Specifications ,-?� r; i: '), FPS 7. 7 12- cam I 7.-9
AUG rW6 2012 IZ2 ?7.5vJ5c alts Ferey
T.,m;, Bulletin 117 Rev S RC(
:1) Model Fl 1.
• Reliab _....„ ° Model Fl Recessed D CD
S tandard Response
Sprinklers
CD
.1
The Designer Model Fl Sprinkler
Standard U ri ht y� %'
Standard Pendent
Extended Coverage Pendent f 1. •,„--",
Conventional `. 1.
Vertical Sidewall ?;;^ -,
Horizontal Sidewall h
— HSW1 Deflector _.- `eh Li ' ma y
The Designer ® II Model Fl Recessed Sprinkler Upright Pendent
Recessed Pendent ""`
Recessed Extended Coverage Pendent �'""r
Approval Organizations '\
1. Underwriters Laboratories Inc. I 4 2. Underwriters' Laboratories of Canada ,11 . ,
3. Factory Mutual Research Corp.
4. Loss Prevention Council .z
5. NYC BS &A No. 587 -75 -SA
6. Pleniere Assembles Vertical Sidewall Conventional
7. Verband der Schadenversicherer
8. NYC MEA 258 -93 -E
UL Listing Category '
Sprinklers, Automatic & Open (VNIV) '`""" a�
e `f, '._ 1 r., ,
- Patents: U.S. Patent No. 6,374,92.
Applies to Model Fl Vertical Sidewall Sprinklers. a
Product Description Horizontal Sidewall Recessed Pendent
The Fl Glass Bulb Sprinkler combines the durability
of a standard sprinkler with the attractive low profile of k
a decorative sprinkler. Whether installed on exposed
piping or in an office ceiling, it is functional and I. ` „ _ >'
attractive. The Horizontal and Vertical Sidewall I i �_ # •
Sprinklers provide an equally attractive appearance fkr
when ceiling piping cannot be used. -
Beautifully versatile is the description for the Reliable • :,::&:,,---.
Model Fl Recessed Designer glass bulb sprinkler. Extended Coverage Recessed Extended
Recessing The Designer enhances its already low Pendent Coverage Pendent
profile decorative appearance, and facilitates a rapid
and perfect installation. At normal temperatures, the glass bulb contains the
Model Fl Recessed Designer's escutcheon is highly fluid in both the liquid phase and in the vapor phase.
adjustable. The two piece construction makes field The vapor phase can be seen as a small bubble. As
installation a very easy and rapid task. This also allows heat is applied, the liquid expands forcing the bubble
ceiling panels to later be removed without shutting smaller and smaller as the liquid pressure increases.
down the fire protection system, thus facilitating Continued heating forces the liquid to push out against
maintenance of above ceiling services. the bulb, causing the glass to shatter, opening the
The Designer Automatic Sprinkler utilizes a frangible waterway and allowing the deflector to distribute the
glass bulb. The glass bulb consists of an accurately discharging water.
controlled amount of special fluid hermetically sealed The Fl Sprinkler temperature rating is identified by
• inside of a precisely manufactured glass capsule. This the color of the glass bulb capsule as well as frame
glass bulb is specially constructed to provide fast color where applicable.
thermal response.
J
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York, 10523
1
Model Fl Upright, Pendent & Conventional Sprinklers I
Installation Wrench: Model D Sprinkler Wrench
le) , _.-5 ...
C h, -„
1 , 4 ::: , P ,.:
C. 4
•.:'':=. 7-= ';'11‘.1%.:-.7.7.0-.7 Ar....-----.—..-
Upright Pendent Conventional
Installation Data:
•
Nominal Nominal K Factor Sprinkler Approval Sprinkler Identification Numbers
Thread Size (SIN) •
Orifice Height Organization
US Metric Upright I Pendent
Standard - Upright (SSU) and pendent Detectors Marked to Indicate Position
h' Yi NPT 5 6 80 2 2' 1,2,3,4,5,6,7 R1725 R1715
(15mm) (R1/2) (56mm)
17/32' e5' NPT 2 3' tat
(20mm) (R3 /4)t't 80 115 (58mm) 1,2,3.4,7,8 R1722 R1712
h' h' NPT 2.2'
(15mm)t (R1/2) 56 80 (56mm) 7
17/32' 3 A . NPT 8 0 115 2 3' 7
(20mm) (R3/4) (58mm)
7/16' 12' NPT 4 2 60 2 2 1.2,8 R1723 R1713
(11mrn) (R1/2) (56mm)
3/8' h' NPT 2.54' I
(10mm) (R1 /2)t2t 28 40 (65mm) • 1.2,8 R1721 R1711
10mm XLH R3/8 4 2 60 56 1mm 4,6.7 R1724 R1714
Conventional-Install in Upright or Pendent Position
10mm XLH R3 /8 4 2 I 60 56 1mm R1774
15mm h NPT 5 6 80 56 1mm 4,6.7 R1775
(R1/2)
20mm
3/4' NPT 80 115 58 1mm 4,7 R1772
(R3/4)
(1) LPC Approval up to 286 °F (141 °C)
(2) FM Approval for SSU up to and including 200 °F (93 °C) only.
(3) (F1S5) VdS Approval for Intermediate Response 155 °F (68 °C) only.
(4) Polycoated upright UL and ULC listed corrosion resistant.
1
I.
.
I
2.
Model Fl Recessed Pendent Sprinkler
Installation Wrench: Model GFR1 Sprinkler Wrench
I
2 1/4 HOLE CIA . -•
(52 2mmJ
1 15/15 Clt -• 1
(.9 2mmJ
COLLAR
t 21 :, - _
L: • -�% 1 x 12 REDUCER
:4 44 U �� (25:mm x r7:mmJ
`1 •�� ∎ II/RN H!
t UNTIL UCH!
�� AGAINST 5PRINVLER
LT "I, .......... �.. 11R(NCH 0055 l ' 1 ( I
1
7r� L - - -
E//7/,
t �i_ J J ` • J
t oDsva 15/;6 -
Recessed Pendent NSfGIe �'� ( -"Ml
( f j Iv 1
155(COIn
If
( nJ 1- (25 .mmJ
,_.:.,,,
n2(COIn 2 2: /J2 00
(22 2mm)
I
(1) When installed directly into a tee, the escutcheon dimension's I
I
adjustment will be reduced. 1
Installation Data:
Nominal Nominal K Factor Approval Sprinkler Identification
Thread Size Sprinkler Height
Orifice US Metric Organization Numbers (SIN)
(15mm) ( q N2) 56 80 (56mm) 1,2.3.4.5,7 R1715
I-
17/32' ' 8.0 115 23 1,2,3.4.8 R1712
(R3 /4)
(20rnm) (R3/4) (58mm)
Ye 'h' NPT 2 2'
(15mm) (R1 /2) 56 80 (56mm) 7
i 17/32' 44' NPT 2 3' f
(20mmf (R3 /4) 8 0 115 (58mm) 7
7/16' 1/2'NPT 42 60 22 1.2,8 R1713
(11mm) (R1/2) (56mm) — I
3/8' 1/2'NPT 28 40 22' 1.2,8 R1711
(10mm) (n1/2) (56mm)
10mm R3/8 42 60 561mm 4,7 R1714 1
(2) FM Approval
• Light Hazard - No Limitations
• Ordinary Hazard - Groups 1 & 2, Wet Systems only.
(3) LPC Approval is for 57 °C through 93 °C ratings.
(4) VdS Approval for Intermediate Response 155F (68 °C) only.
I
:1
3.
Model Fl Vertical Sidewall Sprinkler -- 717 r.. 1
Installation Wrench: Model D Sprinkler Wrench"''
Installation Position: Upright or Pendent _..r+.
Approval Type: Light Hazard Occupancy " -
,
4 SE4 . +n
U.S. Patent No. 6,374,920 r t �. 1r
4 •e ;'
Sprinkler Type Deflector to Ceiling Distance i
(Min. - Max.) ` �;x
Upright 4' (102mm) - 12' (305mm)
Vertical Sidewall
Pendent 4' (102mm) - 12' (305mm)
Installation Data:
Nominal K Factor Sprinkler
Nominal Orifice Thread Size Sprinkler Approval Identification
US Metric Height Organizations Numbers (SIN)
F�' (15 rnm) - - -- - - - W NPT (R1/2) - -- 5 6 8 0_ - - -- - -- 2 2' (56.1mm) — 1,2,3,4,6,8 I P1785 ----
(1) LPC Approval is pendent only, 57 °C through 141 °C ratings. .
Model Fl Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
0
3/16' -5/15'
15mr.. -1.mm/
I 1/. aim•
1 8.17m1
2 1 /. ROLE 014. �'_g•
f57 2mm/ I /., 2 1101 >mm- rsz.,.rml
y Q
�__,�, \�*. �'� y �� CEILING TO
t. - r 1/2 RE000ER - \ DEFLECTOR
;; -.L ; " 'x �° r t � l 1 � :v��, T --t- -- � i 2 2: /.u' 1
1 - -t .` „70. 2 ml
' `\',1I lm
; TURN COLWa 0.�r1L �r I ,
,; , AvmN51 $RRULYLCR t
nRENCR 6055 C AV 1 1
J/.' 112■m
Horizontal Sidewall ',co" .alus A1EN1
i
Installation Data: -•
Nominal K Factor Approval Organizations Light Hazard Sprinkler
Nominal Thread Size Sprinkler I Identification
Orifice US Metric Height Li Ordinary Hazard I Numbers (SIN)
•
/' (15mm) 1/2' NPT 5 6 80 263' (67mm) 1,2,3,5 1,2,5 I R1735
(R1/2) .
Note: UL and ULC Listing permits use with Fl escutcheons, light hazard only.
4.
Model Fl Extended Coverage Pendent Sprinkler r- . ,
Deflector: EC Pendent /';
Installation Wrench: Model D Sprinkler Wrench , , :.
Approval Type: Extended Coverage - Light Hazard Occupancy ..c " ' a` `'1
: '
Pp YP 9 9 P Y �
'
Coverage Area p I
Pressure -.
Max. Area
Flow Rate Nominal �rz
Width x Length _•
K =8.0 (115) K =5.6 (80) • :-
gpm Umin psi bar psi bar ft. x ft. m m
x 4 `
26 98 4 10 6 0.7 21 6 1,5 16 x 16 49 x4.9 E Coverage Pendent
33 1250 170 1,2 347 2,4 18x18 55x55 g
40 151 4 25.0 1,7 51 0 3.5 20 x 20 60 60x60
Installation Data:
Nominal Thread Nominal K Factor Sprinkler Approval Temperature Rating Sprinkler '
Orifice Size Height Organizations ° Identification
US Metric 9 9 F C Numbers (SIN)
17/32' Ye NPT 8 0 115 2 2' (56mm) 12.8 135, 155 57, 68 R1742
(20mm) (R3/4)
W (15mm) %' NPT 5 6 80 1 2 2' (56mm) 1,2,8 135. 155 57, 68 R1745 i
(R1/2)
Model Fl Recessed Extended Coverage Pendent Sprinkler
Deflector: EC Pendent
Installation Wrench: Model GFR1 Sprinkler Wrench ] r, �. ' i(,u
Approval Type: Extended Coverage - Light Hazard Occupancy " l
r r5,r9",u
Y I 1 � (]x . ., • Ia rm J
• � i 'CHI uRR Mawr 7� • av
] " MIX'S v .x51 51,999,L1,7 (i3. • ] •••••••)
RLKM 9,55 n I I1
1
.4- �+' , ,ii:,,, K p may` E-_,,;7,-, r ? - .. —F_ t _ J
e �" r/ - r 4'''� • 4 -7
rain /ra
• __ kid l��� ��_11
[ W ,,,,-__I f
',MON 2 : ] /5] - Gl
Extended Coverage
Recessed (1) When installed directly into a tee• the escutcheon
dimension's adjustment will be reduced ,
Coverage Area
Pressure
Flow Rate Nominal Max. Area
Width x Length
K =8.0 (115) K =5.6 (80)
gpm L./min psi bar psi bar ft. x ft. m x m
26 984 106 0,7 216 1.5 16x16 49x49 -
33 1250 17.0 1,2 347 2,4 18x 18 55x55
40 151 4 25,0 1,7 51 0 3,5 20 x 20 60 x 60
Installation Data:
Nominal K Factor Temperature Rating Sprinkler
Nominal Thread Sprinkler Approval Identification
Orifice Size US Metric Height Organizations °F °C Numbers (SIN) •
•
17/32' IV NPT 8 0 115 2 2' (56mm) 1,2.8 135, 155 57, 68 R1742
(20mm) (R3/4)
Y2' (15mm) (RN 5.6 80 2 Z (56mm) 1,2,8 135, 155 57, 68 R1745
5.
Model Fl & Fl Recessed Sprinklers Ordering Information I
Application Specify.
Model Fl and F1 Recessed sprinklers are used in 1 Sprinkler Model
fixed fire protection systems Wet, Dry, Deluge or 2 Sprinkler Type -
Preaction. Care must exercised that the orifice size, 3 Orifice Size
temperature rating, deflector style and sprinkler type 4 Deflector Type
are in accordance with the latest published standards 5 Temperature Rating
of the National Fire Protection Association or the 6 Sprinkler Finish �
approving Authority Having Jurisdiction. 7 Escutcheon Finish (where applicable)
Installation Temperature Ratings
Model F1 sprinklers are standard response sprinklers Maximum
intended for installation as specified in NFPA 13. They Sprinkler Ambient Bulb
Temperature must also be installed with the Model D Sprinkler C lassification Temperature erature p Color
Wrench specifically designed by Reliable for use with °F °c °F °C I
these sprinklers Ordinary 135 57 100 38 Orange
The Model Fl Recessed Sprinklers are to be installed Ordinary 155 68 100 38 Red
maximum recess of 3 /4 inch 19mm . The Model Intermediate 2 00 79 150 66 Green
with a maximu
( ) Intermediate 200 93 150 66 Green n
Fl Escutcheon illustrated is the only recessed High 286 141 225 107 Bluo
escutcheon to be used with the Model F1 Pendent and Extra High" 360 182 300 149 Mauve
EC Sprinklers. The use of any other recessed (1) Not Available for F1 Recessed
escutcheon will void all approvals and negate all •
warranties When installing Model F1 Recessed Patents: U.S. Patent No. 6,374,920 I
Pendent and EC Pendent Sprinklers, use the Model Applies to Model Fl Vertical Sidewall Sprinklers.
GFR1 Sprinkler Wrench. Any other type of wrench may
damage these sprinklers Finishes
Glass bulb sprinklers have orange covers to protect Standard Finishes
the bulb during the installation process REMOVE THIS
PROTECTION ONLY AFTER THE SYSTEM HAS BEEN Sprinkler Escutcheon
HYDROSTATICALLY TESTED AND, WHEN APPLICABLE, Bronze Brass
THE ESCUTCHEONS HAVE BEEN INSTALLED. RASCO
Chrome
e xel
Polyester Coated Wh i e Painted I
ia
wrenches are designed to install sprinklers when Special Application Finishes l
covers are in place. Sprinkler Escutcheon i
Maintenance Bright Brass Bright Brass
Black Plated Black Plated
The Models Fl and Fl Recessed Sprinklers should Black Paintl' Black Paint
be inspected quarterly and the sprinkler system Off White Off White
maintained in accordance with NFPA 25. Do not clean Satin Plate d x � l Chrome Satin Chrome
Lead Plate o
sprinklers with soap and water, ammonia or any other Wax Coated
cleaning fluid. Remove any sprinkler which has been Wax Over Lea ° x4xs1
painted (other than factory applied) or damaged in any (1) Other colors and finishes are available on special order Consult
way. A stock of spare sprinklers should be maintained factory ) 2° Fr details C)
quick replacement of damaged or operated (2) UL and ( 3 maximum
to allow
q p g p (3) UL and ULC listed, and NYC approved only
sprinklers Prior to installation, sprinklers should be (4) 155 °F to 200 °F (68 °C to 93 °C) ratings only
maintained in the original cartons and packaging until (5) 286 °F (141 °C) sprinklers may be coated for ambient conditions not
used to minimize the potential for damage to sprinklers (6) UL and ULC (66°C).
listed c •
p 9 p (6) UL and ULC listed corrosion •
resistant SIN numbers R1721, R1722,
that would cause improper operation or non - operation R1723 and R1725
Note: For ' /z" orifice pendent FM approved white
polyester coated and UL approved white polyester
corrosion resistant sprinklers refer to Bulletin 013.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,
Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever
applicable
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most
highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries
I
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. ® Recycled Paper
(800) 431 -1588 Sales Offices
Reliabld (800) 848 -6051 Fax
Corp orate Offices lines indicate updated or new data
(914) 829 -2042 Corp
www reiiabiespnnkier corn Internet Address E G Printed in U S A 3/07 P/N 9999970011
Bulletin 153 Rev G co
Reliable ® M odel F3 i.
- Dry Sprinklers w
1
0
Features
1. The Model F3 Sprinkler utilizes Belleville Spring ► ' - I, . #'' L . ' • .:i•:. Y " : ;, `, • Closure Technology .
2. Styles available for Model F3 Dry Sprinklers: , �: •
• Pendent i' f•� =,'j
• Recessed Pendent . �; , ; \ ---^ • • t•,-:.; a
• Concealed :-z . _�. ' i
• Horizontal Sidewall . L. - `' .'`' I`_ -• •" ►' '
• Recessed Horizontal Sidewall - . 1 ' •'`''' .
3. 1' /z' (38mm) escutcheon adjustment on pendent •�` ' i •" 1 t . . ? • :
sprinkler. Concealed
4. 1/2' (13mm) escutcheon adjustment on recessed
sprinkler with push -on /thread -off FP Model
escutcheon ring.
5. %" (9.5mm) cover plate adjustment on concealed
sprinkler with push -on / thread -off CCP cover. I
6. Attractive appearance. Employs 5mm frangible I
glass bulb and galvanized nipple. :. ' .
7. Lengths available to accommodate installation
dimensions from 2" - to - 48" (51 mm - to -
1219mm), in Y4" (6mm) increments.
8. Available in a variety of plated and painted finishes. Recessed Pendent
_. =- ! is
U.S. Patent Numbers 5,775,431 and 5,967,240.
Approvals _ 1. Listed by Underwriters Laboratories Inc. and UL -- --"-° "ti" 51 1.4 .
Certified for Canada (cULus). -
Style Response System Type H i
Pendent A
Recessed Pendent _
CCP Concealed Wet Pipe
(R5314) Standard Dry Pipe Ordinary Pendent
Horizontal Sidewall All Preaction
Recessed Horizontal Sidewall •
(R5334) 2. Certified by FM Approvals ; .. YF
Sp rinkler
Style Response Sysem Type H `=°z
Pendent Light ,.. .1' -..
Recessed Pendent Wet Pipe Ordinary,
CCP Concealed Standard Dry Pipe Groups
f :: . . •
(R5314) All Preaction 182 {
Horizontal Sidewall Wet Pipe •_ -
Recessed Horizontal Sidewall Standard Dry Pipe Light
(R5334) All Preaction
- 3. NYC MEA 258 -93 -E Horizontal Sidewall
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York10552
1
Model F3 Dry Pendent Sprinkler
"A" Dim. 12" to 48' (51 mm to 1219mm) in 1/4; (6mm) increments I I
Inlet Prom,.. it Etc. ., _
n 6o' +e Inside Pipe
Finishes "' .
•
'� - -4
i '
Sprinkler Escutcheon h- -�[- - - -. -I
Bronze Brass : 4th - =_ - - � , _ J __ r !.- blh=_=_7
Chrome Plated Chrome Plated
White Painted'd' ' White% System lee •
Lead Plated '"
Wax Coated °H." I I —]•
Wax Over Lead'" ° I A Dimension (53 I/8 D,o.
I- NPT I
[539Bmm]
'Other finishes and colors are available on special order Consult Adjustment Range Hole In Ced.ng
for details /4 [ 615m ^
1
factory
Y -1 l/4 [ -11 75mm] , 43/64 Dm I — I I /2- [38 ISem]
'White painted sprinklers will have chrome plated can [42 47mm] total Adjustment
'155°F (68 °C) to 200 °F (93 °C) rating only sa nkier con I e "'' "9 ; 1 I /`- [3' ]Shin]
aj i ...... - • - - 1
212 ° F (100 ° C) brown wax may be used on 286 ° F (141 °C) sprinklers E -
Escutcneon _.. 1 t / (635mm1
when maximum ceiling temperatures do not exceed 150 °F (66 °C) , ce,l,n , -,. F Escutcheon
i • D1in9 • Adjustment
r
Standard Temperature Ratings �'\ — !L - - =�1 - f
- -- Nnrninol he k -i
Sprinkler of Escutcheon
(sit 1 /mB
. m]
Temperature Max. Bulb 2 e
Classification Rating Temp. Ambient Tem Color I /4- 16 35mm] • FrolrusIon - - —
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange __ 1 176 20m m] , 1
Ordinary 155 °F (68`C) 100 °F (38 °C) Red DIA ' .9J «,t - `
Intermediate 200 °F (93 °C) 150 °F (66 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
Sprinkler can and escutcheon fabricated of brass for better weather
resistance in exterior applications
Note: The sprinkler can protrudes 1 /4 " when escutcheon
Sprinkler Guard: Model C -2 is in nominal position. Escutcheon adjustment
provides + 1/4" ( +6mm) to -1 ( -32mm) "A"
Sprinkler Installation Wrench: dimension adjustment range.
Model G3 Sprinkler Wrench
Sprinkler Identification Number (SIN): R5314
Model F3 Dry Pendent Recessed Sprinkler
"A" Dim. 31/2' to48'(8 nrn to12i9mm)in'A (6rr1) incrrrrtai
Inlet Protrusion Eteroted C_--_ 1 3 ---- I - - - - r —ilaF - - -C� - •
Finishes "' Above inside PJpe -. - ' -- Iilih ---i. •
Sprinkler Escutcheon '`' = : - 8 b — - I ,_� � E _1 �'n= = =' i
Bronze Brass r ��
Chrome Plated Chrome Plated c =a system Tee I
White Painted [White NNE..
( "Other finishes and colors are available on special order ' NPT
Consult factory for details. Cup remains unfinished
III Only the escutcheon will contain desired finish 2 1/2 D;°.
'u De R on [63i50mm]
Adjustment Ronge Hole in Cang
tl /4 1
Standard Temperature Ratings [t 6.35mm] 2 19/64" Do l
Sprinkler Max. t58 i
Temperature Ambient Bulb
Classification Rating Temp. Color — o Escutcheon
Position spr,nkter
9 p• or ESCUICheon Cup Assembly
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange I t ,
Ordinary 155 °F (08°C) 100 °F (38 °C) Red E e trn CHs "� Escutcnoon
Intermediate 200 °F (93 °C) 150 °F (66°C) Green q ai U
High" 286°F (141°C) 225 °F (107 °C) Blue r r Ceumq�
Sprinkler cup and FP Escutcheon fabricated of steel and 1/ Escutcheon A 5 A just
mm]
p p Escutchheeon enl
recoinlnended for interior applications
I/4 [6 JSmmt 3 7/32 D.o.
`Listed and Certified only by cULus Escuichean Adj [81 76mm] -
1/2 (12.70mm]
Sprinkler Installation Wrench: T°` Adjustment 5 "` °' `
Model G3 R/C Sprinkler Wrench
Sprinkler Identification Number (SIN): R5314 Note: Do not install the Model F3 Dry Pendent Recessed
Sprinkler in ceilings which have positive pressure
in space above
2.
Model F3 Dry Pendent Concealed Sprinkler
"A" Dim. 13%,' to 48" (89mm to 1219mm) in 1/4' (6mm) Increments
k CCP Cover Plates') Finishest Inlet Protrusion Elevated ' -- --- I ---- r'--otti= =__;
Above Inside Pipe . B: _- I . I . 1 . _ j y _
-
Standard Finishes Special Application Finishes (-
��
Chrome Plated Bright Brass Plated ja - - -r_ se r 1 .- ,92k=__5
ti
• White Black Plated r -- M= ti
Black Paint k j system Tee
Off White iKai
Satin Chrome
II 1" NPT
(I) Utilizes they' cover plate with %' total adjustment.
(2) Other finishes and colors are available on special order. 2 I/2 °'a.
Consult facto for de tai l s. - A - Dimension ( in C m] Ceiling
m ry Adjustment Ronge Hole Ceilin
t 3/16'
Standard Temperature Ratings [t4.76mm] 2 19/64' Dia.
[58.34mm] ,
Sprinkler
Temperature Cover Plate Max. Ambient Nominal Position
Classification Rating Temp. Rating Temp. [of Coverptote Sprinkler
9 P• 9 P• Cup Assembl
Ordinary 135 °F (57 °C) 135 °F (57 °C) 100 °F (38°C)
Ordinary 155 °F (68 °C) 135 °F (57 °C) 100 °F (38°C) r p 1e
+ + `c ny 1 J • Asse blr
Intermediate 200 °F (93 °C) 165 °F (74 °C) 150 °F (66 °C) — -• . `I ��I,r . ce 1 m ° ;
High' 286 °F (141 °C) 165 °F (74 °C) 150 °F (66 °C) _I —_1 j
eore
3/ rplo [ le s Adj 7I us tmm ] ment i V
Sprinkler cup fabricated of steel and CCP Cover Plate fabricated of
brass and recommended for interior applications. 3/16' (4.76mm]
Corerplote Adjustment J 5/16' Mo.
' Listed and Certified only by cULus
3/8' [9.53mm] [84.13mm)
Total Adjustment 153/'60.1
Sprinkler Installation Wrench .
Model G3 R/C Sprinkler Wrench Note: Do not install the Model F3 CCP Pendent
Sprinkler Identification Number (SIN): R5314 Concealed Sprinkler in ceilings which have
positive pressure in the space above.
Model F3 Dry Horizontal Sidewall Sprinkler .
"A" Dim. 2 to 48° (51mm to 1219mm) in (6mm) increments
Finishest')
Sprinkler Escutcheon , 1/2 [361omm]
Bronze Brass Total Adjustment ._ .. ....
Chrome Plated Chrome Plated r , r Ceiling
White Painted'' White '1 f I = r"----------- __ f 1
Lead Plated 131 1._i 3 j 4' (101.60mm) Mm.
Wax Coated
tJil'i I I /4' [31 75mm) 12' [304 80mm] ma.
Wax Over Lead j°i1d' Escutcheon Adjustment
1 1/4" [6 35mm]
11 Other finishes and colors are available on special order system Tee 1 NPT f• Escutcheon A°,°slmenl
Consult factory for details. I ,, ', 2 3/32'
j2 ' White painted sprinklers will have chrome plated can. ! �- f,- - -r `. [53 18 rim] t F
"' 155 ° F (68 °C) to 200 °F (93°C) rating only lullllll11l _ _ — _' l
1 ' 1 212 °F (100 °C) brown wax may be used on 286 °F (141 °C) sprinklers � = 3
when maximum ceiling temperatures do not exceed 150 °F (66 °C) -�- � � I [76 2 0mm]
Standard Temperature Ratings 2 1/8" D.o
[53 98mm1 • 3.1 +I
Sprinkler Hole m Well t 1/4' (6.35mm]
Temperature Max. Ambient Spr.nkler Con Protrusion
Classification Rating Temp. Bulb Color 'A Dimension •
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Adjustment of Escutc Escutcheon
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red : v Ronge ! I 1/4'
1/4 (-31 75 , m]
Intermediate 200 °F (93 °C) 150 °F (66 °C) Green
High 286 °F(141 °C) 225 °F(107 °C) Blue -
1
Sprinkler can and escutcheon fabricated of brass for better weather
resistance in exterior applications Note: The sprinkler can protrudes 1 /4" when escutcheon
Sprinkler Installation Wrench: is in nominal position. Escutcheon adjustment
Model G3 Sprinkler Wrench. provides + 1/4" ( +6mm) to -11/4" ( -32mm) "A"
dimension adjustment range. .
. Sprinkler Identification Number (SIN): R5334
3.
Model F3 Dry Horizontal Recessed Sidewall Sprinkler
I "A" Dim. I 3Y °to48"(S91rn to 1219nm)in (Emn)increrents
Finishesw: t --
Sprinkler Escutcheon I t - - r 13/32-
Bronze i Brass E "° ~—
[35 ,mm]
Chrome Plated Chrome Plated = .- f tot 6mm]ue
White Painted White C\ system Tee Coo i s° I 6 [157.mm]uo.
"'Other finishes and colors are available on special order Consult t- MGT
factory for details ))) {_ MEIN i
Sprinkler's can and FP Escutcheon are fabricated of steel and y 4 '+ ; „ " i l� � � l ---- - ; "/52 ° 'o'
[s+ emm
recommended for interior applications 11411H I
z I /: Smm]Dk I =
;
Moo wolt .
2 +9/6.15133mm]DeA. t - -
Standard Temperature Ratings t/1- [+z,mm]
Dmens.on Escutcne°n Adjustment
Adjustment Ronge
—
Sprinkler Max. Bulb i +51 t/2 -o
Classification 1 Temperature Rating _ Ambient Temp_ Color ; [ • 12 7 -St
Ordinary 135 °F (57 °C) 100 °F (38`C) Orange
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 200 °F (93 °C) 150 °F (66`C Green
High' 286 °F (141 °C) 225°F (107 °C) Blue
• Listed and Certified only by cULus. Notes: Do not install the Model F3 Dry Horizontal '
Recessed Sidewall Sprinkler in walls which
have positive pressure in their side space
• Recessed Horizontal Sidewall sprinklers are
Sprinkler Installation Wrench: listed by cULus for installation of min 4" (100mm)
p - to - max. 6” (150mm) below ceiling, and FM
Model G3 R/C Sprinkler Wrench approved for installation of min. 4" (100mm) - to -
Sprinkler Identification Number (SIN): R5334 max. 12" (306mm).
Technical Data Ordering Information
Orifice Size 1/2" (15mm) Specify'
Thread size: 1" NPT per ANSI B2.1 1. Sprinkler Type (select one).
Working Pressure: 175 psi (12 bar) (a) Model F3 Dry Pendent [
Nominal K Factor - US / (Metric): 5 6 / (80) (b) Model F3 Dry Recessed Pendent
Product Description (c) Model F3 Dry Concealed Pendent
Reliable Model F3 Dry Sprinklers are standard (d) Model F3 Dry Horizontal sidewall
response sprinklers utilizing a durable 5mm frangible (e) Model F3 Dry Recessed Horizontal Sidewall
glass bulb. Model F3 Dry Sprinklers are intended for 2. Sprinkler Temperature Rating.
use in dry and preaction systems and in areas
subjected to freezing temperatures, such as freezers 3. Sprinkler Finish
and unheated portions of buildings. 4. Cover Plate /FP Escutcheon Finish.
Environments wherein dry sprinklers are employed 5 Length: "A" Dimension (face of tee to face of ceiling
can be corrosive For this reason, Model F3 Sprinklers or wall) in 1/4" (6.4mm) increments
have a special wax fillet placed in the gap between the
cup that supports the bulb and the wrenching boss. This 6 Model F3 Dry Pendent (a) is available without
wax will not interfere with the operation of the sprinkler, sprinkler can and escutcheon
and it prevents contaminents from entering the internal Note:
portion of the drop nipple. The wax must not be 1. The "A" dimension is based on a nominally gauged
removed. pipe thread "make-up" of 600" 15mm
Operation B2 1 [7'/2 threads approximately]. )Per ANSI
The glass bulb consists of an accurately controlled 2. All platings and paintings are decorative and
amount of special fluid hermetically sealed inside a intended for interior use
precisely manufactured glass capsule. When the
temperature increases sufficiently due to a fire, the bulb 3. Acceptable appearance in conditions such as
shatters allowing operating parts to clear the waterway parking garages is generally provided with bronze
This enables the inlet seal to release air or water and sprinkler, brass cup and escutcheon for the Model F3
subsequently, cause water flow over the deflector in a Pendent only.
uniform spray pattern, controlling or extinguishing the fire. -
4
1
General Installation Instructions • Model G3 Wrench (Fig. 4) is used for installation of
Model F3 dry sprinklers must be installed only in Pendent and Horizontal sidewall sprinklers.
standard (ANSI B 16.3 class 150 and ANSI B 16.4 class • Glass bulb sprinklers have orange bulb protectors to
125) pipe tees even at branch line ends. They should minimize bulb damage during shipping, handling and
not be installed into elbows and pipe couplings located. .installation. REMOVE THIS PROTECTION AT THE .
on drop nipples to the sprinklers. For these and other TIME THE SPRINKLER SYSTEM IS PLACED IN
fittings including CPVC *, the dry sprinkler should be SERVICE FOR FIRE PROTECTION. Removal of the
installed into a fitting to conform to protrusion into the protectors before this time may leave the bulb •
fitting in accordance with the diagrams The "A" vulnerable to damage. RASCO wrenches are
dimension of the dry sprinkler, which extends into the designed to install sprinklers when covers are in
freezers or a freezing zone from wet pipe systems, place. REMOVE PROTECTORS BY UNDOING THE
should be selected to provide, as a minimum, the CLASP BY HAND. DO NOT USE TOOLS TO REMOVE
specified lengths in inches shown in the following chart, THE PROTECTORS.
between face of the fitting and the outside wall or ceiling Maintenance
of the protected area. The following chart is used for The Model F3 Dry Sprinklers should be inspected
freezing zones when the ambient temperature around
the wet pipe system is kept at 40 °F / 4 °C), and specifies quarterly and the sprinkler system maintained in
the minimum length for fitting face to ceiling or wall accordance with NFPA 25. Do not remove the factory
(outside) for different protected area temperatures. applied thermally sensitive wax fillet between the bulb
supporting cup and the wrenching boss. Do not replace
Length (Face to Ceiling/Wall) Temperature (Protected Areal this wax with a substitute substance. An Alternate
1e inches / c00 mm em / - 29°C substance may interfere with proper operation of the
sprinkler. Do not clean sprinklers with soap and water,
18 inches / 450 mm - 40 °F / - 40 °C ammonia or any other cleaning fluids. Remove dust by
24 inches / 600 mm - 60°F/ - 51"C using a soft brush or gently vacuuming. Remove any
•• For temperatures falling between those in the above chart, the sprinkler which has been painted (other than factory
minimum length may be determined by interpolation. applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick
During installation, the following steps must be followed: replacement of damaged or operated sprinklers. Prior
to installation, sprinklers should be maintained in the
1. Cut the specified size hole (see illustrations) for the original cartons and packaging until used to minimize
sprinkler in the ceiling or wall directly in line with the the potential for damage to sprinklers that would cause
tee. improper operation or non - operation.
2. Apply pipe joint compound to the 1" (25mm) pipe
threads and install sprinkler using the Model G3 or
G3 R/C Sprinkler Wrench as specified. " Spears CPVC sprinkler adapter tees (with steel thread
• 3. Install the Model FP push -on / thread -off escutcheon or insert) can only be used with horizontal sidewall
CCP cover plate if required. sprinklers which do not require protrusion into tees to
prevent ice or debris blockage of sprinkler inlets. These
Note: Installation of the Model F3 Sprinklers is not CPVC tees do not permit sufficient sprinkler inlet •
•
recommended in copper pipe systems, as this may protrusion as required for pendent installation. •
reduce the life expectancy of the sprinklers.
Model F3 Concealed and Recessed
Installation Instructions
• The Model G3 R/C Wrench (Fig. 1) is designed to
locate on the wrenching pads of the Recessed
sprinkler while centering in the cup. A standard W
drive ratchet may be used to drive this wrench.
Figures 1 and 2 show sequentially the insertion of the
wrench. First, the wrench, with its jaws above the
sprinkler deflector, is moved laterally until centered
with the cup. Then raise the wrench inside the cup
until its jaws engage the sprinkler's square wrenching
pads (Fig. 3)..• To remove the wrench, follow this
procedure in reverse order. Care should be taken to •
avoid striking the deflector with the wrench.
5.
I
LA
MN . ma c
qres
4
Fig. 1 - G3 R/C Wrench Fig. 2 - G3 R/C Wrench Fig. 3 G3 R/C Wrench
Fig. 4 - G3 Wrench
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years. and are installed and serviced by the most highly qualified and
reputable sprinkler contractors located throughout the United States. Canada and foreign countries
Manufactured by
®
Recycled
- The Reliable Automatic Sprinkler Co., Inc. paper
e h a b , g (800) 431-1588 Sales
(800) 848 -6051 Sales Fax Fax
(914) 668 -3470 Corporate Offices Revision lines indicate updated or new data
www reliablesprinkler corn Internet Address E G Printed in USA 3/06 P/N 9000970746
[Page Too Large for OCR Processing]