Co 31 Cp 5W 72 Ave_ B3 FP-52_010 -co 163
t1jC17 Fire & Building
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series ELO -231 FRB — 11.2 K- factor
Upright and Pendent Sprinklers
Quick Response, Standard Coverage
General ELO- 231FRB Pendent Sprinkler with
the WS -2 Shield. If there is a possibility
of the pendent intermediate level ver-
D escription sion being exposed to mechanical - �Uu-
damage, a G -2 Guard can be added. :
The 11.2 K- factor, Series ELO
231FRB, Quick Response, Standard WARNINGS
Coverage, Upright and Pendent Sprin- The 11.2 K- factor, Series ELO-
klers (Ref. Figure 1) are automatic 231FRB Upright and Pendent Sprin-
sprinklers of the frangible bulb type. klers described herein must be in- k _
They are "quick response - spray stalled and maintained in compliance �- = —
sprinklers" that produce a hemispheri- with this document, as well as with the
cal water distribution pattern below the applicable standards of the National
deflector. Fire Protection Association, in addition _-
The 11.2 K- factor, ELO- 231FRB Up- to the standards of any other authori- ==
right and Pendent Sprinklers were ties having jurisdiction. Failure to do
subjected to full scale, high piled stor- so may impair the performance of
age, fire tests to qualify their use in lieu these devices.
of 5.6 or 8.0 K- factor standard spray The owner is responsible for maintain- - - _
sprinklers for the protection of high- ing their fire protection system and de-
piled storage. vices in proper operating condition.
• Higher flow rates can be achieved at The installing contractor or manufac-
much lower pressures with the 11 . 2 turer should be contacted with any
K- factor, ELO- 231FRB Sprinklers - Questions.
making their use highly advantageous Installation of Series ELO- 231FRB •
in high density applications, such as Pendent Sprinklers in recessed es-
the protection of high -piled storage. cutcheons will void all sprinkler war-
For in rack applications an upright i ranties, as well as possibly void the
termediate level version of the Series sprinkler's Approvals and /or Listings.
ELO- 231FRB Sprinklers can be ob-
tained by utilizing the Series ELO- Model/Sprinkler
231F RB Upright Sprinkler with the
WSG -2 Guard & Shield, and a pendent Identification
intermediate level version of the Se-
ries ELO- 231FRB Sprinklers can be Numbers
obtained by utilizing the Series
TY5131 - Upright 11.2K, 3/4 "NPT
TY5231 - Pendent 11.2K, 3/4 "NPT
IMPORTANT TY5131 is a redesignation for C5131.
Always refer to Technical Data TY5231 is a redesignation for C5231,
Sheet TFP700 for the "INSTALLER G1870, and S2551.
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
{
• Page 1 of 4 MARCH, 2007 TFP344
Page 2 of 4 TFP344 . .
•
SPRINKLER FINISH
w'
• TYPE TEMPERATURE BULB NATURAL CHROME
• LIQUID BRASS PLATED
_ - -- - - -- -- - - -- 155 °F /68 °C Red
UPRIGHT 200 °F /93 °C Green 1, 2, 3, 4
(TY5131)
286 °F /141 °C Blue
155 °F /68 °C Red
PENDENT - 200 ° F /93 °C Green 1, 2, 3, 4
(TY5231)
286 °F /141 °C Blue
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL Listed).
2. Listed by Underwriters Laboratories; Inc. for use in Canada (C -UL Listed).
3. Approved by Factory Mutual Research Corporation (FM Approved).
4. Approved by the City of New York under MEA 291 -04 -E.
TABLE A
LABORATORY LISTINGS AND APPROVALS
FOR 11.2 K- FACTOR SERIES ELO- 231FRB UPRIGHT AND PENDENT SPRINKLERS
(Refer to the Design Criteria Section)
Technical Des Criteria In
Data UL and C -UL Listing The Series ELO- 231FRB Sprinklers
Requirements must be installed in accordance with
Approvals The 11.2 K- factor, Model ELO- the following instructions:
UL and C-UL Listed. FM and NYC Ap 231 FRB (TY5131 & TY5231) Sprin-
proved. (Refer to Table A for complete klers are to be installed in accordance NOTES
approval information including corro- Do not install any bulb type sprinkler if
• . sion resistant status. The approvals with NFPA 13 standard sprinkler posi the bulb is cracked or there is a loss of
apply to the service conditions indi- lion and area /density flow calculation liquid from the bulb. With the sprinkler
cated in the Design Criteria section.) requirements for light, ordinary, or ex held horizontally, a small air bubble
tra hazard occupancies, as well as should be present. The.diameter of the
Maximum Working Pressure high piled storage occupancies (solid air bubble is approximately 1/16 inch
175 psi (12,1 bar) piled, palletized, rack storage, bin box, (1,6 mm) for the 155 °F /68 °C to 3/32
Discharge Coefficient and shelf storage including but not li inch (2,4 mm) for the 286 °F /141 °C
in ited to Cla I -IV and Group A plastics)
. K = 11.2 GPM /psi temperature ratings.
•
(161,4 LPM /bart12) • with •a minimum residual (flowing)
pressure of 7 psi (0,5 bar) for wet pipe A leak tight'3 /4 inch NPT sprinkler joint
Temperature Ratings systems only. should be obtained with a torque of 10
Refer to Table A to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi -
Finishes FM Approval mum of 30 ft.lbs. (40,7 Nm) of torque •
Sprinkler: Refer to Table A Requirements is to be used to install sprinklers with
The 11.2 K-factor, Model ELO 3/4 NPT connections. Higher levels of
231 FRB (TY5131 & TY5231) Sprin- torque may distort the sprinkler inlet
Physical Characteristics klers are to be installed in accordance and cause leakage or impairment of
Frame Bronze with the applicable "control mode den- the sprinkler.
Cap Bronze sity /area" guidelines provided by Fac- Do not attempt to make -up for insuffi-
Sealing Assembly tory Mutual for wet systems only. (FM cient adjustment in the escutcheon
Beryllium Nickel w /Teflont guidelines may differ from UL and C- plate by under- or over - tightening the
Bulb (3 mm dia.) Glass UL Listing criteria.) sprinkler. Readjust the position of the
Compression Screw Bronze sprinkler fitting to suit.
Deflector Bronze Operation The Series ELO- 231FRB Upright
t Registered trademark of DuPont. and Pendent Sprinklers must be in-
The glass bulb contains a fluid that stalled in accordance with the follow -
expands when exposed to heat. When ing instructions.
the rated temperature is reached, the Step 1. Pendent sprinklers are to be
fluid expands sufficiently to shatter the installed in the pendent position, and
• glass bulb, allowing the sprinkler to upright sprinklers are to be installed in
activate and water to flow. the upright position.
. Step 2. With pipe thread sealant ap-
, l
. ,
I
TFP344 Page 3 of 4 '
• Temperature rating is indicated on deflector.
" Pipe thread connections per ISO 7/1 can be
provided on special request. 3/4 '' • ESCUTCHEON
NPT SEATING
- -- = -- — SURFACE 1 / I -- —
/ /,T1 THREAD i
RELIEF / 2 f Components:
1 - Frame
/'� ' K • 2 - Seal
2- 13/16" 011—il WRENCH 3 �` I Assembly
(71,4 mm) FLATS 2 -1/16" 3 - Cap
TYP. 1011
(52,4 mm) 4 I 4- Bulb
/1 �� 5 Compression
IC: Screw
_. _.. 1 5 ___Inf___ 6 - Deflector *
- • 6 U
L 1/2" (12,7 mm)
NOMINAL MAKE -IN
UPRIGHT PENDENT CROSS
TY5131 TY5231 SECTION
FIGURE 1
11.2 K- FACTOR SERIES ELO- 231FRB
UPRIGHT - 3/4" NPT (TY5131) AND PENDENT - 3/4" NPT (TY5231) SPRINKLERS
plied to the pipe threads, hand tighten C a r e an . "FITTING SIDE"
the sprinkler into the sprinkler fitting. TOWARDS SPRINKLER
Step 3. Tighten the sprinkler into the Maintenance FITTING
sprinkler fitting using only the W -Type
3 Sprinkler Wrench (Ref. Figure 2). Series ELO -231 FRB Sprinklers must
With reference to Figure 1, the W -Type be maintained and serviced in accord- f
- 3 Sprinkler Wrench is to be applied to ance with the following instructions:
f.. the wrench flats. WRENCH •
NOTES RECESS
Before closing a fire protection system (END "A")
control valve for maintenance work on
the fire protection system that it con- FIGURE 2
• trols, permission to shut down the al- W_TYPE 3 SPRINKLER
fected fire protection system must be WRENCH
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified. their fire protection system and de-
Sprinklers that are found to be leaking vices in compliance with this docu-
or exhibiting visible signs of corrosion ment, .as well as with the applicable
•
must be replaced. standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
• Automatic sprinklers must never be be addition to the standards of any other
painted, plated, coated or otherwise authorities having jurisdiction. The in-
altered after leaving the factory. Modi- stalling contractor or sprinkler manu-
fied sprinklers must be replaced. facturer should be contacted relative
Sprinklers that have been exposed to to any questions.
corrosive products of combustion, but
have not operated, should be replaced It is recommended that automatic
if they cannot be completely cleaned sprinkler systems be inspected,
by wiping the sprinkler with a cloth or tested, and maintained by a qualified
by brushing it with a soft bristle brush. Inspection Service in accordance with
local requirements and /or national
Care must be exercised to avoid dam- code.
age to the sprinklers — before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb (ref. Installation
Section Note).
The owner is responsible for the in-
1 spection, testing, and maintenance of
•
•
Page 4 of 4 TFP344
Limited P/N 50 - XXX - X - XXX •
Warranty �
Product Tyco Fire 8
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate- SPRINKLER
rial and workmanship when paid for
and properly installed and maintained - TEMPERATURE
under normal use and service. This TYPE 1 NATURAL BRASS RATING
warranty will expire ten (10) years 500 UPRIGHT 9 CHROME PLATED 155 155 ° F /68 °C
from date of shipment by TFBP. No 314" NPT
warranty is given for products or com-
ponents manufactured by companies (TY5131) 200 200 ° F /93 °C
not affiliated by ownership with TFBP 502 PENDENT 286 286 °F /141 °C
or for products and components which 3/4° NPT
have been subject to misuse,improper (TY5231)
installation. corrosion, or which have
not been installed, maintained, modi- TABLE B
fied or repaired in accordance with ap- PRODUCT SYMBOL NUMBER SELECTION
plicable Standards of the National Fire 11.2 K- FACTOR SERIES ELO- 231FRB
Protection Association, and /or the QUICK RESPONSE UPRIGHT AND PENDENT SPRINKLERS
standards of any other Authorities
Having Jurisdiction. Materials found
• by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole Ordering
option. TFBP neither assumes, nor
authorizes any person to assume for. it, Procedure
• any other obligation in connection with
the sale of products or parts of prod- A Product Symbol Number (P /N) is not
ucts. TFBP shall not be responsible for specified when ordering sprinklers
sprinkler system design errors or inac- with thread connections per ISO 7/1.
curate or incomplete information sup- Contact your local distributor for avail-
!, plied by Buyer or Buyer's repre- ability.
sentatives.
- In no event shall TFBP be liable, in Sprinkler Assemblies
contract, tort, strict liability or under with NPT Thread Connection:
any other legal theory, for incidental, Specify: (specify SIN), 11.2 K- factor,
indirect, special or consequential dam- (specify temperature rating), Series
ages, including but not limited to labor ELO- 231FRB Quick Response (spec-
• charges, regardless of whether TFBP ify Pendent or Upright) Sprinkler with
was informed about the possibility of (specify finish), P/N (specify from Ta-
such damages, and in no event shall ble B).
TFBP's liability exceed an amount Sprinkler Wrench:
equal to the sales price. Specify: W -Type 3 Sprinkler Wrench,
•
The foregoing warranty is made in lieu P/N 56- 895 -1 -001.
of any and all other warranties. ex-
• - • " u.. - . • l • • l. , . . I '-
of merchantability and fitness for a par -
ficular purpose,
This limited warranty sets forth.the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
•
• TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
•
h
: _ z, / go olz
- - P.O- Box -3365 SouTH- E- L- MoNTE-•- CA- 91•7. 33-.4626.)444.-0541_•_FAx4626.) 444-388.7_ . __
• 300
RING HANGER
•
MAX
PIPE H CL (NFPA) MRI A REC.
R S — — SIZE RS LOAD LBS. •
3i* l .
MRI 1/2 3 1/8 1 5/8 . 3/8 1 1 1/4 300
l 3/4 31/16 11/2 3/8 1 1 5/16 300
• 1 • 3 3/16 1 1/2 3/8 1 15/16 300
A
1 1/4 3 1/2 1 11/16 3/8 1 7/8 300
l I ` CIL H
1 1/2 3 15 /16 1 15/16 3/8 1 1 ____ 300 _ -
I; K --- I 1 L 2 4 1/2 2 1/4 3/8 1 1 1/16 300 2 1/2 5 3/8 2 15/16 /8 1 1 1/2 525
1 3 6 5/16 3 5/8 3/8 1 1 7/8 525
3 1/2 7 7/16 3 15/16 3/8 1 1 7/8 585
• - 4 7 3/4 4 9/16 3/8 1 2 5/16 650
5 8 7/8 4 15/16 1/2 1 1/4 2 1/8 1000
6 10 7/16 5 15/16 1/2 1 1/4 2 5/8 . 1000
SIZE 8 12 7/8 7 3/16 1/2 1 1/4 3 1/16 1000
1/2 thru 6 inch pipe.
• MATERIAL •
Carbon Steel, Mil. Galvanized to G -90 specification.
FINISH
Mil. Galvanized and Stainless Steel.
APPROVALS
Underwriters' Laboratories listed. Conforms to Federal Specification W W -H -171 E
type 10, and Manufacturers Standardization Society SP -69, type 10.
FUNCTION
For general piping purposes. Knurled swivel nut design permits hanger adjustment
after installation. Spring tension on swivel nut holds it securely in hanger before
installation. Swivel nut easily removed.
ORDERING
i Part # and pipe size.
• NOTE: Maximum Temperature: 650 °F.
1 0/97
•
_ _ P_. O._Box_3365..South_EI_ Monte, CA 91733 Fax 626.444.3887 www. Afcon.org ._ .
001/020
MODEL E
SWAY BRACE FITTING
Part #077
;I
• `'
I
�
•
SIZE - SYSTEM PIPE: Nominal Pipe Size •
Steel 1" thru 4" Schedule 7 thru 40
SIZE - BRACE PIPE: I" and 1 1/4" Schedule 40.
• MATERIAL - Carbon Steel or S.S. (Type 304).
FINISH - Plain or E.G.
PATENT - No. 3,570,794
LISTING /APPROVAL •
203A - EX 2625 • Horizontal Load Ratings
" Listed only for use with AFCON products. Size FM FM FM UL UL
Fro FM Approved Sch. 7 Sch. 10 Sch. 40 Sch. 7 Sch. 1040
OSHPD OPA- 0601 -07 See Website. 1 250 .250 1000 655 2015
1 1/4 250 250 1000 655 2015
FUNCTION - Per NFPA 13. 1 1/2 250 250 1000 655 2015
Lateral fitting of an AFCON sway brace assembly. 2 500 1000 1300 655 2015
INSTALLATION - Per NFPA 13 and these instructions. 3 1/2 500 800 1300 655 2015 3 500 800. 1300 655 2015
Load rating - see chart. 4 500 800 1500 655 2015
Combine with proper AFCON components. 5 500 500 1500 1500 2015
ASSEMBLY 6 500 500 1500 1500 2015
Insert brace pipe through rod bend and under channel bracket 8 -- 800 1500 — 2015
to achieve minimum 1" extension.
Tighten hex nuts until gage spring lays flat or torque to 65 in. -lbs.
FEATURES
* Visual inspection, verifies proper installation.
ORDERING - Part #, pipe size to be braced, brace pipe size and finish.
Specific AFCON products am cnclusivcly designed hl be compatible ONLY with other el FCO.Y products including parts and fasteners. resulting inn listed sway brace. restrainer OT hanger assembly.
lie advised the following warranty restriction will apply. DISCLAIMER - FCON will NOT warrant against the failure of its products when used in combination with other products, pans or systems
not manul'neaured or sold hvAFCON. :I FCO.Y sluts Nor be liable under any circumstances why iaoes for any direct ssr indirect, incidental orconsequcnti.tl damages of any kind. including but nut
limited to less of business or profs, when non -A FCON products have been, or are used.
9/09
•
•
- - - P_:O. Box..3365_South. EL Monte,CA 91733 626..444.0541 Fax 626.444.3887 www. Afcon.org
077
•
ATTACHMENT FITTING
LOCKING
•
�•
(5)
1
•
•
SIZE - BRACE PIPE - 1" and 1 1/4" Sch. 40
• ' MATERIAL - Carbon Steel, Ductile Iron or S.S. (Type 304).
FINISH - Plain or E.G.
LISTING /APPROVAL - -
c Ons
MED 203A- EX2625 •
FM FM Approved
OSHPD OPA- 0601 -07 See Website.
Horizontal Load Ratings
FUNCTION - Structure attachment fitting of an AFCON sway brace assembly. -
Sway brace assemblies are intended to be installed in accordance with Size FM UL
NFPA 13 and the manufacturer's installation instructions. 1 -1 1/4 1500 2015
INSTALLATION - Per NFPA 13 . Load rating - see chart.
ASSEMBLY - Insert brace pipe into fitting against the pivot bolt. Tighten set
bolt until head contacts bracket.
FEATURES
* Swivel allows attachment at any angle.
* Visual inspection, verifies proper installation.
* 17/32" Fastener hole, larger hole available.- Consult factory.
ORDERING - Part #, pipe size and finish.
Specific AFCON products are exclusively d tiigned to be compatible ONLY with other A FCO.v products including parts and fasteners. resulting in a listed sway brace. restrainer or hanger assembly.
Re advised the following warranty rsu-iction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products. parts or systems
not manufactured or sold by AFCOX.:I FCON shall NUT he liable under any circumstances w hasocscr for any direct or indirect incidental or consequential damages of any kind. including but not
limited to loss of business or.protit when non- .4FCON products have been. or are used.
{
•
8/09 •
•
•
•
.
_. _. _- _P_.O. Box_3365_South_EI_Monte, CA 91733 626_444.0541 Fax 626.444.3887 www. Afcon.org_
078
ATTACHMENT FITTING
LOCKING STRAIGHT
Part 6 077 \'
9/16 Ilia.
40
_ Part 6 078
•
Part #410 —
(# )141
til
SIZE - BRACE PIPE - 1" and 1 1/4" Sch. 40
MATERIAL - Carbon Steel or S.S. (Type 304).
FINISH - Plain or E.G.
•
LISTING /APPROVAL -
c ltt us 203A -EX 2625
t Listed only for use with other AFCON bracing products.
• 0 FM Approved
OSHPD OPA -0601 -07 See \'Vebsite.
FUNCTION - Structure attachment fitting of an AFCON sway brace assembly.
Component wit/i #410 in a longitudinal sway brace assembly - see drawing.
Sway brace assemblies are intended to be installed in accordance with NFPA 13
and the manufacturer's installation instructions. Horizontal Load Ratings
INSTALLATION - Per NFPA 13. Load rating - see chart. -
DO NOT BEND - IF ANGLE REQUIRED USE PART #070, #076 or #077. Size FM UL
ASSEMBLY - Insert brace pipe into fitting against the pivot bolt . ' 1 - 1 1/4 1200 2015
Tighten set bolt until head contacts bracket.
FEATURES
Visual inspection, verifies proper installation.
* Bolt hole fits #410 sway brace fitting.
ORDERING - Part #, pipe size and finish.
Specific A FCO:Y products are exclusively designed to be compatible ONLY with other AFCON products including pans and fasteners. resulting inn listed sway brace. restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCI.MMF..R - AFCON will NOT warrant acaiaa the failure of its products when used in combination stub other pmduets. pans or systems
not manufactured or sold by A FCON..4FCON shall NOT be liable under any circumstances whatsoever for any direct or indirect. incidental or consequential damages of any kind. including but not
limited to loss of business or profit. when non - AFC - O.Y products have been, nr arc used.
R /09
•
t.
.4.
•
I
4 ,,t1 / /7g
P.O. Box_3365_South..El._Monte,_CA 91733 626 Fax 626.444.3887 www. Afcon.org
410
SWAY BRACE FITTING
•
i
Part ti m__ O
• • ` Part n 078
- 01
•
Part #410 —
t o��
SIZE - 1 thru 8 inch pipe.
MATERIAL - Carbon Steel or S.S. (Type 304).
FINISH - Plain, E.G., and H.D.G.
LISTING /APPROVAL -
nQun 203A -EX 2625, 203 -EX 2551
Listed only for use with other AFCON bracing products.
OSHPD OPA -0601 See Website:
FUNCTION - Pipc.attachment component of a longitudinal or 4 -way sway brace,
consisting additionally of AFCON 70 series attachment end, AFCON 80 series
adapter as required,and brace pipe clement forming a complete sway bract
assembly.
INSTALLATION - Per NFPA 13. Assemble 410 over pipe to be braced, install
70 series attachment end on outside of clamp cars and tighten bolts to minimum
required torque of 40 Ribs.
078 is the preferred assembly component for use with the 410 see drawing.
FEATURES
* UL Horizontal Load Rating: 1 -3 pipe size = 500#
4 -8 pipe size = 2015#
* Made with 1/2" bolts to conform with sway brace fittings.
ORDERING - Part #, pipe size and finish.
Speci products are exclusively designed to be compatible ONLY with other AFCO.Ypmducts including parts and fasteners. resulting inn listed sway brace. restrainer or hanger assembly.
Be adsised the following warranty restriction w ill apply. DISCLAIMER - AFCO.Y rill NOT warrant against the failure of its products when used in combination with other produ:ts, pans or systems
not manufaetura] or sold by AFCON. A FCO.V' shall NOT be liable under any eirmnnstaoe w hatsoeser for any direct or indirect. incidental or consequential damages of any kind, including but not
limited to loss of business or profit. when non- AFCON products have bent. or are used.
•
5/08 :._._
•
•
•
FPS ZO /O -' oa 1 53
•
•
Hydraulics Summary Sheet
, _ _ _ _ . _ ._EIRESTOP COMPANY,LLC - -.- Designer: - RO - GREEN -- -
3203 NE 65TH STREET SPACE 2 Calc By: RD GREEN
VANCOUVER, WA. 98663 Date: 12/1/2010
360- 718 -8604
• I '
Project Information Hydraulics
Information •
A DISTRIBUTORS
• 16316 SW 72ND'AVE. Demand...
BUILDING #3 Spr Req'd Pres: 45.63 PSI
Spr Req'd Flow: 1438.80 GPM
TIGARD, OR. Add'I Flows: 500.00 GPM
• Hose at Srce: 0.00 GPM.
I Contract No: Total Flow: 1938.80 GPM
• Building: #3
Total Pres: 47.04 PSI
System ID: A 8 I DISTRIBUTORS BLDG. #3 Static Elev: 0.00 Ft
Ref. Drawing No: FP -3
Construction: 16" WOOD PURL INS Supply...
Occupancy: WAREHOUSE Water Flow Test
Static: 103.00 PSI
Authority: CITY OF TIGARD Residual: 92.00 PSI
Oty Flowing: 1964.00 GPM
- -- — - -- - - - - -- Elevation: 0.00 Ft
System Information Date: Time:
'k
�� es
RR - F s
� �GINFF� /p I B y :
Hydraulics Design Criteria 17623 Pump Data
• System Type: WET / / / Rated: 0.0 PSI@ 0.0 GPM
Density: .30.GPM/SqFt �''"�
OREGON � Boost Pres: (NA) PSI
Remote Area: 4,000 SgFt 4D
;1 Discharge Pres: (NA) PSI
\ � Pa
Sprinkler Coverage: 117 ;qFt �, .FU 1 Discharge Flow: (NA) GPM
Design Standard: NEPA #13 (2007) _� '(
Hazard: EXTRA HAZARD
! Combined
Figure: Curve: 1 Static: (NA) PSI
Residual: (NA) PSI
Sprinklers / Nozzles
Qty Flowing: (NA) GPM
Manufacturer: TYCO i
Model: ELO -231 FRB
• Available...
Size: 3/4" NPT P) 92.26 PSI@ 1938.80 GPM
K- Factor: 11.2
F) 47.04 PSI@ 4727.83 GPM
Temp. Rating: 286F
Margin...
• • Pressure: 45.22 PSI
•
Flow: 2789.03 GPM
Sigma Dynamics Corporation
7700 Summary Sheet
•
•
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 1
•A &.I DISTRIBUTORS BLDG. #3
_
.30/4,000 WET SYSTEM
FLOW TEST - RESULTS --
Water Supply
STATIC 103.00 PSI
RESIDUAL 92.00 PSI @ 1964.00 GPM
CITY PRESSURE AVAILABLE AT 1938.8 GPM 92.26 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR • FLOW FLOW K- FACTOR PRESSURE
201 49.95 35.10 11.20 19.89
202 46.10 35.10 11.20 16.94
' 203 43.64 35.10 11.20 15.18
204 38.90 35.10 11.20 12.06
205 36.80 35.10 11.20 10.79
206 36.41 35.10 11.20 10.57
207 36.54 35.10 11.20 10.64
208 37.52 35.10 11.20 11.22
209 49.73 35.10 11.20 19.71
210 45.82 35.10 11.20 16.74
- 211 43.30 35.10 11.20 14.95
212 38.37 35.10 11.20 11.74
213 36.10 35.10 11.20 10.39
214 35.62 35.10 11.20 10.11
215 35.71 35.10 11.20 10.17
216 36.56 35.10 11.20 10.65
217 49.61 35.10 11.20 19.62
218 45.67 35.10 11.20 16.63
219 43.13 35.10 11.20. 14.83
220 38.11 35.10 11.20 11.58
221 35.76 35.10 11.20 10.19
222 35.22 35.10 11.20 9.89
223 35.31 35.10 11.20 9.94
224 36.10 35.10 11.20 10.39
225 49.53 35.10 11.20 19.56
226 45.59 35.10 11.20 16.57
227 43.05 35.10 11.20 14.77
228 38.01 35.10 11.20 11.52
•
•
•
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 2
A'& I DISTRIBUTORS BLDG. #3
.30/4,000 WET SYSTEM
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K- FACTOR PRESSURE
229 35.65 35.10 11.20 10.13
230 35.10 35.10 11.20 9.82
231 35.19 35.10 11.20 9.87
232 35.96 35.10 11.20 10.31
233 39.95 35.10 11.20 12.72
234 38.72 35.10 11.20 11.95
235 38.13 35.10 11.20 11.59
236 37.96 35.10 11.20 11.49
TOTAL WATER REQUIRED FOR SYSTEM 1438.80 GPM
OUTFLOWS AT 2 • • 500.00 GPM
TOTAL WATER REQUIREMENT 1938.80 GPM
PRESSURE REQUIRED AT 0 47.04 PSI
MAXIMUM PRESSURE UNBALANCE IN LOOPS 0.00 PSI
MAXIMUM VELOCITY FROM 121 TO 217 23.26 FPS
•
•
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 3
A & I DISTRIBUTORS BLDG. #3
.30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
142 236 1.710 L 4.30 C =120 PT 11.49 (236)
Q 37.96 F =T F 8.00 PE . 0.00
BN1 T 12.30 0.0394 PF 0.48
PT 11.97 (142)
141 235 1.710 L 4.30 C =120 PT 11.59 (235)
Q 38.13 F =T F 8.00 PE 0.00
BN1 T 12.30 0.0397 PF 0.49
PT 12.08 (141)
140 234 • • 1.710 L 4.30 C =120 PT 11.95 (234)
Q 38.72 F =T F 8.00 PE 0.00
BN1 T 12.30 0.0409 PF 0.50
PT 12.45 (140)
139 233 1.710 L 4.30 C =120 PT 1.2.72 (233)
Q 39.95 F =T F 8.00 PE 0.00
BN1 T 12.30 0.0433 PF 0.53
PT 13.25 (139)
231 230 1.710 L 9.50 C =120 PT 9.82 (230)
Q 3.82 F =0 F 0.00 PE 0.04
BL7 T 9.50 0.0006 PF 0.01
232 231DQ 35.19 1.710 L 9.50 C =120 PT 9.87 (231)
Q 39.00 F =0 F 0.00 PE 0.04
BL7 T 9.50 0.0414 PF 0.39
142 232DQ 35.96 1.710 L 4.00 C =120 PT 10.30 (232)
Q 74.96 F =T F 8.00 PE 0.00
BL7 T 12.00 0.1388 PF 1.67
42 142DQ 37.96 1.710 L 1.60 C =120 PT 11.97 (142)
Q 112.92 F =T F 8.00 PE 0.69
RN2 T 9.60 0.2962 PF 2.84
41 42 3.320 L 12.30 C =120 PT 15.50 ( 42)
Q 112.92 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0117 PF 0.14
PT 15.64 ( 41)
229 230 1.610 L 9.50 C =120 PT 9.82 (230)
Q 31.28 F =0 F 0.00 PE -0.04
BL7 T 9.50 0.0370 PF 0.35
228 229DQ 35.65 1.610 L 9.50 C =120 PT 10.13 (229)
Q 66.93 F =0 F 0.00 PE -0.04
BL7 T 9.50 0.1509 PF 1.43
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 4
A & I DISTRIBUTORS BLDG. #3
.30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
227 228DQ 38.01 1.610 L 9.50 C =120 PT 11.52 (228)
Q 104.94 F =0 F 0.00 PE -0.04
BL7 T 9.50 0.3469 PF 3.30
226 227DQ 43.05 2.067 L 9.50 C =120 PT 14.78 (227)
Q 147.99 F =0 F 0.00 PE -0.04
BL7 T 9.50 0.1940 PF 1.84
225 226DQ 45.59 2.067 L 9.50 C =120 PT 16.58 (226)
Q 193.58 F =0 F 0.00 PE -0.04
' BL7 T 9.50 0.3189 PF 3.03
122 225DQ 49.53 2.067 L 4.30 C =120 PT 19.57 (225)
Q 243.11 F=T F 10.00 PE 0.00
BL7 T 14.30 0.4861 PF 6.95
PT 26.52 (122)
223 222 1.710 L 9.50 C =120 PT 9.89 (222)
Q 4.19 F =0 F 0.00 PE 0.04
BL6 T 9.50 0.0007 PF 0.01
224 223DQ 35.31 1.710 L 9.50 C =120 PT 9.94 (223)
Q 39.50 F =0 F 0.00 PE 0.04
BL6 T 9.50 0.0424 PF 0.40
141 224DQ 36.10 1.710 L 4..00 C =120 PT 10.38 (224)
Q 75.60 F =T F 8.00 PE 0.00
BL6 T 12.00 0.1410 PF 1.69
' 41 141DQ 38.13 1.710 . L 1.60 C =120 PT 12.07 (141)
Q 113.73 F =T F 8.00 PE 0.69
RN2 T 9.60 0.3001 PF 2.88
40 41DQ 112.92 3.320 L 12.30 C =120 PT 15.64 ( 41)
Q 226.65 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0425 PF 0.52
PT 16.16 ( 40)
221 222 1.610 L 9.50 C =120 PT 9.89 (222)
Q 31.04 F =0 F 0.00 PE -0.04
BL6 T 9.50 0.0364 PF 0.35
220 221DQ 35.76 1.610 L 9.50 C =120 PT 10.20 (221)
Q 66.80 F =0 F 0.00 PE -0.04
BL6 T 9.50 0.1504 PF 1.43
i
I
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 5
• A & I DISTRIBUTORS BLDG. #3
• .30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
219 220DQ 38.11 1.610 L 9.50 C =120 PT 11.59 (220)
Q 104.91 F =0 F 0.00 PE -0.04
BL6 T 9.50 0.3467 PF 3.29
218 219DQ 43.13 2.067 L 9.50 C =120 PT 14.84 (219)
Q 148.04 F =0 F 0.00 PE -0.04
BL6 T 9.50 0.1941 PF 1.84
217 218DQ 45.67 2.067 L 9.50 C =120 PT 16.64 (218)
Q 193.71 F =0 F 0.00 PE -0.04
BL6 T 9.50 0.3193 PF 3.03
121 217DQ 49.61 2.067 L 4.30 C =120 PT 19.63 (217)
Q 243.32 F =T F 10.00 PE 0.00
BL6 T 14.30 0.4868 PF 6.96
PT 26.59 (121)
215 214 1.710 L 9.50 C =120 PT 10.11 (214)
Q 5.87 F =0 F 0.00 PE 0.04
BL5 T 9.50 0.0012 PF 0.01
216 215DQ 35.71 1.710 L 9.50 C =120 PT 10.16 (215)
Q 41.59 F =0 F 0.00 PE 0.04
BL5 T 9.50 0.0467 PF 0.44
140 216DQ 36.56 1.710 L 4:.00 C =120 PT 10.64 (216)
Q 78.14 F =T F 8.00 PE 0.00
BL5 T 12.00 0.1499 PF 1.80
40 140DQ 38.72 1.710 L 1.60 C =120 PT 12.44 (140)
Q 116.86 F =T F 8.00 PE 0.69
RN2 T 9.60 0.3156 PF 3.03
39 40DQ 226.65 3.320 L 12.30 C =120 PT 16.16 ( 40)
Q 343.51 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0917 PF 1.13
PT 17.29 ( 39)
213 214 1.610 L 9.50 C =120 PT 10.11 (214)
Q 29.74 F =0 F 0.00 PE -0.04
BL5 T 9.50 0.0337 PF 0.32
212 213DQ 36.10 1.610 L 9.50 C =120 PT 10.39 (213)
Q 65.84 F =0 F 0.00 PE -0.04
BL5 T 9.50 0.1464 PF 1.39
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 6
A & I DISTRIBUTORS BLDG. #3
.30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
_ in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
211 212DQ 38.37 1.610 L 9.50 C =120 PT 11.74 (212)
Q 104.21 F =0 F 0.00 PE -0.04
BL5 T 9.50 0.3424 PF 3.25
210 211DQ 43.30 2.067 L 9.50 C =120 PT 14.95 (211)
Q 147.51 F =0 F 0.00 PE -0.04
BL5 T 9.50 0.1929 PF 1.83
209 210DQ 45.82 2.067 L 9.50 C =120 PT 16.74 (210)
Q 193.33 F =0 F 0.00 PE -0.04
BL5 T 9.50 0.3181 PF 3.02
•
120 209DQ 49.73 2.067 L 4.30 C =120 PT 19.72 (209)
Q 243.06 F =T F 10.00 PE 0.00
BL5 T 14.30 0.4859 PF 6.95
PT 26.67 (120)
207 206 1.710 L 9.50 C =120 PT 10.57 (206)
Q 9.47 F =0 F 0.00 PE 0.04
BL4 T 9.50 0.0030 PF 0.03
208 207DQ 36.54 1.710 L 9.50 C =120 PT 10.64 (207)
Q 46.01 F =0 F 0.00 PE 0.04
BL4 T 9.50 0.0563 PF 0.53
139 208DQ 37.52 1.710 • L 4.00 C =120 PT 11.21 (208)
Q 83.53 F =T F 8.00 PE 0.00
BL4 T 12.00 0.1696 PF 2.04
39 139DQ 39.95 1.710 L 1.60 C =120 PT 13.25 (139)
Q 123.48 F =T F 8.00 PE 0.69
RN2 T 9.60 0.3495 PF 3.36
38 39DQ 343.51 3.320 L 12.30 C =120 PT 17.30 ( 39)
Q 466.99 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.1618 PF 1.99
PT 19.29 ( 38)
205 206 1.610 L 9.50 C =120 PT 10.57 (206)
Q 26.94 F =0 F 0.00 PE -0.04
BL4 T 9.50 0.0280 PF 0.27
204 205DQ 36.80 1.610 L 9.50 C =120 PT 10.80 (205)
Q 63.74 F =0 F 0.00 PE -0.04
BL4 T 9.50 0.1379 PF 1.31
' SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 7
A & I DISTRIBUTORS BLDG. #3
.30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
203 204DQ 38.9 1.610 L 9.50 C =120 PT 12.07 (204)
Q 102.63 F =0 F 0.00 PE -0.04
BL4 T 9.50 0.3329 PF 3.16
202 203DQ 43.64 2.067 L 9.50 C =120 PT 15.19 (203)
Q 146.27 F =0 F 0.00 PE -0.04
BL4 T 9.50 0.1899 PF 1.80
201 202DQ 46.10 2'.067 L 9.50 C =120 PT 16.95 (202)
Q 192.36 F =0 F 0.00 PE -0.04
BL4 T 9.50 0.3152 PF 2.99
119 201DQ 49.95 2.067 L 4.30 C =120 PT 19.90 (201)
Q 242.31 •F =T F 10.00 PE 0.00
BL4 T 14.30 0.4831 PF 6.91
PT 26.81 (119)
22 122 2.469 L 1.60 C =120 PT 26.51 (122)
Q 161.63 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0961 PF 1.31
21 22 6.065 L 12.30 C =120 PT 28.51 ( 22)
Q 161.63 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0012 PF 0.01
PT 28.52 ( 21)
• 21 121 2.469 L 1.60 C =120 PT 26.58 (121)
Q 157.74 F =T F 12.00 'PE 0.69
RN1 T 13.60 0.0919 PF 1.25
20 21DQ 161.63 6.065 L 12.30 C =120 PT 28.52 ( 21)
Q 319.37 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0043 PF 0.05
PT 28.57 ( 20)
20 120 2.469 L 1.60 C =120 PT 26.66 (120)
Q 155.85 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0899 PF 1.22
19 20DQ 319.37 6.065 L 12.30 C =120 PT 28.57 ( 20)
Q 475.22 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0089 PF 0.11
PT 28.68 ( 19)
19 119 2.469 L 1.60 C =120 PT 26.80 (119)
• Q 153.92 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0878 PF 1.19
•
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 8
A & I DISTRIBUTORS BLDG. #3
.30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
18 19DQ 475.22 6.065 L 12.30 C =120 PT 28.68 ( 19)
Q 629.15 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0149 PF 0.18
PT 28.86 ( 18)
138 38 1.710 L 1.60 C =120 PT 19.29 ( 38)
Q 68.90 F =T F 8.00 PE -0.69
RN2 T 9.60 0.1187 PF 1.14
308 138 , 1.710 L 49.00 C =120 PT 19.74 (138)
Q 68.90 F =T • F 8.00 PE -0.13
BL3 T 57.00 0..118 PF 6.77
118 308 2.067 L 23.00 C =120 PT 26.38 (308)
Q 68.90 F =T F 10.00 PE 0.00
BL1 T 33.00 0.0472 PF 1.56
18 118DQ -4.03 2.469 L 1.60 C =120 PT 27.94 (118)
Q 64.86 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0178 PF 0.24
•
17 18DQ 629.15 6.065 L 12.30 C =120 PT 28.87 ( 18)
Q 694.01 F =0 F. 0.00 PE 0.00
CM1 T 12.30 0.0179 PF 0.22
PT 29.09 ( 17)
37 38 3.320 L 12.30 C =120 PT 19.29 ( 38)
Q 398.09 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.1204 PF 1.48
137 37DQ - 334.21 1.710 L 1.60 C =120 PT 20.77 ( 37)
Q 63.88 F =T F 8.00 PE -0.69
RN2 T 9.60 0.1033 PF 0.99
307 137 1.710 L 49.00 C =120 PT 21.07 (137)
Q 63.88 F =T F 8.00 PE -0.13
BL3 T 57.00 0.1033 PF 5.89
117 307 2.067 L 23.00 C =120 PT 26.83 (307)
Q 63.88 F =T F 10.00 PE 0.00
BL1 T 33.00 0.0410 PF 1.35
17 117DQ -2.83 2.469 L 1.60 C =120 PT 28.18 (117)
Q 61.05 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0159 PF 0.22
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 9
. A & I DISTRIBUTORS BLDG. #3
.30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
16 17DQ 694.01 6.065 L 12.30 C =120 PT 29.09 ( 17)
Q 755.06 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0209 PF 0.26
PT 29.35 ( 16)
36 37 3.320 L 12.30 C =120 PT 20.78 ( 37)
Q 334.21 ' F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0871 PF 1.07
136 36DQ.- 275.42 1.710 L 1.60 C =120 PT 21.85 ( 36)
Q 58.80 F =T F 8.00 PE -0.69
RN2 T 9.60 0.0886 PF 0.85
306 136 1.710 L 49.00 C =120 PT. 22.01 (136)
Q 58.80 F =T F 8.00 PE -0.13
BL3 T 57.00 0.0886 PF 5.05
116 306 2.067 L 23.00 C =120 PT 26.93 (306)
Q 58.80 F =T F 10.00 PE 0.00
BL1 T 33.00 0.0352 PF 1.16
• 16 116DQ 44.58 2.469 L 1.60 C =120 PT 28.09 (116)
Q 103.37 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0420 PF 0.57
15 16DQ 755.06 6.065 L 12.30 C =120 PT 29.35 ( 16)
Q 858.43 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0265 PF 0.33
PT 29.68 ( 15)
35 36 3.320 L 12.30 C =120 PT 21.85 ( 36)
Q 275.42 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0609 PF 0.75
135 35DQ - 218.63 1.710 L 1.60 C =120 PT 22.60 ( 35)
Q 56.78 F=T F 8.00 PE -0.69
RN2 T 9.60 0.0830 PF 0.80
305 135 1.710 L 49.00 C =120 PT 22.71 (135)
Q 56.78 F =T F 8.00 PE -0.13
BL3 T 57.00 0.0830 PF 4.73
115 305 2.067 L 23.00 C =120 PT 27.31 (305)
Q 56.78 F =T F 10.00 PE 0.00
BL1 T 33.00 0.0330 PF 1.09
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 10
A & I DISTRIBUTORS BLDG. #3
.30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
15 115DQ 48.37 2.469 L 1.60 C =120 PT 28.40 (115)
Q 105.16 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0434 PF 0.59
14 15DQ 858.43 7.981 L 12.30 C =120 PT 29.68 ( 15)
Q 963. F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0086 PF 0.11
PT 29.79 ( 14)
34 35 3.320 L 12.30 C =120 PT 22.60 ( 35)
218.64 F =0 F 0.00 PE 0.00
CM2 T , 12.30 0.0397 PF 0.49
134 34DQ - 163.51 1.710 L 1.60. C =120 PT 23.09 ( 34)
Q 55.13 F =T F 8.00 PE -0.69
RN2 T 9.60 0.0786 PF 0.75
304 134 1.710 L 49.00 C =120 PT 23.15 (134)
• Q 55.13 F =T F 8.00 PE -0.13
BL3 T 57.00 0.0786 PF 4.48
114 304 2.067 L 23.00 C =120 PT 27.50 (304)
Q 55.13 F =T F 10.00 PE 0.00
BL1 T 33.00 0.0312 PF 1.03
14 114DQ 47.04 2.469 L 1.60 C =120 PT .28.53 (114)
Q 102.17 F =T F 12.00 • PE 0.69
RN1 T 13.60 0.0411 PF 0.56
13 14DQ 963.59 7.981 L 12.30 C =120 PT 29.78 ( 14)
Q 1065.76 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0104 PF 0.13
PT 29.91 ( 13)
318 122 2.067 L 5.50 C =120 PT 26.51 (122)
Q 20.37 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0049 PF 0.08
162 318 1.610 L 51.50 C =120 PT 26.59 (318)
Q 20.37 F =T F 8.00 PE -0.13
BL2 T 59.50 0.0167 PF 0.99
62 162 2.709 L 1.60 C =120 PT 27.45 (162)
Q 20.37 . F =T F 10.80 PE 0.69
RN3 T 12.40 0.0013 PF 0.02
•
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 11
A & I DISTRIBUTORS BLDG. #3
.30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN ' Devices Ft PSI /Ft PSI
61 62 2.709 L 12.30 C =120 PT 28.16 ( 62)
Q 20.37 F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0013 PF 0.02
PT 28.18 ( 61)
317 121 2.067 L 5.50 C =120 PT 26.58 (121)
. Q 19.79 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0047 PF 0.07
161 317 1.610 L 51.50 C =120 PT 26.65 (317)
Q 19.79 F =T F 8.00 PE -0.13
BL2 T 59.50 0.0158 PF 0.94
61 161 2.709 L 1.60 C =120 PT 27.46 (161)
Q 19.79 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0013 PF 0.02
60 61DQ 20.37 2.709 L 12.30 C =120 PT 28.17 ( 61)
Q 40.16 F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0047 PF 0.06
PT 28.23 ( 60)
316 120 2.067 L 5.50 C =120 PT 26.66 (120)
Q 19.55 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0046 PF 0.07
160 316 1.610 L 51.50 C=120 PT 26.73 (316)
Q 19.55 F =T F 8.00 PE • -0.13
BL2 T 59.50 0.0155 PF 0.92
60 160 2.709 L 1.60 C =120 PT 27.52 (160)
Q 19.55 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0012 PF 0.01
59 60DQ 40.16 2.709 L 12.30 C =120 PT 28.22 ( 60)
Q 59.71 F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0097 PF 0.12
PT 28.34 ( 59)
315 119 2.067 L 5.50 C =120 PT 26.80 (119)
Q 19.36 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0045 PF 0.07
159 315 1.610 L 51.50 C =120 PT 26.87 (315)
Q 19.36 F =T F 8.00 PE -0.13
BL2 T 59.50 0.0152 PF 0.90
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 12
' • A & I DISTRIBUTORS BLDG. #3
' .30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
59 159 2.709 L 1.60 C =120 PT 27.64 (159)
Q 19.36 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0012 PF 0.01
58 59DQ 59.71 2.709 L 12.30 C =120 PT 28.34 ( 59)
Q 79.07. F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0163 PF 0.20
PT 28.54 ( 58)
314 118 2.067 L 5.50 C =120 PT 27.94 (118)
• • Q 4.03 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0002 PF 0.00
' 158 314 1.610 L 51.50 C =120 PT 27.94 (314)
Q 4.03 F =T F 8.00 PE -0.13
BL2 T 59.50 0.0008 PF 0.05
58 158 2.709 L 1.60 C =120 PT 27.86 (158)
• Q 4.03 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0001 PF 0.00
' 57 58DQ 79.07 2.709 L 12.30 C =120 PT 28.55 ( 58)
Q • 83.11 F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0179 PF 0.22
PT •28.77 ( 57)
313 117 - 2.067 L 5.50 C =120 PT 28.18 (117)
Q 2.83 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0001 PF 0.00
157 313 1.610 L 51.50 C =120 PT 28.18 (313)
Q 2.83 F =T F 8.00 PE -0.13
BL2 T 59.50 0.0004 PF 0.02
57 157 2.709 L 1.60 C =120 PT 28.07 (157)
Q 2.83 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0000 PF 0.00
56 57DQ 83.11 2.709 L 12.30 C =120 PT 28.76 ( 57)
Q 85.94 F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0190 PF 0.23
PT 28.99 ( 56)
312 122 2.067 L 23.00 C =120 PT 26.51 (122)
Q 61.11 F =T F 10.00 PE 0.00
BL1 T 33.00 0.0378 PF 1.25
'
•
•
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 13
. A & I DISTRIBUTORS BLDG. #3
' .30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
156 312DQ -44.58 1.610 L 51.50 C =120 PT 27.76 (312)
' Q 16.54 F =T F 8.00 PE -0.13
BL2 T 59.50 0.0114 PF 0.68
56 156 2.709 L 1.60 C =120 PT 28.31 (156)
Q 16.54 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0009 PF 0.01
55 56DQ 85.94 2.709 L 12.30 C =120 PT 29.01 ( 56)
Q 102.47 F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0263 PF 0.32
PT 29.33 ( 55)
311 121 2.067 L 23.00 C =120 PT 26.58 (121)
Q 65.79 F =T F 10.00 PE 0.00
BL1 T 33.00 0.0433 PF 1.43
155 311DQ -48.37 1.610 L 51.50 C =120 PT 28.01 (311)
Q 17.42 F =T F 8.00 PE -0.13
BL2 T 59.50 0.0125 PF 0.74
• 55 155 2.709 L 1.60 C =120 PT 28.62 (155)
Q 17.42 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0010 PF 0.01
54 55DQ 102.47 2.709 L 12.30 C =120 PT 29.32 ( 55)
Q 119.89 F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0352 PF 0.43
PT 29.75 ( 54)
310 120 2.067 L 23.00 C =120 PT 26.66 (120)
Q 67.66 F =T F 10.00 PE 0.00
BL1 T 33.00 0.0456 PF 1.50
154 310DQ -47.04 1.610 L 51.50 C =120 PT 28.16 (310)
Q 20.61 F =T F 8.00 PE -0.13
BL2 T 59.50 0.0171 PF 1.02
54 154 2.709 L 1.60 C =120 PT 29.05 (154)
Q 20.61 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0014 PF 0.02
53 54DQ 119.89 2.709 L 12.30 C =120 PT 29.76 ( 54)
Q 140.50 F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0472 PF 0.58
PT 30.34 ( 53)
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 14
A & I DISTRIBUTORS BLDG. #3
.30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
309 119 2.067 L 23.00 C =120 PT 26.80 (119)
Q 69.03 F =T F 10.00 PE 0.00
BL1 T 33.00 0.0473 PF 1.56
153 309DQ -44.54 1.610 L 51.50 C =120 PT 28.36 (309)
Q 24.48 F =T F 8.00 PE -0.13
BL2 T 59.50 0.0235 PF 1.40
53 153 2.709 L 1.60 C =120 PT 29.63 (153)
Q 24.48 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0019 PF 0.02
8 53DQ 140.50 2.709 L 2.50 C =120 PT 30.34 ( 53)
Q 164.99 F =T F 10.80 PE 0.00
CM5 T 13.30 0.0636 PF 0.85
PT 31.19 ( 8)
33 34 3.320 L 12.30 C =120 PT 23.09 ( 34)
Q 163.51 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0232 PF 0.29
133 33DQ - 108.98 1.710 L 1.60 C =120 PT 23.38 ( 33)
Q 54.52 F =T F 8.00 PE -0.69
RN2 T 9.60 0.0770 PF 0.74
303 133 1.710 L 49.00 C =120 PT 23.43 (133)
Q 54.52 F =T F 8.00 PE -0.13
BL3 T 57.00 0.0770 PF 4.39
113 303 2.067 L 23.00 C =120 PT 27.69 (303)
Q 54.52 F =T F 10.00 PE 0.00
BL1 T 33.00 0.0306 PF 1.01
PT 28.70 (113)
32 33 3.320 L 12.30 C =120 PT 23.37 ( 33)
Q 108.98 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0110 PF 0.14
132 32DQ -54.17 1.710 L 1.60 C =120 PT 23.51 ( 32)
Q 54.81 F =T F 8.00 PE -0.69
RN2 T 9.60 0.0778 PF 0.75
302 132 1.710 L 49.00 C =120 PT 23.57 (132)
Q 54.81 F =T F 8.00 PE -0.13
BL3 T 57.00 0.0778 PF 4.43
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 15
A & I DISTRIBUTORS BLDG. #3
.30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
.From To GPM IN Devices Ft PSI /Ft PSI
112 302 2.067 L 23.00 C =120 PT 27.87 (302)
Q 54.81 F =T F 10.00 PE 0.00
BL1 T 33.00 0.0309 PF 1.02
12 112 2.469 L 1.60 C =120 PT 28.89 (112)
Q 54.81 F =T . F 12.00 PE 0.69
• RN1 T 13.60 0.0130 PF 0.18
PT 29.76 ( 12)
• 31 32 3.320 L 12.30 C =120 PT 23.51 ( 32)
Q 54.17 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0030 PF 0.04
131 31 1.710 L 1.60 C =120 PT 23.55 ( 31)
Q 54.17 F =T F 8.00 PE -0.69
RN2 T 9.60 0.0761 PF 0.73
301 131 1.710 L 49.00 C =120 PT 23.59 (131)
. Q 54.17 F =T F 8.00 PE -0.13
BL3 T 57.00 0.0761 PF 4.34
111 301 2.067 L 23.00 C =120 PT 27.80 (301)
Q 54.17 F =T F 10.00 PE '0.00
BL1 T 33.00 0.0302 PF 1.00
11 111 2.469 L 1.60 C =120 PT 28.80 (111)
Q 54.17 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0127 PF 0.17
12 11 2.709 L 12.30 C =120 PT 29.66 ( 11)
Q 54.17 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0081 PF 0.10
9 12DQ 54.81 2.709 L 10.00 C =120 PT 29.76 ( 12)
Q 108.98 F =T F 10.80 PE 0.00
CM1 T 20.80 0.0295 PF 0.61
PT 30.37 ( 9)
116 312 2.067 L 5.50 C =120 PT 27.76 (312)
Q 44.58 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0211 PF 0.33
PT 28.09 (116)
115 311 2.067 L 5.50 C =120 PT 28.01 (311)
Q 48.37 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0245 PF 0.38
PT 28.39 (115)
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 16
A & DISTRIBUTORS BLDG. #3
.30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
114 310 2.067 L 5.50 C =120 PT 28.17 (310)
Q 47.04 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0233 PF 0.36
PT 28.53 (114)
113 309 2.067 L 5.50 C =120 PT 28.36 (309)
Q 44.54 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0210 PF 0.33
13 113DQ • 54.52 2.469 L 1.60 C=120 PT 28.69 (113)
Q 99.07 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0389 PF 0.53
9 13DQ 1065.76 7.981 L 2.30 C =120 PT 29.91 ( 13)
Q 1164.83 F =T F 35.00 PE 0.00
' CM1 T 37.30 0.0123 PF 0.46
8 9DQ 108.98 7.981 L 57.00 C =120 PT 30.37 ( 9)
Q 1273.81 F =0 F 0.00 PE 0.00
CM4 T 57.00 0.0145 PF 0.83
10 8DQ 164.99 7.981 L 1.50 C =120 PT 31.20 ( 8)
Q 1438.80 F =E F 18.00 PE 0.00
FM4 T 19.50 0.0181 PF 0.35
7 10 7.981 L 13.50 C=120 PT 31.55 ( 10)
. Q 1438.80 F =E F . 18.00 PE 5.85
FR3 T . 31.50 0.0181 PF 0.57
6 7 6.065 L 1.90 C =120 PT 37.97 ( 7)
Q 1438.80 F =0 F 0.00 PE 0.82
FR2 T 1.90 0.0690 PF 0.13
5 6 6.065 L 2.10 C =120 PT 38.92 ( 6)
Q 1438.80 F =T,GV F 33.00 PE 0.91
FR1 T 35.10 0.0690 PF 2.42
4 5 7.981 L 1.50 C =120 PT 42.25 ( 5)
Q 1438.80 F =T F 35.00 PE 0.00
FM2 T 36.50 0.0181 PF 0.66
3 4 10.100 L 1.00 C =120 PT 42.91 ( 4)
Q 1438.80 F =0 F 0.00 PE 0.43
FM1 T 1.00 0.0058 PF 0.01
SUBMITTAL SERIAL NO:4126HY1 12 -01 -2010 PAGE 17
• A ;& I DISTRIBUTORS BLDG. #3
.30/4,000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
2 3 10.280 L 25.00 C =140 PT 43.35 ( 3)
Q 1438.80 F =67/0 F 67.00 PE 0.00
UN3 T 92.00 0.0040 PF 0.37
1 2DQ 500.00 10.280 L 300.00 C =140 PT 43.72 ( 2)
Q 1938.80 F =67/0 F 67.00 PE 0.00
UN2 T 367.00 0.0069 PF 2.53
0 1 12.340 L 280.00 C =140 PT 46.25 ( 1)
Q 1938.80 F =0 F 0.00 PE 0.00
UN1 T 280.00 0.0028 PF 0.78
PT 47.03 ( 0)
1
A & I DISTRIBUTORS BLDG. #3 Sigma Dynamics Corporation
250 r I , —_ _ 7700 Supply / Demand Graph
240 - 1 - l - - I -.. - I -
2301---,I-- -- - -... --
Margin
220 -- - - -- -- 1 - -_- ! __.. _ Pressure 45.22 PSI
_ �- - - Flow 2789.03 GPM
210 — -- — —
200 - --1-- -
180 _ — -- I
170 — — — —
—
160 -
150 I I
140 )
130
2 120 1 - --
--
a. 110 -I
100 ° —i —I
90 _ . —. - J - -- -_7
......„1........_
80 r — — -. S 70 I — --
-
50 -- ; ° -- Hoses -- — •
40 — ' 30
,t`K1efs — -
10 ( O
0 �4 N 1.85
250 500 750 1000 1250 1500 1750 2000 2250 2500
Water Flow (GPM)
System Demand.. Water Supply..
Sprinkler Demand 45.63 PSI @ 1438.80 GPM Static 103.00 PSI
Additional Flows 500.00 GPM Residual 92.00 PSI @ 1964.00 GPM
Hose at Source 0.00 GPM Elevation 0.00 PSI
Total Demand 47.04 PSI @ 1938.80 GPM
V
•
•
•
-... :
Section 9.3 o Protection of Piping Against Damage Where Subject to Earthquakes 37
i
astir,__ ' _________
1 i fire- Seismic Bracing Calculations Sheet ` of _
•'ith an . A
1111 are A 4 fl 1 STM 1 g�:) I ) 06
Contractor F1 f.j_1'J P �DlYl m AI Y
ect: -
•r'ario
- Address: Proj I G > I 5 ti) i 7 ,- " AVE Address: '��' N E. � v �' ��' -
• :ICp Dp l/ .+
pt.-b 6 t i 3 ( ,i'^ 1 tb )) L , Telephone: i 6 of 7 1 `S 64. :0 — --
Fax r 6 � ) , 1 1 ?) . 16 r .`,'e a.
11 hers s
uld he
• Brace Information Seismic Brace Attachments
ill(' be • - ;1
10 - ( iv\,N X • Structure attachment fitting or tension -only bracing system:
Limn. Length of brace: •
n
I I i Make: A 1' '12""n 14 , Model: 0 1 7
•
Diameter of brace: 20 1S 1'41+ >,
Type of brace: 51.40 Listed load rating: Adjusted load rating per 9.3.5.10.3:
in the ,1..5-0-b) S 'e Sway brace (pipe attachment) fitting: •
Angle of brace A F (a 0 1.1 1 :
+ E / ,� 0 1
fv1ake: _ Model
I . `ys Least radius of gyration :' — ' 2_ Listed load rating: ?� • Ad l oa d rating per 9.3.5.10.3: SU
out of UR value:• 3 o 0
j. re- Maximum horizontal load: _. -_ _ ._ ______ Seismic Brace Assembly Detail
(Provide detail on plans)
'{-x 1 Pty g.±) 1 U ._.•- A F n T 0 7 7
Fastener Information :.e---- 45'3 a,b j°
f
rider Orientation of connecting surface: )" aLAc r 5/43 PIPE
1 (11 "r k t 1f- 1 t1 t,..
as re- Fastener: _ } revs r1 bn _ ? ,L' N r
-
ThY.
Type: I 1 AFC.or+) An 0bE �.
n_'itu
9.14. Diameter: A t 00 3tt P/�AIN O O 1
S/)
alLral Length (in wood): ' � ''
3 ,�
1 11,<1d Maximum load: 3 S Brace identification no. �1 D 1?
acing (to be used on plans) _ -._. - -. -..- a , Lo • ^,F s);1
Lateral brace I Li Longitudinal brace
i roni
and Sprinkler System Load Calculation [F -__W (default is 0.5)]
Iulta-
Diameter Type Length (ft) Total (ft) Weight per ft 1. p Total Weight
_ 3 11 Si) 0 12 -I- 19 1 ; 1 I - 7. 9 4-
. I; the . 1 ` 1 s/) o 21' . " 1 - - 2 1 ' + ? 1 I / 4' 3 , 0 4 lbift 4 , 5 = 9 lb
,ntal. • -
I I /, " S/ 4- 1 ' -.- it ' 4 -' 3 • Co i lb/ft ' .S = - 7 6 lb
!ward . 0 PROF , . lb /ft lb
..h..re _ /.3.41511 to tb!ft lb
iv - A cr / 1 Total weight 9 6 l
.7
�%� _ ,..��.LlE l, 340 lb
Excludes tension -only bracino systems II 1 ' OREG 1 f4 i
itntal - ;, � k
FIGURE 4.9.3.5(a) Scismic Bracing Calculation Form. ETH D.�
SIRES: 0 1/ /1
• 'book . Automatic Sprinkler Systems Handbook 2002
antic: Section 9.3 • Protection of Piping Against Damage Where Subject to Earthquakes 37.c.:.
1
: — — - - - - - -- — — Seismic Bracing Calculations
fi fire- Sheet of
lt an
tat .are A ` TT b I STR. I btu i i k) .5- F\ R S-m• Q Cite PA P� Y
Project: Contractor: —_ -_
' 'izuion i 6 3 l 6 5 ✓!J '-i A E • 3 —0 3 N E 4 ST .57, _ea "y'
Address: --- - -- — -- Address: — --
Y . _
--i6A R. Y - • VANCOUVER WA... 9'6 oh
:lepee_ �7Lb -. #g(A^Ibb► -0 S6 /1 S ` r
p Tzlephone: ' --- --.- --
nh
Fax: (_ -- cq
ters _
uld'he
Brace Information • Seismic Brace Attachments
• Move-
• uld.be I -
1 NI A x . Structure attachment fitting or tension -only bracing system:
.umn. • Length of brace: Q t 1
l l+ Make: 7 ,1 N . Model: 0 7 7� 0 7 53
Diameter of brace: -w 5 -7 i '' 1 41-2- >
Ski— et Listed load rating 2 _ Adj load r per 9.3.5. t 0.3 _ L_ _
Type of brace:
in the .. 5' 59 o Sway brace (pipe attachment) fitting:
'Angle of brace: _ �, ()
..___ 0
Make " M _... -_
Least radius of gyration:'? 50 0 ' rr 4) 3S
if sys- Listed load rating: ___ Adjusted load rating pa: 9.3.5 10.3: _ —_.
rut of UR value:' 2. 00
IN re- Maximum horizontal load: _ -) J._ 7 3l - -__._ Seismic Brace Assembly Detail
(Provide detail on plans)
( 6 Ls
( . - Arc . - 077
• Fastener Information /
— ' 1.. 7
Orientation of connecting surface: r
cider t +
as're . Fastener: Vz" Tk ravrl >n 6611 t AFGojrJ o7
Type: � ivie - RFGo 0 d-1 0
11.! ltU- ;�
rl. I �. Diameter- j2 II 1" gt,f\ .
:tieriil Length (in uvoodl: r � S /�, pl PE_ �-- '/ I e M p r N
t Irr::d 3 SO- Br ace identification no. S 3 Cr 112)D 1 Z ,
Maximum load:
acing u
(to be used on Dns) --.. S o , n F .,S r
"i .r
Lateral brace iLongitudinat brace
iC(1in
• -I and Sprinkler System Load Calculation [F - W (default is 0.5)]
,ulta- •.
Diameter Type Length (ft) Total (ft) Weight per ft K , ; Total Weight
II 3 t 431 • t
ture.. S /)0 ZS
7,14 Ib!f , lb
le the . —
;�� y� 5 = Z ] O VtQN - IF�e
� ` Ib;ft lb
/ . ` : _ _ � Ib/ft lb
iu °aid
Ib /fl lb
h_rz ' �o / �= /� � 7 !tit It) t .
�, v r Total weight z —7 0 lb
-
F ;. 1. t 5 S i' lb
- -
Excludes tension-only bracing system �
:rmut) _ MIRES: _/
■ FIGURE, A.9.3. 5(a) Seismic Bracing Calculation Form.
book Automatic Sprinkler Systems Handbook 2002
i .
•
Section 9.3 • Protection of Piping Against Damage Where Subject to Earthquakes 75
1 -
--- ast1C— - •— ---- - - - - - -- - --
Seismic Bracing Calculations
h fire. Sheet 3 of
•itha
are A T fl 1 sr' [3'U T) N6- >; \ (L.E5 - To P Conn pA a; Y
Pr oject: 1� Contractor
ratio,/ I- • l S y1 7 2� d AVE • Add ress: 3Z O 3 N E 6, 5 �` C a e 4 L
Address: � _ - - -__ - _ T /
7716 rz- - VANcoUVER. wA c l3G .'
:lepen- st._b Cr - #- 3 (M, bb t....-E) Telephone: t l 6
--
•
F ax,: s 4 *) I B s_6 1 3
't nbers
uld he Brace Information Seismic Brace Attachments
more_
uld be k I
unlit. Length of brace:
-I M A X , Structure attachment fitting or tension -only bracing system:
1 H Make: A Fc N Model: 0 77 i 0 7 8
S
•• Diameter of brace: I .15 5' 1 5- C14- 0 Listed load rating: Adjusted load rating per 9.3.5.10.3: -.4-- � '
Type of brace:
in the / e, Sway brace (pipe attachment) fitting:
Angle of.brace: 1J
• fvlake: / n ` r — Model: _ ) d
Least radius of gyration: -_— . 4 Z l - I 1 \ S c -)�
,I. sys Z O Listed load rating: - Adjusted load rating per 9.3.5.10.3: •__
tint of UR value:•
is re- Maximum 4 Seismic Brace Assembly Maximum aximum horizontal load: _. -_ - f � 2 - 4 ____ Si i B A bl y Detail
e'' BLS (Provide detail on plans)
•
Fastener Information
7 ...-•'/A ��� 3'77
c9 ci
• Skier Orientation of connecting surface: F my.
AFc.•0N a
as•re- • Fastener: 7)
•
C _
Type: T)-,1 1 st . I ••, \ T 'retjc.1 A f' ' \ 41 0
wiitu- 9.14. Diameter: A_ ,t bolt �?��
:,lcral Length (in wood): Z ►7 t 1 l t, 5/ cep 0
Maximum load: _ identification no.
:icing (O 4 (to be used on plans) - - - . 5 g .. ._.. 1 4 t■• CIF /;-1
13 Lateral brace I [C Longitudinal brace
front
and Sprinkler System Load Calculation [F = W (default is 0.5)]
mita-
Diameter Type I (ft) Total (ft) Weight per ft Total Weight
:lure. t, / �2 fi l 3 Z S f 3, 6 Iblft�(,s =3 9 'P lb
le the . . tb/tt lb
' lb /ft lb
petal. . � c� ( � (1 PRO h
.. award .
lb/ft lb
•
!here
tr � 7..c Ib'ft lb
/ Total weight 3 9 4 lb
li„ 1. r i fs. . / Fr 1.15 4. ; lb
' Excludes tension -only bracing systems \ 1 4 J 17,'\•' i
:unta _
�!E7H ®
FIGURE A.9.3.5(a) Seismic Rracin: Calculr„iaa Farr,,. I
1,■.t.IRES •
. 'book . Automatic Sprinkler Systems Handbook 2002
1 3 5 26 JO- 00 /53
AU X- 4'2e4 o X ��C. 0ele klICKS
. so 6 PM lZooc. Sc. Fr'.
• • 1PS2olo -aoI
Hydraulics Summary Sheet
FIRESTOP COMPANY,LLC Designer: RD GREEN
3203 NE 65TH STREET SPACE 2 Calc - By: RD - GREEN - VANCOUVER, WA. 98663 Date: 12/7/2010
360- 718 -8604
• Project Information Hydraulics
Information
A & I DISTRIBUTORS
16316 SW 72ND AVE. Demand...
BUILDING #3 Spr Req'd Pres: 68.37 PSI
TIGARD, OR. Spr Req'd Flow: 1118.77 GPM
Add'I Flows: 500.00 GPM
Hose at Srce: 0.00 GPM
Contract No: AREA BTW GRIDS 10 & 12
Building: RACK AREA OF BLDG. #3 Total Flow: 1618.77 GPM
System ID: A & I DISTRIBUTORS BLDG. #3 Total Pres: 69.55 PSI
Ref. Drawing No: FP -3
Static Elev: 0.00 Ft
Construction: 16" WOOD PURLINS Supply...
Occupancy: WAREHOUSE Water Flow Test
Static: 103.00 PSI
Authority: CITY OF TIGARD Residual: 92.00 PSI
Qty Flowing: 1964.00 GPM
Elevation: 0.00 Ft
System Information Date: Time:
By:
•
Hydraulics Design Criteria Pump Data
System Type: WET Rated: 0.0 PSI@ 0.0 GPM
Density: .50 GPM /SgFt Boost Pres: (NA) PSI
Remote Area: 2,000 SgFt Discharge Pres: (NA) PSI
Sprinkler Coverage: 117 SqFt Discharge Flow: (NA) GPM
Design Standard: NFPA #13 (2007)
Hazard: EXTRA HAZARD Combined
Figure: Curve: Static: (NA) PSI
Residual: (NA) PSI
Sprinklers / Nozzles Qty Flowing: (NA) GPM
Manufacturer: TYCO Q�rcO PROFFS
Model: ELO-231 F-.7 .��GIN64c,02 A P X1 95.31 PSI@ 1618.77 GPM
Size: 3/4" NPT; 4, 1 r
K— Factor: 11.2 / Jr /� �_ - F) 69.55 PSI @ 3580.72 GPM
Temp. Rating: 286F r. OREGON
431 �, Margin...
/i D 0 5 Pressure: 25.76 PSI
MIRES: / j Flow: 1961.95 GPM
Sigma Dynamics Corporation
7700 Summary Sheet ,
SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 1
A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
• FLOW TEST RESULTS
Water Supply
STATIC 103.00 PSI
RESIDUAL 92.00 PSI @ 1964.00 GPM
CITY PRESSURE AVAILABLE AT 1618.8 GPM 95.31 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K- FACTOR PRESSURE
401 63.73 58.50 11.20 32.38
402 64.54 58.50 .11.20 33.20
403 69.53 58.50 11.20 38.54
404 61.73 58.50 11.20 30.38
405 62.47 58.50 11.20 31.11
406 67.01 58.50 11.20 35.80
407 58.94 58.50 11.20 27.69
408 59.54 58.50 11.20 28.26
409 63.11 58.50 11.20 31.75
410 58.50 58.50 11.20 27.28
411 59.05 58.50 11.20 27.79
412 62.15 58.50 11.20 30.80
413 58.75 58.50 11.20 27.52
414 59.27 58.50 11.20 28.00
415 62.22 58.50 11.20 30.86
416 61.74 58.50 11.20 30.39
417 62.14 58.50 11.20 30.78
418 64.35 58.50 11.20 33.01
TOTAL WATER REQUIRED FOR SYSTEM 1118.77 GPM
OUTFLOWS AT 2 500.00 GPM
TOTAL WATER REQUIREMENT 1618.77 GPM
PRESSURE REQUIRED AT 0 69.55 PSI
MAXIMUM PRESSURE UNBALANCE IN LOOPS 0.00 PSI
MAXIMUM VELOCITY FROM 12 TO 9 24.78 FPS
•
" SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 2
A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
1.610 L 9.50 C =120 PT 0.00 (410
Q 22.64 F =0 F 0.00 PE 0.04
BL1 T 9.50 0.0203 PF 0.19
416 413DQ' 58.75 1.710 L 9.50 C =120 PT 0.23 (413)
Q 81.39 F =T F 8.00 PE 0.04
BL1 T 17.50 0.1616 PF 2.83
131 416DQ 61.74 1.710 L 12.00 C =120 PT 3.10 (416)
Q 143.14 F =T F 8.00 PE 0.04
BL1 T 20.00 0.4593 PF 9.19
31 131 1.710 L 1.60 C =120 PT 12.33 (131)
Q 143.14 F =T F 8.00 PE 0.69
RN2 T 9.60 0.4593 PF 4.41
32 31 3.320 L 12.30 C =120 PT 17.43 ( 31)
Q 143.14 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0181 PF 0.22
33 32DQ 142.16 3.320 L 12.30 C =120 PT 17.65 ( 32)
Q 285.30 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0650 PF 0.80
34 33DQ 133.78 3.320 L 12.30 C =120 PT 18.45 ( 33)
Q 419.07 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.1324 PF 1.63
35 34DQ -57.27 3.320 L 12.30 C =120 PT 20.08 ( 34)
Q 361.81 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.1009 PF 1.24
36 35DQ -52.51 3.320 L 12.30 C =120 PT 21.32 ( 35)
Q 309.30 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0755 PF 0.93
37 36DQ -48.59 3.320 L 12.30 C =120 PT 22.25 ( 36)
Q 260.70 F =0. F 0.00 PE 0.00
CM2 T 12.30 0.0550 PF 0.68
38 37DQ -45.56 3.320 L 12.30 C =120 PT 22:93 ( 37)
Q 215.14 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0386 PF 0.47
138 38DQ - 171.82 1.710 L 1.60 C =120 PT 23.40 ( 38)
Q 43.33 F =T F 8.00 PE -0.69
RN2 T 9.60 0.0503 PF 0.48
•
SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 3
A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
308 138 1.610 L 49.00 C =120 PT 23.19 (138)
Q 43.33 F =T F 8.00 PE -0.13
BL3 T 57.00 0.0675 PF 3.85
118 308 2.067 L 23.00 C =120 PT 26.91(308)
Q 43.33 F =T F 10.00 PE -0.09
BL1 T 33.00 0.0200 PF 0.66
PT 27.48 (118)
137 37 1.710 L 1.60 C =120 PT 50.22 ( 37)
Q 45.56 F =T F 8.00 PE -0.69
RN2 T 9.60 0.0553 PF 0.53
307 137 1.610 L 49.00 C =120 PT 50.06 (137)
Q 45.56 F =T F 8.00 PE -0.13
BL3 T 57.00 0.0741 PF 4.22
117 307 2.067 L 23.00 C =120 PT 54.15 (307)
Q 45.56 F =T F 10.00 PE -0.09
BL1 T 33.00 0.0219 PF 0.72
PT 54.78 (117)
136 36 1.710 L 1.60 C =120 PT 49.54 ( 36)
Q 48.59 F =T F 8.00 PE -0.69
RN2 T 9.60 0.0622 PF 0.60
306 136 1.610 L 49.00 C =120 PT 49.45 (136)
Q 48.59 F =T F 8.00 PE -0.13
BL3 T 57.00 0.0835 PF 4.76
116 306 2.067 L 23.00 C =120 PT 54.08 (306)
Q 48.59 F =T F 10.00 PE -0.09
BL1 T 33.00 0.0247 PF 0.82
PT 54.81 (116)
135 35 1.710 L 1.60 C =120 PT 48.62 ( 35)
Q 52.51 F =T F 8.00 PE -0.69
RN2 T 9.60 0.0718 PF 0.69
305 135 1.610 L 49.00 C =120 PT 48.62 (135)
Q 52.51 F =T F 8.00 PE -0.13
BL3 T 57.00 0.0963 PF 5.49
115 305 2.067 L 23.00 C =120 PT 53.98 (305)
Q 52.51 F =T F 10.00 PE -0.09
BL1 T 33.00 0.0285 PF 0.94
PT 54.83 (115)
SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 4
A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM. IN Devices Ft PSI /Ft PSI
134 34 1.710 L 1.60 C =120 PT 47.37 ( 34)
Q 57.27 F =T F 8.00 PE -0.69
RN2 T ,9.60 0.0843 PF 0.81
304 134 1.610 L 49.00 C =120 PT 47.49 (134)
Q 57.27 F =T F 8.00 PE -0.13
BL3 T 57.00 0.1131 PF 6.45
114 304 2.067 L 23.00 C =120 PT 53.81 (304)
Q 57.27 F =T F 10.00 PE -0.09
BL1 T 33.00 0.0335 PF 1.11
PT 54.83 (114)
415 412 1.610 L 9.50 C =120 PT 30.80 (412)
Q 7.20 F =0 F 0.00 PE 0.04
BL1 T 9.50 0.0024 PF 0.02
418 415DQ 62.22 1.710 L 9.50 C =120 PT 30.86 (415)
Q 69.42 F =T F 8.00 PE 0.04
BL1 T 17.50 0.1204 PF 2.11
133 418DQ 64.35 1.710 L 12.00 C =120 PT 33.01 (418)
Q 133.78 F =T F 8.00 PE 0.04
BL1 T 20.00 0.4053 PF 8.11
33 133 1.710 L 1.60 C =120 PT 41.16 (133)
Q 133.78 F =T F 8.00 PE 0.69
RN2 T 9.60 0.4053 PF 3.89
PT 45.74 ( 33)
414 411 1.610 L 9.50 C =120 PT 27.79 (411)
Q 20.75 F =0 F 0.00 PE 0.04
BL1 T 9.50 0.0173 PF 0.16
417 414DQ 59.27 1.710 L 9.50 C =120 PT 27.99 (414)
Q 80.02 F =T F 8.00 PE 0.04
BL1 T 17.50 0.1566 PF 2.74
132 417DQ 62.14 1.710 L 12.00 C =120 PT 30.77 (417)
Q 142.16 F =T F 8.00 PE 0.04
BL1 T 20.00 0.4535 PF 9.07
32 132 1.710 L 1.60 C =120 PT 39.88 (132)
Q 142.16 F =T F 8.00 PE 0.69
RN2 T 9.60 0.4535 PF 4.35
PT 44.92 ( 32)
` SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 5
A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
409 412 1.610 L 9.50 C =120 PT 30.80 (412)
Q 54.95 F =0 F 0.00 PE -0.04
BL1 T 9.50 0.1048 PF 1.00
406 409DQ 63.11 1.610 L 9.50 C =120 PT 31.76 (409)
Q 118.06 F =0 F 0.00 PE -0.04
BL1 T 9.50 0.4313 PF 4.10
403 406DQ 67.01 2.067 L 9.50 C =120 PT 35.82 (406)
Q 185.07 F =0 F 0.00 PE -0.04
BL1 T 9.50 0.2934 PF 2.79
113 403DQ 69.53 2.067 L 16.70 C =120 PT 38.57 (403)
Q 254.60 F =T F 10.00 PE -0.04
BL1 T 26.70 0.5294 PF 14.13
PT 52.66 (113)
408 411 1.610 L 9.50 C =120 PT 27.79 (411)
Q 38.29 F =0 F 0.00 PE -0.04
BL1 T 9.50 0.0537 PF 0.51
405 408DQ 59.54 1.610 L 9.50 C =120 PT 28.26 (408)
Q 97.83 F =0 F 0.00 PE -0.04
BL1 T 9.50 0.3046 PF 2.89
402 405DQ 62.47 2.067 L 9.50 C =120 PT 31.11 (405)
Q 160.30 F =0 F 0.00 PE -0.04
BL1 T 9.50 0.2249 PF 2.14
112 402DQ 64.54 2.067 L 16.70 C =120 PT 33.21 (402)
Q 224.84 F =T F 10.00 PE -0.04
BL1 T 26.70 0.4206 PF 11.23
12 112 2.469 L 1.60 C =120 PT 44.40 (112)
Q 224.84 F =T F 12.00 PE 0.69
RN1 T 13.60 0.1770 PF 2.41
PT 47.50 ( 12)
407 410 1.610 L 9.50 C =120 PT 27.28 (410)
Q 35.86 F =0 F 0.00 PE -0.04
BL1 T 9.50 0.0476 PF 0.45
404 407DQ 58.94 1.610 L 9.50 C =120 PT 27.69 (407)
Q 94.80 F =0 F 0.00 PE -0.04
BL1 T 9.50 0.2874 PF 2.73
SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 6
A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
401 404DQ 61.73 2.067 L 9.50 C =120 PT 30.38 (404)
Q 156.53 F =0 F 0.00 PE -0.04
BL1 T 9.50 0.2152 PF 2.04
111 401DQ 63.73 2.067 L 16.70 C =120 PT 32.38 (401)
Q 220.26 F =T F 10.00 PE -0.04
BL1 T 26.70 0.4049 PF 10.81
11 111 2.469 L 1.60 C =120 PT 43.15 (111)
Q 220.26 F =T F 12.00 PE 0.69
RN1 T 13.60 0.1704 PF 2.32
12 11 2.709 L 12.30 C =120 PT 46.16 ( 11)
Q 220.26 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.1085 PF 1.33
9 12DQ 224.84 2.709 L 10.00 C =120 PT 47.49 ( 12)
Q 445.09 F =T F 10.80 PE 0.00
CM1 T 20.80 0.3986 PF 8.29
PT 55.78 ( 9)
39 38 3.320 L 12.30 C =120 PT 50.69 ( 38)
Q 171.82 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0254 PF 0.31
40 39DQ -43.91 3.320 L 12.30 C =120 PT 51.00 ( 39)
Q 127.91 F =0 F . 0.00 PE 0.00
CM2 T 12.30 0.0147 PF 0.18
41 40DQ -42.97 3.320 L 12.30 C =120 PT 51.18 ( 40)
Q 84.93 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0069 PF 0.08
42 41DQ -42.53 3.320 L 12.30 C =120 PT 51.26 ( 41)
Q 42.41 F =0 F 0.00 PE 0.00
CM2 T 12.30 0.0019 PF 0.02
142 42 1.710 L 1.60 C =120 PT 51.28 ( 42)
Q 42.41 F =T F 8.00 PE -0.69
RN2 T 9.60 0.0484 PF 0.46
232 142 1.710 L 4.00 C =120 PT 51.05 (142)
Q 42.41 F =T F 8.00 PE 0.00
BL7 T 12.00 0.0484 PF 0.58
231 232 1.710 L 9.50 C =120 PT 51.63 (232)
Q 42.41 F =0 F 0.00 PE -0.04
BL7 T 9.50 0.0484 PF 0.46
` SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 7
A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
230 231 1.710 L 9.50 C =120 PT 52.05 (231)
Q 42.41 F =0 F 0.00 PE -0.04
BL7 T 9.50 0.0484 PF 0.46
229 230 1.610 L 9.50 C =120 PT 52.47 (230)
Q 42.41 F =0 F 0.00 PE -0.04
BL7 T 9.50 0.0649 PF 0.62
228 229 1.610 L 9.50 C =120 PT 53.05 (229)
Q 42.41 F =0 F 0.00 ' PE -0.04
BL7 T 9.50 0.0649 PF 0.62
227 228 1.610 L 9.50 C =120 PT 53.63 (228)
Q 42.41 F =0 F 0.00 PE -0.04
BL7 T 9.50 0.0649 PF 0.62
226 227 2.067 L 9.50 C =120 PT 54.21 (227)
Q 42.41 F =0 F 0.00 PE -0.04
BL7 T 9.50 0.0192 PF 0.18
225 226 2.067 L 9.50 C =120 PT 54.35 (226)
Q 42.41 F =0 F 0.00 PE -0.04
BL7 T 9.50 0.0192 PF 0.18
122 225 2.067 L 4.30 C =120 PT 54.49 (225)
Q 42.41 F =T F 10.00 PE 0.00
BL7 T 14.30 0.0192 PF 0.27
PT 54.76 (122)
141 41 1.710 L 1.60 C =120 PT 51.27 ( 41)
Q 42.53 F =T F 8.00 PE -0.69
RN2 T 9.60 0.0486 PF 0.47
224 141 1.710 L 4.00 C =120 PT 51.05 (141)
Q 42.53 F =T F 8.00 PE 0.00
BL6 T 12.00 0.0486 PF 0.58
223 224 1.710 L 9.50 C =120 PT 51.63 (224)
Q 42.53 F =0 F 0.00 PE -0.04
BL6 T 9.50 0.0486 PF 0.46
222.223 1.710 L 9.50 C =120 PT 52.05 (223)
Q 42.53 F =0 F 0.00 PE -0.04
BL6 T 9.50 0.0486 PF 0.46
221 222 1.610 L 9.50 C =120 PT 52.47 (222)
Q 42.53 F =0 F 0.00 PE -0.04
BL6 T 9.50 0.0652 PF 0.62
SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 8
A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
220 221 1.610 L 9.50 C =120 PT 53.05 (221)
Q 42.53 F =0 F 0.00 PE -0.04
BL6 T 9.50 0.0652 PF 0.62
219 220 1.610 L 9.50 C =120 PT 53.63 (220)
Q 42.53 F =0 F 0.00 PE -0.04
BL6 T 9.50 0.0652 PF 0.62
218 219 2.067 L 9.50 C =120 PT 54.21 (219)
Q 42.53 F =0 F 0.00 PE -0.04
BL6 T 9.50 0.0193 PF 0.18
217 2 2.067 L 9.50 C =120 PT 54.35 (218)
Q 42.53 F =0 F 0.00 PE -0.04
BL6 T 9.50 0.0193 PF 0.18
121 217 2.067 L 4.30 C =120 PT 54.49 (217)
Q 42.53 F =T F 10.00 PE 0.00
BL6 T .14.30 0.0193 PF 0.28
PT 54.77 (121)
140 40 1.710 L 1.60 C =120 PT 51.19 ( 40)
Q 42.97 F =T F 8.00 PE -0.69
RN2 T 9.60 0.0496 PF 0.48
216 140 1.710 L 4.00 C =120 PT 50.98 (140)
Q 42.97 F =T F. 8.00 PE 0.00
BL5 T 12.00 0.0496 PF 0.60
215 216 1.710 L 9.50 C =120 PT 51.58 (216)
Q 42.97 F =0 F 0.00 PE -0.04
BL5 T 9.50 0.0496 PF 0.47
214 215 1.710 L 9.50 C =120 PT 52.01 (215)
Q 42.97 F =0 F 0.00 PE -0.04
BL5 T 9.50 0.0496 PF 0.47
213 214 1.610 L 9.50 C =120 PT 52.44 (214)
Q 42.97 . F =0 F 0.00 PE -0.04
BL5 T 9.50 0.0665 PF 0.63
212 213 1.610 L 9.50 C =120 PT 53.03 (213)
Q 42.97 F =0 F 0.00 PE -0.04
BL5 T 9.50 0.0665 PF 0.63
211 212 1.610 L 9.50 C =120 PT 53.62 (212)
Q 42.97 F =0 F 0.00 PE -0.04
BL5 T 9.50 0.0665 PF 0.63
SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 9
A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
•
From To GPM IN Devices Ft PSI /Ft PSI
210 211 2.067 L 9.50 C =120 PT 54.21 (211)
Q 42.97 F =0 F 0.00 PE -0.04
BL5 T 9.50 0.0197 PF 0.19
• 209 210 2.067 L 9.50 C =120 PT 54.36 (210)
Q 42.97 F =0 F 0.00 PE -0.04
BL5 T 9.50 0.0197 PF 0.19
120 209 2.067 L 4.30 C =120 PT 54.51 (209)
Q 42.97 F =T F 10.00 PE 0.00
BL5 T 14.30 0.0197 PF 0.28
PT 54.79 (120)
139 39 1.710 L 1.60 C =120 PT 51.01 ( 39)
Q 43.91 F =T F 8.00 PE -0.69
RN2 T 9.60 0.0516 PF 0.50
208 139 1.710 L 4.00 C =120 PT 50.82 (139)
Q 43.91 F =T F 8.00 PE 0.00
BL4 T 12.00 0.0516 PF 0.62
207 208 1.710 L 9.50 C =120 PT 51.44 (208)
Q 43.91 F =0 F 0.00 PE -0.04
BL4 T 9.50 0.0516 PF 0.49
206 207 1.710 L 9.50 C =120 PT . 51.89 (207)
Q 43.91 F =0 F 0.00 PE -0.04
BL4 T 9.50 0.051'6 PF 0.49
205 206 1.610 L 9.50 C =120 PT 52.34 (206)
Q 43.91 F =0 F 0.00 PE -0.04
BL4 T 9.50 0.0692 PF 0.66
204 205 1.610 L 9.50 C =120 PT 52.96 (205)
Q 43.91 F =0 F 0.00 PE -0.04
BL4 T 9.50 0.0692 PF 0.66
203 204 1.610 L 9.50 C =120 PT 53.58 (204)
Q 43.91 F =0 F 0.00 PE -0.04
BL4 T 9.50 0.0692 PF 0.66
202 203 2.067 L 9.50 C =120 PT 54.20 (203)
Q 43.91 F =0 F 0.00 PE -0.04
BL4 T 9.50 0.0205 PF 0.19
201 202 2.067 L 9.50 C =120 PT 54.35 (202)
Q 43.91 F =0 F 0.00 PE -0.04
BL4 T 9.50 0.0205 PF 0.19
SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 10
A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
119 201 2.067 L 4.30 C =120 PT 54.50 (201)
Q 43.91. F =T F 10.00 PE 0.00
BL4 T 14.30 0.0205 PF 0.29
PT 54.79 (119)
22 122 2.469 L 1.60 C =120 PT 54.75 (122)
Q 36.05 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0060 PF 0.08
21 22 6.065 L 12.30 C =120 PT 55.52 ( 22)
Q 36.05 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0001 PF 0.00
PT 55.52 ( 21)
21 121 2.469 L 1.60 C =120 PT 54.75 (121)
Q 36.14 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0060 PF 0.08
20 21DQ 36.05 6.065 L 12.30 C =120 PT 55.52 ( 21)
Q 72.20 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0003 PF 0.00
PT 55.52 ( 20)
20 120 2.469 L 1.60 C =120 PT 54.76 (120)
Q 36.46 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0061 PF 0.08
19 20DQ 72.20 6.065 L 12.30 C =120 PT 55.53 ( 20)
Q 108.66 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0006 PF 0.01
PT 55.54 ( 19)
19 119 2.469 L 1.60 C =120 PT 54.76 (119)
Q 37.13 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0063 PF 0.09
18 19DQ 108.66 6.065 L 12.30 C =120 PT 55.54 ( 19)
Q 145.79 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0010 PF 0.01
PT 55.55 ( 18)
18 118 2.469 L 1.60 C =120 PT 54.78 (118)
Q 36.29 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0061 PF 0.08
17 18DQ 145.79 6.065 L 12.30 C =120 PT 55.55 ( 18)
Q 182.07 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0015 PF 0.02
PT 55.57 ( 17)
SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 11
A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location -- - Flow Pipe Fittings Equiv Friction Pressure -
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
17 117 2.469 L 1.60 C =120 PT 54.79 (117)
Q 37.84 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0066 PF 0.09
16 17DQ 182.07 6.065 L 12.30 C =120 PT 55.57 ( 17)
Q 219.91 F =0 F 0.00 PE .0.00
CM1 T 12.30 0.0021 PF 0.03
PT 55.60 ( 16)
16 116 2.469 L 1.60 C =120 PT 54.81 (116)
Q 39.96 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0072 PF 0.10
15 16DQ 219.91 6.065 L 12.30 C =120 PT 55.60 ( 16)
Q 259.87 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0029 PF 0.04
PT 55.64 ( 15)
15 115 2.469 L 1.60 C =120 PT 54.83 (115)
Q 42.66 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0082 PF 0.11
14 15DQ 259.87 7.981 L 12.30 C =120 PT 55.63 ( 15)
Q 302.53 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0010 PF 0.01
PT 55.64 ( 14)
14 114 2.469 . L 1.60 C =120 PT 54.83 (114)
Q 45.37 F =T F 12.00 PE 0.69
RN1 T 13.60 0.0092 PF 0.13
13 14DQ 302.53 7.981 L 12.30 C =120 PT 55.65 ( 14)
Q 347.90 F =0 F 0.00 PE 0.00
CM1 T 12.30 0.0013 PF 0.02
PT 55.67 ( 13)
318 122 2.067 L 5.50 C =120 PT 54.75 (122)
Q 6.35 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0006 PF 0.01
162 318 1.610 L 51.50 C =120 PT 54.76 (318)
Q 6.35 F =T F 8.00 PE -0.13
BL2 T 59.50 0.0019 PF 0.11
62 162 2.709 L 1.60 C =120 PT 54.74 (162)
Q 6.35 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0002 PF 0.00
D .
SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 12
A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location - Flow - - - Pipe -- Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
61 62 2.709 L 12.30 C =120 PT 55.43 ( 62)
Q 6.35 F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0002 PF 0.00
PT 55.43 ( 61)
317 121 2.067 L 5.50 C =120 PT 54.75 (121)
Q 6.38 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0006 PF 0.01
161 317 1.610 L 51.50 C =120 PT 54.76 (317)
Q 6.38 F =T F 8.00 PE -0.13
BL2 T 59.50 0.0020 PF 0.12
61 161 2.709 L 1.60 C =120 PT 54.75 (161)
. Q 6.38 F =T F 10.80 PE . 0.69
RN3 T 12.40 0.0002 PF 0.00
60 61DQ 6.35 2.709 L 12.30 C =120 PT 55.44 ( 61)
Q 12.74 F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0006 PF 0.01
PT 55.45 ( 60)
316 120 2.067 L 5.50 C =120 PT 54.76 (120)
• Q 6.51 F =T F 10.00 PE 0.00
BL2 , 15.50 0.0006 PF 0.1
160 316 1.610 L 51.50 C =120 PT 54:77 (3.6
Q 6.51 F =T F 8.00 PE -0.13 , ,
BL2 T 59.50 0.0020 PF 0.12
60 160 2.709 L 1.60 C =120 PT 54.76 (160)
Q 6.51 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0002 PF 0.00
59 60DQ 12.74 2.709 L 12.30 C =120 PT 55.45 ( 60)
Q 19.25 F =0 F 0.00 PE _0.00
CM3 T 12.30 0.0012 PF O.OT '' 1 '
PT 55.46 ( 59)
315 119 . 2.067 L 5.50 C =120 PT 54.76 (119)
Q 6.78 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0006 PF 0.01
159 315 1.610 L 51.50 C =120 PT 54.77 (3i
Q _ 6.78 F =T F 8.00 PE -0.13 . . .�.
BL2 T 59.50 0.0022 PF 0.13 '
SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 13
' A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location -- Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI •
59 159 2.709 L 1.60 C =120 PT 54.77 (159)
Q 6.78 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0002 PF 0.00 • •
58 59DQ 19.25 2.709 L 12.30 C =120 PT 55.46 ( 59)
Q 26.03 F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0021 PF 0.03
PT 55.49 ( 58) •
314 118 2:067 L 5.50 C =120 PT 54.78 (118).
Q 7.04 F =T F 10.00 PE 0.00 •
BL2 T 15.50 0.0007 PF 0.01
158 314 1.610 L 51.50 C =120 PT 54.79 (314)
Q . 7.04 F =T F 8.00 PE - 0.13
BL2 T 59.50 0.0023 PF 0.14 -
58 158 2.709 L 1.60 C =120 PT 54.80 (158)
Q 7.04 F =T F 10.80 PE ., __ 0 .69
RN3 T 12.40 0.0002 PF 0.00
57 58DQ 26.03 2.709 L 12.30 C =120 PT 55:49 ( 58)
. Q 33.07 F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0032 PF '0.04 '
PT 55.53 ( 57)
313 117. 2.067 L 5.50 C =120. PT 54.79(117)
Q 7.72 F =T F 10.00 PE 0.00 '
BL2 T 15..50 0.0008 PF 0:01
157 313. 1.610 L 51.50 C =120 PT 54:80 (313)
Q 7.72 F =T F 8.00 PE -0.13 , �,,:
BL2 T 59.50 0.0028 PF 0.17
57 157 2.709 L 1.60 C =120 PT 54.84 (157) .
Q 7.72 F =T F 10.80 PE .0.69 .
RN3 T 12.40 0.0002 PF 0.00
56 57DQ 33.07 2.709 L 12.30 C =120 PT 55.53 ( 57)
Q 40.79 F =0 F 0.00 PE 0.00 , , . ,
CM3 T 12.30 0.0048 PF 0.06
. . PT 55:9 •( 56)
312 116,. 2.067 L 5.50 C =120 PT 54.81 (116) .
Q 8.64 F =T F 10.00 PE 0.00 '
BL2 T 15.50 0.0010 PF 0.02
SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 14
' A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location - Flow Pipe Fittings Equio Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
156 312 1.610 L 51.50 C =120 PT 54.83 (312)
Q 8.64 F =T F 8.00 PE -0.13
BL2 T 59.50 0.0034 PF 0.20
56 156 2.709 L 1.60 C =120 PT 54.90 (156)
Q 8.64 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0003 PF 0.00
55 56DQ 40.79 2.709 L 12.30 C =120 PT 55.59 ( 56)
Q 49.42 F =0 F 0.00 PE 0.00
CM3 T 12.30 0.0068 PF 0.08
PT 55.67 ( 55)
311 115 2.067 L 5.50 . 0 =120 PT 54.83 (115)
Q 9.85 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0013 PF 0.02
155 311 1.610 L 51.50 C =120 PT 54.85 (311)
Q 9.85 F =T F 8.00 PE -0.13_
BL2 T 59.50 0.0044 PF 0.'26
55 155 2.709 L 1.60 C =120 PT 54.98 (155)
Q 9.85 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0003 PF 0.00
54 55DQ 49.42 2.709 L 12.30 C =120 PT 55.67 ( 55)
Q 59.28 F =0 F 0.00 PE .0.00
CM3 T 12.30 0.0096 PF 0.12
PT 55.79 ( 54)
310 114 2.067 L 5.50 C =120 PT 54.83 (114)
Q 11.90 F =T F 10.00 PE 0.00 ' ,..
BL2 T 15.50 0.0018 PF 0.03
154 310 1.610 L 51.50 C =120 PT 54.86 (310)
Q 11.90 F =T F 8.00 PE -0.13 .
BL2 T 59.50 0.0062 PF 0.37 -
54 154 , 2.709 L 1.60 C =120 PT 55.10 (154)
Q 11.90 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0005 PF 0.01
53 54DQ 59.28 2.709 L 12.30 C =120 PT 55.80 ( 54)
Q 71.17 F =0 F 0.00 PE 0.00 ._
CM3 T 12.30 0.0134 PF 0:16 '
PT 55:96 ( 53)
•
SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 15
A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
Location Flow Pipe Fittings - - Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
309 113 2.067 L 5.50 C =120 PT 52.64 (113)
Q 33.68 F =T F 10.00 PE 0.00
BL2 T 15.50 0.0125 PF 0.19
153 309 1.610 L 51.50 C =120 PT 52.83 (309)
Q 33.68 F =T F 8.00 PE -0.13
BL2 T 59.50 0.0424 PF 2.52
53 153 2.709 L 1.60 C =120 PT 55.22 (153)
Q 33.68 F =T F 10.80 PE 0.69
RN3 T 12.40 0.0034 PF 0.04
8 53DQ 71.17 2.709 L 2.50 C =120 PT 55.95 ( 53)
Q 104.85 F =T F 10.80 PE 0.00„
CM5 T 13.30 0.0275 PF 0.37
PT 56.32 ( 8)
13 113 2.469 L 1.60 C =120 PT 52.64 (113)
Q 220.92 F =T F 12.00 PE 0:69
RN1 T 13.60 0.1714 PF 2:33
9 13DQ 347.90 7.981 L 2.30 C =120 PT 55.66 ( 13)
Q 568.82 F =T F 35.00 PE 0.00
CM1 T 37.30 0.0033 PF 0.12
8 9DQ 445.09 7.981 L 57.00 C =120 PT 55.78 ( 9)
Q 1013.92 F =0 F 0.00 PE ,.0.00 ;
CM4 T 57.00 0.0095 PF 0.54
10 8DQ 104.85 7.981 L 1.50 C =120 PT 56.32 ,( 8)
Q 1118.77 F =E F 18.00 PE 0.00
FM4 T 19.50 0.0114 PF 0.22
7 10 7.981 L 13.50 C =120 PT 56.54 ( 10)
Q 1118.77 F =E F 18.00 PE . 5.85
FR3 T 31.50 0.0114 PF 0.36 '
6 7 6.065 L 1.90 C =120 PT 62.75 ( 7)
Q 1118.77 F =0 F 0.00 PE 0:82 ' '`'
FR2 T . 1.90 0.0433 PF .. 0.08
5 6 6.065 L 2.10 C =120 PT 63.65 ( 6)
Q 1118.77 F =T,GV F 33.00 PE 0.91
FR1 T 35.10 0.0433 PF 1.52 .
SUBMITTAL SERIAL NO:4126HY1 12 -07 -2010 PAGE 16
` A & I DISTRIBUTORS BLDG. #3
.50/2000 WET SYSTEM
•
- Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI /Ft PSI
4 5 7.981 L 1.50 C =120 PT 66.08 ( 5)
Q 1118.77 F =T F 35.00 PE 0.00
FM2 T 36.50 0.0114 PF 0.42
3 4 10.100 L 1.00 C =120 PT 66.50 ( 4)
Q 1118.77 F =0 F 0.00 PE 0.43
FM1 T 1.00 0.0036 PF 0.00
2 3 10.280 L 25.00 C =140 PT 66.93 ( 3)
Q 1118.77 F =67/0 F 67.00 PE 0.00
UN3 T 92.00 .0.0025 PF 0.23
1 2DQ 500.00 10.280 L 300.00 C =140 PT 67.16 ( 2)
Q 1618.77 F =67/0 F 67.00 PE 0.00
UN2 T 367.00 0.0049 PF 1.80
0 1 12.340 L 280.00 C =140 PT 68.96 ( 1)
Q 1618.77 F =0 F 0.00 PE 0.00
UN1 T 280.00 0.0020 PF 0.56
PT 69.52 ( 0)
•
•
-
�
A & I DISTRIBUTORS BLDG. #3 Sigma Dynamics Corporation
250 7700 Supply / Demand Graph
240
230 Margin
Pressure 25.76 PSI
220 Flow 1961.95 GPM
210
200
190
•
180
170
160
150
N 140
130 �
I 120 �
0 . 110
100
80
70 • Hoses O
60
50
40
30 y • —
20 O
10 .
N 1115
o 250 500 750 1000 1250 1500 1750 2000 2250 2500
Water Flow (GPM)
System Demand.. Water Supply..
Sprinkler Demand 68.37 PSI @ 1118.77 GPM Static 103.00 PSI
Additional Flows 500.00 GPM Residual 92.00 PSI @ 1964.00 GPM
Hose at Source 0.00 GPM Elevation 0.00 PSI
Total Demand 69.55 PSI @ 1618.77 GPM