Plans E Lczo t o- 004F75 .
Portland General Electric Company
N
07/21/10 ME
CONTACT: Mitch Bramlitt
PHONE: 800 - 285 -2223 x8714
CUSTOMER NAME: Autozone
ADDRESS: 13405 SW Pacific Hwy, Tigard, OR
SDC /ENGR: Lorraine Katz WR: 614040
PHONE: (503) 570 -4407
3 -PHASE SECONDARY LINE -LINE FAULT CURRENT (RMS)
TRANSFORMER DATA
XFMR Impedance ( %): 1.3 % 3 -PHASE SUBMERSIBLE
TRANSFORMER SIZE: 300 KVA XFMR ? NO
Secondary VOLTAGE (L to L): 208 v WYE
VAULT - -> VAULT ( or Pole - -> Pole) SECONDARY
• Secondary Wire LENGTH: 0 Feet WIRE SIZE
Number of SECONDARY RUNS: 1 Run(s) of:
Secondary WIRE Resistance R: 0.0180 Ohms /1000'
Secondary WIRE Reactance X: 0.0258 Ohms /1000'
VAULT ( or Pole) - -> PANEL SECONDARY (or Svc Drop)
Service Wire LENGTH: 60 Feet WIRE SIZE
Number of Service RUNS: 2 Run(s) of: 350 QX UG I
Service WIRE Resistance R: 0.0600 Ohms /1000'
Service WIRE Reactance X: 0.0330 Ohms /1000'
MAXIMUM FAULT CURRENT *: 30,564 Amps
'Maximum fault current based upon transformers /conductors sized for 100% of electrical panel rating.
Based on a panel size of: 600 Amps
To Print This Page: "Ctrl M" and choose "Print 3 -Phase Data"
•