Series RFII - 5.6 K- factor
"Royal Flush II" Concealed Pendent Sprinklers
Quick lir Standard Response, Standard Coverage
General The Series RFII Sprinklers are shipped
with a Disposable Protective Cap. The
Descr iption Protective Cap is temporarily removed
p during installation and replaced to help
protect the sprinkler during ceiling in-
The Tyco® Series RFII Quick Response p p g g ( :"'"'
stallation or finish. The tip of the Pro-
( 3 -mm bulb) and Standard Response tective Cap can be used to mark the bulb), 5.6 K- Factor, "Royal k- •
Flush II" Concealed Pendent Sprin center of the ceiling hole into plaster —
klers are decorative sprinklers featur board or ceiling tiles by gently push-
ing a flat cover plate designed to con- ing the ceiling product against the Pro- �.
ceal the sprinkler. These sprinklers are tective Cap. When ceiling installation
optimal for architecturally sensitive ar is complete, the Protective Cap is re
eas such as hotel lobbies, office build- moved and the Cover Plate /Retainer
ings, churches, and restaurants. Assembly is installed. Sprinkler
Each sprinkler includes a Cover Plate/ As an option, the Series RFII Standard
Retainer Assembly and a Sprinkler! Response (5 -mm bulb) "Royal Flush II" Identification
Support Cup Assembly. The separa- Concealed Pendent Sprinklers can be
ble, two-piece assembly design pro- fitted with a silicone Air and Dust Seal. Number (SIN)
vides the following benefits: (Refer to Figure 5.) The Air and Dust
Seal is intended for sensitive areas TY3531 — 3 mm bulb
• Allows installation of the sprinklers where it is desirable to prevent air and TY3551 — 5 mm bulb
and pressure testing of the fire pro- dust from the area above the ceiling to
tection system prior to installation pass through the cover plate.
of a suspended ceiling or applica-
tion of the finish coating to a fixed NOTICE
ceiling. The Series RFII Concealed Pendent
• Permits the removal of suspended Sprinklers described herein must be
ceiling panels for access to building installed and maintained in compliance
service equipment without having with this document and with the appli-
to first shut down the fire protection cable standards of the National Fire
system and remove sprinklers. Protection Association, in addition to
• Provides for 1/2 inch (12,7 mm) of the standards of any authorities having
vertical adjustment to allow a mea jurisdiction. Failure to do so may impair
sure of flexibility in determining the the performance of these devices.
length of fixed piping to cut for the The owner is responsible for maintain -
sprinkler drops. ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer . should be contacted
IMPORTANT with any questions.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
.
stallation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to •
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 6 OCTOBER 2009 TFP181
•
1 ' TFP98I
Page 2 of 6
a. .
Technical 1/2" NPT 7 SEALING
• / / ASSEMBLY
•F at'. : • • • �
Sprinkler, Approvals FRAME i -/ F
�el
Approvals apply only to the service ��� - - - -1 CAP
conditions indicated in the Design Cri- �
teria section. 1 1 11 1 � 0 TY3531 (3 -mm Bulb) is UL Listed, PP roved ( ROLL SUPPORT
C -UL Listed, LPCB Approved (Ref. CUP FO WITH RMED r BULB
No. 094a/10), VdS Approved (Cer- THREADS
tificate No. G 4090007), and NYC _
Approved (MEA 353 -01 -E) as Quick \ COMPRESSION
Response.. r �� _,� ( SCREW
1
• TY3531 (3 -mm Bulb) is FM Ap- PINS GUIDE ) 1 wi � '
proved as Standard Response. AZ _4
Factory Mutual does not approve
' DEFLECTOR
•
any concealed sprinklers for quick , (DROPPED
response. DEFLECTOR i - i , % � POSITION)
cm,,-
- Z r
Y TY3551 (5 -mm Bulb) is UL Listed, ; SPRINKLER /SUPPORT CUP
I
C -UL Listed, FM Approved, LPCB I ASSEMBLY
Approved (Ref. No. 094a/9), and
NYC Approved (MEA 353 -01 -E) as THREAD INTO , RETAINER •
. Standard Response. SUPPORT CUP ) I WITH THREAD
Approvals for Air and Dust Seal UNTIL MOUNTING '� O O ) DIMPLES
UL and C -UL Listed for use with the SURFACE IS
RFII Standard Response Concealed FLUSH EJECTION
Sprinkler (TY3551). CEILINNG G SPRING
Maximum Working Pressure
. Maximum 250 psi (17,3 bar) by UL,
1 C -UL, and NYC r� w„
Maximum 175 psi (12,1 bar) by FM, SOLDER COVER
VdS, and LPCB TABS (3) COVER PLATE/RETAINER PLATE
Temperature Rating ASSEMBLY
155 °F /68 °C Sprinkler with •
139 °F /59 °C Plate FIGURE 1
200'F/93°C Sprinkler with • MODEL RFII CONCEALED SPRINKLER
165`F/74 °C Plate ASSE .
Discharge Coefficient • •.
K= 5.6 GPM /psil' (80,6 LPM /barli
4
•
l} e sa `NOTICE °
Adjustment '
• 1/2 inch (12,7 mm) Do not use the Series RFII in applica
•
Finishes Criteria tions where the air pressure above the
ceiling is greater than that below. Down
See the Ordering Procedure section. The Tyco® Series RFII Concealed Pen- drafts through the Sprinkler /Support
• Physical Characteristics dent Sprinklers are intended for fire Cup Assembly can delay sprinkler op-
Frame Bronze protection systems designed in ac- eration in a fire situation.
Support Cup... Chrome Plated Steel cordance with the standard instal -
Guide Pins Stainless Steel lation rules recognized by the appli- •
Deflector Bronze cable Listing or Approval agency; for
Compression Screw Brass example, UL Listing is based on NFPA
Bulb Glass 13 and VdS Approval is based on the
Cap Bronze or Copper • CEA 4001.
Sealing Assembly Beryllium
Nickel w/ Teflon? For more information on LPCB and
•
Cover Plate Brass VdS Approvals, contact Tyco Fire Sup -
Retainer Brass Pression & Building Products at the
Ejection Spring Stainless Steel following office:
•
Enschede, Netherlands
• • Telephone: 31 -53- 428 -4444
- Fax: 31-53-428-3377
The Series RFII Concealed Pendent
•
Sprinklers are only listed and approved
• with the Series RFII Concealed Cover
•
,. Plates having a factory applied finish.
•
TDuPont Registered Trademark
•
•
1 TFIP98I
.Page 3 of 6
FACE OF CLEARANCE HOLE ®peea fl .
\SPRINKLER I DIAMETER When exposed to heat from a fire, the
FITTING DIMENSION C Cover Plate, normally soldered to the •
Retainer at three points, falls away to _ -
SPRINKLER i expose the Sprinkler /Support Cup
SUPPORT CUP \ , - - -� Assembly.
ASSEMBLY 1i� The Deflector— supported by the
1/2° (12 7 mm) j Guide Pins —then drops down to its
THREADED 1 operational position.
D ADJUSTMENT (ji The glass Bulb contains a fluid that ex-
l( • pands when exposed to heat. When
FACE OF CEILING, the rated temperature is reached, the
RETAINING RING \ '
o fluid expands sufficiently to shatter the
MOUNTING t / glass Bulb, activating the sprinkler and
SURFACE / 1 allowing water to flow. • ,,
y • CLEARANCE
A r j . R
• .
i HOLE
3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE ---- -!_�
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER
REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY r I '
COVER PLATE COVER PLATE ,
': i
PROFILE DEPTH DIAMETER r M ']
DIMENSION B DIMENSION A
_III_
A: 3 -1/4 inches (82,6 mm) C: 2 -3/8 to 2 -5/8 inches (60,3 to 66,7 mm)
B: 3/16 inches (4,8 mm) D: 1 -3/4 to 2 -1/4 inches (44,5 to 57,2 mm)
. FIGURE 2 •.
• • - SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS FIGURE 4
DISPOSABLE PROTECTIVE CAP
_Il =l._—__ FRAME • __i=lL__
11111T111 ARM i I P T I SUPPORT
ICI % . =
SQUARE
ALIGN J ilit
•
ARROWS WITH
FRAME ARMS _ \ a �
l
r
ACCEPTS. �
1/2' SOCKET \ —�
DRIVE
•
FIGURE 3
RFII SPRINKLER WRENCH
•
1 TPP181 _
Page 4 of 6
°_
®s'et:iiali,-;:n - Do hot attempt - to modify or rep s n
aiF a This air gap is for - prop
�� "' ���� ®`�' - damaged sprinkler. operation of the sprinkler. If the ceil-
The Tyco® Series RFII must be in- Step 7. When installing an Air and Dust ing requires repainting after sprinkler
stalled in accordance with the follow- Seal, refer to Figure 5; otherwise, pro- installation, ensure that the new paint
• ing instructions. ceed to Step 8. To attach the Air and does not seal off any of the air gap.
• Dust Seal, verify the angle of the out- Do not pull the Cover Plate relative to
• fiNOTIGE side edge of -the seal is oriented ac- the Enclosure. Separation may result.
Do not install any bulb -type sprinkler if cording to Figure 5. Start the edge of Replace sprinklers that:
the bulb is cracked or there is a loss the Retainer in the grooved slot of the
of liquid from the bulb. With the sprin- Air and Dust Seal and continue around • are leaking or exhibiting visible signs
' kler held hdrizontally, a small air bub the retainer until the entire Air and Dust of corrosion.
ble should be present. The diameter Seal is engaged • were modified or over - heated.
of the air bubble is approximately 1/16 Step 8. Screw on the Cover Plate/ Never paint, plate, coat, or otherwise
inch (1,6 mm) for the 155 °F /68 °C and Retainer Assembly until the Retainer alter automatic sprinklers after they
3/32 inch (2,4 mm) for the 200°F/93°C (shown in Figure 2) or the Air and Dust leave the factory. Never repaint facto-
. temperature ratings. Seal (shown in Figure 5) contacts the
ry-painted Cover Plates. If necessary,
Obtain a 1/2 inch NPT sprinkler joint ceiling. Do not continue to screw on replace them with factory - painted •
by applying a minimum to maximum the Cover P a ceiling panel Assembly ut of it units. Non-factory applied y so that it lifts a ceiling panel out of its Y PP paint can
torque of 7 to 14 ft-lbs. (9,5 to 19,0 normal position. If you cannot engage adversely delay or prevent sprinkler
Nm). Higher levels of torque can dis- the Cover Plate /Retainer • Assembly operation in the event of a fire.
tort the sprinkler Inlet with consequent with the Support Cup or you cannot Exercise care to avoid damage to
leakage or impairment of the sprinkler. engage the Cover Plate /Retainer As- sprinklers before, during, and after in-
Do not attempt to compensate for in- sembly sufficiently to contact the ceil- stallation. Replace sprinklers damaged -
sufficient adjustment in the Sprinkler ing, you must reposition the Sprinkler by dropping, striking, wrench twisting,
by under- or over - tightening the Sprin- Fitting. wrench slipping, or the like. Also, re-
kler /Support Cup Assembly. Re- adjust place any sprinkler that has a cracked
the position of the sprinkler fitting to . Care a . . bulb or that has lost liquid from its
suit. � bulb. (Refer to the Installation section.)
Step 1. Install the sprinkler only in the a®ntenance If you must remove a sprinkler, do not
pendent position with the center -line reinstall it or a replacement without re-
of the sprinkler perpendicular to the The Tyco® Series RFII must be installing the Cover Plate /Retainer As-
` 4 mounting surface. maintained and serviced in accordance sembly. If a Cover Plate /Retainer As-
T Step 2. Remove the Protective Cap. with the following instructions. sembly becomes dislodged during
Step 3. With pipe thread sealant ap service, replace it immediately.
_ N - . ---- Responsibility lies with sprinkler plied to the pipe threads, hand - tighten P Y p ' kler own -
the sprinkler into the sprinkler fitting.- Before closing a fire protection sys- ers for the inspection, testing, and
Step 4. Wrench tighten the sprinkler tem main control valve for maintenance maintenance of their -fire protection
using only the RFII Sprinkler Wrench. work on the fire protection system that . system and devices in compliance with
(Refer to Figure 3.) Apply the RFII it controls, obtain permission to shut this document, as well as with the ap-
Sprinkler Wrench to the Sprinkler as . down the affected fire protection sys- plicable standards of the National Fire
shown in Figure 3. tem from the proper authorities and no- Protection Association (for example, .
tify all personnel who may be affected NFPA 25), in addition to the standards
Step 5. Replace the Protective Cap by this action. of any other authorities having jurisdic-
by pushing it upwards until it bottoms Absence of the Cover Plate /Retainer tion: Contact the installing contractor
out against the Support Cup. (Refer Assembly delay sprinkler opera- or sprinkler manufacturer regarding
to Figure 4.) The Protective Cap helps Y can Y P P era- any questions.
prevent damage to the Deflector and tion in a fire situation.
Arms during ceiling installation and /or When properly installed, there is a Automatic sprinkler systems should be
finish. You can also use the Protective nominal 3/32 inch (2,4 mm) air gap be- inspected, tested, and maintained by a
Cap to locate the center of the clear qualified Inspection Service in accor-
ance hole by gently pushing the ceiling tween the lip of the Cover Plate and the dance with local requirements and /or
Y 9 Y P 9 9 ceiling, as shown in Figure 2. national code.
material up against the center point of
the Protective Cap.
SUPPORT SPRINKLER FACE OF ORIENT
fNOAtc..E; CUP =.-------- CEILING SEAL
AS
As long as the Protective Cap remains I j BEVEL N
in place, the system is considered ��` — I COVER .,� '� � �'
SHOWN
"Out of Service ". ; PLATE
RETAINER - `__C'
Step 6. After the ceiling has been com % � ASSEMBLY ���«
pleted with the 2 -1/2 inch (63,5 mm) i, - -�•
diameter clearance hole and in prepa (i
ration for installing the Cover Plate /Re- • I - E i CLEAN
tamer A ssembly, remove and discard AL „■" �L j�� -� ROM
the Protective Cap. Verify that the De- _ 1 ∎1_ - __ LIP OF COVER
SEAL
flector moves up and down freely. - RETAINER PLATE
• If the Sprinkler is damaged and the FIGURE 5
Deflector replace does not move enup tire and down O PTIONAL AIR AND DUST SEAL FOR SERIES RFII TY3551
freely, replace the entire Sprinkler. ( )
•
•
• TFP181
Page 5 of 6
•
rra# ty • Proce 4• ure
Products manufactured by Tyco Fire Contact your local distributor for •
• Suppression & Building Products availability. When placing an order,
(TFSBP) are warranted solely to the indicate the full product name.
original Buyer for ten (10) years against
• • defects in material and workmanship Sprinkler /Support Cup Assembly • when paid for and properly installed S pec i fy: ( ( temperature rating
and maintained under normal use and from below) Series RFII Concealed
service. This warranty will expire ten Pendent Sprinkler, P/N (specify).
(10) ,years from date of shipment by
TFSBP. No warranty is given for prod- 155 °F /68 °C 200 °F /93 °C
ucts or components manufactured by TY3531 51- 792 -1 -155 51 -792 -1 -200
companies not affiliated by ownership TY3551 51- 790 -1 -155 51- 790 -1 -200
with TFSBP or for products and tom- • •
ponents which have been subject to Separately Ordered Cover Plate/
misuse, improper installation, corro-
sion, or which have not been installed, Retainer Assembly:
maintained, modified or repaired in ac- Specify: (temperature rating from be-
cordance with applicable Standards of low) Series RFII Concealed Cover Plate
the National Fire Protection Associa- with (finish), P/N (specify).
tion, and /or the standards of any other 139 °F /59 °C(a) 165 °F /74 °C(b)
Authorities Having Jurisdiction. Mate- Brass 56- 792 -1 -135 56 -792 -1 -165
rials found by TFSBP to be defective Chrome 56- 792 -9 -135 56- 792 -9 -165
shall be either repaired or replaced, at Signal White
TFSBP's sole option. TFSBP neither (RAL 9003) 56 -792 -4 -135 56 -792 -4 -165
assumes, nor authorizes any person Grey White
to assume for it, any other obligation (RAL 9002) 56- 792 -0 -135 56- 792 -0 -165
in connection with the sale of prod- Pure White (c)
ucts or parts of products. TFSBP shall (RAL 9010) 56- 792 -3 -135 56- 792 -3 -165
not be responsible for sprinkler system Custom 56 -792 -X -135 56- 792 -X -165
design errors or inaccurate or incom- (a) For use with 155 °F /68 °C sprinklers.
plete information supplied by.Buyer or (b) For use with 200 °F /93 "C sprinklers.
Buyer's representatives. (c) Eastern Hemisphere sales only.
° In no event. shall TFSBP be liable, in
Sp
rinkler Wrench
contract, tort, strict liability or under
any other legal theory, for incidental, S pecify: RFII Sprinkler Wrench,
indirect, special or consequential dam- P/N 56-000-1-075.
• ages, including but not limited to labor •
charges, regardless of whether TFSBP Air and Dust Seal •
was informed about the possibility of Specify: Air and Dust Seal,
such damages, and in no event shall P/N 56- 908 -1 -001.
• TFSBP's liability exceed an amount
equal to the sales price. -
• The foregoing warranty is made in lieu
of any and all other w ex-
press or implied, including warranties
of merchantability and fitness for a
particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
• is made in contract, tort, strict liability
or any other legal theory. •
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder. •
•
•
•
•
•
•
•
•
•
•
•
' TFPI89 -