Loading...
Specifications . ••P5 20 l oo-c 3 G l 9573 'l R • Baca xr 800- 381 -9312 r � J r 4 r Technical Services +1 -4 . 43 Y 4 : tI T� 1�C x �Gx > a> a+ r �f a v 1J WWW.1y. �� i •i.. - - — -- -- - - - - -- -- -- - MARX 5 2J12 Series RFII' ® 5 ®6 K- factor CITY OFTIGARD "Royal Flush II" Concealed Pendent Sprinklers BUILDING DIVISION Quick & Standard Response, Standard Coverage • G eneral • tective Cap can be used to mark the center of the ceiling hole into plaster Description board or ceiling tiles by gently push- ing the ceiling product against the Pro- tective Ca When ceiling installation The TYCO Series RFII Quick Response is complete, the Protective Cap is re- (3-mm bulb) and Standard Response P P -:- „._� -• ; (5 -mm bulb), 5 :6 K- Factor, "Royal moved and the Cover Plate /Retainer :::., Assembly is installed. Flush II" Concealed Pendent Sprin- Y klers are decorative sprinklers featur- As an option, the Series RFII Standard ing a flat cover plate designed to con- Response (5 -mm bulb) "Royal Flush II" ceal the sprinkler. ,These sprinklers are Concealed Pendent Sprinklers can be . — optimal for architecturally sensitive ar- fitted with a silicone Air and Dust Seal. eas such as hotel lobbies, office build- (Refer to Figure 5.) The Air and Dust ings, churches, and restaurants. Seal is intended for sensitive. areas Each sprinkler includes a Cover Plate/ where it is desirable to prevent air and Spr Retainer Assembly and a Sprinkler/ dust from the area above the ceiling to Support Cup Assembly. The separa- pass through the cover plate. Identification ble, two -piece assembly design pro- Number vides the following benefits: pro- ;.. • Allows installation of the sprinklers The Series RFII Concealed Penden TY3531 — 3 mm bulb and pressure testing of the fire pro- Sprinklers described herein must be tection system prior to installation of installed and maintained in compli TY3551 — 5 mm bulb • a suspended ceiling or application of ance with this document and with the the finish coating to a fixed ceiling. applicable standards of the National Fire Protection Association, in addi- • Permits the removal of suspended tion to the standards of any authori- ceiling panels for access to building ties having jurisdiction. Failure t do so service equipment without having may impair the performance of these to first shut down the fire protection devices. system and remove sprinklers. The owner is responsible for maintain- • Provides for 1/2 inch (12,7 mm) of ing their fire protection system and de- vertical adjustment to allow a mea vices in proper operating condition. sure of flexibility in determining the The installing contractor or sprinkler length of fixed piping to cut for the manufacturer should be contacted sprinkler drops. with any questions. The Series RFII Sprinklers are shipped with a Disposable Protective Cap. The Protective Cap is temporarily removed during installation and replaced to help protect the sprinkler during ceiling in- stallation or finish. The tip of the Pro - IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- • lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 SEPTEMBER 2011 TFP181 ,, TFP181 • Page2of6 Technical 1/2" NPT ASSEMBLY - - — • -" S prinkler Approvals . Approvals apply only to the service FRAME conditions indicated in the Design CAP • Criteriasection. 1 ' i l l TY3531 (3 -mm Bulb) is UL Listed, SUPPORT C -UL Listed, VdS Approved (Certif- CUP WITH ( BULB icate No. and NYC Ap- ROLL FORMED proved . (MEA 353 -01 -E) as Quick THREADS Response. i ) • TY3531 3 -mm Bulb is FM and 1 COMPRESSION LPCB Approved (Ref. No 094a/10) ,1' 1 SCREW A roved as Standard Res onse. GUID ) = � ` � Factory Mutual and . LPCB do not PINS (2) � / I I approve any concealed sprinklers DEFLECTOR for quick response. — — (DROPPED • TY3551 (5 mm Bulb) is UL Listed, DEFLECTOR � i . I z._.....__._. l fi - '/ POSITION) C -UL Listed, FM Approved, LPCB I c- ~ j == ===z- r Approved (Ref. No. 094a/9), and , - NYC Approved (MEA 353 -01 -E) as I : SPRINKLER /SUPPORT CUP I Standard Response. ASSEMBLY Approvals for Air and Dust Seal THREAD INTO 1 RETAINER UL and C -UL Listed for use with the SUPPORT CUP ) I WITH THREAD RFII Standard Response Concealed UNTIL MOUNTING \ O O I DIMPLES Sprinkler (TY3551). SURFACE IS ) Maximum Working Pressure FLUSH CEILING EJECTION Maximum 250 psi (17,3 bar) by UL, SPRING C -UL, and NYC Maximum 175 psi (12,1 bar) by FM, VdS, and LPCB � Temperature Rating 155 °F (68 °C) Sprinkler with SOLDER ' _ COVER 139°F (59°C) Plate TABS (3) COVER PLATE/RETAINR PLATE 200 ° F (93 °C) Sprinkler with . . ASSEMBLY 165 °F (74 °C) Plate Discharge Coefficient FIGURE 1 K. 5.6 GPM /psi (80,6 LPM /barl' MODEL RFII CONCEALED SPRINKLER • Adjustment ASSEMBLY 1/2 inch (12,7 mm) Finishes See the Ordering Procedure section. Physical Characteristics Frame Bronze Support Cup Chrome Plated Steel Guide Pins Stainless Steel Deflector Bronze Compression Screw Brass Bulb Glass Cap Bronze or Copper Sealing Assembly Beryllium Nickel w/ TEFLON Cover Plate Brass Retainer Brass Ejection Spring Stainless Steel TFP181 Page 3 of 6 • FACE OF, _CLEARANCE HOLE--. _.— — ® _ es _ ®gn _ 1 SPRINKLER -- - ` DIAMETER - - Criteria — — FITTING DIMENSION C f J The TYCO Series RFII Concealed Pen- • SPRINKLER dent Sprinklers are intended for fire SUPPORT CUP - ---- -- protection systems designed in ac- ASSEMBLY \ i� cordance with the standard instal - `I lation rules recognized by the appli- 1/2" (12,7 mm) I cable Listing or Approval agency; for THREADED t � example, UL Listing is based on NFPA D ADJUSTMENT ` 13 and VdS Approval is based on the ll CEA 4001. FACE OF CEILING, ; i — For more information on LPCB and RETAINING RING �'I VdS A rovals, contact T co Fire Su MOUNTING � 1 pression & Building Products at the SURFACE � � \ A L following office: .1 ���� / Enschede, Netherlands ._ I I.m. - , ! Telephone: 31 -53- 428 4444 • -- Fax: 31-53-428-3377 • The Series RFII Concealed Pendent ` ~ r -- j ' • • Sprinklers are only listed and approved 3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE with the Series RFII Concealed Cover • (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER. - Plates having a factory applied finish. REFERENCE 3/32" (2,4 mm) • POSITION ASSEMBLY „_,..•„ 'NOTICE;,; • COVER PLATE • COVER PLATE Do not use the Series RFII in applica- - PROFILE DEPTH DIAMETER tions where the air pressure above DIMENSION B DIMENSION A the ceiling is greater than that be- low. Down drafts through the Sprin- kler /Support Cup Assembly can delay A: 3 -1/4 inches (82,6 mm) C: 2 -3/8 to 2 -5/8 inches (60,3 to 66,7 mm) sprinkler operation in a fire situation. - B: 3/16 inches (4,8 mm) D: 1 -3/4 to 2 -1/4 inches (44,5 to 57,2 mm) Operati . n FIGURE • When exposed to heat from a fire, the SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS Cover Retainer Plate, nee points, soldered to the Retainer at three points, falls away y to • • • • expose. the Sprinkler /Support Cup Assembly. • The Deflector— supported by the Guide Pins -then drops down to its operational position. The glass Bulb contains a fluid that ex- pands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass Bulb, activating the sprinkler and allowing water to flow. • • TFP181 Page 4 of 6 - - •- - - - - •• - - • - -- - CLEARANCE HOLE _ (j !� -_ FRAME l =�L_ -- �, ARM 4L'tl l ' \ SUPPORT i - ■ ■ in__ 7/8" (23 mm) SQUARE ALIGN 4 , 0 , ......J ARROWS WITH FIGURE4 FRAME ARMS OE \ ‘- DISPOSABLE PROTECTIVE CAP a l ACCEPTS ` 0 1/2" SOCKET M - . DRIVE • FIGURE 3 RFII SPRINKLER WRENCH SUPPORT SPRINKLER FACE OF ORIENT CUP CEILING • �I SEAL 1 BEVEL AS i =1�_ �_1 COVER .Ile' �" IIIII ASSEMBLY SHOWN PLATE � RETAINER ®,v, �' �( • ';,�; � ' I Vii) . / 1011 l ' 4r . 11111k AND DUST r -_1 1 ; LIP OF COVER SEAL RETAINER PLATE FIGURE 5 OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551) • TFP181 Page 5 of 6 • Installation - NOTICE ti • Absence of the Cover Plate /Retainer Assembly can delay sprinkler opera - The TYCO Series RFII 'must be in - As long as the Protective Cap - - - tion in afire situation. • stalled in accordance with the follow- in place, the system is considered "Out of Service". When properly i nstalled, there i s a ing instructions. nominal 3/32 inch (2,4 mm) air gap be- Step 6. After the ceiling has been corn- tween the lip of the Cover Plate and the ,NOTICE,; pleted with the 2 -1/2 inch (63,5 mm) di- ceiling, as shown in Figure 2. Do not install any b sprinkler if ameter clearance hole and in prepa- e ration for installing the Cover Plate/ This air.gap is necessary for proper • the not liquid is cracked b the or bulb re is a loss s s s Retainer Assembly, remove and dis- operation of the sprinkler. If the ceil- of l i held horizontally, from the bulb. With it small h the a card the Protective Cap. Verify that the ing requires repainting after sprinkler k should be n a air bun a diameter Deflector moves up and down freely installation, ensure that the new paint le sh l held of the air bubble is approximately 1/16 If the Sprinkler is damaged and the does not seal off any of the air gap. inch (1,6 mm) for the 155 °F /68 °C and Deflector does not move up and down Do not pull the Cover Plate relative to 3/32 inch (2,4 mm) for the 200 °F /93 °C freely, replace the entire Sprinkler. the Enclosure. Separation may result. temperature ratings. Do not attempt to modify or repair a Replace sprinklers that: damaged sprinkler. Obtain a 1/2 inch NPT sprinkler joint • are leaking.or exhibiting visible signs by applying a minimum to maximum Step 7. When installing an Air and Dust of corrosion. torque of 7 to 14 ft. - lbs. (9,5 to 19,0 Seal, refer to Figure 5; otherwise, pro - Nm). Higher levels of torque can dis ceed to Step 8. To attach the Air and • were modified or over - heated. tort the sprinkler Inlet with consequent Dust Seal, .verify the angle of the out- Never paint, plate, coat, or otherwise leakage or impairment of the sprinkler. side edge of the seal is oriented ac- alter automatic sprinklers after they cording to Figure 5. Start the edge of leave the factory. Never repaint facto - Do not attempt to compensate for in the Retainer in the grooved slot of the • r - ainted Cover Plates. If necessary, • sufficient adjustment in the Sprinkler Air and Dust Seal and continue around y p by under or over - tightening the Sprin the retainer until the entire Air and Dust replace them with factory-painted units. kler /Support Cup Assembly. Re adjust Seal is engaged. , adversely delay o e. Non-factory delay or applied paint prevent spri nkler s r can the position of the sprinkler fitting to suit. Step 8. Screw on the Cover Plate/ operation in the event of a fire. Retainer Assembly until the. Retainer Exercise care to avoid damage to Step 1. Install the sprinkler only in the (shown in Figure 2) or the Air and Dust sprinklers before, during, and after in- pendent position with the center -line Seal (shown in Figure 5) contacts the stallation. Replace sprinklers damaged of the sprinkler perpendicular to the ceiling. Do not continue to screw on by dropping, striking, wrench twisting, mounting surface. the Cover Plate /Retainer Assembly wrench slipping, or the like. Also, re- Step 2. Remove the Protective Cap. so that it lifts a ceiling panel out of its place any sprinkler that has a cracked Ste p pipe p 3. W ith i e thread sealant a normal position. If you cannot engage bulb or that has lost liquid from its the Cover Plate /Retainer Assembly plied to the pipe threads, hand - tighten bulb. (Refer to the Installation section.) the sprinkler into the sprinkler fitting. with the Support Cup or you cannot engage the Cover Plate /Retainer As- If you must remove a sprinkler, do not Step 4. Wrench- tighten the sprinkler sembly sufficiently to contact the ceil- reinstall it or a replacement without re- using only the RFII Sprinkler Wrench. ing, you must reposition the Sprinkler installing the Cover Plate /Retainer As- (Refer to Figure 3.) . Apply the RFII Fitting. • . sembly. If a Cover Plate /Retainer As- Sprinkler Wrench to the Sprinkler as sembly becomes dislodged during shown in Figure 3. service, replace it immediately. Step 5. Replace the Protective Cap Care and . Responsibility lies with sprinkler own - by pushing it upwards until u 'bottoms out against the Support Cup. (r Maintenance ers for the inspection, testing, and maintenance of their fire protection • to Figure 4.) The Protective Cap helps The TYCO Series RFII must be system and devices in compliance prevent damage to the Deflector and maintained and serviced in accordance with this document, as well as with the Arms during ceiling installation and /or with the following instructions. applicable standards of the National finish. You can also use the Protective Fire Protection Association (for exam - Cap to locate the center of the clear- le, NFPA 25 ante hole by gently pushing the ceiling NOTICE:" d 25), in addition to the stan- dards of any other authorities having material up against the center point of Before closing a fire protection sys jurisdiction. Contact the installing con - the Protective Cap. tem main control valve for maintenance tractor or sprinkler manufacturer re- work on the fire protection system that garding any questions. it controls, obtain permission to shut down the affected fire protection sys Automatic sprinkler systems should be tem from the proper authorities and no- inspected, tested, and maintained by a tify all personnel who may be affected qualified Inspection Service in accor- by this action. dance with local requirements and /or national code. TFP181 Page 6 of 6 Limited i rder®ng Warranty r®ce Mere Products manufactured by Tyco Fire Contact your local distributor for Protection Products (TFPP) are war- availability. When placing an order, ranted solely to the original Buyer for indicate the full product name. ten (10) years against defects in ma- terial and workmanship when paid for Sprinkler /Support Cup Assembly and properly installed and maintained Specify: (SIN), (temperature rating under normal use and service: This from below) Series RFII Concealed warranty will expire ten (10) years from Pendent Sprinkler, P/N (specify). date of shipment by TFPP. No warran- ty is given for products or components 155F/68°C 200 °F /93 °C manufactured by companies not af- TY3531 51- 792 -1 -155 51- 792 -1 -200 filiated by ownership with TFPP or for TY3551 51- 790 -1 -155 51- 790 -1 -200 products and components which ,have been subject to misuse, improper in- Separately Ordered Cover Plate/ stallation, corrosion, or which have not Retainer Assembly: been installed, maintained, modified or Specify: (temperature rating from be- repaired in accordance with applicable low) Series RFII Concealed Cover Standards of the National Fire Protec- Plate with (finish), P/N (specify). tion Association, and /or the standards of any other Authorities Having Juris- 139 °F /59 °C(a) 165 °F /74 °C(b) diction.. Materials found by TFPP to be Brass 56- 792 -1 -135 , 56- 792 -1 -165 defective shall be either repaired orre- Chrome 56- 792 -9 -135 56- 792 -9 -165 Brushd placed, at TFPP's sole option.. TFPP Chrome 56 -792 -8 -135 56- 792 -8 -165 neither assumes, nor authorizes any Si gnal White person to assume for it, any other ob- (RAL 9003) 56 -792 -4 -135 56- 792 -4 -165 ligation in connection with the sale of Grey White products or parts of products. TFPP (RAL 9002) 56- 792 -0 -135 56- 792 -0 -165 shall not be responsible for sprinkler Pure White (c) system design errors or inaccurate or (RAL 9010) 56- 792 -3 -135 56- 792 -3 -165 Incomplete information supplied by Custom 56- 792 -X -135 56- 792 -X -165 Buyer or Buyer's representatives. (a) For use with 155 °F /68 °C sprinklers. In no event shall TFPP be liable, in (b) For use with 200 °F /93 °C sprinklers. contract, tort, strict liability or under (c) Eastern Hemisphere sales only. any other legal theory, for inciden- Sprinkler Wrench tal, indirect, special or consequential Specify: RFII 'Sprinkler Wrench, damages, including but not limited to P/N 56- 000 -1 -075. labor charges, regardless of whether TFPP was informed about the possibil- Air and Dust Seal • ity of such damages,. and in no event • shall TFPP's,liability exceed an amount Specify: Air and Dust Seal, • equal to the sales price. P/N 56- 908 -1 -001. The foregoing warranty is made in lieu of any and all other warranties, ex- press or implied. including warranties of merchantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on • failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Copyright © 2008, 2011 Tyco Fire Protection Products. All rights reserved. two TEFLON is trademark of The DuPont Corporation. • tijc� Fire Suppression • & Buildin g Products Technical Services 800-381-93121+1-401-781-8220 www.tyco - fire.com Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K- Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage G eneral Corrosion - resistant coatings, where .--...7- applicable, are utilized to extend the Description life of copper alloy sprinklers beyond F• : :'Cr'; l Y�ri ti that which would otherwise be obtained � The TYCO Series TY -FRB, 2.8, 4.2, 5.6, when exposed to corrosive atmo- i :,, 1:., and 8.0 K- factor, Upright and Pendent spheres. Although corrosion- resistant coated sprinklers have passed the l i ' J I _ .11 Sprinklers described in this data sheet P P are quick response, standard coverage, standard corrosion tests of the appli- I ) � decorative 3 mm glass bulb -type spray cable approval agencies, the testing is ;; /ft.,/ —.Lb ::•«‘. . sprinklers designed for use in light or not representative of all possible cor- ;;f ''/ ~ -- oi ordinary hazard, commercial occupan- rosive atmospheres. Consequently, •.. -� ±' :`' cies such as banks, hotels, and shop- it is recommended that the end user = -' ping malls. be consulted with respect to the suit- ' ability of these coatings for any given The recessed version of the Series TY- corrosive environment. The effects of FRB Pendent Sprinkler, where applica- ambient temperature, concentration of I N ble, is intended for use in areas with a chemicals, and gas /chemical velocity, finished ceiling. This recessed pendent should be considered, as a minimum, MOM sprinkler uses one of the following, along with the corrosive nature of the i • — chemical to which the sprinklers ' rinklers will be , A two -piece Style 10 (1/2 inch NPT) P / �.'';� 4 t or Style 40 (3/4 inch NPT) Recessed exposed. t� l' ilf"' r I , 1 r Escutcheon with 1/2 inch (12,7 mm) of An intermediate level of the Series TY- ''� E� 1 ' recessed adjustment or up to 3/4 inch FRB Pendent Sprinklers is detailed ----:- ' (19,1 mm) of total adjustment from the in Technical Data Sheet TFP356, and . - w , -. flush pendent position, or a Sprinkler Guards are detailed in Tech- ��� • • A two -piece Style 20 (1/2 inch NPT) nical Data Sheet TFP780. or Style 30 (3/4 inch NPT) Recessed Escutcheon with 1/4 inch (6,4 mm) of NOTICE recessed adjustment or up to 1/2 inch The Series TY-FRB Concealed Pendent Model /Sprinkler (12,7 mm) of total adjustment from the Sprinklers described herein must be flush pendent position. installed and maintained in compliance Identification The adjustment provided by the with this document and with the appli- Number (SIN) Recessed Escutcheon reduces the cable standards of the National Fire accuracy to which the fixed pipe drops Protection Association, in addition to to the sprinklers must be cut. the standards of any authorities having TY1131: Upright 2.8K, 1/2" NPT jurisdiction. Failure to do so may impair TY1231: Pendent 2.8K, 1/2" NPT the performance of these devices. TY2131: Upright 4.2K, 1/2" NPT Owners are responsible for maintaining TY2231: Pendent 4.2K, 1/2 " NPT their fire protection system and devices TY3131: Upright 5.6K, 1/2 " NPT in proper operating condition. The TY3231: Pendent 5.6K, 1/2" NPT IMPORTANT installing contractor or sprinkler manu- TY4131: Upright 8.0K, 3/4" NPT Always refer to Technical Data facturer should be contacted with any TY4231: Pendent 8.0K, 3/4" NPT Sheet TFP700 for the "INSTALLER questions. TY4831: Upright* 8.0K, 1/2" NPT WARNING" that provides cautions TY4931: Pendent* 8.0K, 1/2" NPT with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. 'Eastern Hemisphere Sales Only Page 1 of 10 JULY 2010 TFP171 • • TFP171 Page 2 of 10 • • • - - 7/16" (11 mm) . ESCUTCHEON STYLE 10 or 20 * NOMINAL PLATE SEATING RECESSED • SSU MAKE -IN 1/2" SURFACE ESCUTCHEON DEFLECTOR I NIT 6* :"ate!.f.h. ra' t + „=,.._„,.. j 5 �O 7/16" ill . q I (11,1 mm) f 2 -1/q" MEM �r I i NOMINAL I 4 M0 (57,2 mm) � �MN 2 If MAKE -IN 1 vi; Fr 2- 3/16" 11,,,,... 1 -9/16° � mr 3 -�� (55,6 mm) WRENCH I ( 39.7 mm) 1�; - FLATS 1/2" NPT SSP DEFLECTOR * - 2 -7/8° (73,0 mm) DIA. - CROSS SECTION UPRIGHT . PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 -Bulb 6 - Deflector • Temperature rating is indicated on deflector o a d Compression p g adjacent to Assembly 5 - Com I 2 - Button p 7 - Bushing orifice seat on frame. Screw • FIGURE 1 • QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT • 7/16" (11,1 mm) ESCUTCHEON STYLE 10 or 20 * NOMINAL PLATE SEATING RECESSED SSU MAKE -IN 1/2° SURFACE ESCUTCHEON 6* DEFLECTOR i_____ NPT 5 '�' 7/16" -- - ;��° (11,1 mm) 2 -3/16° ' 111' , 4 li NOMINAL • • IN��1 (55,6 mm) � 2 MAKE -IN I 1 � 3� 2 I A ♦fi I 1 1/2" � �= (38,1 mm 3 ( 55,6 mm). WRENCH � � .FLA 1 -- - - -_.. • i .-- ! 1/2" NPT SSP DEFLECTOR -.•-- 2 -7/8" (73,0 mm) DIA. -. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 Asse bl 4 - Bulb 6 - Deflector • Temperature rating is indicated on deflector or adjacent to 2 - Button y 5 - Compression • orifice seat on frame. Screw FIGURE 2 • QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT • • TFP171 . Page 3 of 10 • - - .7/16" (11,1 mm) - -- ESCUTCHEON -- -- • STYLE 20 - - .. - * NOMINAL PLATE SEATING RECESSED SSU MAKE -IN 1/2" SURFACE ESCUTCHEON DEFLECTOR NPT 6* \ i.,7 ri l l - 11.. f _,. . �— • 5 tEl 7/16" m� 4 I N 1��A (55,6 / mm) !• � � Iiiir I MAKE -IN I IL w�pi�� 2 ' 2- 3/16" I I 1 -1/2" Ulf 3 (55,6 mm) + WRENCH (38,1 mm) ------ FLATS 1/2" NPT --..==...-.. SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. -- CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly 5 - Compression orifice seat on frame. *Temperature indicated on deflector or adjacent to • 2 - Button Screw • FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TV3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT 1/2" (12,7 mm) ESCUTCHEON STYLE 30 or 40 SSU * NOMINAL 3/4 PLATE SEATING RECESSED • DEFLECTOR MAKE-IN NPT SURFACE ESCUTCHEON 6* — t 6 .' ?T t =''TT',� IT - r- i 'Ct c J tz . • 5 �' 1/2 " I (12,7 mm) W (58,7 2-5/16" 5 "kV 4 I NOMINAL 01W141i } I I MAKE -IN �� .2.' ill 2 -1/4" 1r O I� 1- 9/16 ". 3 (57,2 mm) ! (39,7 mm) . i 11 i . i i ,-- I 3/4" NPT SSP DEFLECTOR 2 -7/8" (73,0 mm) DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector • Temperature rating is indicated on deflector or ad Assembly 5 - Compression p g adjacent to f 2 - Button p orifice seat on frame. Screw FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT • • • • TFP171 . Page 4 of 10 • • 7/16" (11,1 mm) - •.. .. - - - SSU * • NOMINAL - 1/2" - - DEFLECTOR MAKE -IN NPT • 6 * f,. 1 I ITT, *f'1'S1 ii �� 5 �l ` 7/16" _ 1, mm 4 NOMINAL gi ' ��� (57,2 / mm) 111 r MAKE -IN - 2 F/' f� mm) I ' gip 1- 9/16 ") 3 / 9 � ¢ 2- 3/16" (55,6 mm � WRENCH (39,7 mm � __ FLATS . 1 CROSS 1/2 NPT DEFLECTOR SECTION UPRIGHT PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly 5 - Compression Temperature rating is indicated on deflector or adjacent to 2 - Button p orifice seat on frame. Screw FIGURE 5 • . • QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS 8.0 K- FACTOR, 1/2 INCH NPT • Technical Operation inch (1,6 mm) for the 135 °F /57 °C and 3/32 inch (2,4 mm) for the 286 °F /141 °C Data The glass Bulb contains a fluid that temperature ratings. expands when exposed to heat. When Obtain a leak -tight 1/2 inch NPT sprin- Approvals the rated temperature is reached, the kler joint by applying a minimum to UL and C -UL Listed fluid expands sufficiently to shatter the maximum torque of 7 to 14 ft.lbs. (9,5 FM, LPCB, and NYC Approved glass Bulb, allowing the sprinkler to to 19,0 Nm). Higher levels of torque Refer to Table A and B for complete activate and,water to flow. can distort the sprinkler Inlet with con - approval information including sequent leakage or impairment of the • corrosion- resistant status. Design sprinkler. Maximum Working Pressure o Do not attempt to compensate for Refer to Table C. Criteria insufficient adjustment in the Escutch- The TYCO Series TY -FRB Pendent eon Plate by under- or over - tightening Discharge Coefficient the sprinkler. Re- adjust the position of K =2.8 GPM /psiti (40,3 LPM /bary2) and Upright Sprinklers are intended the sprinkler fitting to suit. for fire protection s K =4.2 GPM /psis / (60,5 LPM /bar1/2) systems designed in The Series TY -FRB Pendent and K =5.6 GPM /psit� (80,6 LPM /bart�2 accordance with the standard installa- tion rules recognized by the applicable Upright Sprinklers must be installed K =8.0 GPM /psis / (115,2 LPM /bar1I2) Listing or Approval agency (such as, UL in accordance with the following Listing is based on the requirements of instructions. Temperature Rating NFPA 13, and FM Approval is based on Refer to Table A and B. PP 1. Install Pendent sprinklers in the the requirements of FM's Loss Preven- pendent position. Install upright Finishes tion Data Sheets). Only the Style 10, sprinklers in the upright position. Sprinkler: Refer to Table A and B. 20, 30, or. 40 Recessed Escutcheon, as 2. With pipe- thread sealant applied to Recessed Escutcheon: White Coated, applicable, is to be used for recessed the I e threads, hand-tighten the Chrome Plated, or Brass Plated. pendent installations. sprinkler into the sprinkler tt ng Physical Characteristics Installation 3. Tighten the sprinkler into the sprin- Frame Bronze kler fitting using only the W-Type 6 Button Brass /Copper The TYCO Series TY -FRB Sprinklers Sprinkler Wrench (Figure 14). With Sealing Assembly Beryllium must be installed in accordance with reference to Figures 1 through Nickel w/Teflont the following instructions. 5, apply the W -Type 6 Sprinkler Bulb Glass Wrench to the sprinkler wrench Compression Screw Bronze NOTIC flats. Deflector Copper /Bronze Bushing (K =2.8) Bronze Do not install any bulb -type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bub- ble should be present. The diameter t Registered Trademark of Dupont of the air bubble is approximately 1/16 • . • 1 . FPI71 Page 5 of 10 SPRINKLER FINISH (See Note 5) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME WHITE * ** FACTOR COLOR BRASS PLATED POLYESTER 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY1231) and 175 °F /79 °C Yellow 1, 2, 3, 4 UPRIGHT (TY1131) 200 °F /93 °C Green 286 °F /141 °C Blue 135 °F /57 °C Orange 2.8 RECESSED 155 °F /68 °C Red 1/2" NPT PENDENT (TY1231)* 175 °F /79 °C Yellow Figure 6 . 200 °F /93 °C Green 1,2,4 135 °F /57 °C Orange RECESSED PENDENT 155 °F /68 °C Red • (TY1231) ** 175F/79°C• Yellow • • Figure 7 200 °F /93 °C . Green • • 135 °F /57 °C Orange" PENDENT 155 °F /68 °C Red ' • (TY2231) . and 175 °F /79 °C Yellow UPRIGHT (TY2131) 200 °F /93 °C Green • 286 °F /141 °C Blue 135 °F /57 °C Orange 4.2 RECESSED 1/2" NPT PENDENT 155 °F /68 °C Red 1, 2 (TY2231)* 175 °F /79 °C Yellow Figure 8 200F/93°C Green 135 °F /57 °C Orange . • RECESSED PENDENT 155 °F /68 °C Red • (TY2231) ** 175F/79°C Yellow Figure 9 200F/93°C , .. Green • NOTES: ' ' • . • • 1. Listed by Underwriters. Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C -UL) as Quick Response Sprinklers. • 3. ' Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. ' Approved by the City of New York under MEA 354 -01 -E. 5. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion- Resistant Sprinklers. • Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. " Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. "' Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K- FACTOR SPRINKLERS • • • • • • • • TFP171 • Page 6 of 10 SPRINKLER FINISH (See Note 8) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME WHITE*** LEAD FACTOR COLOR BRASS PLATED POLYESTER COATED 135F/57°C Orange PENDENT 155 °F /68 °C • Red (TY3231) and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 • UPRIGHT 200 °F /93 °C Green (TY3131) 286 °F /141 °C Blue 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red 5.6 PENDENT 175 °F /79 °C Yellow 1, 2, 4, 5 N/A 1/2" NPT (TY3231)' Figure 10 200 °F /93 °C Green 286 °F /141 °C Blue 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 175 °F /79 °C Yellow 1, 2, 3, 4, 5 N/A (TY3231 Figure 11 200 °F /93 °C • Green 286 °F /141 °C ' .,Blue 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red . (TY4231) • • and • 175 °F /79 °C Yellow.' 1, 2, 3, 4, 5, 6, 7 1, 2, 5 UPRIGHT 200 °F /93 °C Green (TY4131) 286 °F /141 °C Blue 135F/57°C Orange RECESSED 155 °F /68 °C Red 8.0 PENDENT 175 °F /79 °C Yellow 1, 2, 5 N/A 3/4" NPT (TY4231)' Figure 12 200 °F /93 °C Green • 286 °F /141 °C Blue • 135 °F /57 °C Orange . RECESSED 155 °F /68 °C Red • PENDENT 175 °F /79 °C Yellow 1. 2, 3, 5 N/A • (TY4231)" Figure 13 200 °F /93 °C Green • 286 °F /141 °C Blue 135 °F /57 °C• Orange PENDENT 155 °F /68 °C Red (TY4931) 1/2 /2$ NPT and 175F/79°C Yellow , 1, 2, 4, 5, 6 .1, 2, 5 • UPRIGHT 2O0F/93°C Green (TY4831) 286 °F /141 °C Blue NOTES: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details, contact Tyco Fire Suppression & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444 /Fax 31 -53 -428- 3377.) 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead - Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion - Resistant Sprinklers. Where Lead - Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved • as a Corrosion- Resistant Sprinklers. Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K- FACTOR SPRINKLERS • • • TFP171 Page 7 of 10 .. - - - - - - - - - - - - - SPRINKLER FINISH -..- -- .- - -- - .. . - • . K TYPE NATURAL CHROME WHITE LEAD FACTOR BRASS PLATED POLYESTER COATED PENDENT (TY1231) and UPRIGHT (TY1131) • 1/2 NPT 175 PSI (12,1 BAR) N/A RECESSED PENDENT (TY1231) PENDENT (TY2231) and UPRIGHT (TY2131) 1/2 NPT 175 PSI (12,1 BAR) N/A ' RECESSED PENDENT (TY2231) PENDENT (TY3231) 175 PSI 5.6 UPRIGHT (TY3131) 250 PSI (17,2 BAR) (12,1 BAR) 1/2" NPT ' OR 175 PSI (12,1 BAR) , — ' RECESSED (SEE NOTE 1) . • PENDENT (TY3231) N/A PENDENT (TY4231) 175 PSI and (12,1 BAR) 8 UPRIGHT 3/4" NPT - 175 PSI (12,1 BAR) — RECESSED N/A PENDENT (TY4231) PENDENT (TY4931) 175 PSI 1/2" PT and 175 PSI (12,1 BAR (12,1 BAR) UPRIGHT (TY4831) - NOTES: 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters, Laboratories, Inc. for use in Canada (C -UL); and, the Approval by the City of New York. • ' TABLE C MAXIMUM WORKING PRESSURE ' The Series TY -FRB Recessed Pendent Care and • Exercise care to avoid damage to Sprinklers must be installed in accor- sprinklers before, during, and after dance with the following instructions. • installation. Never paint, plate, coat, Maintenance or otherwise alter automatic sprinklers 1. After installing the Style 10, 20, 30, after they leave the factory. or 40 Mounting Plate, as applica- The TYCO Series TY -FRB must be ble, over the sprinkler threads and maintained and serviced in accordance Replace sprinklers that: with pipe- thread sealant applied to with the following instructions. • were modified or over-heated. the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. • were damaged by dropping, striking, MOTICEk wrench twisting, wrench slippage, or 2. Tighten the sprinkler into the sprin- Before closing a fire protection system the like. kler fitting using only the W-Type 7 main control valve for maintenance are leakin or exhibiting g Recessed Sprinkler Wrench (Fig - work on the fire protection system of corrosi g vi Bible signs ure 15). With reference to Figures 1 that it controls, obtain permission to n. to 4, apply the W -Type 7 Recessed shut down the affected fire protection • were exposed to corrosive products Sprinkler Wrench to the sprinkler systems from the proper authorities of combustion but have not oper- wrench flats. and notify all personnel who may be ated, if you cannot easily remove • 3. After ceiling installation and finish- affected by this action. combustion by- products with a cloth. ing, slide on the Style 10, 20, 30, or Absence of the outer piece of an • have a cracked bulb or have lost liq- 40 Closure over the Series TY -FRB escutcheon, which is used to cover uid from the bulb. Refer to the Instal - • Sprinkler push the Closure over a clearance hole, can delay sprinkler lotion section in this data sheet. the Mounting Plate until its flange operation in a fire situation. comes in contact with the ceiling. TFP171 Page 8 of 10 2 -7/8" DIA. 2 -7/8" DIA. -- - 5/8 ±1/4" - (73,0 mm) 3/4" (19,1 mm) (73;0 mm) • ' 1/2" (12,7 mm) -- , 1/211/8" ( (15,9 ±6,4 mm) 1/4" (6,4 mm) (12,7 ±3,2 2 -1/4" DIA. mm) ) 2 -1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) FACE OF ~ (57,2 mm) MOUNTING MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING / 1/8" I 8" ( 3,2 mm) 'a l (3,2 mm) I / if 1} d ' Ar ■. m.■ 1 IM I 11 I I 1 ,, , MOUNTING ,I' MOUNTING SURFACE SURFACE • i CLOSURE SERIES 1- 5/16" (33,3 mm) CLOSURE SERIES 1- 5/16" (33,3 mm) TY-FRB 13/16" (20,6 mm) TY-FRB 1- 1/16" (27,0 mm) FIGURE 6 FIGURE 7 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT • -WITH TWO - PIECE 1/2 INCH TOTAL - ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON . . 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA. _ 2 -7/8" DIA. 5/8 ±1/4" (73,0 mm) 3/4" (19,1 mm) ~ (73,0 mm) 1/2 ±1/8" 1/2" (12,7 mm) (15,9 ±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 1/4" (6,4 mm) (57,2 mm) 1 2-1/4" DIA. FACE OF MOUNTING FACE OF (57,2 mm) SPRINKLER MOUNTING PLATE SPRINKLER PLATE FITTING FITTING 1 /8" / 1/8" ��� (3,2 mm) .. I (3 mm) i J11IIIi 1 ,, , MOUNTING 1 ? �J1 MOUNTING f SURFACE SURFACE 1 CLOSURE SERIES . . 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm) TY-FRB 3/4" (19,1 mm) TY -FRB ' 1" (25,4 mm) FIGURE 8 FIGURE 9 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT Initial and frequent visual inspections of Responsibility lies with the owner for Care must be exercised to avoid dam - random samples are recommended for the inspection, testing, and mainte- age to the sprinklers - before, during, corrosion - resistant sprinklers to verify nance of their fire protection system and after installation. Sprinklers dam - the integrity of the corrosion - resistant and devices in compliance with this aged by dropping, striking, wrench material of construction. Thereafter, document, as well as with the appli- twist /slippage, or the like, must be annual inspections per NFPA 25 should cable standards of the National Fire replaced. Also, replace any sprinkler suffice. Protection Association (for example, that has a cracked bulb or that has lost Inspections of corrosion- resistant NFPA 25), in addition to the standards liquid from its bulb. (Ref. Installation sprinklers are recommended at close of any other authorities having jurisdic- Section). Lion. Contact the installing contractor or . range, instead of from the floor level sprinkler manufacturer regarding any per NFPA. Inspection at close range Initial and frequent visual inspections of random samples are recommended for can better determine the exact sprin- questions. corrosion- resistant sprinklers to verify kler condition and the long -term integ- Automatic sprinkler systems are rec- the integrity of the corrosion- resistant • rity of the corrosion - resistant material, ommended to be inspected, tested, material of construction. Thereafter, which can be affected by the corrosive and maintained by a qualified Inspec- annual inspections per NFPA 25 should conditions present. tion Service in accordance with local suffice. requirements and /or national codes. • YFP171 Page 9 of 10 2 -7/8" DIA. _ 2 -7/8" DIA. 5/8±1/4" . (73,0 mm) - (19,1 mm) - • ' • • (73,0 mm) - • (15,9 ±6,4 mm) 1/2 ±1/8" 1/2" (12,7 mm) 2 -1/4" DIA. 1/4 "(6,4 mm) (12,7 ±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) 1 (57,2 mm) MOUNTING FACE OF MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING I 1/8" 1/8" u (3 mm) �. / . Ma_ _1.1.11.j nor fillip (3,2 mm) N'Llit MO 1I' MOUNTING SURFACE SURFACE -r- _ CLOSURE SERIES 1 -1/4° (31,8 mm) SERIES 1 -1/4" (31,8 mm) CLOSURE TY-FRB 3/4" (19,1 mm) . TY-FRB 1" (25,4 mm) FIGURE 10 FIGURE 11 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON • • 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT • 2 -7/8° DIA. 2 -7/8" DIA. 5/8 +1/4" _ (73,0 mm) 3/4 "(19,1 mm) (73,0 mm). 1/2 "(12,7 mm) (15,9 ±6,4 mm) 1/4" (6,4 mm) _ 8" • 2 -1/4" DIA. (12,,7 ±37±3,,2 2 mm) 2 -1/4" DIA. 1/4 "(6,4 mm) FACE OF (57,2 mm) ~ MOUNTING ~ (57,2 mm) FACE OF MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" ,r (3,2 mm) n (3,2 mm) WALIf I A4 1 \ - ■ I MOUNTING II/ MOUNTING '�, SURFACE SURFACE Al CLOSURE SERIES 1 -5/16° (33,3 mm) CLOSURE SERIES 1 -5/16° (33,3 mm) TY-FRB 13/16" (20,6 mm) TY -FRB. 1- 1/16" (27,0 mm) FIGURE 12 FIGURE 13 • SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT Inspections of corrosion- resistant sprinklers are recommended at close � WRENCH range, instead of from the floor level RECESS per NFPA. Inspection at close range WRENCH RECESS can better determine the exact sprin- kler condition and the long -term integ- (END "A" USED FOR ���1 1/2" NPT MODELS) rity of the corrosion - resistant material, which can be affected by the corrosive conditions present. WRENCH RECESS 1 (END "B" USED FOR # 3/4" NPT MODELS) PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH • FIGURE 14 SPRINKLER WRENCHING AREA W -TYPE 6 SPRINKLER FIGURE 15 WRENCH W -TYPE .7 RECESSED SPRINKLER WRENCH • • • TFP171 Page 10 of 10 P/N 57 - XXX - X - XXX I - TEMPERATURE MODEUSIN SPRINKLER RATINGS FINISH 330 2.8K UPRIGHT (1 /2 "NPT) TY1131 1 NATURAL BRASS 135 135 °F (57°C) 331 2.8K PENDENT (1 /2 "NPT) TY1231 4 WHITE POLYESTER 155 155 °F (68 °C) 340 4.2K UPRIGHT (1 /2 "NPT) TY2131 3 WHITE (RAL9010)' 175 175 °F (79 °C) 341 4.2K PENDENT (1 /2 "NPT) TY2231 9 CHROME PLATED 200 200 °F (93 °C) 370 5.6K UPRIGHT (1 /2 "NPT) TY3131 7 LEAD COATED 286 286 °F (141 °C) 371 5.6K PENDENT (1 /2 "NPT) TY3231 • 390 8.0K UPRIGHT (3 /4 "NPT) TY4131 391 8.0K PENDENT (3 /4 "NPT) TY4231 360 8.0K UPRIGHT (1 /2 "NPT) TY4831' * Eastern Hemisphere sales only. 361 8.0K PENDENT (1 /2 "NPT) TY4931° • TABLE D PART NUMBER SELECTION SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS Limited responsible for sprinkler system design errors or inaccurate or incomplete infor- Ordering • Warranty mation supplied by Buyer or Buyer's Procedure representatives. Products manufactured by Tyco Fire In no event shall TFSBP be liable, in Contact your local distributor for Suppression & Building Products contract, tort, strict liability or under availability. When placing an .order, ( TFSBP) are warranted solely to the any other legal theory, for incidental, indicate the full product name and Part original Buyer for ten (10) years against indirect, special or consequential dam- Number (P /N). defects in material and workmanship ages; including but not limited to labor when paid for and properly installed charges, regardless of whether TFSBP Sprinkler Assemblies with NPT and maintained under normal use and was informed about the possibility of Thread Connections service. This warranty will expire ten such damages, and in no event shall (10) ea from date i of shipment toby TFSBP's liability exceed an amount Response, (specify K- factor), ) (spec ) (specify ucts or components manufactured by equal to the sales price. temperature rating), Series TY-FRB companies not affiliated by ownership The foregoing warranty is made in lieu (specify Pendent or Upright) Sprinkler with TFSBP or for products and corn- of any and all other warranties. express with (specify type of finish or coating), ponents which have been subject to or implied. including warranties of mer- P/N (specify from Table D). misuse, improper installation, corro- chantability and fitness for a particular Recessed Escutcheon: sion, or which have not been installed, purpose. Specify: Style (10, 20, 30, or 40) maintained, modified or repaired in This limited warranty sets forth the Recessed Escutcheon with (specify') accordance with applicable Standards exclusive remedy for claims based on finish, P/N (specify'). of the National Fire Protection Associa- failure of or defect in products, materi- tion, and /or the standards of any other als or components, whether the claim is Sprinkler Wrench Authorities Having Jurisdiction. Mate- made in contract, tort, strict liability or Specify: W -Type 6 Sprinkler Wrench, rials found by TFSBP to be defective any other legal theory. P/N 56- 000 -6 -387. • • • shall be either repaired or replaced, at TFSBP's sole option. TFSBP neither This warranty will apply to the full Specify: W -Type 7 Sprinkler Wrench, • assumes, nor authorizes any person extent permitted by law. The invalidity, P/N 56- 850 -4 -001. • to assume for it, any other obligation in in whole or part, of any portion of this • Refer to Technical Data Sheet TFP770. • connection with the sale of products or warranty will not affect the remainder. parts of products. TFSBP shall not be Copyright © 2007 -2010 Tyco Fire Suppression & Building Products. All rights reserved. •