Specifications fl E C &,1 JAN 1 i Project Plan: Windmill Apartments Ductless Heat Pump Installati ICY 3 2 014 Submitted by: Jonathan Moscatello, The Heat Pump Store G '1SION Date: 1/13/12 Address: 10587 SW Tigard St, Tigard, OR 97223 Owners: Jim and Sharon Richards Description: There are 20 identical structures at the property. Each structure is two stories tall, with two apartments on the CITyaF ARD loweJ' level and two on the upper level. SEE ATTACHED FLOOR Approved .� [ N. Conditionally Approved [ See Letter to: Follow [ %tie will install one ductless heat pump system (see attached Att• hed 1 Permit Number , _ V--- - doe 4 bmittal, Mitsubishi MUZ /MSZ- FE12NA) for each apartment. Ad. ess• APAP WAN By: 4 Date: r T hese are split systems, with an indoor "head" and an outdoor heat pump unit. The indoor and outdoor units are Approved pia Shall be on job site connected by BUNDLE containing two small refrigerant lines, a power and communications wire, and a condensate drain. OFFICE COPY UP I Installation Plan: X - 7S ) , OUTDOOR HEAT PUMP UNIT: The outdoor heat pump for each unit will be attached to the wall of each structure, just opposite of the storage unit for each apartment, using a manufacturer approved bracket (see BRACKET submittal, see exterior FRONT and BACK photos). The heat pumps will be installed approximately 12 inches above the ground level. They will be supplied with a 230V single phase electric circuit per the manufacturer's specifications using an outdoor disconnect. INDOOR "HEAD ": The indoor "head" unit for each outdoor heat pump will be attached to the living room wall of each apartment (see FLOOR PLAN). It will be connected to the outdoor unit by a so- called "bundle" of refrigerant lines, power /communications wire, and condensation drain line. The "bundle" will travel along the following pathway: from the outdoor unit, the bundle will travel to the nearest foundation vent, and enter into the crawlspace. The bundle will run through the crawlspace and penetrate into the storage unit through the floor. The bundle will run up the wall of the storage unit inside specialized conduit call "line cover ". At about head height, one of the sets of refrigerant lines, one power /communication wore and condensate drain will penetrate the storage unit wall and terminate at the head in the living room. All connections to the "head" will be made. Again the penetration will be sealed with fire caulk. The remainder of the bundle will continue upward toward the second story and the head in the living room of the upper unit. The remaining items in the bundle will penetrate the ceiling of the lower storage unit, enter the upper unit, and continue to the head for the upper unit. Again, connections will be made and penetrations sealed with fire caulk. I t MITSUBISHI ELECTRIC Mir.SUM C O O L I N G & HEATING Split - ductless A/C and Heat Pumps SUBMITTAL DATA: CWMB1.' HEAVY DUTY PAINTED STEEL WALL BRACKETS Job Name: Winmill Apartments Location: Tigard, OR' Date: 1/13/12 Purchaser: The Heat Pump Store Engineer: Submitted to: For LiReference LApproval ElConstruction System Designation: Schedule No.: GENERAL FEATURES ASSEMBLY INSTRUCTION • The CWM61 wall brackets are designed to provide a 1 Fit the vertical component to the honzontat arm by means to mount the Mr Slim M- Series, S- Seres. P- Series inserting two TEM8X90 screws with four lock washers and CITY MULTI PUMY -Senes outdoor units on a suitable four flat washers + two self - locking nuts into the bracket wall or structure and keep the equipment off the ground components as illustrated The CWMB1 consists of two independently mounted wall brackets to allow proper leveling and support SELF - LOCKING WASHERS 1 WASHERS t 8X90 SCREWS NUTS • The formed mild carbon steel two piece bracket is a (D x4 J; x8 © x8 x4 rugged. fabricated, heavy duty accessory constructed for �it1 long reliable service life. The bracket is finished with an electrostatically applied, thermally fused acrylic or polyester powder coating for corrosion protection r o; : x2 The CWMB1 meets the intent and provides compliance with '°' 'o • ` ` -_ those codes requiring mounting HVAC equipment above ground level PLEASE NOTE a The Wall Bracket load capacity can only be assured if the installation is carried out properly (see drawing A) Drawing B illustrates an improper installation 2 Make sure the chosen installation location meets with specified requirements and wall design and construction is suitable als anc and har strong dware enouare gh the to hold respons the brackets and associated equipment loads Anchors and related mounting 440 Ibs mater ibility of the installer 3 Avoid mounting the brackets and attached load on weak walls. 9 soft siding. veneer panels. perforated bricks / blocks or other A insufficient mounting surfaces. h It is the responsibility of the Project Engineer and/or the Installing Contractor / Dealer to specify furnish. and install a x b any anchor or attachment materials required for the wall construction at the selected mounting location We are not 20.47" x 15.75" responsible for any installation faults or defects c It is strongly recommended to have the installation periodically inspected by a skilled technician ASSEMBLY Notes: 02011 MITSUBISHI Et ECTRIC & ELECTRONICS, INC V DIMENSIONS: CWMB1 /r 1 j .O, 0 . 1 , i, , hl ^ I i tx l / • >p .Pi ' J ' I d '` r � ., x.e ,.../... i � . Self Wong r • .1.' a Class &H Inc Plated steel V \!rD • 9 PWlcrf MR nut. wMte ldN74741 SUM. whhe. T1.11411)(154' (1504014) T.E. M8x90' I ' t l HEAVY DUTY WALL BRACKETS -;.- Mtk ME COOLING $ HEATING PARTNER L ve Better 3400 Lawrencewne Suwanee Rd Suwanee. GA 30024 Tele 678 - 376-2900 • Fax 800- 889 -9904 To Free 800 -433 -4822 (#3) FORM# CVvM81. 201108 mm 2011 MI TSUBISHI ELECTRIC &ELECTRONICS INC SpeNf icaBonHat. stubjectta change without CoNu. MITSUBISHI ELECTRIC M� ir. SLIT( 1. COOLING & HEATING Split- ductku A/C and Heat Pumps SUBMITTAL DATA: MSZ- FE12NA -8 8 MUZ-FE12NA1 12.000 BTUiH WALL - MOUNTED HEAT PUMP SYSTEM Job Name: Windmill Apartments Location Tigard, OR Date: 1/13/12 Purchaser: The Heat Pump Store Engineer: Submitted to: For rJReference ElApproval ilConstruction System Designation: Schedule No.: GENERAL FEATURES • Highly energy - efficient system that features 92% heating capacity at 5`F. 75% at -4 "F, and 58% at -13'E . . : • Updated sleek, compact indoor unit design e I • Includes Standard. Platinum Deodorizing. and Anti--allergy En- t . • 1 '" f zyme filters for a complete air purifying system • — - -- - - -- Powerful Mode' function permits system to temporarily run at ' a lower/higher temperature with an increased fan speed. which Indoor urn MSL- FE12NA.o I quickly brings the room to the optimum comfort level • Integrated i -see Sensor automatically adjusts the unit's operation* ' f according to temperature differences detected between the floor A and the intake air. ensuring optimum comfort and energy usage • "'' ( w C icier 0 • Hand -held Wireless Remote Controller °taloa Unit MwZ- FE12NA1 • Base heater is available as an option • Limited warranty: five years on parts and defects and seven years on compressors OPERATING RANGE OPTIONAL ACCESSORIES "`°0gf""'" 0A000f11y° Outdoor Unit maxim= = 30•F (32 De. T3•F QTCI we 115°F k41YC) 06 cocurj Base Heater (MAC- 640BH -U) Mwmun OM (19'C> OB. srF (14Cn we 14•F c•ta"cn 043 Drain Socket (MAC-8510S) Mammon SW arc) DO. 62 (te c)1M3 75`F (24•C) DB, WI' iirrc) we ee Indoor Unit "" n Mo .... 70•F Q„CI o6. eo'F OM Y%6 • 13•F ( - 08. -15'F 1.26V) we•• Li Condensate Pump (SI3100 -230; 230V) •• System Ms on a1 .19•F (-26•C)10 avoid ewmstor error. but recovers from CaOut ❑ Replacement Platinum Deodorizing Filter (MAC -308F T) 1 er+o weaMeucaN restate at -13 (25•C) it Replacement Anti- allergy Enzyme Filter (MAC- 418F MERV 8) Indoor Unit Controller Options MCA . . _ . 1 A ❑ Wireless Remote Controller Kit (MHK1) with Remote Controller Fan Motor 0.76 F.L A (MRCH1). Wireless Receiver (MIFH1.). and cable (MRC1)• Airflow ❑ Setback down to 50`F when used with MRCH1 Remote Controller Cooling (Lo - Med - Hi • Powerful) ..162 - 226 - 381 -410 Dry CFM ❑ Portable Central Controller (MCCH1: for use with Wireless Remote 144 - 202 - 350 • 367 Wet CFM Controller Kit MHK1)' Heating (Lo - Med - Hi - Powerful) .166 - 240 - 399 - 420 Dry CFM o Outdoor Air Sensor (MOS1; for use with Remote Controller (MRCH1), Sound Pressure Level Wireless Remote Controller Kit (MHK1) and Portable Central Cooling (Lo - Med - Hi - Powerful) .. 22 - 33 - 43 - 45 dB(A) • Controller (MCCH1)' Heating (Lo - Med - Hi - Powerful) 22 33 - 43 - 44 dB(A) bee s tx'Htd ex 'transom on eact∎ °Fenn DIMENSIONS UNIT INCHES / MM ❑ Wall- mounted Wired Remote Controller (PAR-21MAA. req. MAC- 3971F) W 31 ❑ MA Contact Terminal Interface (MAC- 3971F) D 10 -1/8 / 257 ❑ M -NET Control Adapter (MAC- 3991F) H 11 - 5/8 / 295 ❑ Remote Temperature Sensor (M21 •JKO.307) o Lockdown Bracket for Hand -held Controller (RCMKP1CB) Weight 27 lbs. 1 12 kg Cooling" External Finish . . .. . Munsell No. 1.OY 9.2 / 0.2 Field Drainpipe Size 0.1) 518' l 15.88 mm Rated Capacity . .. . 12,000 Btu/h Remote Controller Wireless Minimum Capacity ..... .... 2,800 Btu/h Outdoor Unit SEER ... . . 23.0 BtumlW Total Input. .....930 W Compressor DC Inverter-driven Twin - Rotary MCA . - . . A Heating at 47' F• Fan Motor 056 F.L.A. Rated Capacity .. 13.600 Btu/h Sound Pressure Level Minimum Capacity .. 3.000 Btulh Cooling . . .48 dB(A) I ISM- - . 10.6 Btu/h/W Heating 49 dB(A) Total Input ...950 W Heating at 17° F' DIMENSIONS INCHES / MM Rated Capacity 7900Btu/h W 31 - v2 /80C Rated total Input . . 750 W D 11 -1/4 i 286 Maximum Capacity .13.600 Bluth H 21 - /8 / 549 Maximum Total Input 1 780 W • Relent) CorxMwne tCooiny,) - indoor 80'F (27•CI 06.67 (19•C) WB: outdoor 951' Weight . .. . . .80 lbs / 36 kg (35•CI OB 75Y (24°C1 wB External Finish .. Munsell No. 3.OY 7 8 / 1 1 IHeebq at47°F) indoor MK OK) 06. GM nrct we akmor 47F tegoe •.43•FeMWe Refrigerant Type R410A o- esng at 1mi . naxr 7o•F (21•cl toe isOW (16•C, we. outdoor 1rF t De. ts•Ft4 C) a Refrigerant Pipe Size O.D. Heating at 5° F Gas Side ..... . .. ... .. .. ... 3/8• / 9 52 mm Maximum Capacity .. . 12.500 Btu/h liquid Side. . . . . 1W/6.35 mm Electrical Requirements Max. Refrigerant Pipe Length.. 65' I 20 m Power Supply . 208 1 230V, 1- Phase, 60 Hz Max. c ant Pipe Height Difference 40' 1 12 in Breaker Size .. .15 A Conne Method Flared Voltage Indoor - Outdoor S1-52 . . . .. AC 208 / 230V Q I & R Indoor • Outdoor S2 -S3 . DC 12 -24V Wireless Remote Controller ... DC e) 2011 MITSUBISHI ELECTRIC s ELECTRONICS. INC. DIMENSIONS: MSZ- FEI2NA -8 & MUZ FE12NA1 MSZ- FEI2NA -8 Unit: inch 31- : 7/16 X 1 Oblong hole 7116 X 13/16 Oblong hole 30-718 1/2 2 - 112 : t: : 7 _ I Installation plate Y � • • I _ MIMI Indoor uni -1 : •• /1 n Air in Wall hole 02-9/16 / 0 Installation r ate I - 11 _ 2 7 -1116 - 1 11 1 1 P. _ I 1 -1 I6 I i , ' 0 t4 m ^? Th -- ` .I - Drain c r Insulation 01-3/8 0.0 M - t' -` Limed Ltd Ime 0114 19-11/16 (Flared connection 01/4) Air out 1 _ 1 . a Gas I ne 0318 16 -15/16 (Flared connection 03/8) Drain base Insulation al-1/8 O D Connected part 05/8 O.D MUZ- FE12NA1 Unit: inch Drain hole 01 -5/0- • t At j Dra REQUIRED S P AC E 9as (S y open 4 mc3■ ix more i wthout any obstruction .n front .- and on both sides of the unit 1 ' .. „ ,,,. Ai' n b n d i m r A •II o 0 mow / 149/119 ''O 441 �� 1 2- 318 a 13/1 8 Oval tale 1 18 7 7 I _ � �e handle Illllminil iniiiiiillllllmiiiiii 1 29f32 _ 11- 111 . ini IIIIIIIIIIIIIIIIIIIIIIIIIIIIilllllllllil 1 - _ Open two soles of lee. IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII nght. « rear sole. . IIIIIIIIiIIIIIIIIIIIIIIIIIIIIIIIIIIIIM C4 IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII e IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII " ""I " "°IIIIIIIIIIIIIIIIIIIIIHII , aluminium oN1 1.29132 Liquid p+pe t;0- (flared) Gas pipe 3/8 (hared) 19.nne 31-1/2 2 -23132 62313 A MrISUBISHI AMR! CERTIFIED . - � COOLING ` HEATING PARTNER L.ve Better . " .., GUS 3400 Law Su renoevAe wanee Rd Smoot, GA 30024 n tertek Tele: 678. 376-2900 • Fax: 800.889.9904 Toll Free 800.433 -4822 (#3) ewe rnehvac corn 0 2011 # ITSUBISHI ELECTR IC &ELECTRONICS INC Specifications are subject to change without notice. FLOOR PLAN Two Bedrooms with Two Baths Approx. 987 Sq.Ft. + 98 Sq.Ft. Storage & Patio = 1085 Sq.Ft. Total Living Space Y O Bath / Q sto rage �1 [` e Living st „ Room ; � Bedroom Patio/ Deck Batlt I � Kitchen [ Bedroom Entry Dining rii Room • ■/\ 1 a i t 1 .. Left Kitchen Floorplan n Batb ® Q x al torsge F ' 1 Bedroom 8 Living �- ,..\ Room At Patio/ t ( ` Deck Bedroom 10 mi Kitchen -- Entry F Dining 2 Room , al Right Kitchen Floorplan Qo V J FRONT "- , It. _AL .... �•- �+�"�� r. - � - -. �- �• ..« �rw'�A►r ` ..r. rte• v.� -M ..� - _ -. ��'- - -- _ ^• -..�.r _� �� ...�r� •. . .I•'�' _-......- -. --_. ` .ter ..... ... .. - '" ... .ti. K. v w-.�- _.._ "- �_� -....... w . a � --ter --- l Vii • It =J . . • • .. ter BACK e IN, , . .0. & ill .1. ft ..11. . •.._. _. .... .... IP ..r. I — . .... , • .. .. . ' ,.• , ,, ; _f , ' i;i ' - ..r- ....• - -.. . - ..-..._ 4...... -.7...... .... 1 111.1.•,. • " - ,.. . illiir . s • f I, - .... ' .1111111111111111111.111p II* lalt ..- • ' 3 ". lir • le . _.....- . ..k. 42 lik, 4212 t.1 iiiiiii/ft • ... • , • . . - , . . . ,-,..........-„,.......4.22,....--••••■•-,-........................................4,...........,,,...,,,, , .. 1 1 . - i . 4 , .. .....' '''''''"' '• . f',4. ,,!.,,,,-.. „ _ ......„, 44 v.... --4.,••2■22.0.,......,-•-•'■-...-.411 „,b, ,. ' i i .,- _ ..# . . ... 4 ..4 4 • t .il . ' . . - .. ',... "- 1 .. -ii . • . _ . . -- ii- • '- -- --- - - imighl ...- .,...., ... .........._ . . . . ..........-.-- .• . . ir . Ili_ ... _ . . . fl E C &,1 JAN 1 i Project Plan: Windmill Apartments Ductless Heat Pump Installati ICY 3 2 014 Submitted by: Jonathan Moscatello, The Heat Pump Store G '1SION Date: 1/13/12 Address: 10587 SW Tigard St, Tigard, OR 97223 Owners: Jim and Sharon Richards Description: There are 20 identical structures at the property. Each structure is two stories tall, with two apartments on the CITyaF ARD loweJ' level and two on the upper level. SEE ATTACHED FLOOR Approved .� [ N. Conditionally Approved [ See Letter to: Follow [ %tie will install one ductless heat pump system (see attached Att• hed 1 Permit Number , _ V--- - doe 4 bmittal, Mitsubishi MUZ /MSZ- FE12NA) for each apartment. Ad. ess• APAP WAN By: 4 Date: r T hese are split systems, with an indoor "head" and an outdoor heat pump unit. The indoor and outdoor units are Approved pia Shall be on job site connected by BUNDLE containing two small refrigerant lines, a power and communications wire, and a condensate drain. OFFICE COPY UP I Installation Plan: X - 7S ) , OUTDOOR HEAT PUMP UNIT: The outdoor heat pump for each unit will be attached to the wall of each structure, just opposite of the storage unit for each apartment, using a manufacturer approved bracket (see BRACKET submittal, see exterior FRONT and BACK photos). The heat pumps will be installed approximately 12 inches above the ground level. They will be supplied with a 230V single phase electric circuit per the manufacturer's specifications using an outdoor disconnect. INDOOR "HEAD ": The indoor "head" unit for each outdoor heat pump will be attached to the living room wall of each apartment (see FLOOR PLAN). It will be connected to the outdoor unit by a so- called "bundle" of refrigerant lines, power /communications wire, and condensation drain line. The "bundle" will travel along the following pathway: from the outdoor unit, the bundle will travel to the nearest foundation vent, and enter into the crawlspace. The bundle will run through the crawlspace and penetrate into the storage unit through the floor. The bundle will run up the wall of the storage unit inside specialized conduit call "line cover ". At about head height, one of the sets of refrigerant lines, one power /communication wore and condensate drain will penetrate the storage unit wall and terminate at the head in the living room. All connections to the "head" will be made. Again the penetration will be sealed with fire caulk. The remainder of the bundle will continue upward toward the second story and the head in the living room of the upper unit. The remaining items in the bundle will penetrate the ceiling of the lower storage unit, enter the upper unit, and continue to the head for the upper unit. Again, connections will be made and penetrations sealed with fire caulk. I t MITSUBISHI ELECTRIC Mir.SUM C O O L I N G & HEATING Split - ductless A/C and Heat Pumps SUBMITTAL DATA: CWMB1.' HEAVY DUTY PAINTED STEEL WALL BRACKETS Job Name: Winmill Apartments Location: Tigard, OR' Date: 1/13/12 Purchaser: The Heat Pump Store Engineer: Submitted to: For LiReference LApproval ElConstruction System Designation: Schedule No.: GENERAL FEATURES ASSEMBLY INSTRUCTION • The CWM61 wall brackets are designed to provide a 1 Fit the vertical component to the honzontat arm by means to mount the Mr Slim M- Series, S- Seres. P- Series inserting two TEM8X90 screws with four lock washers and CITY MULTI PUMY -Senes outdoor units on a suitable four flat washers + two self - locking nuts into the bracket wall or structure and keep the equipment off the ground components as illustrated The CWMB1 consists of two independently mounted wall brackets to allow proper leveling and support SELF - LOCKING WASHERS 1 WASHERS t 8X90 SCREWS NUTS • The formed mild carbon steel two piece bracket is a (D x4 J; x8 © x8 x4 rugged. fabricated, heavy duty accessory constructed for �it1 long reliable service life. The bracket is finished with an electrostatically applied, thermally fused acrylic or polyester powder coating for corrosion protection r o; : x2 The CWMB1 meets the intent and provides compliance with '°' 'o • ` ` -_ those codes requiring mounting HVAC equipment above ground level PLEASE NOTE a The Wall Bracket load capacity can only be assured if the installation is carried out properly (see drawing A) Drawing B illustrates an improper installation 2 Make sure the chosen installation location meets with specified requirements and wall design and construction is suitable als anc and har strong dware enouare gh the to hold respons the brackets and associated equipment loads Anchors and related mounting 440 Ibs mater ibility of the installer 3 Avoid mounting the brackets and attached load on weak walls. 9 soft siding. veneer panels. perforated bricks / blocks or other A insufficient mounting surfaces. h It is the responsibility of the Project Engineer and/or the Installing Contractor / Dealer to specify furnish. and install a x b any anchor or attachment materials required for the wall construction at the selected mounting location We are not 20.47" x 15.75" responsible for any installation faults or defects c It is strongly recommended to have the installation periodically inspected by a skilled technician ASSEMBLY Notes: 02011 MITSUBISHI Et ECTRIC & ELECTRONICS, INC V DIMENSIONS: CWMB1 /r 1 j .O, 0 . 1 , i, , hl ^ I i tx l / • >p .Pi ' J ' I d '` r � ., x.e ,.../... i � . Self Wong r • .1.' a Class &H Inc Plated steel V \!rD • 9 PWlcrf MR nut. wMte ldN74741 SUM. whhe. T1.11411)(154' (1504014) T.E. M8x90' I ' t l HEAVY DUTY WALL BRACKETS -;.- Mtk ME COOLING $ HEATING PARTNER L ve Better 3400 Lawrencewne Suwanee Rd Suwanee. GA 30024 Tele 678 - 376-2900 • Fax 800- 889 -9904 To Free 800 -433 -4822 (#3) FORM# CVvM81. 201108 mm 2011 MI TSUBISHI ELECTRIC &ELECTRONICS INC SpeNf icaBonHat. stubjectta change without CoNu. MITSUBISHI ELECTRIC M� ir. SLIT( 1. COOLING & HEATING Split- ductku A/C and Heat Pumps SUBMITTAL DATA: MSZ- FE12NA -8 8 MUZ-FE12NA1 12.000 BTUiH WALL - MOUNTED HEAT PUMP SYSTEM Job Name: Windmill Apartments Location Tigard, OR Date: 1/13/12 Purchaser: The Heat Pump Store Engineer: Submitted to: For rJReference ElApproval ilConstruction System Designation: Schedule No.: GENERAL FEATURES • Highly energy - efficient system that features 92% heating capacity at 5`F. 75% at -4 "F, and 58% at -13'E . . : • Updated sleek, compact indoor unit design e I • Includes Standard. Platinum Deodorizing. and Anti--allergy En- t . • 1 '" f zyme filters for a complete air purifying system • — - -- - - -- Powerful Mode' function permits system to temporarily run at ' a lower/higher temperature with an increased fan speed. which Indoor urn MSL- FE12NA.o I quickly brings the room to the optimum comfort level • Integrated i -see Sensor automatically adjusts the unit's operation* ' f according to temperature differences detected between the floor A and the intake air. ensuring optimum comfort and energy usage • "'' ( w C icier 0 • Hand -held Wireless Remote Controller °taloa Unit MwZ- FE12NA1 • Base heater is available as an option • Limited warranty: five years on parts and defects and seven years on compressors OPERATING RANGE OPTIONAL ACCESSORIES "`°0gf""'" 0A000f11y° Outdoor Unit maxim= = 30•F (32 De. T3•F QTCI we 115°F k41YC) 06 cocurj Base Heater (MAC- 640BH -U) Mwmun OM (19'C> OB. srF (14Cn we 14•F c•ta"cn 043 Drain Socket (MAC-8510S) Mammon SW arc) DO. 62 (te c)1M3 75`F (24•C) DB, WI' iirrc) we ee Indoor Unit "" n Mo .... 70•F Q„CI o6. eo'F OM Y%6 • 13•F ( - 08. -15'F 1.26V) we•• Li Condensate Pump (SI3100 -230; 230V) •• System Ms on a1 .19•F (-26•C)10 avoid ewmstor error. but recovers from CaOut ❑ Replacement Platinum Deodorizing Filter (MAC -308F T) 1 er+o weaMeucaN restate at -13 (25•C) it Replacement Anti- allergy Enzyme Filter (MAC- 418F MERV 8) Indoor Unit Controller Options MCA . . _ . 1 A ❑ Wireless Remote Controller Kit (MHK1) with Remote Controller Fan Motor 0.76 F.L A (MRCH1). Wireless Receiver (MIFH1.). and cable (MRC1)• Airflow ❑ Setback down to 50`F when used with MRCH1 Remote Controller Cooling (Lo - Med - Hi • Powerful) ..162 - 226 - 381 -410 Dry CFM ❑ Portable Central Controller (MCCH1: for use with Wireless Remote 144 - 202 - 350 • 367 Wet CFM Controller Kit MHK1)' Heating (Lo - Med - Hi - Powerful) .166 - 240 - 399 - 420 Dry CFM o Outdoor Air Sensor (MOS1; for use with Remote Controller (MRCH1), Sound Pressure Level Wireless Remote Controller Kit (MHK1) and Portable Central Cooling (Lo - Med - Hi - Powerful) .. 22 - 33 - 43 - 45 dB(A) • Controller (MCCH1)' Heating (Lo - Med - Hi - Powerful) 22 33 - 43 - 44 dB(A) bee s tx'Htd ex 'transom on eact∎ °Fenn DIMENSIONS UNIT INCHES / MM ❑ Wall- mounted Wired Remote Controller (PAR-21MAA. req. MAC- 3971F) W 31 ❑ MA Contact Terminal Interface (MAC- 3971F) D 10 -1/8 / 257 ❑ M -NET Control Adapter (MAC- 3991F) H 11 - 5/8 / 295 ❑ Remote Temperature Sensor (M21 •JKO.307) o Lockdown Bracket for Hand -held Controller (RCMKP1CB) Weight 27 lbs. 1 12 kg Cooling" External Finish . . .. . Munsell No. 1.OY 9.2 / 0.2 Field Drainpipe Size 0.1) 518' l 15.88 mm Rated Capacity . .. . 12,000 Btu/h Remote Controller Wireless Minimum Capacity ..... .... 2,800 Btu/h Outdoor Unit SEER ... . . 23.0 BtumlW Total Input. .....930 W Compressor DC Inverter-driven Twin - Rotary MCA . - . . A Heating at 47' F• Fan Motor 056 F.L.A. Rated Capacity .. 13.600 Btu/h Sound Pressure Level Minimum Capacity .. 3.000 Btulh Cooling . . .48 dB(A) I ISM- - . 10.6 Btu/h/W Heating 49 dB(A) Total Input ...950 W Heating at 17° F' DIMENSIONS INCHES / MM Rated Capacity 7900Btu/h W 31 - v2 /80C Rated total Input . . 750 W D 11 -1/4 i 286 Maximum Capacity .13.600 Bluth H 21 - /8 / 549 Maximum Total Input 1 780 W • Relent) CorxMwne tCooiny,) - indoor 80'F (27•CI 06.67 (19•C) WB: outdoor 951' Weight . .. . . .80 lbs / 36 kg (35•CI OB 75Y (24°C1 wB External Finish .. Munsell No. 3.OY 7 8 / 1 1 IHeebq at47°F) indoor MK OK) 06. GM nrct we akmor 47F tegoe •.43•FeMWe Refrigerant Type R410A o- esng at 1mi . naxr 7o•F (21•cl toe isOW (16•C, we. outdoor 1rF t De. ts•Ft4 C) a Refrigerant Pipe Size O.D. Heating at 5° F Gas Side ..... . .. ... .. .. ... 3/8• / 9 52 mm Maximum Capacity .. . 12.500 Btu/h liquid Side. . . . . 1W/6.35 mm Electrical Requirements Max. Refrigerant Pipe Length.. 65' I 20 m Power Supply . 208 1 230V, 1- Phase, 60 Hz Max. c ant Pipe Height Difference 40' 1 12 in Breaker Size .. .15 A Conne Method Flared Voltage Indoor - Outdoor S1-52 . . . .. AC 208 / 230V Q I & R Indoor • Outdoor S2 -S3 . DC 12 -24V Wireless Remote Controller ... DC e) 2011 MITSUBISHI ELECTRIC s ELECTRONICS. INC. DIMENSIONS: MSZ- FEI2NA -8 & MUZ FE12NA1 MSZ- FEI2NA -8 Unit: inch 31- : 7/16 X 1 Oblong hole 7116 X 13/16 Oblong hole 30-718 1/2 2 - 112 : t: : 7 _ I Installation plate Y � • • I _ MIMI Indoor uni -1 : •• /1 n Air in Wall hole 02-9/16 / 0 Installation r ate I - 11 _ 2 7 -1116 - 1 11 1 1 P. _ I 1 -1 I6 I i , ' 0 t4 m ^? Th -- ` .I - Drain c r Insulation 01-3/8 0.0 M - t' -` Limed Ltd Ime 0114 19-11/16 (Flared connection 01/4) Air out 1 _ 1 . a Gas I ne 0318 16 -15/16 (Flared connection 03/8) Drain base Insulation al-1/8 O D Connected part 05/8 O.D MUZ- FE12NA1 Unit: inch Drain hole 01 -5/0- • t At j Dra REQUIRED S P AC E 9as (S y open 4 mc3■ ix more i wthout any obstruction .n front .- and on both sides of the unit 1 ' .. „ ,,,. Ai' n b n d i m r A •II o 0 mow / 149/119 ''O 441 �� 1 2- 318 a 13/1 8 Oval tale 1 18 7 7 I _ � �e handle Illllminil iniiiiiillllllmiiiiii 1 29f32 _ 11- 111 . ini IIIIIIIIIIIIIIIIIIIIIIIIIIIIilllllllllil 1 - _ Open two soles of lee. IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII nght. « rear sole. . IIIIIIIIiIIIIIIIIIIIIIIIIIIIIIIIIIIIIM C4 IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII e IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII " ""I " "°IIIIIIIIIIIIIIIIIIIIIHII , aluminium oN1 1.29132 Liquid p+pe t;0- (flared) Gas pipe 3/8 (hared) 19.nne 31-1/2 2 -23132 62313 A MrISUBISHI AMR! CERTIFIED . - � COOLING ` HEATING PARTNER L.ve Better . " .., GUS 3400 Law Su renoevAe wanee Rd Smoot, GA 30024 n tertek Tele: 678. 376-2900 • Fax: 800.889.9904 Toll Free 800.433 -4822 (#3) ewe rnehvac corn 0 2011 # ITSUBISHI ELECTR IC &ELECTRONICS INC Specifications are subject to change without notice. FLOOR PLAN Two Bedrooms with Two Baths Approx. 987 Sq.Ft. + 98 Sq.Ft. Storage & Patio = 1085 Sq.Ft. Total Living Space Y O Bath / Q sto rage �1 [` e Living st „ Room ; � Bedroom Patio/ Deck Batlt I � Kitchen [ Bedroom Entry Dining rii Room • ■/\ 1 a i t 1 .. Left Kitchen Floorplan n Batb ® Q x al torsge F ' 1 Bedroom 8 Living �- ,..\ Room At Patio/ t ( ` Deck Bedroom 10 mi Kitchen -- Entry F Dining 2 Room , al Right Kitchen Floorplan Qo V J FRONT "- , It. _AL .... �•- �+�"�� r. - � - -. �- �• ..« �rw'�A►r ` ..r. rte• v.� -M ..� - _ -. ��'- - -- _ ^• -..�.r _� �� ...�r� •. . .I•'�' _-......- -. --_. ` .ter ..... ... .. - '" ... .ti. K. v w-.�- _.._ "- �_� -....... w . a � --ter --- l Vii • It =J . . • • .. ter BACK e IN, , . .0. & ill .1. ft ..11. . •.._. _. .... .... IP ..r. I — . .... , • .. .. . ' ,.• , ,, ; _f , ' i;i ' - ..r- ....• - -.. . - ..-..._ 4...... -.7...... .... 1 111.1.•,. • " - ,.. . illiir . s • f I, - .... ' .1111111111111111111.111p II* lalt ..- • ' 3 ". lir • le . _.....- . ..k. 42 lik, 4212 t.1 iiiiiii/ft • ... • , • . . - , . . . ,-,..........-„,.......4.22,....--••••■•-,-........................................4,...........,,,...,,,, , .. 1 1 . - i . 4 , .. .....' '''''''"' '• . f',4. ,,!.,,,,-.. „ _ ......„, 44 v.... --4.,••2■22.0.,......,-•-•'■-...-.411 „,b, ,. ' i i .,- _ ..# . . ... 4 ..4 4 • t .il . ' . . - .. ',... "- 1 .. -ii . • . _ . . -- ii- • '- -- --- - - imighl ...- .,...., ... .........._ . . . . ..........-.-- .• . . ir . Ili_ ... _ . . . fl E C &,1 JAN 1 i Project Plan: Windmill Apartments Ductless Heat Pump Installati ICY 3 2 014 Submitted by: Jonathan Moscatello, The Heat Pump Store G '1SION Date: 1/13/12 Address: 10587 SW Tigard St, Tigard, OR 97223 Owners: Jim and Sharon Richards Description: There are 20 identical structures at the property. Each structure is two stories tall, with two apartments on the CITyaF ARD loweJ' level and two on the upper level. SEE ATTACHED FLOOR Approved .� [ N. Conditionally Approved [ See Letter to: Follow [ %tie will install one ductless heat pump system (see attached Att• hed 1 Permit Number , _ V--- - doe 4 bmittal, Mitsubishi MUZ /MSZ- FE12NA) for each apartment. Ad. ess• APAP WAN By: 4 Date: r T hese are split systems, with an indoor "head" and an outdoor heat pump unit. The indoor and outdoor units are Approved pia Shall be on job site connected by BUNDLE containing two small refrigerant lines, a power and communications wire, and a condensate drain. OFFICE COPY UP I Installation Plan: X - 7S ) , OUTDOOR HEAT PUMP UNIT: The outdoor heat pump for each unit will be attached to the wall of each structure, just opposite of the storage unit for each apartment, using a manufacturer approved bracket (see BRACKET submittal, see exterior FRONT and BACK photos). The heat pumps will be installed approximately 12 inches above the ground level. They will be supplied with a 230V single phase electric circuit per the manufacturer's specifications using an outdoor disconnect. INDOOR "HEAD ": The indoor "head" unit for each outdoor heat pump will be attached to the living room wall of each apartment (see FLOOR PLAN). It will be connected to the outdoor unit by a so- called "bundle" of refrigerant lines, power /communications wire, and condensation drain line. The "bundle" will travel along the following pathway: from the outdoor unit, the bundle will travel to the nearest foundation vent, and enter into the crawlspace. The bundle will run through the crawlspace and penetrate into the storage unit through the floor. The bundle will run up the wall of the storage unit inside specialized conduit call "line cover ". At about head height, one of the sets of refrigerant lines, one power /communication wore and condensate drain will penetrate the storage unit wall and terminate at the head in the living room. All connections to the "head" will be made. Again the penetration will be sealed with fire caulk. The remainder of the bundle will continue upward toward the second story and the head in the living room of the upper unit. The remaining items in the bundle will penetrate the ceiling of the lower storage unit, enter the upper unit, and continue to the head for the upper unit. Again, connections will be made and penetrations sealed with fire caulk. I t MITSUBISHI ELECTRIC Mir.SUM C O O L I N G & HEATING Split - ductless A/C and Heat Pumps SUBMITTAL DATA: CWMB1.' HEAVY DUTY PAINTED STEEL WALL BRACKETS Job Name: Winmill Apartments Location: Tigard, OR' Date: 1/13/12 Purchaser: The Heat Pump Store Engineer: Submitted to: For LiReference LApproval ElConstruction System Designation: Schedule No.: GENERAL FEATURES ASSEMBLY INSTRUCTION • The CWM61 wall brackets are designed to provide a 1 Fit the vertical component to the honzontat arm by means to mount the Mr Slim M- Series, S- Seres. P- Series inserting two TEM8X90 screws with four lock washers and CITY MULTI PUMY -Senes outdoor units on a suitable four flat washers + two self - locking nuts into the bracket wall or structure and keep the equipment off the ground components as illustrated The CWMB1 consists of two independently mounted wall brackets to allow proper leveling and support SELF - LOCKING WASHERS 1 WASHERS t 8X90 SCREWS NUTS • The formed mild carbon steel two piece bracket is a (D x4 J; x8 © x8 x4 rugged. fabricated, heavy duty accessory constructed for �it1 long reliable service life. The bracket is finished with an electrostatically applied, thermally fused acrylic or polyester powder coating for corrosion protection r o; : x2 The CWMB1 meets the intent and provides compliance with '°' 'o • ` ` -_ those codes requiring mounting HVAC equipment above ground level PLEASE NOTE a The Wall Bracket load capacity can only be assured if the installation is carried out properly (see drawing A) Drawing B illustrates an improper installation 2 Make sure the chosen installation location meets with specified requirements and wall design and construction is suitable als anc and har strong dware enouare gh the to hold respons the brackets and associated equipment loads Anchors and related mounting 440 Ibs mater ibility of the installer 3 Avoid mounting the brackets and attached load on weak walls. 9 soft siding. veneer panels. perforated bricks / blocks or other A insufficient mounting surfaces. h It is the responsibility of the Project Engineer and/or the Installing Contractor / Dealer to specify furnish. and install a x b any anchor or attachment materials required for the wall construction at the selected mounting location We are not 20.47" x 15.75" responsible for any installation faults or defects c It is strongly recommended to have the installation periodically inspected by a skilled technician ASSEMBLY Notes: 02011 MITSUBISHI Et ECTRIC & ELECTRONICS, INC V DIMENSIONS: CWMB1 /r 1 j .O, 0 . 1 , i, , hl ^ I i tx l / • >p .Pi ' J ' I d '` r � ., x.e ,.../... i � . Self Wong r • .1.' a Class &H Inc Plated steel V \!rD • 9 PWlcrf MR nut. wMte ldN74741 SUM. whhe. T1.11411)(154' (1504014) T.E. M8x90' I ' t l HEAVY DUTY WALL BRACKETS -;.- Mtk ME COOLING $ HEATING PARTNER L ve Better 3400 Lawrencewne Suwanee Rd Suwanee. GA 30024 Tele 678 - 376-2900 • Fax 800- 889 -9904 To Free 800 -433 -4822 (#3) FORM# CVvM81. 201108 mm 2011 MI TSUBISHI ELECTRIC &ELECTRONICS INC SpeNf icaBonHat. stubjectta change without CoNu. MITSUBISHI ELECTRIC M� ir. SLIT( 1. COOLING & HEATING Split- ductku A/C and Heat Pumps SUBMITTAL DATA: MSZ- FE12NA -8 8 MUZ-FE12NA1 12.000 BTUiH WALL - MOUNTED HEAT PUMP SYSTEM Job Name: Windmill Apartments Location Tigard, OR Date: 1/13/12 Purchaser: The Heat Pump Store Engineer: Submitted to: For rJReference ElApproval ilConstruction System Designation: Schedule No.: GENERAL FEATURES • Highly energy - efficient system that features 92% heating capacity at 5`F. 75% at -4 "F, and 58% at -13'E . . : • Updated sleek, compact indoor unit design e I • Includes Standard. Platinum Deodorizing. and Anti--allergy En- t . • 1 '" f zyme filters for a complete air purifying system • — - -- - - -- Powerful Mode' function permits system to temporarily run at ' a lower/higher temperature with an increased fan speed. which Indoor urn MSL- FE12NA.o I quickly brings the room to the optimum comfort level • Integrated i -see Sensor automatically adjusts the unit's operation* ' f according to temperature differences detected between the floor A and the intake air. ensuring optimum comfort and energy usage • "'' ( w C icier 0 • Hand -held Wireless Remote Controller °taloa Unit MwZ- FE12NA1 • Base heater is available as an option • Limited warranty: five years on parts and defects and seven years on compressors OPERATING RANGE OPTIONAL ACCESSORIES "`°0gf""'" 0A000f11y° Outdoor Unit maxim= = 30•F (32 De. T3•F QTCI we 115°F k41YC) 06 cocurj Base Heater (MAC- 640BH -U) Mwmun OM (19'C> OB. srF (14Cn we 14•F c•ta"cn 043 Drain Socket (MAC-8510S) Mammon SW arc) DO. 62 (te c)1M3 75`F (24•C) DB, WI' iirrc) we ee Indoor Unit "" n Mo .... 70•F Q„CI o6. eo'F OM Y%6 • 13•F ( - 08. -15'F 1.26V) we•• Li Condensate Pump (SI3100 -230; 230V) •• System Ms on a1 .19•F (-26•C)10 avoid ewmstor error. but recovers from CaOut ❑ Replacement Platinum Deodorizing Filter (MAC -308F T) 1 er+o weaMeucaN restate at -13 (25•C) it Replacement Anti- allergy Enzyme Filter (MAC- 418F MERV 8) Indoor Unit Controller Options MCA . . _ . 1 A ❑ Wireless Remote Controller Kit (MHK1) with Remote Controller Fan Motor 0.76 F.L A (MRCH1). Wireless Receiver (MIFH1.). and cable (MRC1)• Airflow ❑ Setback down to 50`F when used with MRCH1 Remote Controller Cooling (Lo - Med - Hi • Powerful) ..162 - 226 - 381 -410 Dry CFM ❑ Portable Central Controller (MCCH1: for use with Wireless Remote 144 - 202 - 350 • 367 Wet CFM Controller Kit MHK1)' Heating (Lo - Med - Hi - Powerful) .166 - 240 - 399 - 420 Dry CFM o Outdoor Air Sensor (MOS1; for use with Remote Controller (MRCH1), Sound Pressure Level Wireless Remote Controller Kit (MHK1) and Portable Central Cooling (Lo - Med - Hi - Powerful) .. 22 - 33 - 43 - 45 dB(A) • Controller (MCCH1)' Heating (Lo - Med - Hi - Powerful) 22 33 - 43 - 44 dB(A) bee s tx'Htd ex 'transom on eact∎ °Fenn DIMENSIONS UNIT INCHES / MM ❑ Wall- mounted Wired Remote Controller (PAR-21MAA. req. MAC- 3971F) W 31 ❑ MA Contact Terminal Interface (MAC- 3971F) D 10 -1/8 / 257 ❑ M -NET Control Adapter (MAC- 3991F) H 11 - 5/8 / 295 ❑ Remote Temperature Sensor (M21 •JKO.307) o Lockdown Bracket for Hand -held Controller (RCMKP1CB) Weight 27 lbs. 1 12 kg Cooling" External Finish . . .. . Munsell No. 1.OY 9.2 / 0.2 Field Drainpipe Size 0.1) 518' l 15.88 mm Rated Capacity . .. . 12,000 Btu/h Remote Controller Wireless Minimum Capacity ..... .... 2,800 Btu/h Outdoor Unit SEER ... . . 23.0 BtumlW Total Input. .....930 W Compressor DC Inverter-driven Twin - Rotary MCA . - . . A Heating at 47' F• Fan Motor 056 F.L.A. Rated Capacity .. 13.600 Btu/h Sound Pressure Level Minimum Capacity .. 3.000 Btulh Cooling . . .48 dB(A) I ISM- - . 10.6 Btu/h/W Heating 49 dB(A) Total Input ...950 W Heating at 17° F' DIMENSIONS INCHES / MM Rated Capacity 7900Btu/h W 31 - v2 /80C Rated total Input . . 750 W D 11 -1/4 i 286 Maximum Capacity .13.600 Bluth H 21 - /8 / 549 Maximum Total Input 1 780 W • Relent) CorxMwne tCooiny,) - indoor 80'F (27•CI 06.67 (19•C) WB: outdoor 951' Weight . .. . . .80 lbs / 36 kg (35•CI OB 75Y (24°C1 wB External Finish .. Munsell No. 3.OY 7 8 / 1 1 IHeebq at47°F) indoor MK OK) 06. GM nrct we akmor 47F tegoe •.43•FeMWe Refrigerant Type R410A o- esng at 1mi . naxr 7o•F (21•cl toe isOW (16•C, we. outdoor 1rF t De. ts•Ft4 C) a Refrigerant Pipe Size O.D. Heating at 5° F Gas Side ..... . .. ... .. .. ... 3/8• / 9 52 mm Maximum Capacity .. . 12.500 Btu/h liquid Side. . . . . 1W/6.35 mm Electrical Requirements Max. Refrigerant Pipe Length.. 65' I 20 m Power Supply . 208 1 230V, 1- Phase, 60 Hz Max. c ant Pipe Height Difference 40' 1 12 in Breaker Size .. .15 A Conne Method Flared Voltage Indoor - Outdoor S1-52 . . . .. AC 208 / 230V Q I & R Indoor • Outdoor S2 -S3 . DC 12 -24V Wireless Remote Controller ... DC e) 2011 MITSUBISHI ELECTRIC s ELECTRONICS. INC. DIMENSIONS: MSZ- FEI2NA -8 & MUZ FE12NA1 MSZ- FEI2NA -8 Unit: inch 31- : 7/16 X 1 Oblong hole 7116 X 13/16 Oblong hole 30-718 1/2 2 - 112 : t: : 7 _ I Installation plate Y � • • I _ MIMI Indoor uni -1 : •• /1 n Air in Wall hole 02-9/16 / 0 Installation r ate I - 11 _ 2 7 -1116 - 1 11 1 1 P. _ I 1 -1 I6 I i , ' 0 t4 m ^? Th -- ` .I - Drain c r Insulation 01-3/8 0.0 M - t' -` Limed Ltd Ime 0114 19-11/16 (Flared connection 01/4) Air out 1 _ 1 . a Gas I ne 0318 16 -15/16 (Flared connection 03/8) Drain base Insulation al-1/8 O D Connected part 05/8 O.D MUZ- FE12NA1 Unit: inch Drain hole 01 -5/0- • t At j Dra REQUIRED S P AC E 9as (S y open 4 mc3■ ix more i wthout any obstruction .n front .- and on both sides of the unit 1 ' .. „ ,,,. Ai' n b n d i m r A •II o 0 mow / 149/119 ''O 441 �� 1 2- 318 a 13/1 8 Oval tale 1 18 7 7 I _ � �e handle Illllminil iniiiiiillllllmiiiiii 1 29f32 _ 11- 111 . ini IIIIIIIIIIIIIIIIIIIIIIIIIIIIilllllllllil 1 - _ Open two soles of lee. IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII nght. « rear sole. . IIIIIIIIiIIIIIIIIIIIIIIIIIIIIIIIIIIIIM C4 IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII e IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII " ""I " "°IIIIIIIIIIIIIIIIIIIIIHII , aluminium oN1 1.29132 Liquid p+pe t;0- (flared) Gas pipe 3/8 (hared) 19.nne 31-1/2 2 -23132 62313 A MrISUBISHI AMR! CERTIFIED . - � COOLING ` HEATING PARTNER L.ve Better . " .., GUS 3400 Law Su renoevAe wanee Rd Smoot, GA 30024 n tertek Tele: 678. 376-2900 • Fax: 800.889.9904 Toll Free 800.433 -4822 (#3) ewe rnehvac corn 0 2011 # ITSUBISHI ELECTR IC &ELECTRONICS INC Specifications are subject to change without notice. FLOOR PLAN Two Bedrooms with Two Baths Approx. 987 Sq.Ft. + 98 Sq.Ft. Storage & Patio = 1085 Sq.Ft. Total Living Space Y O Bath / Q sto rage �1 [` e Living st „ Room ; � Bedroom Patio/ Deck Batlt I � Kitchen [ Bedroom Entry Dining rii Room • ■/\ 1 a i t 1 .. Left Kitchen Floorplan n Batb ® Q x al torsge F ' 1 Bedroom 8 Living �- ,..\ Room At Patio/ t ( ` Deck Bedroom 10 mi Kitchen -- Entry F Dining 2 Room , al Right Kitchen Floorplan Qo V J FRONT "- , It. _AL .... �•- �+�"�� r. - � - -. �- �• ..« �rw'�A►r ` ..r. rte• v.� -M ..� - _ -. ��'- - -- _ ^• -..�.r _� �� ...�r� •. . .I•'�' _-......- -. --_. ` .ter ..... ... .. - '" ... .ti. K. v w-.�- _.._ "- �_� -....... w . a � --ter --- l Vii • It =J . . • • .. ter BACK e IN, , . .0. & ill .1. ft ..11. . •.._. _. .... .... IP ..r. I — . .... , • .. .. . ' ,.• , ,, ; _f , ' i;i ' - ..r- ....• - -.. . - ..-..._ 4...... -.7...... .... 1 111.1.•,. • " - ,.. . illiir . s • f I, - .... ' .1111111111111111111.111p II* lalt ..- • ' 3 ". lir • le . _.....- . ..k. 42 lik, 4212 t.1 iiiiiii/ft • ... • , • . . - , . . . ,-,..........-„,.......4.22,....--••••■•-,-........................................4,...........,,,...,,,, , .. 1 1 . - i . 4 , .. .....' '''''''"' '• . f',4. ,,!.,,,,-.. „ _ ......„, 44 v.... --4.,••2■22.0.,......,-•-•'■-...-.411 „,b, ,. ' i i .,- _ ..# . . ... 4 ..4 4 • t .il . ' . . - .. ',... "- 1 .. -ii . • . _ . . -- ii- • '- -- --- - - imighl ...- .,...., ... .........._ . . . . ..........-.-- .• . . ir . Ili_ ... _ . . . fl E C &,1 JAN 1 i Project Plan: Windmill Apartments Ductless Heat Pump Installati ICY 3 2 014 Submitted by: Jonathan Moscatello, The Heat Pump Store G '1SION Date: 1/13/12 Address: 10587 SW Tigard St, Tigard, OR 97223 Owners: Jim and Sharon Richards Description: There are 20 identical structures at the property. Each structure is two stories tall, with two apartments on the CITyaF ARD loweJ' level and two on the upper level. SEE ATTACHED FLOOR Approved .� [ N. Conditionally Approved [ See Letter to: Follow [ %tie will install one ductless heat pump system (see attached Att• hed 1 Permit Number , _ V--- - doe 4 bmittal, Mitsubishi MUZ /MSZ- FE12NA) for each apartment. Ad. ess• APAP WAN By: 4 Date: r T hese are split systems, with an indoor "head" and an outdoor heat pump unit. The indoor and outdoor units are Approved pia Shall be on job site connected by BUNDLE containing two small refrigerant lines, a power and communications wire, and a condensate drain. OFFICE COPY UP I Installation Plan: X - 7S ) , OUTDOOR HEAT PUMP UNIT: The outdoor heat pump for each unit will be attached to the wall of each structure, just opposite of the storage unit for each apartment, using a manufacturer approved bracket (see BRACKET submittal, see exterior FRONT and BACK photos). The heat pumps will be installed approximately 12 inches above the ground level. They will be supplied with a 230V single phase electric circuit per the manufacturer's specifications using an outdoor disconnect. INDOOR "HEAD ": The indoor "head" unit for each outdoor heat pump will be attached to the living room wall of each apartment (see FLOOR PLAN). It will be connected to the outdoor unit by a so- called "bundle" of refrigerant lines, power /communications wire, and condensation drain line. The "bundle" will travel along the following pathway: from the outdoor unit, the bundle will travel to the nearest foundation vent, and enter into the crawlspace. The bundle will run through the crawlspace and penetrate into the storage unit through the floor. The bundle will run up the wall of the storage unit inside specialized conduit call "line cover ". At about head height, one of the sets of refrigerant lines, one power /communication wore and condensate drain will penetrate the storage unit wall and terminate at the head in the living room. All connections to the "head" will be made. Again the penetration will be sealed with fire caulk. The remainder of the bundle will continue upward toward the second story and the head in the living room of the upper unit. The remaining items in the bundle will penetrate the ceiling of the lower storage unit, enter the upper unit, and continue to the head for the upper unit. Again, connections will be made and penetrations sealed with fire caulk. I t MITSUBISHI ELECTRIC Mir.SUM C O O L I N G & HEATING Split - ductless A/C and Heat Pumps SUBMITTAL DATA: CWMB1.' HEAVY DUTY PAINTED STEEL WALL BRACKETS Job Name: Winmill Apartments Location: Tigard, OR' Date: 1/13/12 Purchaser: The Heat Pump Store Engineer: Submitted to: For LiReference LApproval ElConstruction System Designation: Schedule No.: GENERAL FEATURES ASSEMBLY INSTRUCTION • The CWM61 wall brackets are designed to provide a 1 Fit the vertical component to the honzontat arm by means to mount the Mr Slim M- Series, S- Seres. P- Series inserting two TEM8X90 screws with four lock washers and CITY MULTI PUMY -Senes outdoor units on a suitable four flat washers + two self - locking nuts into the bracket wall or structure and keep the equipment off the ground components as illustrated The CWMB1 consists of two independently mounted wall brackets to allow proper leveling and support SELF - LOCKING WASHERS 1 WASHERS t 8X90 SCREWS NUTS • The formed mild carbon steel two piece bracket is a (D x4 J; x8 © x8 x4 rugged. fabricated, heavy duty accessory constructed for �it1 long reliable service life. The bracket is finished with an electrostatically applied, thermally fused acrylic or polyester powder coating for corrosion protection r o; : x2 The CWMB1 meets the intent and provides compliance with '°' 'o • ` ` -_ those codes requiring mounting HVAC equipment above ground level PLEASE NOTE a The Wall Bracket load capacity can only be assured if the installation is carried out properly (see drawing A) Drawing B illustrates an improper installation 2 Make sure the chosen installation location meets with specified requirements and wall design and construction is suitable als anc and har strong dware enouare gh the to hold respons the brackets and associated equipment loads Anchors and related mounting 440 Ibs mater ibility of the installer 3 Avoid mounting the brackets and attached load on weak walls. 9 soft siding. veneer panels. perforated bricks / blocks or other A insufficient mounting surfaces. h It is the responsibility of the Project Engineer and/or the Installing Contractor / Dealer to specify furnish. and install a x b any anchor or attachment materials required for the wall construction at the selected mounting location We are not 20.47" x 15.75" responsible for any installation faults or defects c It is strongly recommended to have the installation periodically inspected by a skilled technician ASSEMBLY Notes: 02011 MITSUBISHI Et ECTRIC & ELECTRONICS, INC V DIMENSIONS: CWMB1 /r 1 j .O, 0 . 1 , i, , hl ^ I i tx l / • >p .Pi ' J ' I d '` r � ., x.e ,.../... i � . Self Wong r • .1.' a Class &H Inc Plated steel V \!rD • 9 PWlcrf MR nut. wMte ldN74741 SUM. whhe. T1.11411)(154' (1504014) T.E. M8x90' I ' t l HEAVY DUTY WALL BRACKETS -;.- Mtk ME COOLING $ HEATING PARTNER L ve Better 3400 Lawrencewne Suwanee Rd Suwanee. GA 30024 Tele 678 - 376-2900 • Fax 800- 889 -9904 To Free 800 -433 -4822 (#3) FORM# CVvM81. 201108 mm 2011 MI TSUBISHI ELECTRIC &ELECTRONICS INC SpeNf icaBonHat. stubjectta change without CoNu. MITSUBISHI ELECTRIC M� ir. SLIT( 1. COOLING & HEATING Split- ductku A/C and Heat Pumps SUBMITTAL DATA: MSZ- FE12NA -8 8 MUZ-FE12NA1 12.000 BTUiH WALL - MOUNTED HEAT PUMP SYSTEM Job Name: Windmill Apartments Location Tigard, OR Date: 1/13/12 Purchaser: The Heat Pump Store Engineer: Submitted to: For rJReference ElApproval ilConstruction System Designation: Schedule No.: GENERAL FEATURES • Highly energy - efficient system that features 92% heating capacity at 5`F. 75% at -4 "F, and 58% at -13'E . . : • Updated sleek, compact indoor unit design e I • Includes Standard. Platinum Deodorizing. and Anti--allergy En- t . • 1 '" f zyme filters for a complete air purifying system • — - -- - - -- Powerful Mode' function permits system to temporarily run at ' a lower/higher temperature with an increased fan speed. which Indoor urn MSL- FE12NA.o I quickly brings the room to the optimum comfort level • Integrated i -see Sensor automatically adjusts the unit's operation* ' f according to temperature differences detected between the floor A and the intake air. ensuring optimum comfort and energy usage • "'' ( w C icier 0 • Hand -held Wireless Remote Controller °taloa Unit MwZ- FE12NA1 • Base heater is available as an option • Limited warranty: five years on parts and defects and seven years on compressors OPERATING RANGE OPTIONAL ACCESSORIES "`°0gf""'" 0A000f11y° Outdoor Unit maxim= = 30•F (32 De. T3•F QTCI we 115°F k41YC) 06 cocurj Base Heater (MAC- 640BH -U) Mwmun OM (19'C> OB. srF (14Cn we 14•F c•ta"cn 043 Drain Socket (MAC-8510S) Mammon SW arc) DO. 62 (te c)1M3 75`F (24•C) DB, WI' iirrc) we ee Indoor Unit "" n Mo .... 70•F Q„CI o6. eo'F OM Y%6 • 13•F ( - 08. -15'F 1.26V) we•• Li Condensate Pump (SI3100 -230; 230V) •• System Ms on a1 .19•F (-26•C)10 avoid ewmstor error. but recovers from CaOut ❑ Replacement Platinum Deodorizing Filter (MAC -308F T) 1 er+o weaMeucaN restate at -13 (25•C) it Replacement Anti- allergy Enzyme Filter (MAC- 418F MERV 8) Indoor Unit Controller Options MCA . . _ . 1 A ❑ Wireless Remote Controller Kit (MHK1) with Remote Controller Fan Motor 0.76 F.L A (MRCH1). Wireless Receiver (MIFH1.). and cable (MRC1)• Airflow ❑ Setback down to 50`F when used with MRCH1 Remote Controller Cooling (Lo - Med - Hi • Powerful) ..162 - 226 - 381 -410 Dry CFM ❑ Portable Central Controller (MCCH1: for use with Wireless Remote 144 - 202 - 350 • 367 Wet CFM Controller Kit MHK1)' Heating (Lo - Med - Hi - Powerful) .166 - 240 - 399 - 420 Dry CFM o Outdoor Air Sensor (MOS1; for use with Remote Controller (MRCH1), Sound Pressure Level Wireless Remote Controller Kit (MHK1) and Portable Central Cooling (Lo - Med - Hi - Powerful) .. 22 - 33 - 43 - 45 dB(A) • Controller (MCCH1)' Heating (Lo - Med - Hi - Powerful) 22 33 - 43 - 44 dB(A) bee s tx'Htd ex 'transom on eact∎ °Fenn DIMENSIONS UNIT INCHES / MM ❑ Wall- mounted Wired Remote Controller (PAR-21MAA. req. MAC- 3971F) W 31 ❑ MA Contact Terminal Interface (MAC- 3971F) D 10 -1/8 / 257 ❑ M -NET Control Adapter (MAC- 3991F) H 11 - 5/8 / 295 ❑ Remote Temperature Sensor (M21 •JKO.307) o Lockdown Bracket for Hand -held Controller (RCMKP1CB) Weight 27 lbs. 1 12 kg Cooling" External Finish . . .. . Munsell No. 1.OY 9.2 / 0.2 Field Drainpipe Size 0.1) 518' l 15.88 mm Rated Capacity . .. . 12,000 Btu/h Remote Controller Wireless Minimum Capacity ..... .... 2,800 Btu/h Outdoor Unit SEER ... . . 23.0 BtumlW Total Input. .....930 W Compressor DC Inverter-driven Twin - Rotary MCA . - . . A Heating at 47' F• Fan Motor 056 F.L.A. Rated Capacity .. 13.600 Btu/h Sound Pressure Level Minimum Capacity .. 3.000 Btulh Cooling . . .48 dB(A) I ISM- - . 10.6 Btu/h/W Heating 49 dB(A) Total Input ...950 W Heating at 17° F' DIMENSIONS INCHES / MM Rated Capacity 7900Btu/h W 31 - v2 /80C Rated total Input . . 750 W D 11 -1/4 i 286 Maximum Capacity .13.600 Bluth H 21 - /8 / 549 Maximum Total Input 1 780 W • Relent) CorxMwne tCooiny,) - indoor 80'F (27•CI 06.67 (19•C) WB: outdoor 951' Weight . .. . . .80 lbs / 36 kg (35•CI OB 75Y (24°C1 wB External Finish .. Munsell No. 3.OY 7 8 / 1 1 IHeebq at47°F) indoor MK OK) 06. GM nrct we akmor 47F tegoe •.43•FeMWe Refrigerant Type R410A o- esng at 1mi . naxr 7o•F (21•cl toe isOW (16•C, we. outdoor 1rF t De. ts•Ft4 C) a Refrigerant Pipe Size O.D. Heating at 5° F Gas Side ..... . .. ... .. .. ... 3/8• / 9 52 mm Maximum Capacity .. . 12.500 Btu/h liquid Side. . . . . 1W/6.35 mm Electrical Requirements Max. Refrigerant Pipe Length.. 65' I 20 m Power Supply . 208 1 230V, 1- Phase, 60 Hz Max. c ant Pipe Height Difference 40' 1 12 in Breaker Size .. .15 A Conne Method Flared Voltage Indoor - Outdoor S1-52 . . . .. AC 208 / 230V Q I & R Indoor • Outdoor S2 -S3 . DC 12 -24V Wireless Remote Controller ... DC e) 2011 MITSUBISHI ELECTRIC s ELECTRONICS. INC. DIMENSIONS: MSZ- FEI2NA -8 & MUZ FE12NA1 MSZ- FEI2NA -8 Unit: inch 31- : 7/16 X 1 Oblong hole 7116 X 13/16 Oblong hole 30-718 1/2 2 - 112 : t: : 7 _ I Installation plate Y � • • I _ MIMI Indoor uni -1 : •• /1 n Air in Wall hole 02-9/16 / 0 Installation r ate I - 11 _ 2 7 -1116 - 1 11 1 1 P. _ I 1 -1 I6 I i , ' 0 t4 m ^? Th -- ` .I - Drain c r Insulation 01-3/8 0.0 M - t' -` Limed Ltd Ime 0114 19-11/16 (Flared connection 01/4) Air out 1 _ 1 . a Gas I ne 0318 16 -15/16 (Flared connection 03/8) Drain base Insulation al-1/8 O D Connected part 05/8 O.D MUZ- FE12NA1 Unit: inch Drain hole 01 -5/0- • t At j Dra REQUIRED S P AC E 9as (S y open 4 mc3■ ix more i wthout any obstruction .n front .- and on both sides of the unit 1 ' .. „ ,,,. Ai' n b n d i m r A •II o 0 mow / 149/119 ''O 441 �� 1 2- 318 a 13/1 8 Oval tale 1 18 7 7 I _ � �e handle Illllminil iniiiiiillllllmiiiiii 1 29f32 _ 11- 111 . ini IIIIIIIIIIIIIIIIIIIIIIIIIIIIilllllllllil 1 - _ Open two soles of lee. IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII nght. « rear sole. . IIIIIIIIiIIIIIIIIIIIIIIIIIIIIIIIIIIIIM C4 IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII e IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII " ""I " "°IIIIIIIIIIIIIIIIIIIIIHII , aluminium oN1 1.29132 Liquid p+pe t;0- (flared) Gas pipe 3/8 (hared) 19.nne 31-1/2 2 -23132 62313 A MrISUBISHI AMR! CERTIFIED . - � COOLING ` HEATING PARTNER L.ve Better . " .., GUS 3400 Law Su renoevAe wanee Rd Smoot, GA 30024 n tertek Tele: 678. 376-2900 • Fax: 800.889.9904 Toll Free 800.433 -4822 (#3) ewe rnehvac corn 0 2011 # ITSUBISHI ELECTR IC &ELECTRONICS INC Specifications are subject to change without notice. FLOOR PLAN Two Bedrooms with Two Baths Approx. 987 Sq.Ft. + 98 Sq.Ft. Storage & Patio = 1085 Sq.Ft. Total Living Space Y O Bath / Q sto rage �1 [` e Living st „ Room ; � Bedroom Patio/ Deck Batlt I � Kitchen [ Bedroom Entry Dining rii Room • ■/\ 1 a i t 1 .. Left Kitchen Floorplan n Batb ® Q x al torsge F ' 1 Bedroom 8 Living �- ,..\ Room At Patio/ t ( ` Deck Bedroom 10 mi Kitchen -- Entry F Dining 2 Room , al Right Kitchen Floorplan Qo V J FRONT "- , It. _AL .... �•- �+�"�� r. - � - -. �- �• ..« �rw'�A►r ` ..r. rte• v.� -M ..� - _ -. ��'- - -- _ ^• -..�.r _� �� ...�r� •. . .I•'�' _-......- -. --_. ` .ter ..... ... .. - '" ... .ti. K. v w-.�- _.._ "- �_� -....... w . a � --ter --- l Vii • It =J . . • • .. ter BACK e IN, , . .0. & ill .1. ft ..11. . •.._. _. .... .... IP ..r. I — . .... , • .. .. . ' ,.• , ,, ; _f , ' i;i ' - ..r- ....• - -.. . - ..-..._ 4...... -.7...... .... 1 111.1.•,. • " - ,.. . illiir . s • f I, - .... ' .1111111111111111111.111p II* lalt ..- • ' 3 ". lir • le . _.....- . ..k. 42 lik, 4212 t.1 iiiiiii/ft • ... • , • . . - , . . . ,-,..........-„,.......4.22,....--••••■•-,-........................................4,...........,,,...,,,, , .. 1 1 . - i . 4 , .. .....' '''''''"' '• . f',4. ,,!.,,,,-.. „ _ ......„, 44 v.... --4.,••2■22.0.,......,-•-•'■-...-.411 „,b, ,. ' i i .,- _ ..# . . ... 4 ..4 4 • t .il . ' . . - .. ',... "- 1 .. -ii . • . _ . . -- ii- • '- -- --- - - imighl ...- .,...., ... .........._ . . . . ..........-.-- .• . . ir . Ili_ ... _ . . .