 10.31 125
3/8" 8057957 45 SWT 15 12 -24 X 1 -1/2 25 7.81 125
( �- loncrete
( 1/4" 8062957 1900 SWC 200 5/16 X 1 -1/2 25 9.38 125
■
3/8" 8061957 65 SWC 20 5/16 X 1 -1/2 25 9.38 125
• Most Items Available in Stainless Steel
it
NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! NEW! * Use with 3/8" Rod
Sammy Swivel Head'"
Approvals Part # Item # Model Screw Box Weight Case o
iliP* , \
Descriptions Qty. (per 125) Qty U.S. Patent No. • 17 rn deflection from vertical
• 6,443,680 • Accornodates up to
'Q 8139957 4702 SH -GST 20 1/4 x 2 25 9.38 125 3-1/2 x 12 pitch roof
• 8140957 4703 SH -GST 22SS 1/4 x 2 25 9.38 125 \ • Also available in stainless steel
• 8141957 4704 SH -GST 30 1/4 x 3 25 10.94 125
Q' 8142957 4705 SH-GST 30SS 1/4 x 3 25 10.94 125 ' / • Use #14 Nut Driver (black)
12' 8137957 4700 SH -DSTR 1 1/4 -20 x 1 25 9.38 125 •
I' 8138957 4701 SH -DSTR 1 - SS 1/4 -20 x 1 25 9.38 125
R DtreCtlY Patent Pending SAMMY X-PRESS
Thread Ga . eta/ Steel Screw Box Weight Cast
H ang Thin e M A pp ro vals Part # Item # Model
f ro m Dew & Purltn _ Ga. Descriptions Qty. (per 125) Qty.
t ! r _
` 1/4 -20 x 1 -1 /8
‘-� 1 , ' \O- 22 -20 8150922 500 XP 20 25 10.3 125
Sammy X -Press 20
l 18 -16 8153922 503 XP 35 1/4 -20 x 1-1/8 25 10.3 125
= �y Sammy X -Press 35
Uninstalled : •' ; IR t Sammy X -Press It
8151910 501 XPIT Installation Tool 1 1.02 1
swM ' (Kit includes: Sleeve. Bit Receiver. Hex Wrench. and 25164" Drill Bit)
�RESS
TM 8152910 502 XPDB 25/64" Drill Bit 1 0.14 1
Installed
Bulletin 1 17R Q
Reliabld Model Fl
M
7 .
odel Fl Recessed
Standard Response
S • rinklers o
The Designer Model Fl Sprinkler
Standard Upright 7 614 ‘ • I
Standard Pendent _'
Extended Coverage Pendent
Conventional a" ,
Vertical Sidewall
Horizontal Sidewall Upright Pendent
- HSW 1 Deflector
Horizontal Sidewall Extended Coverage _
- EC-6 Deflector irt,
Sprinkler Desi ner Model Fl Recessed rinkler
il . 9
Recessed Pendent
Recessed Extended Coverage Pendent
Recessed Extended Coverage Horizontal Sidewal Vertical Sidewall Conventional
Approval Organizations _ _
1. Underwriters Laboratories Inc.
2. Underwriters' Laboratories of Canada C. { , «11 . :I. ) Al
3. Factory Mutual Research Corp. ° • i " �' -.
4. Loss Prevention Council'
5. NYC BS&A No. 587 -75 -SA Horizontal Sidewall Recessed Pendent
6. Pleniere Assemblee
7. Verband der Schadenversicherer
8. NYC MEA 258- 93 -E
•4 '4 OA /0m�J .
UL Listing Category k !A M -7- ,e " , -
Sprinklers, Automatic & Open (VNIV)'
Product Description Extended Coverage Recessed Extended
The Fl Glass Bulb Sprinkler combines the durability of a Horizontal Sidewall Coverage Horizontal
standard sprinkler with the attractive low profile of a decora- Sidewall
tive sprinkler. Whether installed on exposed piping or in an
office ceiling, it is functional and attractive. The Horizontal # 1 : �=
and Vertical Sidewall Sprinklers provide an equally attractive . ",
k .
appearance when ceiling piping cannot be used.
Beautifully versatile is the description for the Reliable I �'i'
Model Fl Recessed Designer glass bulb sprinkler. Re- L. I
cessing The Designer enhances its already low profile dec-
orative appearance, and facilitates a rapid and perfect Extended Coverage Recessed Extended
installation. Pendent Coverage Pendent
Model Fl Recessed Designer's escutcheon is highly ad- At normal temperatures, the glass bulb contains the fluid in
justable. The two piece construction makes field installation a both the liquid phase and in the vapor phase. The vapor
very easy and rapid task. This also allows ceiling panels to phase can be seen as a small bubble. As heat is applied, the
later be removed without shutting down the fire protection liquid expands forcing the bubble smaller and smaller as the
system, thus facilitating maintenance of above ceiling ser- liquid pressure increases. Continued heating forces the liq-
vices. uid to push out against the bulb, causing the glass to shatter,
The Designer Automatic Sprinkler utilizes a frangible opening the waterway and allowing the deflector to distribute
. glass bulb. The glass bulb consists of an accurately con- the discharging water.
trolled amount of special fluid hermetically sealed inside of a The Fl Sprinkler temperature rating is identified by the
precisely manufactured glass capsule. This glass bulb is color of the glass bulb capsule as well as frame color where
specially constructed to provide fast thermal response. applicable.
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
Model Fl Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
T ..
. ( .---tr-:. : ......: ' I 1 •
I
s 1 flA I
;;•;"' T j .
RAS
CO
Upright Pendent Conventional Upright (2)
Installation Data:
Nominal Sprinkler
Nominal Thread K Factor Sprinkler Approval Identification
Orifice Size Height Organization Numbers (SIN)
US Metric Upright Pendent
Standard - Upright (SSU) and Pendent (SSP) Deflectors Marked to Indicate Position
1/2" (15mm) 1/2" NPT (R1/2) 5.6 80 2.2" (56mm) 1,2,3,4,5,6,7 R1725 R1715
' %2" (20mm) 3 4" NPT (R ") 8.0 115 2.3" (58mm) 1,2,3,4,7,8 R1722 R1712
I 'h" (15mm) 1/2" NPT (R') 5.6 80 2.2" (56mm) 7 R1795 R1705
'%3z" (20mm) 3 /4" NPT (R 8.0 115 2.3" (58mm) 7 R1792 R1702
X. (11 mm) 'h NPT (R1/2) (Z 4.2 60 2.54" (65mm) 1,2,8 R1723 R1713
3 (10mm) 1/2" NPT (R1/2) (2)(3) 2.8 40 2.54" (65mm) 1,2,8 R1721 R1711
• 1Omm XLH R % 4.2 60 56.1mm 4,6,7 R1724 R1714
Conventional - Install in Upright or Pendent Position
10mm XLH R% 4.2 60 56.1mm R1774
• 15mm '/2 NPT (R1/2) 5.6 80 56.1mm 4,6,7 R1775
20mm 3 /4" NPT (R 8.0 115 58.1mm 4,7 R1772
(') LPC Approval up 286 °F (141 °C)
(2) Small Orifice identified by a pintle extending beyond the deflector.
(3) FM Approval for SSU only, up to 200 °F (93 °C).
(4) VdS Approval for Intermediate Response 155 °F (68 °C) only.
•
•
2.
Model Fl Recessed Pendent Sprinkler
Installation Wrench: Model RC1 Sprinkler Wrench
2 1/4 "0 Z 2M
(37,2nvn
117/16'Mk.r
L- -�--._J
^-w* r t = - — - - + z. - i ,
. 1ua'N Gd.LIR / l y % / / [25...m X l7.lmmJ
j//��'+ ` �, AG I nun t
\� i *J ALNN51 SoRMNfCE»
4NEF
1 } , 7' 8055 \ t 2) , r
N.;24441" f1) Wil
17/16'
(7J.}nmJ
F1 Recessed Ii 1/6•—t t
i
I 11FGOFA 2 27 7II DM
(n.
(2) When installed directly into a tee, the escutcheon dimension's
adjustment will be reduced.
Installation Data:
Nominal Sprinkler
Nominal Thread Sprinkler Approval
Orifice Size K Factor Height Organizations Identification
US Metric Numbers (SIN)
Y" (15mm) y," NPT (R ) 5.6 80 2.2" (56mm) 1,2,3 R1715
%" (20mm) y4" NPT (Fiy 8.0 I 115 2.3" (58mm) 1,2,3 ",4,8 R1712
• I y," (15mm)( y," NPT (Ry,) 5.6 80 2.2" (56mm) 7 R1705
IX," (20mm) 3;" NPT (R y,) 8.0 115 2.3" (58mm) 7 R1702
%' (11mm) (2) y," NPT (R1) 4.2 60 2.54" (65mm) 1,2,8 R1713
Y" (10mm) (2) y," NPT (R'h) 2.8 40 2.54" (65mm) 1,2,8 R1711
10mm R% 4.2 60 56.1mm 4 R1714
(1) FM Approval
• Light Hazard - No Limitations.
• Ordinary Hazard - Groups 1 & 2, Wet Systems only
(2) Identified by a pintle extending beyond the deflector.
(3) LPC Approval is XLH, 0H1 and OHII Occupancies only,
57 °C through 93 °C ratings.
(4) VdS Approval for Intermediate Response 155 °F (68 °C) only
3.
Model Fl Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
1
Vertical Sidewall
U.S. Patent No. 6,374,9201
Installation Data:
Nominal Sprinkler
Nominal Thread K Factor Sprinkler Approval
Orifice Size Height Organizations Identification
US Metric Numbers (SIN)
72 (15mm) 72 NPT (Ry) 5.6 60 2.2" (56.1mm) 1,2,3,4' 6 ,8 R1765
(11 LPC Approval is pendent only, 57 °C through 93 °C ratings.
Sprinkler Deflector to
Type Ceiling Distance
(Min. - Max.)
Upright 4 "(102mm) - 12 "(305mm)
Pendent 4 "(102mm) - 12 "(305mm)
. Model Fl Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench _ `...
,
C
Horizontal Sidewall
Installation Data:
Nominal Approval Organizations PP 9 Sprinkler
Nominal Thread K Factor Sprinkler Identification
Orifice Size Length Light Ordinary Numbers (SIN)
US Metric Hazard Hazard
'h" (15mm) '/z" NPT (R'h) 5.6 80 2.63" (67mm) 1,2,3,5 1,2,5 R1735
Note: UL and ULC Listing permits use with F1 escutcheons, light hazard only.
4.
Model Fl Extended Coverage Pendent Sprinkler , _
Deflector: EC Pendent , _Yr
Installation Wrench: Model D Sprinkler Wrench
Approval Type: Extended Coverage - Light Hazard Occupancy 1 ' '' f
Installation Data: • 4
I
Nominal Temperature Sprinkler
Nominal Thread K Factor Sprinkler Approval Rating Identification
Orifice Size Height Organizations
US Metric °F °C Numbers (SIN)
' %„" (20mm) %" NPT (R3/4) 8.0 115 2.2" (56mm) 1,2,8 135; 155 57; 68 R1742 Extended Coverage
y," (15mm) y," NPT (R' /) 5.6 80 2.2" (56mm) 1,2,8 135; 155 57; 68 R1745 Pendent
COVERAGE AREA
Pressure
Flow Rate Nominal Max. Area
Width x Length
K =8.0 (115) K =5.6 (80)
gpm L/min psi bar psi bar ft. x ft. m x m
26 98.4 10.6 0,7 21.6 1,5 16 x 16 4.9 x 4.9
33 125.0 17.0 1,2 34.7 2,4 18x18 5.5x5.5
40 151.4 25.0 1,7 51.0 3,5 20x20 6.0 x 6.0
Model Fl Recessed Extended Coverage Pendent Sprinkler
Deflector: EC Pendent
Installation Wrench: Model RC1 Sprinkler Wrench ,^ °" "" ,,.40,/
Approval Type: Extended Coverage - Light Hazard Occupancy
-- A rq/rs; OM
�- i
RAM COLLAR 1 /2 REDUCIN
x s/• oue[ , (n nx rs. r
1 f� (?D.rm" x r2.71..,4
fl
VINES ROSS ir ✓ T L -J
IS/16
ra•
v LT
,� S/4 !` ,�aesncwr
‚ r ) Extended Coverage A __ °r ^ " ^]
Recessed
,121 1 27 /32 OK
(72?m"J
( "When installed directly into a tee, the escutcheon
dimension's adjustment will be reduced.
Installation Data:
Nominal Temperature Sprinkler
Nominal Thread Sprinkler Approval
Orifice Size K Factor Height Organizations ° Rating °C Identification
US Metric F C Numbers (SIN)
V. " (20mm) ;;" NPT (R3/4) 8.0 115 2.2" (56mm) 1,2,8 135; 155 57; 68 R1742
y," (15mm) y," NPT (R') 5.6 80 2.2" (56mm) 1,2,8 135; 155 57; 68 R1745
COVERAGE AREA
Pressure
Flow Rate Nominal Max. Area
Width x Length
K =8.0 (115) K =5.6 (80)
gpm L/min psi bar psi bar ft. x ft. m x m
26 98.4 10.6 0,7 21.6 1,5 16 x 16 4.9 x 4.9
33 125.0 17.0 1,2 34.7 2,4 18 x 18 5.5 x 5.5
40 151.4 25.0 1,7 51.0 3,5 20x20 6.0x6.0
5.
Model Fl Extended Coverage Horizontal Sidewall Sprinkler
Deflector: EC -6
Glass Bulb: 3mm 155 °F (68 °C) Standard, Unless 5mm 135 °F (57 °C) is Specified
Installation Wrench: Model D Sprinkler Wrench
Approval Type: Extended Coverage — Light Hazard Occupancy
j I
,,," IF
Extended Coverage Horizontal Sidewall
Installation Data:
K Factor Temperature Sprinkler
Nominal Thread Sprinkler Approval Rating Identification
Orifice 1 Size US Metric Height Organizations °F aC Numbers (SIN)
135 (5mm bulb) 57
1 732" (20mm) y;" NPT (R 8.0 115.3 2.75" (70mm) 1,2,8 R1762
155 (3mm bulb) 68
COVERAGE AREA
1 Deflector to
Flow Rate Pressure Max Area Ceiling Dimensions
Width x Length i (Min. - Max.)
gpm 1../min psi bar ft. x ft. m x m
36 136.3 20.3 1,4 16 x 22 4.9 x 6.7 4 "(102mm) - 6 "(152mm)
39 147.6 23.8 1,6 16 x 24 4.9 x 7.3 4 "(102mm) - 6 "(152mm)
6.
Model Fl Recessed Extended Coverage Horizontal Sidewall Sprinkler
Deflector: EC -6
Glass Bulb: 3mm 155 °F (68 °C) Only
Installation Wrench: Model GFR1 Sprinkler Wrench
Approval Type: Extended Coverage — Light Hazard Occupancy
„22(10, ‘ —
WM6" r r /e' (.Smm)
(2J.8) \ • n3 e
001.8 ro rea.+.�.R)
■1 , VOW
r - - - - - wry. DONE ,�cwrsr ilm ALE»
(
I �, suss — 1111114
, )... , 1- .
1 : II, - 1111'+Id,� ■ 1 n
, , v (-2—] , t -Ill
Recessed Extended Coverage �� 1
Horizontal Sidewall RECOMMENDED �:r
2 / Ci L_ (X./2Z
(e (I)
u
I. J/e u A,SI1Nr
(ra. rte)
(') When installed directly into a tee, the escutcheon dimension's
adjustment will be reduced.
Installation Data:
• Temperature Sprinkler
Nominal Thread K Factor
Sprinkler Approval Rating Identification
Orifice Size Height Organizations SIN
US Metric °F °C Numbers (SIN)
• 1 % (20mm) %" NPT (R /s) 8.0 115.3 2.75" (70mm) 1,2,8 155 68 R1762
COVERAGE AREA
Max. Area Deflector to Ceiling
Flow Rate Pressure Width x Length Dimensions
(Min. - Max.)
gpm Vmin psi bar ft. x ft. m x m
36 136.3 20.3 1,4 16 x 22 4.9 x 6.7 4 "(102mm) - 6 "(152mm)
39 147.6 23.8 1,6 16 x 24 4.9 x 7.3 4 "(102mm) - 6 "(152mm)
7.
Model Fl & Fl Recessed Sprinklers Maintenance
Application The Models Fl and Fl Recessed Sprinklers should
Model Fl and Fl Recessed sprinklers are used in fixed be inspected quarterly and the sprinkler system main -
fire protection systems: Wet, Dry, Deluge or Preaction. tained in accordance with NFPA 25. Do not clean sprin-
• Care must exercised that the orifice size, temperature rat- klers with soap and water, ammonia or any other
cleaning fluid. Remove any sprinkler which has been
ing, deflector style and sprinkler type are in accordance
with the latest published standards of the National Fire Pro- painted (other than factory applied) or damaged in any
tection Association or the approving Authority Having way. A stock of spare sprinklers should be maintained
Jurisdiction. to allow quick replacement of damaged or operated
sprinklers. Prior to installation, sprinklers should be
Installation maintained in the original cartons and packaging until
Model Fl sprinklers are standard response sprinklers in- used to minimize the potential for damage to sprinklers
tended for installation as specified in NFPA 13. They must that would cause improper operation or non - operation.
also be installed with the Model D Sprinkler Wrench specifi-
cally designed by Reliable for use with these sprinklers.
The Model Fl Recessed Sprinklers are to be installed Temperature Ratings
with a maximum recess of 3 /4 inch (19mm). The Model Fl Sprinkler Maximum Ambient
Escutcheon illustrated is the only recessed escutcheon to Classification Temperature Temperature Bulb
be used with the Model Fl Pendent and EC Sprinklers. The °F °C °F °C Color
use of any other recessed escutcheon will void all approv- Ordinary 135 57 100 38 Orange
als and negate all warranties. When installing Model Fl Re- Ordinary 155 68 100 38 Red
cessed Pendent, EC Pendent, and EC HSW Sprinklers, use Intermediate 175 79 150 66 Yellow
the Model GFR1 Sprinkler Wrench. Any other type of Intermediate 200 93 150 66 Green
High 286 141 225 107 Blue
wrench may damage these sprinklers. Extra High (1) 360 182 300 149 Mauve
Glass bulb sprinklers have orange covers to protect the
bulb during the installation process. REMOVE THIS PRO- (" Not Available For Fl Recessed
TECTION ONLY AFTER THE SYSTEM HAS BEEN HYDRO- Patents: U.S. Patent No. 6,374,920
STATICALLY TESTED AND, WHEN APPLICABLE, THE Applies to Model Fl Vertical Sidewall Sprinklers.
ESCUTCHEONS HAVE BEEN INSTALLED. RASCO
wrenches are designed to install sprinklers when covers Finishes (1)
are in place.
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Chrome
Ordering Information White Polyester Coated"' White Painted
Specify: Special Application Finishes
1. Sprinkler Model Sprinkler Escutcheon
2. Sprinkler Type Bright Brass ( Bright Brass
Black Plated ` °' Black Plated
3. Orifice Size Black Paint" Black Paint
4. Deflector Type Off White "' Off White
5. Temperature Rating:
Satin
ead Chrome a ed "' Satin Chrome
Specify Bulb Size when ordering Wax Coated ' 3)(41°)
Model Fl EC HSW Sprinkler.
Wax Over Lead' '' `°'
"
6. Sprinkler Finish ' Other colors and finishes are available on special order.
Consult factory for details.
7. Escutcheon Finish (where applicable) 'A 200 °F (93 °C) maximum.
` UL and ULC Listed, and NYC Approved Only.
"' 155 °F to 200 °F (68 °C to 93 °C) ratings only.
(3) 286 °F (141 °C) Sprinklers may be coated for ambient conditions
not exceeding 150 °F (66 °C).
'" LPC approved for 10mm and 15mm sprinklers only.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over B0 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries
• Manufactured by
The Reliable Automatic Sprinkler Co., Inc. �� a
H eUiab,o (800) 431 -1588 Sales Offices °- ��bo
(800) 848 Sales Fax Revision lines indicate updated or new data.
(914) 668 Corporate Offices
www. reliablesprinkler corn Internet Address EG printed in USA. 12/03 P/N 9999970011