Loading...
Specifications 7z/yo 61,/ 3avt Rd .2608- O 2g RECEIVED • . . ., _ _ ` - AUG 2 5 2008 r _ CITY OF TIGARD _ BUILDING DIVISION • . `l. .:AP, M+S .-(34-6 Cl ... Fire Protection by Computer Design • AFP SYSTEMS INC 19435 SW 129TH. AVE. TUALATIN,OR. 503 - 692 -9284 Job Name : ASSOCIATED BUSINESS Building : Location : AREA #1 System : Contract • : 8134 Data File : Associat.WX1 Computer Programs by Hydratec Inc. Route 111 Windham N H USA 03087 SEP-- 03- 2008(WED) 14:14 P. 008/015 • • AFP SYSTEMS INC • Page 1 . ASSOCIATED BUSINESS- OVERHEAD PIPING • Date 062208 • • HvcJraul.i.c Design Information Sheet • Name - ASSOCIATED BUSINESS SYSTEMS - OVERHEAD SYSTEMS Date - 8 -22 -08 Location - AREA #2 Building - System No. - Contractor - AFP SYSTEMS INC Contract No. - 8134 Calculated By - R.COLE Drawing No. - 1 Construction: ( ) Combustible (x) Non - Combustible Ceiling Height - 20' • Occupancy - BALANCING WITH RACK SYSTEM • S (x) NFPA 13 ( ) Lt. Haz. Ord.Hae..Gp. ( ) 1 ( ) 2 ( 1 3 (X) Ex Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve S Other T Specific Ruling Made By Date M Area of Sprinkler O - 2500 System Type Sprinkler. /Nozzle Density. - .2900 (x) Wet Make TYCO D Area Per Sprinkler - 85.00 ( ) Dry Model TYR E Elevation at Highest Outlet - 25.00 ( ) Deluge Size 1/2 S Hose Allowance - Inside - ( ) Predctiori K- Factor 5.6 I Rack Sprinkler Allowance - 228 ( I Other Temp.Rat.165 G Hose Allowance = Outside - 500 N Note BALANCED WITH RACK SYSTEM NODE POINT 12 Calculation Flow Required - 1464.61 Press Required - 66.758 Summary C- Factor Used: 120 Overhead 140 Underground W Water Flow Test: Pump Data: Tank or Reservoir: A Date of. Test - Cap. - T Time of Test - Rated Cap.- El.ev'•- E Static Press - 119 @ Press - R Residual Press - 115 Elev. - Well • Flow - 6190 Proof Flow S Elevation - 0 U P Location - 8 SW BONITA ROAD P L Source of Information - TVF&R WATER DEPT. Y C Commodity I -IV Class I -IV Location O Storage Ht. 18' Area Aisle W. M Storage Method: Solid Piled Palletized Rack M - -( j Row ( ) Conven. Pallet ( ) Auto. Storage ( ) Encap. • S R ( ) Double Row ( ) Slave Pal lei, ( I Solid Shelf ( ) Non T A ( ) Mult. Row ( ) Open Shelf O C R K Flue Spacing Clearance:Storage to Ceiling A Longitudinal Transverse G _ or_ E Hizontal Barriers Provided: • • • Computer Programs by Hydratec Inc. Route 111 Windham N.W. USA 03087 Water Supply Curve (C) • • AFP SYSTEMS INC Page 1 ASSOCIATED BUSINESS Date 082208 - City Water Supply: Demand: C1 - Static Pressure 119 D1 - Elevation 6.063 C2 - Residual Pressure 115 D2 - System Flow 228.133 C2 - Residual Flow 6190 D2 - System Pressure 60.966 Hose Adj City ) Hose Demand ) D3 - System Demand 228.133 Safety Margin 58 025 150 140 130 p 120 Cl o C2 R 110 E 100 S 90 S 80 . U 70 D2 R 60 E 50 40 30 20 10 ,. ..D1. . 1 ... . , . . • . . . . . . . • . . . , 750 1500 2250 3000 3750 4500 5250 6000 6750 FLOW (NA1.85) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary • • AFP SYSTEMS INC Page 2 • ASSOCIATED BUSINESS Date 082208 Fitting Legend Abbrev. Name 1 /2 ' 1 1% 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24 _ B Generic Butterfly Valve 0 0 0 0 0 0 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 T 90' Flow Thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Z Generic Flow Switch 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Zac Ames 2000SS Fitting generates a Fixed Loss Based on Flow • • Computer Programs by Hydratec Inc. Route 111 Windham N H. USA 03087 Pressure / Flow Summary - STANDARD AFP.SYSTEMS INC Page 3 ASSOCIATED BUSINESS Date 082208 • Node ' Elevation K -Fact Pt Pn Flow Density Area Press No. Actual Actual R 1 14.0 8 15 0 na 30.98 0 3 100 15.0 2 14 0 8 15.07 na 31 06 0.3 100 15.0 3 14.0 8 15 32 na 31 32 0.3 100 15.0 4 14.0 8 15.86 na 31.86 0.3 100 15.0 5 14 0 8 16.79 na 32.78 0.3 100 15.0 . 6 14 0 8 18 21 na 34 14 0.3 100 15.0 7 14.0 8 20.25 na 36 0 0.3 100 15 0 8 18.5 24 61 na 9 18 5 28 4 na 10 18.5 35.84 na 11 18.5 48 49 na 12 18.5 52.76 na TEST 0.0 60 97 na The maximum velocity is 20.03 and it occurs in the pipe between nodes 7 and 8 Computer Programs by Hydratec Inc Route 111 Windham N H USA 03087 Final Calculations - Hazen - Williams AFP SYSTEMS INC Page 4 ' ASSOCIATED BUSINESS Date 082208 • Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** Point Qt Pf /UL Eqv Ln. Total Pf Pn *P -6 1 30.98 2.157 0.0 8.000 15.000 K Factor = 8.00 to 120 0.0 0.0 0.0 2 30.98 0.0088 0.0 8 000 0.070 Vel = 2.72 2 31.06 2.157 0.0 8.000 15.070 K Factor = 8.00 to 120 0.0 0.0 0.0 3 62.04 0.0315 0.0 8.000 0.252 Vel = 5.45 3 31.31 2.157 0.0 8.000 15.322 K Factor = 8.00 to 120 0 0 0.0 0.0 4 93.35 0.0672 0.0 8.000 0.538 Vel = 8.20 4 31.87 2.157 0.0 8.000 15.860 K Factor = 8.00 to 120 0.0 0.0 0.0 5 125.22 0.1158 0.0 8.000 0.926 Vel = 10.99 5 32.77 2.157 0.0 8.000 16.786 K Factor = 8.00 to 120 0.0 0.0 0.0 6 157.99 0.1780 0.0 8.000 1.424 Vel = 13.87 6 34.14 2.157 0.0 8.000 18.210 K Factor = 8.00 to 120 0.0 0.0 0.0 - 7 192.13 0.2555 0.0 8.000 2.044 Vel = 16.87 7 36.00 2.157 1E 6.153 11.790 20.254 K Factor = 8.00 to 120 0.0 6.153 -1.949 8 228.13 0.3511 0.0 17.943 6.300 Vel = 20.03 8 0.0 2.157 1E 6.153 4.660 24.605 to 120 0.0 6.153 0.0 9 228.13 0.3512 0 0 10.813 3.797 Vel = 20.03 9 0.0 2.157 1T 12.307 8.870 28.402 to 120 0.0 12.307 0.0 10 228.13 0.3511 0.0 21.177 7.435 Vel = 20.03 10 0.0 3.26 5E 47.038 159.080 35.837 to 120 2T 40.319 110.205 0.0 11 228.13 0.0470 1B 13.44 269.285 12.652 Vel = 8.77 1Z 9.408 11 0.0 4.26 2E 26.334 91.580 48.489 to 120 1 Zac 0.0 26.334 2.768 12 228.13 0.0128 0.0 117.914 1.505 Vel = 5.14 12 0.0 6.16 1E 20.084 100.000 52.762 to 140 0 0 20.084 8.012 • TEST 228.13 0.0016 0.0 120.084 0.192 Vel = 2 46 0.0 228.13 60.966 K Factor = 29.22 Computer Programs by Hydratec Inc. Route 111 Windham N H USA 03087 • • • • • • • - Fire Protection by Computer Design AFP SYSTEMS INC 19435 SW 129TH. AVE. TUALATIN,OR. 503- 692 -9284 Job Name : ASSOCIATED BUSINESS- OVERHEAD PIPING Building : Location : AREA #2 System Contract : 8134 Data File : Associat WX2 Computer Programs by Hydratec Inc Route 111 Windham N.H. USA 03087 Water Supply Curve (C) . AFP SYSTEMS INC Page 1 ASSOCIATED BUSINESS- OVERHEAD PIPING Date 082208 City Water Supply: Demand: C1 - Static Pressure 119 D1 - Elevation 10.827 C2 - Residual Pressure 115 D2 - System Flow 1464.62 C2 - Residual Flow 6190 D2 - System Pressure 66.758 Hose (Adj City ) Hose Demand ) D3 - System Demand 1464.62 Safety Margin 51.964 150 140 130 : Cl p 120 4 _ C2 0 R 110 E 100: S 90 s 80 • • U 70 D2 R 60 E 50 40 30 20 - 10 ° D1 1 750 1500 2250 3000 3750 4500 5250 6000 6750 FLOW ( N A 1 85 ) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary • • AFP SYSTEMS INC Page 2 ASSOCIATED BUSINESS- OVERHEAD PIPING Date 082208 Fitting Legend Abbrev. Name 1/2 % 1 1% 1% 2 2% 3 31/2 4 5 6 8 10 12 14 16 18 20 24 E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 T 90' Flow Thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zac Ames 2000SS Fitting generates a Fixed Loss Based on Flow • Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Pressure / Flow Summary - STANDARD AFP SYSTEMS INC Page . 3 ASSOCIATED BUSINESS- OVERHEAD PIPING Date 082208 Node Elevation K -Fact Pt Pn Flow Density Area Press No. Actual Actual Req 33 25.0 8 9 51 na 24.67 0.29 85 7.0 34 25.0 8 9.9 na 2517 0.29 85 7.0 35 25.0 8 10.6 na 26.04 0.29 85 7.0 36 25.0 8 12.11 na 27.84 0 29 85 7.0 29 25.0 8 9 55 na 24 73 0.29 85 7.0 30 25.0 8 9 95 na 25.23 0.29 85 7 0 31 25.0 8 10.65 na 26.11 0.29 85 7.0 32 25.0 8 12.17 na 27.91 0.29 85 7.0 25 25.0 8 9 65 na 24.85 0.29 85 7.0 26 25.0 8 10.05 na 25 36 0 29 85 7 0 27 25.0 8 10 76 na 26.24 0.29 85 7.0 28 25.0 8 12.29 na 28 05 0.29 85 7 0 21 25.0 8 9 82 na 25 07 0.29 85 7.0 22 25.0 8 10.22 na 25.58 0.29 85 7.0 23 25.0 8 10 94 na 26 46 0 29 85 7 0 24 25.0 8 12 5 na 28.29 0.29 85 7.0 17 25.0 8 10.07 na . 25 39 0 29 85 7.0 18 25.0 8 10.49 na 25.91 0.29 85 7.0 19 25.0 8 11 22 na 26.8 0.29 85 7 0 20 25.0 8 12.82 na 28.65 0.29 85 7.0 13 25.0 8 10.43 na 25.84 0.29 85 7.0 14 25.0 8 10.86 na 26.36 0.29 85 7.0 15 25.0 8 11.62 na 27.27 0.29 85 7 0 16 25.0 8 13.27 na 29.14 0.29 85 7.0 1 25.0 8 9 49 na 24.65 0.29 85 7 0 2 25.0 8 9.89 na 2516 0.29 85 7.0 3 25.0 8 10.58 na 26.03 0.29 85 7 0 4 25.0 8 12.1 na 27.83 0.29 85 7.0 5 23.0 20.0 na 6 23.0 20.02 na 7 23.0 20.11 na - 8 23.0 20 3 na 9 23.0 20 62 na 10 23.0 21.11 na 11 23.0 21.81 na 12 23.0 54 04 na 228 0 TEST 0.0 66.76 na 500.0 The maximum velocity is 16.58 and it occurs in the pipe between nodes 11 and 12 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen - Williams AFP SYSTEMS INC Page 4 ' ASSOCIATED BUSINESS- OVERHEAD PIPING ' Date 082208 . - Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** Point Qt Pf /UL Eqv. Ln. Total Pf Pn *P -6 ........ .... -- - - - --- 33 24.67 1.452 0.0 10 000 9.507 K Factor = 8.00 to 120 0.0 0.0 0.0 34 24.67 0.0394 0.0 10.000 0.394 Vel = 4.78 34 25.17 1.687 0.0 10.000 9 901 K Factor = 8.00 to 120 0.0 0.0 0.0 35 49.84 0.0697 0.0 10.000 0.697 Vel = 7.15 35 26.04 1.687 0.0 10.000 10.598 K Factor = 8.00 to 120 0.0 0.0 0.0 36 75.88 0.1516 0.0 10.000 1.516 Vel = 10.89 36 27.85 1.687 1T 10.044 16.000 12.114 K Factor = 8.00 to 120 0.0 10.044 0.866 6 103.73 0.2704 0.0 26.044 7.042 Vel = 14.89 0.0 103.73 20 022 K Factor = 23.18 *P-9 29 24.73 1.452 0.0 10.000 9.553 K Factor = 8.00 to 120 0.0 0.0 0.0 - 30 24.73 0.0396 0.0 10.000 0.396 Vel = 4.79 30 25.23 1.687 0.0 10.000 9.949 K Factor = 8.00 • to 120 0.0 0.0 0 0 31 49.96 0.0699 0.0 10.000 0.699 Vel = 7.17 31 26.10 1.687 0.0 10.000 10.648 K Factor = 8.00 to 120 0.0 0.0 0.0 32 76.06 0.1524 0.0 10.000 1.524 Vel = 10.92 32 27.92 1.687 1T 10.044 16.000 12.172 K Factor = 8.00 to 120 0.0 10.044 0.866 7 103.98 0.2716 0.0 26.044 7 074 Vel = 14.92 0.0 103.98 20.112 K Factor = 23.19 *P -12 25 24.85 1.452 0.0 10.000 9.651 K Factor = 8.00 to 120 0.0 0.0 0.0 26 24.85 0.0399 0.0 10.000 0.399 Vel = 4 81 26 25.36 1.687 0.0 10.000 10.050 K Factor = 8.00 to 120 0.0 0.0 0.0 27 50.21 0.0707 0.0 10.000 0.707 Vel = 7.21 27 26.24 1.687 0.0 10.000 10.757 K Factor = 8.00 to 120 0.0 0.0 0.0 28 76.45 0.1537 0.0 10.000 1.537 Vel = 10.97 28 28.05 1.687 1T 10.044 16.000 12.294 K Factor = 8.00 to 120 0.0 10.044 0 866 8 104.5 0.2742 0.0 26.044 7 141 Vel = 15.00 Computer Programs by Hydratec Inc. Route 111 Windham N.H USA 03087 Final Calculations - Standard AFP SYSTEMS INC Page 5 - ASSOCIATED BUSINESS- OVERHEAD PIPING Date 082208 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv * * * * * ** Notes * * * * ** Point - Qt Pf /UL Eqv. Ln. Total Pf Pn 0.0 104.50 20.301 K Factor = 23.19 *P -15 21 25.07 1.452 0.0 10.000 9.818 K Factor = 8.00 to 120 0.0 0.0 0.0 22 25.07 0.0406 0.0 10.000 0.406 Vel = 4.86 22 25.58 1.687 0.0 10.000 10.224 K Factor = 8.00 to 120 0.0 0.0 0.0 23 50.65 0.0718 0.0 10.000 0.718 Vel = 7.27 23 26.46 1.687 0.0 10.000 10.942 K Factor = 8.00 to 120 0.0 0.0 0.0 24 77.11 0.1562 0.0 10.000 1.562 Vel = 11.07 24 28.29 1.687 1T 10.044 16.000 12.504 K Factor = 8.00 to 120 0.0 10.044 0.866 9 105.4 0.2785 0.0 26.044 7.254 Vel = 15.13 0.0 105.40 20.624 K Factor = 23.21 *P -18 17 25.39 1.452 0.0 10.000 10.072 K Factor = 8.00 to 120 0.0 0.0 0.0 • 18 25.39 0.0416 0.0 10.000 0.416 Vel = 4 92 18 25.91 1.687 0.0 10.000 10.488 K Factor = 8.00 to 120 0.0 0.0 0.0 19 51.3 0.0735 0.0 10.000 0.735 Vel = 7.36 19 26.80 1.687 0.0 10.000 11.223 K Factor = 8.00 to 120 0.0 0.0 0.0 20 78.1 0.1599 0.0 10.000 1.599 Vel = 11.21 20 28.64 1.687 1T 10.044 16.000 12.822 K Factor = 8.00 to 120 0.0 10.044 0 866 10 106.74 0.2851 0.0 26.044 7.426 Vel = 15.32 0.0 106.74 21.114 K Factor = 23.23 *P-21 13 25.84 1.452 0.0 10.000 10.431 K Factor = 8.00 to 120 0.0 0.0 0 0 14 25.84 0.0429 0.0 10.000 0.429 Vel = 5.01 14 26.36 1.687 0.0 10.000 10.860 K Factor = 8.00 to 120 0.0 0.0 0.0 15 52.2 0.0760 0.0 10.000 0.760 Vel = 7.49 15 27.27 1.687 0.0 10.000 11.620 K Factor = 8.00 to 120 0.0 0.0 0.0 16 79.47 0.1652 0.0 10.000 1.652 Vel = 11.41 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 i • Final Calculations - Standard • AFP SYSTEMS INC Page 6 ASSOCIATED BUSINESS- OVERHEAD PIPING Date 082208 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv * * * * *" Notes * *" " ** Point Qt Pf /UL Eqv Ln. Total Pf Pn 16 29.15 1.687 1T 10.044 16.000 13.272 K Factor = 8.00 to 120 0.0 10.044 0.866 11 108.62 0.2944 0.0 26.044 7.668 Vel = 15.59 • 0.0 108.62 21.806 K Factor = 23.26 *P -24 1 24.65 1.452 0.0 10.000 9.494 K Factor = 8.00 to 120 0.0 0.0 0.0 2 24.65 0.0393 0.0 10.000 0.393 Vel = 4 78 2 25.16 1.687 0.0 10.000 9 887 K Factor = 8.00 to 120 0.0 0.0 0.0 3 49.81 0.0696 0.0 10.000 0.696 Vel = 7.15 3 26.02 1.687 0.0 10.000 10.583 K Factor = 8.00 to 120 0.0 0.0 0.0 4 75.83 0.1515 0.0 10.000 1.515 Vel = 10.88 4 27.83 1.687 1T 10.044 16.000 12.098 K Factor = 8.00 to 120 0.0 10.044 0.866 5 103.66 0.2701 0.0 26.044 7.034 Vel = 14.88 5 0.0 4.26 0.0 8.330 19.998 to 120 0.0 0.0 0.0 • 6 103.66 0.0029 0.0 8.330 0.024 Vel = 2.33 6 103.72 4.26 0.0 8.330 20.022 to 120 0.0 0.0 0.0 7 207.38 0.0108 0.0 8.330 0.090 Vel = 4.67 7 103.98 4.26 0.0 8.330 20.112 to 120 0 0 0.0 0.0 8 311.36 0.0227 0.0 8.330 0.189 Vel = 7.01 8 104.50 4 26 0.0 8.330 20.301 to 120 0.0 0.0 0.0 9 415.86 0.0388 0.0 8.330 0.323 Vel = 9.36 9 105.40 4.26 0.0 8.330 20.624 to 120 0.0 0.0 0.0 10 521.26 0.0588 0.0 8.330 0.490 Vel = 11.73 10 106.74 4.26 0.0 8.330 21.114 to 120 0.0 0.0 0.0 11 628.0 0.0831 0.0 8.330 0 692 Vel = 14.14 11 108.62 4.26 2E 26.334 148.830 21.806 to 120 1T 26.334 52.668 9.740 12 736.62 0.1116 1Zac 0.0 201.498 22.496 Vel = 16.58 12 228.00 6.16 1E 20.084 100.000 54.042 Qa = 228.00 to 140 0.0 20.084 9 961 TEST 964.62 0 0229 0 0 120 084 2.755 Vel = 10 38 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 . .1 ' Final Calculations - Standard AFP SYSTEMS INC Page 7 • ASSOCIATED BUSINESS- OVERHEAD PIPING Date 082208 Hyd. Qa Dia. Fitting Pipe Pt Pt • Ref. "C" or Ftng's Pe Pv * * * * * ** Notes * * ** ** - Point — - Qt Pf /UL Eqv- LP - Total Pf Pn 500.00 Qa = 500.00 1464.62 66.758 K Factor = 179.26 Computer Programs by Hydratec Inc Route 111 Windham N.H. USA 03087 . tqC0 I Fire & Building RECEVD Products AUG 5 20t'i Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791-5500 die CITV OF DIVISION I BUILDING Series TY -B — 2.8, 5.6, and 8.0 K- factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage cable approval agencies, the testing is G eneral not representative of all possible cor- -)- rosive atmospheres. Consequently, it'" ' . ' D escription is recommended that the end user be r" `; ��,� consulted with respect to the suitability The Series TY -B, 2.8, 5.6, and 8.0 of these coatings for any given corro- r, K- factor, Upright and Pendent Sprin- sive environment. The effects of ambi- l fit-- 4 . klers described in this data sheet are ent temperature, concentration of (. i standard response - standard cover- chemicals, and gas /chemical velocity, . age, decorative 5 mm glass bulb type should be considered, as a minimum, , .mod spray sprinklers designed for use in along with the corrosive nature of the light, ordinary, or extra hazard, corn- chemical to which the sprinklers will be — ;,, mercial occupancies such as banks, exposed. — • hotels, shopping malls, factories, refin- An intermediate level version of the eries, chemical plants, etc. Series TY -B Pendent Sprinkler can be The recessed version of the Series obtained by utilizing the Series TY -B„.. TY -B Pendent Sprinkler, where appli- Pendent Sprinkler in combination with cable, is intended for use in areas with the Model S2 Shield. - - Nk a finished ceiling. It uses a two-piece =_ _ • Style 10 (1/2 inch NPT) or Style 40 (3/4 WARNINGS �,' a l l inch NPT) Recessed Escutcheon. The The Series TY-B Sprinklers described r` Recessed Escutcheon provides 1/2 herein must be installed and main l ! inch (12,7 mm) of recessed adjust- tained in compliance with this docu i ~ d ment or up to 3/4 inch (19,1 mm) of ment, as well as with the applicable y1J! '' *t • r- ' total adjustment from the flush pen- standards of the National Fire Protec- —. dent position. The adjustment pro- Lion Association, in addition to the `..„ , c •`0 vided by the Recessed Escutcheon re- standards of any other authorities hay- ` -,,,... - _ ,,. duces the accuracy to which the fixed ing jurisdiction. Failure to do so may •...r — r A" pipe drops to the sprinklers must be impair the performance of these de- cut. vices. Corrosion resistant coatings, where The owner is responsible for maintain - applicable, are utilized to extend the ing their fire protection system and de- life of copper alloy sprinklers beyond vices in proper operating condition that which would otherwise be ob- The installing contractor or sprinkler tained when exposed to corrosive at- manufacturer should be contacted mospheres Although corrosion resis- with any questions. tant coated sprinklers have passed the standard corrosion tests of the appli- Model/Sprinkler IMPORTANT Identification Always refer to Technical Data Sheet TFP700 for the "INSTALLER Numbers WARNING" that provides cautions with respect to handling and instal- TY1151 - Upright 2.8K, 1/2 "NPT lation of sprinkler systems and com- TY1251 - Pendent 2.8K, 1/2"NPT ponents. Improper handling and in- TY3151 - Upright 5.6K, 1/2"NPT stallation can permanently damage TY3251 - Pendent 5.6K, 1/2 "NPT a sprinkler system or its compo- TY4151 - Upright 8.0K, 314 "NPT nents and cause the sprinkler to fail TY4251 - Pendent 8.0K, 3l4 "NPT to operate in a fire situation or cause TY4851 - Upright 8.0K, 112 "NPT it to operate prematurely. TY4951 - Pendent 8.0K, 1/2 "NPT Page 1 of 8 DECEMBER, 2007 TFP151 ti Page 2 of 8 TFP151 ESCUTCHEON 7/16" (11,1 mm) PLATE SEATING ** NOMINAL SSU * - -- SURFACE NF T MAKE -IN - DEFLECTOR- - - - -- 6 I m i'"R = �Zif u :...... !ai 5 2 -1/4" } 2- 3/16" (57,2 mm) NSA' ' (55,6 mm) 4 i ,� � _ . 2 3 2 1- 9/16" 1 ij Jii WRENCH � 5 4 (39,7 mm) FLATS y� II SSP 7 DEFLECTOR CROSS PENDENT UPRIGHT SECTION 1- Frame 3 - Sealing 4 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. . FIGURE 1 STANDARD RESPONSE SERIES TY -B UPRIGHT (TY1151) AND PENDENT (TY1251) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 7/16" (11,1 mm) STYLE 10 PLATE SEATING 1/2" ** NOMINAL RECESSED SURFACE NPT MAKE -IN ESCUTCHEON SSU* 1 DEFLECTOR i 5 ;te = W I =s 2 -3/16" 11;�� ' 7/16 (55,6 mm) I � (11,1 mm) - NOMINAL I 4 `, i, ( 1 -1/2 " Rh I e , .r �� 2 38,1 mm) WRENCH `�� (55,6 mm) ; ;/ V 1 3 IS „ i� _. ._.„.fir_. FLATS 1 y o 1 SSP DEFLECTOR - - 2 -7/8" (73,0 mm) DIA. - - - 1 1/2" NPT ** 1 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to ii 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request FIGURE 2 STANDARD RESPONSE SERIES TY -B UPRIGHT (TY3151) AND PENDENT (TY3251) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT TFP151 Page 3 of 8 ESCUTCHEON 1/2" (12,7 mm) STYLE 40 PLATE SEATING „ ** NOMINAL RECESSED SURFACE NFT MAKE -IN — — ESCUTCHEON - DEFLECTOR 6 � _- . E 5 2- 5/16 "' , 'uv - ' 1i (12,7 mm) (58,7 mm) 1 cji �� NOMINAL 4 if! , MAKE -IN 1- 9/16" _— 2 -1/4” Wei 2 (39,7 mm) I (57,2 mm) 0' WRENCH 3 FLATS ! *i 1 SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA - -1 3/4" NPT ** PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame Screw * * Pipe thread connections per ISO 7/1 can be provided on special request FIGURE 3 STANDARD RESPONSE SERIES TY -B UPRIGHT (TY4151) AND PENDENT (TY4251) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT ESCUTCHEON 7/16" (11,1 mm) PLATE SEATING ** NOMINAL SSU SURFACE NPT MAKE -IN DEFLECTOR �_� *r * 6 t . _= imp - t ,•• � T�� i3; 5 _ -- 11 2-1/4" 2-3/16" . (57,2 mm) I II.., II.., ' (55,6 mm) 4 1 1-9/16" 1 WRENCH r�� � - ti ' 2 F (39,7 mm) FLATS ' — 7 7' f 3 SSP 1 DEFLECTOR CROSS PENDENT UPRIGHT SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 4 STANDARD RESPONSE SERIES TY -B UPRIGHT (TY4851) AND PENDENT (TY4951) SPRINKLERS 8.0 K- FACTOR, 1/2 INCH NPT • Page 4 of 8 TFP151 • SPRINKLER FINISH (See Note 8) _____ _ __K. . ___TYPE__ _ TEMP. _ BULB NATURAL _ CHROME _ WHITE *" LEAD _ _ WAX WAX OVER _ LIQUID BRASS PLATED POLYESTER COATED COATED LEAD COATED 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red 2 8 (TY1251) 1, 2, 3 N/A 1/2° and 175F/79°C Yellow NPT UPRIGHT 200 °F /93 °C Green (TY1151) 286 °F /141 °C Blue 360 °F /182 °C Mauve 1, 2 135 °F /57 °C Orange PENDENT 155 °F /68 ° C Red (TY3251) 1,2,3,4,5,6,7 1,2,3,5 1,2,3,5 1,2,3,5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 5.6 (TY3151) 28&F/141°C Blue 1/2" NPT 360 °F /182 °C Mauve N/A 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 N/A (TY3251)' 175 °F /79 °C Yellow Figure 4 200 °F /93 ° C Green 286 °F /141 ° C Blue 1, 2 135 °F /57 °C Orange PENDENT 155 °F /68 ° C Red (TY4251) 1, 2, 5 1, 2, 3, 5 1, 2, 5 and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7 8 0 UPRIGHT 200F/93°C Green 3/4' (TY4151) 286 °F /141 °C Blue 1' 2" 3" 5" I 1°° 2", 5" NPT 360F/182°C Mauve N/A 135F/57°C Orange RECESSED 155F/68°C Red PENDENT 1, 2, 3, 4, 5 N/A (TY4251)* 175 °F /79 °C Yellow Figure 5 200F/93°C Green 286 °F /141 °C Blue 1,2 135 °F /57 ° C Orange PENDENT 155 °F /68 °C Red 8.0 (TY4951) 1/2" and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6 N/A NPT UPRIGHT 200 °F /93 °C Green (TY4851) 286 °F /141 ° C Blue 360 °F /182 ° C Mauve NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) 2 Listed by Underwriters Laboratories, Inc for use in Canada (C -UL) 3. Approved by Factory Mutual Research Corporation (FM) 4. Approved by the Loss Prevention Certification Board (LPCB Ref No 007k/03) 5. Approved by the City of New York under MEA 354 -01 -E 6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel 31 -53- 428 - 4444 /Fax 31 -53- 428 - 3377). 7 Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05). 8. Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable " 150 °F /66 °C Maximum Ceiling Temperature. Frame and deflector only. Listings and approvals apply to color (Special Order). TABLE A, LABORATORY LISTINGS AND APPROVALS TFP151 Page 5 of 8 SPRINKLER FINISH _ - _ _ _ _____ __K. _ _. —_ _.T_YPE _ NATURAL_ CHROME WHITE _ LEAD _ WAX_ _ _ WAX_OVER _ _ BRASS PLATED POLYESTER COATED COATED LEAD COATED 2 8 PENDENT (TY1251) 1/2" and 175 PSI (12,1 BAR) N/A NPT UPRIGHT (TY1151) PENDENT (TY3251) 5.6 and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR) 1/2" UPRIGHT (TY3151) OR NPT RECESSED PENDENT 175 PSI (12,1 BAR) (TY3251) N/A (SEE NOTE 1) 8 0 PENDENT (TY4251) 3/4" and 175 PSI (12,1 BAR) NPT UPRIGHT (TY4151) RECESSED PENDENT (TY4251) 175 PSI (12,1 BAR) N/A 8.0 PENDENT (TY4951) 1/2" and ' 175 PSI (12,1 BAR) NPT UPRIGHT (TY4851) NOTE: 1 The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc (UL); the Listing by Underwriters Laboratories, Inc for use in Canada (C -UL): and, the Approval by the City of New York TABLE B, MAXIMUM WORKING PRESSURE Technical Operation Data The glass Bulb contains a fluid which expands when exposed to heat When Approvals the rated temperature is reached, the UL and C -UL Listed. fluid expands sufficiently to shatter the FM, LPCB, VdS, and NYC Approved. glass Bulb, allowing the sprinkler to (Refer to Table A for complete ap- activate and water to flow proval information including corrosion resistant status.) Design Maximum Working Pressure Refer to Table B. Criteria Discharge Coefficient K = 2.8 GPM /psi / (40,3 LPM /bar1 /2) The Series TY -B Pendent and Upright K = 5.6 GPM /psi / (80,6 LPM /bar1 /2) Sprinklers are intended for fire protec- K = 8.0 GPM /psi / (115,2 LPM /bar1/2) tion systems designed in accordance with the standard installation rules rec- Temperature Ratings ognized by the applicable Listing or Refer to Table A. Approval agency (e.g., UL Listing is Finishes based on the requirements of NFPA Sprinkler: Refer to Table A. 13, and FM Approval is based on the Recessed Escutcheon: White Coated, requirements of FM's Loss Prevention Chrome Plated, or Brass Plated. Data Sheets). Only the Style 10 or 40 Recessed Escutcheon, as applicable, ci, Physical Characteristics is to be used for recessed pendent m Frame . . . . . . . . . . Bronze installations. Button . Brass /Copper Sealing Assembly Beryllium Nickel w /Teflont o, Bulb Glass cc Compression Screw . . . Bronze Deflector . . . . . . Copper a Bushing (K =2.8) Bronze 0 1- Page 6 of 8 TFP151 • 2 -7/8" DIA. (73,0 mm) 3/4".(19,1 -mm — 5/8 ±1/4" - -- ) /RENCH — - - — - (15,9 ±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) E (57,2 mm) 2 NPT MODEL FACE OF MOUNTING SPRINKLER PLATE FITTING 1/8" WRENCH RECESS •!' (3,2 mm) (END "B" USED FOR Kjlill 1 - I 3/4 NPT MODELS) FIGURE 7 / �✓ W -TYPE 6 SPRINKLER w WRENCH MOUNTING SURFACE - =- ' WRENCH CLOSURE SERIES 1 -1/4" (31,8 mm) RECESS TY -B 3/4" (19,1 mm) s"` FIGURE 5 ^ • SERIES TY -B RECESSED PENDENT SPRINKLER ASSEMBLY / ) i r WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT j<g--; U STYLE 10 RECESSED ESCUTCHEON \.' 5.6 K- FACTOR, 1/2 INCH NPT 1.1;..., PUSH WRENCH IN TO ENSURE 2 - 7/8" DIA. ENGAGEMENT - WITH SPRINKLER (73,0 mm) 3/4" (19,1 mm) WRENCHING AREA 5/8 ±1 /4" — (15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) FIGURE 8 (57,2 mm) FACE OF MOUNTING W -TYPE 7 RECESSED SPRINKLER PLATE SPRINKLER WRENCH FITTING 1/8" i (3,2 mm) Installation / / 711 ' 1 The Series TY -B Sprinklers must be I� installed in accordance with the follow - VIP ing instructions: MOUNTING . NOTES SURFACE Do not install any bulb type sprinkler if -'- - -- - -" the bulb is cracked or there is a loss of CLOSURE SERIES 1 -5/16" (33,3 mm) liquid from the bulb. With the sprinkler TY -B 13/16" 20,6 mm) held horizontally, a small air bubble ( ) should be present The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135 °F /57 °C to 3/32 FIGURE 6 SERIES TY -B RECESSED PENDENT SPRINKLER ASSEMBLY tech mm) for the 360 ° F /182 ° C WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT temperratat ure ratings. STYLE 40 RECESSED ESCUTCHEON A 1/2 inch NPT sprinkler joint should 8.0 K- FACTOR, 3/4 INCH NPT be obtained with a minimum to maxi- mum torque of 7 to 14 ft.lbs. (9,5 to 19,0 Nm). A 3/4 inch NPT sprinkler joint should be obtained with a mini- mum to maximum torque of 10 to 20 ft.lbs (13,4 to 26,8 Nm). Higher levels . of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler. Do not attempt to make -up for insuffi- cient adjustment in the escutcheon plate by under- or over - tightening the TFP151 Page 7 of 8 . sprinkler. Readjust the position of the The Series TY -B Recessed Pendent and after installation Sprinklers dam - sprinkler fitting to suit. Sprinklers must be installed in ac- aged by dropping, striking, wrench The Series TY -B Pendent and Up- cordance with- the - following - instruc- twist/slippage, or- the -like, -must be- re - - -- - - tions placed. Also, replace any sprinkler right Sprinklers must be installed in that has a cracked bulb or that has lost accordance with the following instruc- Step A. After installing the Style 10 or tions. 40 Mounting Plate, as applicable, over liquid from its bulb. (Ref. Installation the sprinkler threads and with pipe Section) Step 1. Pendent sprinklers are to be thread sealant applied to the pipe Frequent visual inspections are rec- installed in the pendent position, and threads, hand tighten the sprinkler into ommended to be initially performed for upright sprinklers are to be installed in the sprinkler fitting. corrosion resistant coated sprinklers, the upright position. after the installation has been com- Step B. Tighten the sprinkler into the after the to verify the integrity of the cor- Step lied to the With pipe ea threads, hnd tighten sprinkler fitting using only the W -Type f eted resistant c Thereafter, p p p e tighten 7 Recessed Sprinkler Wrench (Ref the sprinkler into the sprinkler fitting Figure 8) With reference to Figure 3 annual inspections per NFPA 25 Step 3. Tighten the sprinkler into the or 4, the W -Type 7 Recessed Sprinkler should suffice; however, instead of in- sprinkler fitting using only the W -Type Wrench is to be applied to the sprinkler specting from the floor level, a random 6 Sprinkler Wrench (Ref. Figure 7), wrench flats. sampling of close -up visual - better except that an 8 or 10 inch adjustable lions should be made, so as to better Crescent wrench is to be used for wax Step C. After the ceiling has been in- determine the exact sprinkler condi- coated sprinklers. With reference to stalled or the finish coat has been ap- tion and the long term integrity of the Figures 1, 2, 3, and 4 the W -Type 7 plied, slide on the Style 10 or 40 Clo- corrosion resistant coating, as it may sure over the Series TY -B Sprinkler be affected by the corrosive conditions Sprinkler Wrench or the adjustable Crescent wrench, as applicable is to and push the Closure over the Mount- present. be applied to the wrench flats ing Plate until its flange comes in con- tact with the ceiling. The owner is responsible for the in- When installing wax coated sprinklers spection, testing, and maintenance of with the adjustable Crescent wrench, their fire protection system and de- additional care needs to be exercised Care and vices in compliance with this docu- to prevent damage to the wax coating ment, as well as with the applicable on the sprinkler wrench flats or frame Nla in tenanee standards of the National Fire Protec- arms and, consequently, exposure of tion Association (e.g , NFPA 25), in bare metal to the corrosive environ- The Series TY -B Sprinklers must be addition to the standards of any other ment. The jaws of the wrench should maintained and serviced in accord- authorities having jurisdiction The in- be opened sufficiently wide to pass ance with the following instructions stalling contractor or sprinkler manu- over the wrench flats without damag- facturer should be contacted relative ing the wax coating. Before wrench NOTES to any q uestions. tightening the sprinkler, the jaws of the Before closing a fire protection system wrench are to be adjusted to just con- main control valve for maintenance Automatic sprinkler systems should be . tact the sprinkler wrench flats. After work on the fire protection system that inspected, tested, and maintained by wrench tightening the sprinkler, loosen it controls, permission to shut down the a qualified Inspection Service in ac- the wrench jaws before removing the affected fire protection system must be cordance with local requirements wrench. obtained from the proper authorities and /or national codes. . and all personnel who may be affected After installation, the sprinkler wrench by this action must be notified. flats and frame arms must be in- spected and the wax coating re- The owner must assure that the sprin- touched (repaired) whenever the coat- klers are not used for hanging of any ing has been damaged and bare metal objects; otherwise, non - operation in is exposed. The wax coating on the the event of a fire or inadvertent opera - wrench flats can be retouched by gen- lion may result. tly applying a heated 1/8 inch diameter Absence of an escutcheon, which is steel rod to the areas of wax that have used to cover a clearance hole, may been damaged, to.smooth it back over delay the time to sprinkler operation in areas where bare metal is exposed. a fire situation. NOTES Sprinklers that are found to be leaking Only retouching of the wax coating ap- or exhibiting visible signs of corrosion plied to the wrench flats and frame must be replaced arms is permitted, and the retouching Automatic sprinklers must never be is to be performed only at the time of painted, plated, coated or otherwise the initial sprinkler installation. . altered after leaving the factory. Modi- The steel rod should be heated only to fled sprinklers must be replaced. the point at which it can begin to melt Sprinklers that have been exposed to the wax, and appropriate precautions corrosive products of combustion, but need to be taken, when handling the have not operated, should be replaced - heated rod, in order to prevent the if they cannot be completely cleaned installer from being burned. by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid dam- age to the sprinklers - before, during, Page 8 of 8 TFP151 P/N 57 - XXX - X - XXX SPRINKLER TEMPERATURE MODEL /SIN RATING 530 2.8K UPRIGHT (1/2 "NPT) TY1151 1 NATURAL BRASS 135 135 °F /57 °C 531 2.8K PENDENT (1/2 "NPT) TY1251 4 WHITE POLYESTER 155 155 °F /68 °C 570 5.6K UPRIGHT (1/2 "NPT) TY3151 3 WHITE (RAL9010) 175 175 °F /79 °C 571 5.6K PENDENT (1/2 "NPT) TY3251 9 CHROME PLATED 200 200 °F /93 °C 590 8.0K UPRIGHT (3/4 "NPT) TY4151 7 LEAD COATED 286 286 °F /141 °C 591 8 OK PENDENT (3/4 "NPT) TY4251 6 WAX COATED 360 360 °F /182 °C 286 °F /141 °C MAX. 560 8.0K UPRIGHT (1/2 "NPT) TY4851 8 WAX OVER LEAD 561 8 OK PENDENT (1/2 "NPT) TY4951 286 °F /141 °C MAX ' Eastern Hemisphere sales only TABLE C PART NUMBER SELECTION SERIES TY -B PENDENT AND UPRIGHT SPRINKLERS any other legal theory, for incidental, Li mited indirect, special or consequential dam- Ordering ages, including but not limited to labor Warranty charges, regardless of whether TFBP Procedure was informed about the possibility of Products manufactured by Tyco Fire & such damages, and in no event shall When placing an order, indicate the Building Products (TFBP) are war- TFBP's liability exceed an amount full product name. Refer to the Price ranted solely to the original Buyer for equal to the sales price. List for complete listing of Part Num- . ten (10) years against defects in mate- bers. rial and workmanship when paid for The foregoing warranty is made in lieu and properly installed and maintained of any and all other warranties. ex- Contact your local distributor for avail - under normal use and service. This press or implied. including warranties ability. warranty will expire ten (10) years of merchantability and fitness fora par - from date of shipment by TFBP. No ticular purpose Sprinkler Assemblies with NPT warranty is given for products or corn- This limited warranty sets forth the ex- Thread Conneif Specify: (Specif y y Model/SIN), ponents manufactured by companies clusive remedy for claims based on (specify as not affiliated by ownership with TFBP failure of or defect in products, maters- Response, tu K-factor), or for products and components which als or components, whether the claim (spp ecify temperature a e ra rating), Series TY -B (specify Pendent or Upright) have been subject to misuse, improper is made in contract, tort, strict liability Sprinkler with (specify type of finish or installation, corrosion, or which have or any other legal theory. coating), P/N (specify from Table C). not been installed, maintained, modi- fied or repaired in accordance with ap- This warranty will apply to the full ex- plicable Standards of the National Fire tent permitted by law The invalidity, in Recessed Escutcheon: Protection Association, and /or the whole or part, of any portion of this Specify Style (specify 10 or 40 ) Re- standards of any other Authorities warranty will not affect the remainder cessed Escutcheon with (specify') fin - Having Jurisdiction. Materials found ish, P/N (specify'). by TFBP to be defective shall be either • Refer to Technical Data Sheet TFP770 repaired or replaced, at TFBP's sole option TFBP neither assumes, nor Sprinkler Wrench: authorizes any person to assume for it, Specify. W -Type 6 Sprinkler Wrench, any other obligation in connection with P/N 56- 000 -6 -387. the sale of products or parts of prod- ucts. TFBP shall not be responsible for Specify: W -Type 7 Sprinkler Wrench, sprinkler system design errors or inac P/N 56-850-4-001. • curate or incomplete information sup- - plied by Buyer or Buyer's repre- sentatives. In no event shall TFBP be liable, in contract, tort, strict liability or under © 2007 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446