Correspondence City of Tigard, Oregon 0 13125 SW Hall Blvd. • Tigard, OR 97223
November 1, 2007 732 c 6
1 •
RE: RACK STORAGE
lrimAIM•
Building Permit: BUP2007 -00507 Construction Type: 5- B °IPV
Tenant Name: Horizon Restoration Occupancy Type: S -1
Address: 7235 SW Bonita Rd. Occupant Load: NA
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2007 edition; and the Oregon Fire Code (OFC) 2007 Edition.
Fire Extinguishers: Provide 2 -A rated fire extinguishers as required per table 906.3 (1)
of OFC the extinguisher shall be located so that no usable space has a distance greater
than 75 feet to the extinguishers. OFC 906.3
Clearance: The clearance between the sprinkler deflector and the top of storage shall
be 18 in. or greater. NFPA 13 8.5.6.1
Loads Posted: The racks shall display in one or more conspicuous locations a
permanent plaque not less than 50 square inches in area, showing the maximum
permissible unit load in clear legible print. OSSC 1603
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp,
shall be maintained on the jobsite. The plans shall be available to the Building Division
inspectors throughout all phases of construction. 106.4.2 OSSC
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectful y, -
a n Nelson,
Senior Plans Examiner
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772