Plans E Lczo t o- 004F75 . Portland General Electric Company N 07/21/10 ME CONTACT: Mitch Bramlitt PHONE: 800 - 285 -2223 x8714 CUSTOMER NAME: Autozone ADDRESS: 13405 SW Pacific Hwy, Tigard, OR SDC /ENGR: Lorraine Katz WR: 614040 PHONE: (503) 570 -4407 3 -PHASE SECONDARY LINE -LINE FAULT CURRENT (RMS) TRANSFORMER DATA XFMR Impedance ( %): 1.3 % 3 -PHASE SUBMERSIBLE TRANSFORMER SIZE: 300 KVA XFMR ? NO Secondary VOLTAGE (L to L): 208 v WYE VAULT - -> VAULT ( or Pole - -> Pole) SECONDARY • Secondary Wire LENGTH: 0 Feet WIRE SIZE Number of SECONDARY RUNS: 1 Run(s) of: Secondary WIRE Resistance R: 0.0180 Ohms /1000' Secondary WIRE Reactance X: 0.0258 Ohms /1000' VAULT ( or Pole) - -> PANEL SECONDARY (or Svc Drop) Service Wire LENGTH: 60 Feet WIRE SIZE Number of Service RUNS: 2 Run(s) of: 350 QX UG I Service WIRE Resistance R: 0.0600 Ohms /1000' Service WIRE Reactance X: 0.0330 Ohms /1000' MAXIMUM FAULT CURRENT *: 30,564 Amps 'Maximum fault current based upon transformers /conductors sized for 100% of electrical panel rating. Based on a panel size of: 600 Amps To Print This Page: "Ctrl M" and choose "Print 3 -Phase Data" • [Page Too Large for OCR Processing] [Page Too Large for OCR Processing] [Page Too Large for OCR Processing] [Page Too Large for OCR Processing] [Page Too Large for OCR Processing] [Page Too Large for OCR Processing]