Hydraulic Calculations
For
H & M- Washington Square
9585 SW WA. Sq. Road
Tigard, OR 97223
Contract No. C10-4007
Date: 09 /13/10
Design data:
Occupancy classification Below New Mezzanine
Density .20 gpm/ft2 Ordinary Hazard II
Area of application 990 sq. ft. (Reduced Area)
Coverage per sprinkler 130 sq. ft. max. ft2
Sprinkler Temperature K =5.60 ''A " 155 degree : .
1 No. of sprinklers calculated Remote Area — 9 heads @ Mezz. Deck
,
In -rack demand N/A -•• -
Hose streams 250_ gpm
1 -, , Total PSI required 70.9 psi
Total water required 510.5.gpm
Source of Water Flow Data Flow Test
Name of contractor Wyatt Fire Protection
Name of project manager Eugene Lathan
Address 9095 SW Burnham, Tigard, OR 97223
Authority having jurisdiction City of Tigard
is 1
SPRINKLER SYSTEM• HYDRAULIC ANALYSIS Page 1 •
DATE: 8/30 /2010 C: \HASS74 \HNMLWRLVL.SDF
JOB "TITLE: H &M Wa Sq
WATER SUPPLY DATA -
SOURCE. STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
'TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
18 80.0 75.0 1200.0 79.0 510.5 70.9
' i
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 510.5 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 250.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 260.5 GPM
NODE ANALYSIS DATA.
NODE TAG ELEVATION • • NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) - (GPM)
1 12.2 K= 5.60 21.6 26.0
2 12.2 K= 5.60 22.1 26.3
3 12.2 K= 5.60 24.2 27.5
4 12.2 K= 5.60 28.7 30.0
5 12.9 - - - 58.3 - - -
6 12.2 K= 5.60 21.7 26.1
7 12.2 K= 5.60 22.3 26.4
8 12.2 K= 5.60 24.3 27.6
9 12.2 K= 5.60 28.9 30.1
10 12.9 - - - - 58.7 - - -
e 11 12.2 K= 5.60 51.9 40.3
12 12.9 - - - - 60.1•
13 14.3 - - 63.9 - - -
- .14 14.3 - - - - 64.2 -.- -
15 14.3 - - - - 64.4 - - -
16 14.3 - - - - 64. -,- -
17 1.0 - - - - 70.4 - - -
18 0.0 SOURCE 70.9 260.5
A .� .O PROF
Gr <0' .NE'+`Si'
y
. 13,' 98PE
..
0 9 `, � .76..1 S S44Z"
J. G_E
• t I EXPIRES //
f
SPRINKLER SYSTEM HYDRAULIC ANALYSIS. Page 2
DATE: :8 /30/2010 C: \HASS74 \HNMLWRLVL.SDF •
JOB .TITLE: H &M Wa Sq
PIPE•DATA
PIPE. TAG Q(GPM) DIA(IN) LENGTH PRESS.
''END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) _ SUM. _
NODES (FT) (K) . (PSI) (GPM) FL /FT (PSI)
Pipe: 1 -26.0 1.452 PL 13.00 PF 0.6
',.1 12.2 5.6 21.6 26.0 5.0 120 FTG - - -- PE 0.0
2 12.2 5.6 22.1 26.3 0.043 TL 13.00 PV
Pipe: 2 -52.3 1.452 PL 13.00 PF 2.1
2 12.2 5.6 22.1 26.3 10.1 120 FTG - - -- PE 0.0
• 3 12.2 5.6. 24.2'. 27.5 0.158 TL 13.00 PV
•
Pipe: 3 . • -79.9 1.452 PL 13.00 PF 4.5
3 12.2 5.6. 24.2 ' 27.5 .15.5 120 FTG - - -- PE 0.0
4 12 :.2 5.6 28.7 .30.0 , 0.346 TL 13.00 PV
Pipe: 4 • •. ' - 109.9 • 1.452. PL 40.00 PF 30.0
4 12..2 5.6 28,7' 30.0 21..3 120. FTG T PE -0.3
5 • '12.9 0.0 58.3 . 0.0 . - 0 :•624 'TL ' 48.00 PV -
Pipe: 5 -26.1 1.452 PL 13.00 PF 0.6
6 12.2 5.6 21.7 26.1 5.1 120 FTG - - - -• PE 0.0
7 12.2 5.6 22.3 26.4 0.044 TL 13.00 PV
Pipe: 6 -52.5 1.452 PL 13.00 PF 2.1
7 12.2 5.6 22.3 26.4 10.2 120 FTG - - -- PE 0.0
8 12.2 5.6 24.3 27.6 0.159 TL 13.00 PV
Pipe: 7 -80.1 1.452 PL 13.00 PF 4.5
. 8, 12.2 5.6 24.3 27.6 15.5 120 FTG ' - - -- PE 0.0
-9 . 12.2 5.6 28.9 30.1 0.348 TL 13.00 PV
Pipe: 8 -110.2 1.452 PL 40.00 . PF 30.2
- 9 . 12 :2 . 5.6 28.9 30.1 21.4. .120 •FTG. T :PE -0.3
10 12.9 0.0 58.7 • .0.0 0..62.8 TL .48.00 PV
Pipe: '9 -40.3 • 1.452 PL 79.00 PF 8.5
11 12.2 5.6 51.9 40.3 7.8 • 120 FTG T PE -0.3
12 12.9 0.0 60.1 0.0 0.098 TL 87.00 PV
Pipe: 10 -109.9 2.581 PL 10.00 PF 0.4
•
• 5 12.9 0.0 58.3 0.0 6.7 120 FTG - - -- PE 0.0
10 12.9 0.0 58.7 0.0 0.038 TL 10.00 PV
Pipe: 11 -220.1 2.581 PL 10.00 PF 1.4
10 12.9 0.0 58.7 0.0 13.5 120 FTG - - -- PE 0.0
12 12.9 0.0 60.1 0:0 0.137 TL 10.00 PV
Pipe: 12 -260.4 2.581 PL 7.50 PF 4.4
12 12.9 0.0 60.1 0.0 16.0 120 FTG 2E PE -0.6
"13 14.3 0.0 63.9 0.0 0.187 TL 23.50 PV
Pipe: 13 -260.4 3.200 PL 5.00 PF 0.3
.13 14.3 0.0 63.9 0.0 10.4 120 FTG - - -- PE 0.0
.14 14.3 0.0 64.2 0.0 0.066 TL 5.00 PV
•
•
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 8/30/2010 C: \HASS74 \HNMLWRLVL.SDF
JOB TITLE: H &M Wa Sq
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL /FT (PSI)
Pipe: 14 -260.4 3.500 PL 5.00 PF 0.2
• 14 14.3 0.0 64.2 0.0 8.7 120 FTG - - -- . PE 0.0
15 14.3 0.0 64.4 0.0 0.042 TL 5.00 PV
Pipe: 15 -260.4 5.000 PL 15.00 PF 0.1
15 14.3 0.0 64.4 0.0 4.3 120 FTG - - -- PE 0.0
16 14.3 0.0 64.5 0.0 0.007 TL 15.00 PV
Pipe: 16 -260.4 6.000 PL 25.00 PF 0.1
16 14.3 0.0 64.5 0.0 3.0 120 FTG - - -- PE 5.8
17 1.0 0.0 70.4 0.0 0.003 TL 25.00 PV
Pipe: 17 -260.5 8.000 PL 30.00 PF 0.1
17 1.0 0.0 70.4 0.0 1.7 120 FTG ETGA PE 0.4
18 0.0 SRCE 70.9 (N /A) 0.001 TL 119.02 PV •
NOTES:
(1) Calculations were performed by the HASS 7.4 computer program
under license no. 5010113212 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
(2) The system has been calculated to provide an average
imbalance at each node of 0.009 gpm and a maximum
imbalance at any node of 0.148 gpm.
•
(3) Total pressure at each node is used in balancing the system.
Maximum water velocity is 21.4 ft /sec at pipe 8.
(4) PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
PAGE: * MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v NPTee
3.548 8.00 17.00 5.00 19.00 11.00 1.00 14.00 14.00 17.00
5.047 12.00 25.00 8.00 27.00 9.00 2.00 21.00 21.00 25.00
6.065 14.00 30.00 9.00 32.00 10.00 3.00 28.00 28.00 30.00
7.981 18.00 35.00 13.00 45.00 12.00 4.00 31.00 31.00 35.00
•
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 8/30/2010 C: \HASS74 \HNMLWRLVL.SDF •
JOB TITLE: H &M Wa Sq
PAGE.: C MATERIAL: XL HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Ell Tee LngEll ChkVly BfyVly GatVly A1mChk DPV1v NPTee
1.452 4.00 8.00 3.00 9.00 8.00 1.00 13.00 13.00 8.00
2.581 8.00 15.00 4.00 17.00 9.00 1.00 13.00 13.00 15.00
3.200 9.00 19.00 6.00 20.00 12.00 1.00 16.00 16.00 19.00
� r •
o �
Uy 1-3
WATER SUPPLY ANALYSIS
100.0 Static: 80.00 psi Resid: 75.00 psi Flow: 1200.0 gpm y °
rte.
o
�
•LEGEND
• m
a,
x
Available pressure z °
78.97 psi @ 510.5 gpm
2 Required pressure 4 G 80.0 70..89 psi @ 510.5 gpm ,�.
A
H
U z
G x
L-1
E th
P 60.0 '<
R -3
E 3
S x
S d
R C
E 40.0
n
p en
s u'
H
1
20.0
. x
z
3
0.0 r
• 4
to m
0
N ..
-14.7
I I I I I I I I
400 600 800 1000 1200 1400 1600 1800 2000
FLOW (GPM)
tqcci Fire & Building
. Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K- factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
tamed when exposed to corrosive at-
mospheres. Although corrosion resis-
tent coated sprinklers have passed the �' ' -_
Description standard corrosion tests of the appli- -- •
cable approval agencies, the testing is
The Tyco® Series TY -FRB, 2.8, 4.2, not representative of all possible cor-
5.6, and 8.0 K- factor, Upright and Pen- rosive atmospheres. Consequently, it !
dent Sprinklers described in this data is recommended that the end user be ( ''
i i iii 1
sheet are quick response - standard consulted with respect to the suitability
coverage, decorative 3 mm glass bulb of these coatings for any given corro- e
type spray sprinklers designed for use sive environment. The effects of ambi- , _ - • •
in light or ordinary r
9 rY hazard, comme rcial ent temperature, concentration of — r ,,� - ;
occupancies such as banks, hotels, chemicals, and gas /chemical velocity, ''_'
shopping malls, etc. should be considered, as a minimum, ,
The recessed version of the Series along with the corrosive nature of the
TY -FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be ��`
plicable, is intended for use in areas exposed.
with a finished ceiling. It uses either a An intermediate level versions of the
two -piece Style 10 (1/2 inch NPT) or Series TY -FRB Pendent Sprinklers - l r N rt
Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet t '
cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de- ` s
recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780 ,
(19,1 mm) of total adjustment from the ;IE.
flush pendent position, or a two -piece WARNINGS a ' , .. ,
-,....r: Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY -FRB Sprinklers de- -,....r: •
inch NPT) Recessed Escutcheon with scribed herein must be installed and •--
1/4 inch (6,4 mm) of recessed adjust maintained in compliance with this
ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica-
total adjustment from the flush pen ble standards of the National Fire Pro -
dent position. The adjustment pro tection Association, in addition to the
vided by the Recessed Escutcheon re - standards of any other authorities hay- Model /Sprinkler
duces the accuracy to which the fixed ing jurisdiction. Failure to do so may
pipe drops to the sprinklers must be impair the performance of these de- Identification
cut. vices.
Corrosion resistant coatings, where The owner is responsible for maintain- Numbers
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2 "NPT
that which would otherwise be ob - The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2"NPT
manufacturer should be contacted TY2131 - Upright 4.2K, 1/2 "NPT
with any questions. TY2231 - Pendent 4.2K, 1/2 "NPT
IMPORTANT TY3131 - Upright 5.6K, 1/2 "NPT
Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2 "NPT
Sheet TFP700 for the "INSTALLER TY4131 - Upright 8.0K, 3/4"NPT
WARNING" that provides cautions TY4231 - Pendent 8.0K, 314 "NPT
with respect to handling and instal - TY4831- Upright 8.0K, 1/2"NPT
lation of sprinkler systems and corn- TY4931- Pendent 8.0K, 1/2 "NPT
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 AUGUST, 2007 TFP171
•
•
Page 2 of 10 TFP171
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
• -- • PLATE SEATING NOMINAL RECESSED
. SURFACE 1/2 MAKE -IN ESCUTCHEON
NPT DEFLECTOR
I DEFLECTOR
= 5
ir -.----- 7/ 16" . -1 / 4 " } (11 ,1 mm) I q
(57,2 mm) � INAL � � NOM I I
1 � MAKE -IN 2
1- 9%16" I �I' I WRENC H52536/16) , 3�
FLATS _ If 1
SSP DEFLECTOR. - 2 -7/8" (73,0 mm) DIA. 1/2" NPT f 7
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
•
1 - Frame 3 - Sealing 4 - Bulb . 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
•
. Screw •
• FIGURE 1 • • -
• -
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT .
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or '20
PLATE SEATING NOMINAL RECESSED *
SURFACE
1/2" T M A MAKE-IN ESCUTCHEON DEFLECTOR
i —..--
r 7/16" �� 5
2 -3/16" f 1!• (11,1 mm) •
(55,6 mm) } 11.1.111111 Ate— NOMINAL 11 4
� MAKE -1N •
1 1/2 " 11110 1 ii 1S1=r - 2- 3/16" tj 2
(38,1 mm) WRENCH
_ i (55,6 mm) 3
' . ----=—_---. . 1 0
SSP DEFLECTOR * -- •• - 2 -7/8" (73,0 mm) DIA. • 1/2" NPT 1
• PENDENT - RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 2
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K- FACTOR, 1/2 INCH NPT
•
•
•
TFP171 Page 3 of 10
. ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 •
PLATE SEATING NOMINAL • RECESSED * • SURFACE 1/2" T MAKE -IN • ESCUTCHEON DEFLECTOR
i —___
6
\ ,-_—_— fi W sir 5
2-3/16" } �i1' P•11,11 7/16"
�� I (OMINA mm
• (55,6 mm) �
) I
} NL i 4
MAKE -IN
• 1 -1/2" id �II! �� L 2 -3/16 V!, 2
(3,1m) WRENCH ts
i �_ � FLATS I 3
SSP DEFLECTOR. — 2 -7/8" (73,0 mm) DIA. 1 1/2" NPT 1 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3•- Sealing 4 - Bulb. 6 - Deflector • * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
• . • Screw
• •
•
. FIGURE 3 • •
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
•
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40
PLATE SEATING NOMINAL RECESSED *
•
• SURFACE 3/4" MAKE -IN ESCUTCHEON SSU
NPT I DEFLECTOR
_ 6 *
1/2"
�; 5
2 -5/16" � (12,7 mm) I
=
(58,7 mm) IA � ����� 11111 NOMINAL MAKE -IN
11 i 1 4
1 -9/16"
• 1 2 -1/4" 1 2
•
(39,7 mm) I WRENCH (57,2 mm) 9'
I1 FLATS s$1,4 - 3
1 1
SSP DEFLECTOR �— 2 -7/8" (73,0 mm) DIA. 3/4 ".NPT I
• PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 4
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
•
Page 4 of 10 • TFP171
•
7/16" (11,1 mm)
1/2" NOMINAL SSU
NPT MAKE -IN DEFLECTOR
*6
•
} mrI
2-3/16" S
2 -1/4" (57,2 mm) r ' (55,6 mm) 4
• 14 W
1 -9/16" I WRENCH � ' 2
(39,7 mm) FLATS 1
1 -- - 3
SSP * . 1
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 -Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
•
Screw
FIGURE 5
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K- FACTOR, 1/2 INCHNPT
Technical Operation
Data The glass Bulb contains a fluid which
expands when exposed to heat. When
Approvals the rated temperature is reached, the
UL and C -UL Listed. fluid expands sufficiently to shatter the
•
FM, LPCB, and NYC Approved. glass Bulb, allowing the sprinkler to •
(Refer to Table A and B for complete activate and water to flow. • '
•
approval information including corro-
sion resistant status.) Design.
. Maximum Working Pressure . .
• Refer to Table C. • . criteria.
Discharge Coefficient
K = 2.8 GPM /psi (40,3 LPM /barl/2) ' The Series TY -FRB Pendent and Up-
K = 4.2 GPM /psi / (60,5 LPM /bar1 /2) right Sprinklers are intended for fire
K = 5.6 GPM /psi / (80,6 LPM /bar1/2) protection systems designed in ac-
K = 8.0 GPM /psi / (115,2 LPM /bars /) cordance with the standard installation
rules recognized by the applicable
Temperature Ratings Listing or Approval agency (e.g., UL
Refer to Table A and B Listing is based on the requirements of
Finishes NFPA 13, and FM Approval is based
Sprinkler: Refer to Table A and B. on the requirements of FM's Loss Pre -
Recessed Escutcheon: White Coated, vention Data Sheets ). Only the Style
Chrome Plated, or Brass Plated. 10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Physical Characteristics
Frame Bronze E
. Button Brass /Copper 0
Sealing Assembly
Beryllium Nickel w /Teflont 0
Bulb Glass
Compression Screw Bronze N
Deflector Copper /Bronze
ce
Bushing (K =2.8) Bronze E'
0
a
. a
•
•
•
•
•
•
•
TFP171 Page 5 of 10
. SPRINKLER FINISH (See Note 7)
K• TYPE TEMP.- BULB NATURAL CHROME WHITE*** •
LIQUID BRASS PLATED POLYESTER
135 °F /57 °C Orange
PENDENT 155"F/68°C Red
(TY1231) 1, 2, 3, 5
and 175 °F /79 °C Yellow
UPRIGHT 200 °F /93 °C Green
2.8 (TY1131)
286"Ft141°C Blue
1/2"
NPT 135 °F /57 °C Orange
RECESSED
155"F168°C Red
PENDENT
(TY1231)* 175 °F /79 °C Yellow
Figure 6 200 °F /93 °C Green 1, 2, 5
135 °F /57 °C Orange
•
RECESSED 155 °F /68 °C Red
PENDENT
(TY1231)** 175 °F /79 °C Yellow •
Figure 7 200 °F /93 °C Green
135 °F /57 °C Orange • •
PENDENT 155 °F /68 °C Red •
(1Y2231)
and 175 °F /79 °C Yellow
UPRIGHT 200 °F /93 °C Green •
4.2 (TY2131)
286"F1141°C Blue
1/2" 1 2
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT
• (TYY431)* 175 °F /79 °C Yellow
Figure 8 200"F/93°C Green
135 °F /57°C Orange •
RECESSED 155 °F /68 °C Red
• PENDENT
(TY2231)** 175"F179°C Yellow
Figure 9 200"F/93°C Green •
NOTES: •
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Re-
sponse Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354 -01 -E.
7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin-
klers are UL and C -UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
* ** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K- FACTOR SPRINKLERS
•
°
•
•
•
•
•
•
•
•
Page 6 of 10 TFP171
• SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB - NATURAL - CHROME WHITE"' - - LEAD -- • • •
LIQUID BRASS PLATED POLYESTER COATED
135 °F /57 °C Orange
• PENDENT 155 °F /68 °C Red
(TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5
and 175 °F /79 °C Yellow
•
• UPRIGHT 200 °F /93 °C Green
5.6 (TY3131)
286"F/141°C Blue •
• 1/2"
NPT 135"F/57°C • Orange
RECESSED 155 °F /68 °C • Red
PENDENT • 1, 2, 4, 5 N/A
(TY3231)" 175 °F /79 °C Yellow.
Figure 10 200 °F /93 °C Green
• 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
• PENDENT - 1, 2, 3, 4, 5 N/A
(TY3231)" 175 °F /79 °C Yellow
•
Figure 11 200 °F /93 °C Green •
•
• . 135 °F /57 °C Orange • •
PENDENT 155 °F /68 °C Red
(TY4231) 1, 2, 5
and 175"F/79°C Yellow 1, 2, 3, 4, 5, 6, 7
UPRIGHT 200 °F /93 °C Green
8.0 (TY4131)
286 °F /141 °C Blue
3/4"
NPT 135 °F /57 °C Green •
RECESSED 155"F/68°C Orange
PENDENT 1, 2, 4, 5 N/A
(TY4231)* 175 °F /79 °C Red
Figure 12 200 °F /93 °C Yellow
•
135"F/57°C Orange
RECESSED 155"F/66°C Red • PENDENT 1, 2, 3, 4, 5 - N /A
(TY4231)" 175 °F /79 °C Yellow •
Figure 13 200 °F /93 °C Green •
•
•
135"F/57°C Orange
•
PENDENT 155 °F /68 °C Red •
8.0 (TY4931) 1, 2, 5
1/2" and 175 °F /79 °C Yellow 1, 2, 4, 5, 6
NPT UPRIGHT 200 °F /93 °C Green
(TY4831)
286 °F /141 °C Blue
NOTES:
• 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers. .
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428 -4444 /Fax 31 -53- 428 - 3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
• Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
"' Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
• TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K- FACTOR SPRINKLERS
•
•
•
•
•
•
•
•
•
•
•
TFP171 Page 7 of 10
•
SPRINKLER FINISH
- K - - TYPE- NATURAL CHROME WHITE LEAD •
•
BRASS PLATED POLYESTER COATED
PENDENT (TY3231)
. and
2 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/2" RECESSED PENDENT
NPT (TY323)
•
PENDENT (TY4231)
and
4 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
3/4" RECESSED PENDENT •
NPT (TY4231)
PENDENT (TY3231)
•
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 UPRIGHT (TY3131) OR
1/2" RECESSED PENDENT 175 PSI (12,1 BAR)
NPT (TY3231)
(SEE NOTE 1) N/A
•
PENDENT - (TY4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8 UPRIGHT (TY4131)
3/4" RECESSED PENDENT
NPT (TY4231) N/A
8.0 PENDENT (TY4931)
1/2" and 175 PSI (12,1 BAR) • 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4831)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
• Underwriters Laboratories, Inc. for use in Canada (C -UL); and , the Approval by the City of New York.
- - TABLE C, MAXIMUM WORKING PRESSURE '
•
tained with a torque of 10 to 20 ft.lbs. the sprinkler into the sprinkler fitting.
Installation (13,4 to 26,8 Nm). A maximum of 30 Step 3. Tighten the sprinkler into the
ft.lbs. (40,7 Nm) of torque is to be used
sprinkler fitting usin onl the W T e
The Series TY -FRB Sprinklers must to install sprinklers with 3/4 NPT con p g g y 4
be installed in accordance with the fol- nections. Higher levels of torque may 6 Sprinkler Wrench (Ref. Figure 1 14).
Instructions: With reference to Figures 1, 2, 3, 4,
lowing distort the sprinkler inlet and cause and 5, the W -Type 6 Sprinkler Wrench
NOTES leakage or impairment of the sprinkler. i to be appl to the sprinkler wrench
Do not install any bulb type sprinkler if Do not attempt to make -up for insuffi- flats.
the bulb is cracked or there is a loss of cient adjustment in the escutcheon The Series TY -FRB Recessed Pen -
liquid from the bulb. With the sprinkler plate by under- or over - tightening the dent Sprinklers must be installed in
held horizontally, a small air bubble sprinkler. Readjust the position of the accordance with the following instruc
should be present. The diameter of the sprinkler fitting to suit. tions.
air bubble is approximately 1/16 inch The Series TY -FRB Pendent and Up- Step A. After installing the Style 10.
(1,6 mm) for the 135F/57°C to 3/32 right Sprinklers must be installed in 20, 30, or40 Mounting Plate, as appli-
inch (2,4 mm) for the 286 °F /141 °C accordance with the following instruc- cable, over the sprinkler threads and
temperature ratings. tions. with pipe thread sealant applied to the
A leak tight 1/2 inch NPT sprinklerjoint Step 1. Pendent sprinklers are to be pipe threads, hand tighten the sprin-
• should be obtained with a torque of 7 installed in the pendent position, and kler into the sprinkler fitting.
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi upright sprinklers are to be installed in Step B. Tighten the sprinkler into the
mum of 21 ft. lbs. (28,5 Nm) of torque the upright position. sprinkler fitting using only the W -Type
may be used to install sprinklers with Step 2. With pipe thread sealant 7 Recessed Sprinkler Wrench (Ref.
e
1/2 NPT connections. A leak tight 3/4 p 2 . pipe thread
ea, hand a a Figure 15). With reference to Figure 1,
e
inch NPT sprinkler joint should be ob plied the p p tighten 2, 3, and 4, the W -Type 7 Recessed
•
Page 8 of 10 TFP171
2 -7/8° DIA. 2 -7/8" DIA.
5/8±1/4" (73,0 mm) 3/4" (19,1 mm) (73,0 mm)
1/2±1/8 _ 1/2" (12,7 mm) . .
(15,9±6,4 mm) 2 -1/4° DIA. 1/4° (6,4 mm) (12,7±3,2 mm)
2 -1/4° DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) 1
SPRINKLER PLATE SPRINKLER MOUNTING
PLATE
FITTING FITTING
1/8° 1/8"
•T' (3,2 mm) •� I (3,2 mm)
cl�lI ■ � 181U ///.' I ,
�� i1�-Imo_ 1
■i �% �i
MOUNTING
II/ f
MOUNTING SURFAC .
y �
SURFACE .�.� ,ter -r\r. ,
•
CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1 -5/16° (33,3 mm)
TY -FRB 13/16° (20,6 mm) TY -FRB 1 -1/16° (27,0 mm)
FIGURE 6 FIGURE 7
•
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR; 1/2 INCH NPT
2 -7/8" DIA. 2 -7/8" DIA. ' _
5/8±1/4" , (73,0 mm) . 3/4" (19,1 mm) 1/2±1/8" (73,0 mm) 1/2" (12,7 mm)
(15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm)
•
2 -1/4" DIA. 1/4" (6,4 mm)
FACE OF (67,2 mm) MOUNTING FACE OF (57.2 mm)
SPRINKLER PLATE SPRINKLER • MOUNTING
PLATE
FITTING FITTING
1/8" (,2 mm)
1/8"
I (3,2 mm) 1 � ' , 3
61811,4 /. � M .
=J t
�: } SURFACE ly
MOUNTING
SURFACE • ___..
CLOSURE SERIES . 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm)
TY -FRB 3/4' (19,1 mm) TY-FRB 1" (25,4 mm)
FIGURE 8 FIGURE 9
SERIES TY -FRB RECESSED PENDENT • SERIES TY -FRB RECESSED PENDENT
. WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT .
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
. 4.2 K- FACTOR, 1/2 INCH NPT _4.2 K- FACTOR, 1/2 INCH NPT
•
Sprinkler Wrench is to be applied to work on the fire protection system that altered after leaving the factory. Modi-
the sprinkler wrench flats. it controls, permission to shut down the fied sprinklers must be replaced.
Step C. After the ceiling has been in- affected fire protection system must be Sprinklers that have been exposed to
stalled or the finish coat has been in- obtained from the proper authorities corrosive products of combustion, but
plied, slide on the Style 10, 20, 30, or and all personnel who may be affected have not operated, should be replaced
40 Closure over the Series TY -FRB by th act must be not if they cannot be completely cleaned
Sprinkler and push the Closure over The owner must assure that the sprin by wi the sprinkler with a cloth or
the Mounting Plate until its flange klers are not used for hanging of any by brush i t w a soft br brush.
comes in contact with the ceiling. objects; otherwise, non - operation in Care must be exercised to avoid dam -
the event of a fire or inadvertent opera age to the sprinklers - before, during,
C are and tion may result. and after installation. Sprinklers dam -
Absence of an escutcheon, which is aged by dropping, striking, wrench
Maintenance used to cover a clearance hole, may twist/slippage, or the like, must be re-
delay the time to sprinkler operation in placed. Also, replace any sprinkler
a situation. that has a cracked bulb or that has lost
The Series TY -FRB Sprinklers must liquid from its bulb. (Ref. Installation
. be maintained and serviced in accord- Sprinklers that are found to be leaking Section).
ance with the following instructions: or exhibiting visible signs of corrosion
must be replaced. Frequent visual inspections are rec
NOTES ommended to be initially performed for
Before closing a fire protection system Automatic sprinklers must never be corrosion resistant coated sprinklers,
main control valve for maintenance painted, plated, coated or otherwise after the installation has been com-
TFP171 Page 9 of 10
2 -7/8" DIA. 2 -7/8" DIA. •
• 5/8±1/4" (73,0 mm) 3/4° (19.1 mm) (73.0 mm) _
. .. (15,9±6,4 mm) 1/4" 1/4 (6,4 mm) 1/2±1/8" 1/2" (12,7 mm)
2 -1/4° DIA. ( ) (12,7±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm)
SPRINKLER PLATE SPRINKLER MOUNTING
PLATE
.' FITTING FITTING
1/8" 1/8'
'�' (3,2 mm) '. (3,2 mm)
i , • r M9pm - r• , MOUNTING
�� , ` -J SURFACE
MOUNTING lir f ,
- - -- _ -
SURFACE :- f
CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm) •
TY-FRB 3/4" (19,1 mm) TY -FRB 1" (25,4 mm)
FIGURE 10 FIGURE 11
SERIES. TY -FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON • STYLE 20 RECESSED ESCUTCHEON . • 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR; 1/2 INCH NPT
. 2 -7/8" DIA. 2 -7/8" DIA. • 5/8±1/4" (73,0 mm) • 3/4° (19,1 mm) 1/2±1/8" (73,0 mm) 1/2" (12,7 mm)
• (15,9±6,4 mm) 2 -1/4" DIA. ( 1/4" (6,4 mm) .(12,7±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) I . MOUNTING (57,2 mm)
FACE OF MOUNTING • SPRINKLER PLATE SPRINKLER • PLATE
. FITTING FITTING
1/8" 1/8°
" (3;2 mm) ° (3,2 mm)
�'rlll . ■Ili ���"
/ --II-
711 } ` �o>. }
, MOUNTING IIP MOUNTING � � SURFACE SURFACE i S • ,
• CLOSURE ' SERIES . 1 -5/16" (33,3 mm) CLOSURE SERIES;. • • 1 -5/16" (33,3 mm)
TY -FRB 13/16" (20,6 mm) TY-FRB 1 -1/16" (27,0 mm)
• • , FIGURE 12 . • ' FIGURE 13'
•
• . . SERIES TY -FRB RECESSED PENDENT .. • SERIES TY -FRB RECESSED PENDENT
• _ WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON " STYLE 30 RECESSED ESCUTCHEON
• 8.0 K- FACTOR, 3 /4.INCH NPT "8.0 K- FACTOR, 3/4 INCH NPT
• pleted, to verify the integrity of the cor WRENCH
rosion resistant coating. Thereafter, �' RECESS
annual inspections per NFPA 25
should suffice; however, instead of in- WRENCH RECESS f��
specting from the floor level, a random (END "A" USED FOR
sampling Of close -up visual inspec- 1/2 " NPT MODELS) ).
tions should be made, so as to better ,..d `I
determine the exact sprinkler condi- `+
tion and the long term integrity of the ..41,..
• corrosion resistant coating, as it may WRENCH RECESS
be affected b y the corrosive conditions (END "B" USED FOR PUSH WRENCH
3/4" NPT MODELS IN TO ENSURE
present. ) •ENGAGEMENT
The owner is responsible for the in- F 14 WITH SPRINKLER WRENCHING AREA
spection, testing, and maintenance of W - TYPE 6 SPRINKLER
their fire protection system and de- WRENCH FIGURE 15
vices in compliance with this docu- W - TYPE 7 RECESSED
• ment, as well as with the applicable SPRINKLER WRENCH
standards of the National Fire Protec facturer should be contacted relative
tion Association (e.g., NFPA 25), in to any questions.
addition to the standards of any other It is recommended that automatic Inspection Service in accordance with
authorities having jurisdiction. The in- sprinkler- systems be inspected, local requirements and /or national
stalling contractor or sprinkler manu- tested, and maintained by a qualified codes.
•
•
•
Page 10 of 10 TFP171
•
P/N 57 - XXX - X XXX .. .
I
TEMPERATURE
MODEUSIN RATING
SPRINKLER -
330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135F/57°C
331 2.8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C
340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C
341 4.2K PENDENT (1/2 "NPT) . TY2231 3 WHITE (RAL9010)* 200 200F/93°C
370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C
371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED
390 8.0K UPRIGHT (3/4 "NPT) TY4131
391 8.0K PENDENT (3/4 "NPT) . TY4231 • Eastern Hemisphere sales only.
360 8.0K UPRIGHT (1/2 "NPT) TY4831*
361 8.0K PENDENT (1/2 "NPT) TY4931' •
TABLE D
PART NUMBER SELECTION
• SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS
Limited contract, no event shall TFBP be Ordering
contract, tort, strict or under liability or under
Warranty any other legal theory, for incidental, -
indirect, special or consequential dam- P rocedure
ages, including but not limited to labor
Products manufactured by Tyco Fire & charges, regardless of whether TFBP When placing an order, indicate the
Building Products (TFBP) are war- was informed about the possibility of full product name. Refer to the Price
ranted solely to the original Buyer for such damages, and in -no event shall List for complete listing of Part Num-
.
. ten (10) years against defects in mate- TFBP's liability exceed an amount bers.
• rial and workmanship when paid for equal to the sales price. Contact your local distributor for avail-
and properly installed and'maintained •
under normal use and service: This The foregoing warranty is made in lieu ability.
warranty will expire ten (10) years
of any and all other warranties. ex-
from date of shipment by TFBP. No press or implied. including warranties Sprinkler Assemblies with NPT
warranty is given for products or corn- of merchantability and fitness for a par- Thread Connections:
ponents manufactured by companies. ticular purpose. Specify: (Specify Model /SIN), Quick
not affiliated by ownership with TFBP This limited warranty sets forth the ex- Response, (specify K- factor), (specify
(sm
or for products and components which clusive remedy for claims based on cif Pee ype rating), Series pri FRB
(specify
have been subject to misuse, improper failure of or defect in products, materi- with (specify Pendent or Upright) Sprinkler
w (specci fy type of finish or coating),
installation, corrosion, or which have als or components, whether the claim P/N (specify from Table D).
not been installed, maintained, modi- is made in contract, tort, strict liability
fled or repaired in accordance with ap- or any other legal theory. Recessed Escutcheon:
plicable Standards of the National Fire
Protection Association, and /or the This warranty will apply to the full ex- Specify: Style (10, 20, 30, or 40) Re-
standards of any other Authorities tent permitted by law. The invalidity, in cessed Escutcheon with (specify *) fin -
Having Jurisdiction. Materials found whole or part, of any portion of this ish, P/N (specify *).
by TFBP to be defective•shall be either warranty will not affect the remainder.
• repaired or replaced, at TFBP's sole
Refer to Technical Data Sheet TFP770.
option. TFBP neither assumes, nor Sprinkler Wrench:
authorizes any person to assume for it, Specify: W -Type 6 Sprinkler Wrench,
any other obligation in connection with P/N 56- 000 -6 -387.
the sale of products or parts of prod-
.
ucts. TFBP shall not be responsible for Specify: W -Type 7 Sprinkler Wrench,
sprinkler system design errors or inac- P/N 56- 850 -4 -001.
curate or incomplete information sup-
. plied by Buyer or Buyer's repre-
sentatives.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
. .. • . .
i / 7/
Dyna1mreaci®
Full Line S Replacement
Dyne- Thread' offers the life expectancy of Sch40 with superior hydraulics and greater value.
Dyna- Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety
. • and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages.
Comparison to Schedule 40
Cotnpatlsoir to U .W.T Pipes
• DPI- Thread's inside diameter la uP • With its increased strength and lighter • More wall thickness at the thread
to 3.6% larger than Soh -40 giving it weight, Dyna- Thread reduces (CRR -1.00) gives Dyna- Thread
superior hydraulics. And, when used installation fatigue and is ideal for better life expectancy than lightwall
in combination with Dyne -Flow pipe, repo -fit applications. threadable pipe joints.
down sizing often occurs.
Corrosion Resistance Ratio (CRR) is a • Unlike lightwall threadable pipe,
• Dyna- Thread is fully listed and UL (Underwriters Laboratory) term for Dyna - Thread has no thread gauge
approved by UL, ULC, and FM fir the estimated life expectancy of a pipe warning.
fire sprinkler applications. joint This is based on the calculated
wall thickness at the base of the first
•
The life • Dyne- Thread is approved for
life expectancy of Dyna- Thread standard hanger spacing (15 ft.
and Sch-40 are equal based on the • exposed thread assumed to be the O.C.), can be used as earthquake
calculated. wall thicknesses per UL weakest point of the pipe length, Dyaa- sway bracing, and is safe to use eta
Thread and Sch-40 have the same
• The consistent quality of steel used to calculated wall thicknesses at this point GPs' -
make Dyne- Thread fbotlitatea smooth. and are bath assigned the same CRR of . Dm- Thread is safer to weld on,
threading and lower maintenance 1.00.
costs. • Dyne- Thread is more widely
The internal aur>boe'of all black Allied accepted than lightwall threadable
• The exterior of Dyna- Thread is where Sob-40 is specified.
promoted by a clean, durable mill Tubs & Conduit Fire Sprinkler pipe
coating fix extended shntf life and products UP to 4.5000" in diameter is
easy paint application. coated with our now Antibacterial
Formula, "ABF". In scientific laboratory • • -
teat, ABS proved to have superior Specifications & Approy;.
resistance to microbial colonization of
- ® G pipe walls, thereby delaying or possibly Super 40/Dyna- Thread pipe is
preventing the onset of manufactured to meet: ASTM A -135,
Usted Approved Listed - Microbiologically Influenced corrosion . ' Grade A and is in eomplianco with
. (MIC) when the First Sprinkler System 1VFPA -13. All sizes of Super 40/Dyna-
is Brat installed. Thread are rated at 300 psi working
pressure. Super 40/Dyna- Thread is UL
5Necifications and ULC Listed for wet, dry deluge and
pre- action sprinkler systems and FM
NM Namhtal 1,0, WI, Wt. (H20 F1114 Pay WI1Jtt (21') W1/1111124') WA (25' Approved for use in wet systems. Super
In: mm In: mm Lbs ft Kp4n Lbaft K4/nz Lift Lbs; Kg Lbs: Kg Lbs; Kg 40/Dyne- Thread can bo "hot -dip"
1' 1.080 1.330 1,75 70 1955 2234 2327 galvanized to meet FM requirement for
25 27.4 2.0 2.80 70 887 1013 105: thy ayetoms. Super 40/Dyne -Thread is
1W 1,408 1,870 2.54 51 2002 2288 2984 approved for all threaded couplings and
32 55.8 2.8 3,78 51 908 1038 108 welded outlets and is suitable for all
1'4' 1.698 2 290 3.22 44 2116 2418 261 roll grooved, and plain -end fittings.
40 41.6 3.4 4,79 44 959 1097 114 (See listing inftrrmation).
2' 2.104 3.080 4.57 30 1821 2195 2287
50 53.4 4.6 9.80 30 871. 906 103
t8lC17/Rowco � obis,,,,1 16100 S. Lathrop • Harvey, IL 60428 Customer Service:
Cr) ( � d 11350 Noncom Rd. •Philadelphia, PA 19154 (B00) 882 -5543
TUBE aoNDUfT 2626 N, 27th Ave, • Phoenix, AZ 85009 Fax 708 -339 -1806
S3.3
•
•
Submittal Data Sheet .
Dyna- Threads SnmPHer •
Full Line Sch-40 Replacement
Dyne- Thread sprinkler pipe represents an c advancement for the sprinkler
• pipe industry. It combines the safety and longevity of traditional Soh-40 pipe with
. giiality and suparlor hydsatilic advantages.
Comparison to Schedule 40 Dyna- Threader inside dimmer is up to 3.6% larger than
Sch-40 giving it superior hydraulics. Also, when used in combination with Dyna.Flow
. pipe, drnvn siting often occurs. Dyne- Thread is filly listed and approved UL, ULC,
and FM for fire sprinkler applications. The life expectancy of Dyna- Thread and Sch-40 •.' . •
are equal based on the calculated wall thicltnesscs per UL. The consistent quality of steel used to make Dyne-Thread facilitates smooth threading and lower maintenance - -- -- I.. • !`. ' _ . .;
costs.. The exterior of Dyne- Thread is protected bye clean, durable mill coating for
=tended shelf life and easy paint application. With its increased strength and lighter
. weight, Dyne - Thread reduces installation fatigue and is ideal for retro -fit applications. p • ' Corrosion Rcsiatance Retie (CRR) is a UL (Uadetwritem Laboratory) term for the x `':
esomared life ctimeetiatey ofapipe joint This is based on the calculated wall thickness - .:f:' - •. '
at the base of the first exposed thread, aaatmred to be the weakest paint of the pipe ..,1
' length. Dyna.Tbrtad and Soh-40 have the game calculated wall thitlmesses at this
point and are both assigned the same CRR o f 1.00. , ?t, t >) . i' �`'
P �. era :s t�::y •
Comparison to L.W.T. Pipe . Mom wall thickness at the thread CRR =1.00 ' r N ' •
Coen
P p ( �. y • � . • Dynaa- Tbncad better hitb espectsory than lightwall threadabic pipe joints. Unlike ' _ 4 lt
lightwell threadahic pipe Dyne- Thread has no thread gauge warning. Dyna- Thread is x `l _ '. ' < " . � 9
. approved for mawl r d hangar spacing (15 ft O.C.), can be used as earthquake sway Li,„ 'r � , e .9
bracing,- and is s a f e to use.as'dropa. Dyna - Thread is s a f e r to weld on than many M 'r'. ;�:•.::.::.•; ,.
coated lightwall thrcadable pipe products. Dyne-Thread is more widely aeecpted than hA Rj s �7y .`;.: .. • 4's' '' � � !∎ '•;•::, :
lightwall threadable where Soh-40 is specified. ,,:�. ?s:',:
Specifications & Approvals. Super 40/ •
a- Thread Specifications •
meet: ASTM A 135, Grade A and is in • NP8 Nsmisal I.O. W. WI (820 Filled) Pty WILIR (21') WVLin (24') WW h an
compliance with NFPA -13. All sizes of In: mm hr mm LAM Kpth1 LIAR; Kg/n Leif . Lela; Kg Lk; Kg Lbs• Kg
Super 40/Dyna- Thread are rated at 300 1' 1.080 1.330 1.75 ' 70 1955 2234 2927
psi working pressure. Super 40/ Dyna- 25 27.4 2.0 260 70 887 1013 105E
Thread is IJL and ULC L stud for Wet, 11/4' - 1.408 1.870 2.54' 51 -2002 2288 2384
dry and pro-action Sprinkler systems and 92 36.8 ?.8 .8.78 51 808 7098 1081
FM Approved for use in wet systems.
Super 40/Dyne- Thread oar be "hot-dip" 114' 1.639 2280 3.22 • . 44 2115 2418 2519
galvanized to meet FM requirement for . 40 414 3.4 • 4.79 44 959 1097 114.1
dry systems. Super 40✓Dyna- Thread is 2' . 2.104 3.050 - • 4.67 30 1921 2196 • • 2287
approved for all threaded couplings and 60 . 534 4.5 . 6.80 30 871 . 998 .1031
welded outlets and is suitable for all roll- .
grooved, and plain -end fittings. (See American Tlmbc and Pipe visa acquired by Allied Tube and Conduit on February 1,
listing information), • . 1997. The engineered lightwall and standard wall family of products although they
r have difkrent names arc the same in all respects with regard to ausngth, weight,
Tho internal surface of all black Fits
bundle count, listings and
' . Sprinkler pipe up to 4.5000" in diameter
approvals. For easmpk,
m
shall be coated with Allied Tube & Dyne -Flow and Super Flo arc the same product as (g)
Conduit Antibacterial Form ula "ABF ", me Dyes Thread and Super 40. XL is manufactured 4,0 E-)
with Exterior galvanized coating. BLT is •
manufactured with Black lacquer costing. Crated Approved Listed
•
Project: 8prinkter Contractor: Data:
Engineer: Specification Reference: System Type:
Locations: comments:
. S3 -4
•
•
. Dyn
Frow ® .
High Strength Steel Pipe
The original high-strength lightwall sprinkler pipe with hydraulics superior io Schedule 1O.
•
Dyne -Flow pipe is the "original" high- Specifications
strength lightwallsprinkler pipe. Dyne-
• Flow has outstanding hydraulic MPS Union I.O. ' Wt. Wt. (H20 Filled) 'Pest WWI (21') Waift (21 WULIR (25')
capabilities and is recognized as the In; mm In: mm Lbs/FL• Wm UDR: KO) VII Lba; Kg Liss; Kg Lbs; Kg
most popular alternative to Schedule -10 1' 1.181 0.830 1.31 91 1,586 1,812 ' 1,888
•
pipe. Lightweight, easy to out and easy . 25 30.3 12 1.95 91 719 822 856
to handle for installation. Dyna -Flow is a 110 1.536 1.059 1.87 81 1,356 1,550 1,615
valuable addition to any fire protection 32 39.0 1.8 2.78 ' 61 815 703 733
• system. :: 1W 1.728 1.687. 2.71 61 2,135 2,440 2142
Superior Hydraulics 40 43,9 2.5 403 81 888 1107.. 1163
2' 2.203 2.104 3.79 97 1,634 1,888 1,946
. With an inside diameter of up to 119i 50 580 3.1 5.84 97 741 847 883
larger than Schedule -40 and up to 7% 2W 2.703 2.564 5,10 ' . 30 1,615 1,848 1,923
larger than Schedule -10, Dyne -Flow 85 657 18 759 30 733 837 872
. pipe hydraulics are exceptionaL Larger ' 3' 3.314 3.387 ' 7,18 . 19 1,951 1,544 1,608
I.D.s enable Dyna -Flow, and related 80 842 6.0 . 10.69 19 613 700. 729
components, to be down -sized within the 4. 4,310 4.479 10,88 • 19 ' 1,784 2,039 2,124
, e system, thus increasing the potential for 90 109.5 8.7 1616 19 809 925 283
,, job cost savings. For complete Rarest -
Williams charts, refer to "Dyne -Flow
Hydraulic Data 'nobles" '
Coatings & Fabrication Specifications & ANpiouals , Additional 13eneiits ' •
Dyna -Flow products are coated with Dyna -Flow /Super Flo pipe is tnanufac- • Lightweight and easy to install,
an environmentally approved and Lured to meet A-795 Type B, resulting in more efficient use of your
specially formulated modified -acrylic or Cirede A and is in compliance with freight and labor dollars.
water -based coating. Tbis durable coating NFPA -I3 and NNW-14. All sizes of •Provides stability needed to comply
is paintable. The black coating acts as Dyne Flow/Super Flo are UL Listed, FM
as excellent primer and is resistant t0 Approved and ULC Listed. with standard hanger spacing
(15 R O.C.) per NFPA-
- weathering and U.V. degradation from
outdoor storage: ' • Available in Standard lengths for your
Metallurgical properties provide excellent Dated Approved Listed convenience, or can be ordered in
fabrication characteristics for end prep custom lengths upon approval.
Dysa,Flow /Super Flo is ULNLC Listed
finishes. welding and roll grooving. use with roll grooved, plain -end • Feat cutting sad welding, as well as
There is no spacial prooeas or equipment couplings, and welded joints for wet, dry, easy roll grooving and end preparation.
needed fbr fabrication and installation. presence end
The internal iurtce of all black Allied Approved for roll u grooved, plain -end, and • for quicckk is Featary roll g er shop turcarouoraved tbrm
Tube & Conduit Fire Sprinkler pipe welded joints fbr wet systems. Refer to for q
products up to 43000" in diameter is appropriate documentation for up -to -date • Clean, durable mill coating provides
coated with ow new Antibacterial listing and approval information. Dyne- longer "shelf life" and acts as an
Formula. "ABP". In scientific laboratory Flow/Super Flo is now available "hot- excellent primer for oust= paint
test, ABS proved to have superior dip" galvanized and has been specifically applications.
resistance to microbial colonization of approved by FM for dry systems uses.
pipe walls, thereby delaying or possibly
preventing the onset of Microbiologically
Influenced corrosion (MIC) when the
First Sprinkler System is first installed
'NCO/ . 16100 S. Lathrop • Harvey, IL 60428 Customer Service:
1 oiled 11350 Noreom Rd. • Philadelphia, PA 19194 (800) 882-5543
TUSE a amour r 2525 N. 27th Ave. • Phoenix, AZ 85009 Fax 708 -339 -1806
S2 -3
. .
• I.
. . . . .
D yna-Flow®
_
..
High Strength Steel Pipe
The original high4trength lightwall sprinkler pipe with hydraulics superior to Schedule -10.
.Dyne -Flow pipe is the "original" high- - Specifications
strength lightwall sprinkler pipe. Dyne. .
MP8 Nomiael I.D. WI, WI. (H20 Filled) Peal wain (21') W11lIN (24') WUUD (25'(
Plow has outstanding hydraulic In; mm In; mm Lbs/R; Kg /m Lbw�Ft; Kg/m Lit Las; Kg Lbe; KO . Lbs; Kg
capabilities and is recognized as the
most popular alternative to Schedule-I 0 1' 1.191 0.530 1.31 91 1,586 1,812 1,888
pipe. Lightweight, easy to out and easy 25 30.3 1.2 1.85 91 719 822 858
to handle for installation Dyna -Flow is a 1W 1.538 1.058 1.87 61 1,358 1,550 1,815
valuable addition to any Bre protection 32 39.0 1.8 2.78 81 618 ' 703 733
system. 1W 1.728 1,887 2.71 81 2,135 2,440 2.542
Superior Hydraulics 40 499 2.5 4.03 ; 61 988 1107 1153
2' 2.203 • 2.104 3.79 • 37 1,834 1,888 1,946
With an inside diameter of up to 11% 50 56.0 3.1 5.84 ' 37 741 847 883 •
larger than Schedule -40 and up to 7% 2'ri' 2,703 2.584 5.10 30 1,615 1,846 1,823
larger than Schedule -10, Dyna -Flaw 65 68.7 3.8 7.59 80 733 • 837 872
pipe hydraulics are exceptional. Larger 3' . 3,314 3,387 . .7.18 ... 19 1,351 1,544 1,808
I.D.s enable Dyna -Flow, and related 80 84.2 5.0 10.69 19 613 . . - 700 729
components, to be down -sized within the 4• 4,310 4.473 10.88 19 . 1,784 2,039 2,124
system, thus increasing the potential for 80 109.5 5.7 18.15 19 809 926 953
job cost savings. For complete Hazen- • .
Williams charts, refer to "Dyna -Flow .
Hydraulic Data Tables."
_ Coatings & Fabrication Specitications & Approvals Additional Benefits
Dyna -Flow products are coated with • Dyna•F1ow /Super Flo pipe i9 rnanufao • Lightweight and easy to install,
an environmentally approved and tured to meet ASTM A•795 Type 3, resulting in more efficient use of your
- specially formulated modified - acrylic or Grade A and is in compliance with freight and labor dollars.
water -based coating. This durable coating NFPA -13 and NFPA -14. All sizes of •provides stability needed to comply
is paintable, The black coating acts as Dyna Flow/Super Plo are UL Listed, FM standard hanger spacing
an excellent primer and is resistant to Approved and ULC Listed.
(15 ft O.C.) per NFPA.
weathering and U.V. degradation from ei L� .Available in Standard lengths for your
outdoor storage. convenience, or can be ordered in
Metallurgical properties provide excellent Listed Approved Listed custom lengths upon approval.
fabrication characteristics for end prep Dyna-Flow/Super Flo is UL/ULC Listed
finishes, welding and roll grooving. fbr use with roll grooved, plain-end
• Fast cutting and welding, as well as
There is no special process or equipment couplings, and welded Joints for wet, dry, easy roll grooving and end preparation.
• needed for fabrication and installation. preaction and deluge systems. It is FM • Available in Factory roll grooved farm
The internal surface of all black Allied Approved for roll grooved, plain -end, and for quicker shop turnaround.
Tube & Conduit Fire Sprinkler pipe welded joints fbr wet systems. Refer to
products up to 4.5000" in diameter is appropriate documentation for up -to -date • Clean, durable mill coating provides
coated with our new Antibacterial listing and approval information. Dyna- longer "shelf life" and acts as an
Formula, "ABF". In scientific laboratory Flow /Super Flo is now available "hot- excellent primer for custom paint
test, ABS proved to have superior dip" galvanized and has been specifically applications.
resistance to microbial colonization of approved by FM for dry systems uses.
. pipe walls, thereby delaying or possibly
preventing the onset of Microbiologically
Influenced corrosion (MIC) when the
First Sprinkler System is Brat installed.
1 6100 S. Lathrop • Harvey, IL 60426 Customer Service: (800) 882 - 5543
�+ allied L'Q /flo wCcmVO/ 11350 S. Lathrop
Rd. • Philadelphia, 6 19154
TUBE 8 coNDUIT 2525 N. 27th Ave. • Phoenix. AZ 85009 Fox 708 -339 -1806
32 -
7,7 lr,P'rw 1810cl 32II3 3IJIDtld 1-1tiTt7 :9 E002'S 'd3S
vfht.. _
1 .. __1. 1 e ir e_. ) . 1 , 'I' TrA - kV , . , 1.0 .
'UN IT!' ' If 1 :L - 1 -..--. 'V' -='...
a
• Fittings and Flange Ir
12600 CARDINAL MEADOW
SUGAR LAND, TX 77498
Toll: 888.999.3588
• Fax: 281.275.3995
SPECIFICATIONS =_ _. - -- - -.
CAST IRON THREADED FITTINGS
ALL CAST IRONS MANUFACTURED FOR AND BY F M
UNIQUE FITTINGS & FLANGES® CONFORM TO, COMPLY WITH, AND ARE
MANUFACTURED TO THE FOLLOWING STANDARDS: APPROVED
ASTM Al26- Class B Standard Spec for Cupola Cast Iron { > <,.
ANSI B 16.4- Cast Iron Threaded Fittings Classes 125 t .
ANSI /ASME B1.20.1- Pipe Threads, General Purpose (inch) NPT I;, Y ' US
D C.I. THREADED FITTINGS ARE UL. CUL LISTED AND FACTORY MUTUAL APPROVED FOR 300 PSI SERVCE. GRAY IRON
PER ASTM 126 CLASS B. DIMENSIONS CONFORM TO ANSI B 16.4 CLASS 125 EXCEPT PLUGS CONFORM TO ASME
B 16.14. THREADS ARE NPT PER ANSUASME 81.20.1.
I'
. ,, i . . : ::-,' !' k.„
....h
...._ ._...
I
w I
FIELD INFORMATION f`:- : -. '
CONTRACTOR
JOB
LOCATION
• ,�. i -
s :g1
Fining 2nd F fang s it
TOLL FREE: 188 B. 999. 3588 ,
UNIQUEFITTINGSANDFLANGES.COM
•
t qco & Building
Products CENTRAL
•
Customer Service/Sales:
• Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Tel: (215) 362 0700 / (800) 523-651 2
www.tyco - fire.com Fax: (215) 362 -5385
Grinnell Grooved Fire Protection Products
Grooved Fittings
General Material: Limited
Cast: Figures: 201, 210, 219, 250, 260, 501, 510,
Description 519, 510DE, 501S, 510S and 519S - Warranty
See Fire Protection Ductile iron conforming to ASTM A -536, Products manufactured by Tyco Fire Products are
VdS Submittal Sheet for Grade 65 -45 -12 warranted solely to the original Buyer for ten (10) •
Pressure Rating and Fabricated Steel: Figures 391, 392, 393, 312, years against defects in material and workmanship
61,0 ,}'� Lis n f ormation' l
Information 313, 321, 327, 341 and 350 - Carbon Steel,
(Sizes 1'/,° - 6° are Schedule 40); when paid for and p ro p eri y mstalledand maintained
(1�f� 1��
® (Sizes 8" - 12" Schedule chedule 30), under normal use and service. This warranty will
conforming to are Sc A 53 Grade B expire ten (10) years from date of shipment by Tyco
Fire Products. No warranty is given for products or
The grooved fittings provide an economical Protective Coatings: components manufactured by companies not
and efficient method of changing direction, • Non-lead orange paint affiliated by ownership with Tyco Pre Products orfor
adding an outlet, reducing, or capping • Fire brigade red (optional) non -lead paint products and components which have been subject
grooved piping systems. Grooved fittings • Hot dipped galvanized conforming to ASTM tomisuse, improperinstallation ,corrosion,orwhich
are available in durable ductile iron or A -153 have not been installed, maintained, modified or
fabricated steel as indicated. repaired in accordance with applicable Standards of
Note: Figure 510S and 519S fittings are Ordering the National Fire Protection Association (NFPA),
special short radius fittings with smaller of anyotherAuthoritiesHaving
center to end dimensions than standard P rocedure Jurisdiction. Materials found by Tyco Fire Products
grooved fittings. Depending on the size and When placing an order, indicate the full product to be defective shall be either repaired orreplaced,at
coupling used, there may be interferences at name. Please specify the quantity, figure number, Tyco Fire Products' sole option. Tyco Fire Products
the bolt pads that require repositioning of the � wall thickness, and size. neither assumes, nor authorizes any person to
coupling orientation. The use of flange Grinnell Grooved Piping Products, valves, assume forit, anyotherobligationin connection with
adapters is not recommended with Figures accessories and other products are available the sale of products or parts of products. Tyco Fire
.510S and 519S fittings. Contact Tyco Fire throughout the U.S., Canada, and internationally, • Productsshallnotberesponsibleforsprinklersystem
Products for details: through a network of distribution centers. You designerrorsorinaccurateorincompleteinformation
WARNING may write directly or call 215 - 362 -0700 for the supplied by Buyer or Buyer's representatives.
The Fittings described herein must be installed distributor nearest you. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE
and maintained in compliance with this document, LIABLE, IN CONTRACT; TORT, STRICT LIABILITY
as well as with the applicable standards of the Care and OR UNDER ANY OTHER LEGAL THEORY, FOR
National Fire Protection Association, in addition Maintenance INCIDENTAL, INDIRECT, SPECIAL OR
to the standards of any other authorities having CONSEQUENTIAL DAMAO ES, INCLUDING BUT NOT
jurisdiction. Failure to do so may impair the The owner is responsible for the inspection, LIMITED TO LABOR CHARGES, REGARDLESS OF
performance of this device. testing, and maintenance of their fire protection WHETHERTYCOFIREPRODUCTSWASINFORMED
The owner is responsible for maintaining their system and devices in accordance with the ABOUT THE POSSIBILITY OF SUCH DAMAGES,
fire protection system and devices in proper applicable standards of the National Fire Protection AND IN NO EVENT SHALL TYCO FIRE PRODUCTS'
operating condition. The installing contractor or Association (e.g., NFPA 25), in addition to the LIABILITY EXCEED AN AMOUNT EQUAL TO THE
sprinklermanufacturershou ldbecontacted with standards of any authority having jurisdiction. SALES PRICE.
any questions. The installing contractor or product manufacturer THE FOREGOING WARRANTY IS MADE IN LIEU OF
should be contacted relative to any questions. ANY AND ALL OTHER WARRANI/ES EXPRESS OR
Technical Any impairment must be immediately corrected. IMPLIED. INCLUDING WARRANTIES OF
It is recommended that automatic sprinkler MERCHANTABILITY AND FITNESS FOR A
Data systems be inspected, tested, and maintained by PARTICULAR PURPOSE,
Approvals: a qualified Inspection Service.
UL, FM, ULC, VdS, and LPCB;
Note: See Fire Protection Submittal Sheet for
exact Listing / Approval information.
Page 1 of 6 September 2004 TFP1810
•
, Page 2 of 6 TFP1810 •
Figures 201, 210, 219, and 260
c to \ Figure 201 Figure 210 Figure 219 Figure 260$
45° Elbow 90° Elbow Tee End Cap
Nominal C to E Appx. Wt. C to E Appx. Wt. C to E Appx. Wt. E to E Appx. Wt.
• . \ -
Size
Inches Lbs. Inches Lbs. Inches Lbs. Inches Lbs.
C to E c to E . mm Kg. mm Kg. mm Kg. mm Kg.
1.75 0.9 2.75 1.0 2.75 1.4 0.88 0.4
L ......... a 1,1.„
• 44.5 0.4 69.9 0.5 69.9 0.6 22.4 0.2
- C to E 1.75 1.1 2.75 1.2 2.75 1.8 0.88 0.6
Figure 201 1' /2° 44.5 0.5 69.9 0.5 69.9 0.8 22.4 0.3
Figure 210 2.00 1.8 3.25 2.0 3.25 2.7 0.88 0.9
2"
50.8 0.8 82.6 0.9 82.6 1.2 22.4 0.4
2' /z° 2.25 2.2 3.75 3.0 3.75 5.8 0.88 0.9
!-- 1 --+ EtoE - 1 r - 57.2 1.0 95.3 1.4 95.3 2.6 22.4 0.4
' 2.25 2.2 3.75 3.0 3.75 5.8 0.94 1.1
I I r 76.1 mm 57.2 1.0 95.3 1.4 95.3 2.6 23.9 0.5 •
•
• • • [ 2.50 3.5 • 4.25 4.5 4.25 • 7.0 0.88 1.1
e L 3 63.5 1.6 108.0 2.0 108.0 3.2 22.4 0.5
' c to E 108.0mm 2.88
3.0 2.5 120.7 3.9 120.7 1 5.2
tsem. - I Figure 260 3.00 5.2 5.00 8.5 5.00 11.8 1.00 2.6
4° 76.2 2.4 127.0 3.9 127.0 5.4 25.4 1.2
Figure 219 133.0mm 3.25 7.7 5.25 11.3 5.25 . 10.6
82.6 3.5 133.4 5.1 - 133.4 - 4.8
139.7mm 3.25 7.7 5.50 11.3 5.50 15.3 0.92 4.7
• 82.6 3.5 139.7 5.1 139.7 ' 6.9 23.4 2.1
3.25 8.5 5.50 • 13.5. 5.50 .17.0 1.00 5.0
Friction Resistance'
5° . 82.6 3.9 . 139.7 6.1 . '139.7 7.7 25.4 2.3
(Expressed as Equivalent Straight Pipe) 3.50 12.0 6.00 14.6 6.00 13.9
. Elbow Tee . 159.Omm 88 9 5.4 152.4 6.6 • • 152.4 6.3 "
Size 90° 45° Branch Run 165.1 mm 3.50 . 12.0 6.50 18.5 6.50 26.0 1.00 7.5 •
Inches Feet Feet Feet Feet • 88.9 5.4 165.1 8.4 165.1 11.8 25.4 3.4
mm Meters Meters Meters Meters 3.50 12.0 6.50 '18.5 • 6.50 26.0 1.00 7.5 •
11/4 1.9 1.0 4.8 1.9 6° 88.9 5.4. 165.1 8.4 165.1 11.8 25.4 3.4
42.4 0.6 0.3 1.5 0.6 4.25 23.0 7.75 36.5 7.75 45.0 -
• 11/2 2.3 1.2 5.8 • 2.3 216.3mm 108.0 10.4 196.9 16.6 196.9 20.4
48.3 0.7 0.4 1.8 0.7 4.25 23.0 7.75 36.5 7.75 45.0 1.19 12.8
2 3.2 1.6 8.0 3.2 e° 108.0 10.4 196.9 16.6 196.9 20.4 30.2 5.8
60.3 1.0 0.5 2.5 1.0 4.75 31.0 9.00 60.0 .9.00 72.1 1.25 20.0
21/2 3.9 2.0 9.8 3.9 10 120.7 14.1 228.6 27.2 228.6 32.7 31.8 9.1
73.0 1.2 0.6 3.0 1.2 12„ 5.25 40.0 10.00 67.0 10.00 92.5 1.25 36.0
76.1 mm 4.1 2.1 10.3 4.1 133.4 18.1 254.0 30.4 254.0 42.0 31.8 16.3
1.2 0.6 3.1 1.2
• 3 4.9 2.4 - 12.2 4.9 , t - Available with tapped plugs, contact Tyco Fire 8 Building Products.' • '
• 88.9 1.5 0.7 • 3.7 . 1.5 •
108.Omm 6:5 3.3 • 16.3• 6.5.
2.0 1.0 5.0 2.0 ..
4 6.5 3.3 16.3 6.5
•
114.3 . 2.0 • 1.0 5.0 2.0 .
133.Omm 8.0 4.0 20.0 8.0
2.4 1.2 6.1 2.4
139.7mm 8.0 4.1 20.0 8.0
2.4 1.3 6.1 2.4
5 8.2 4.1 20.5 8.2
141.3 2.5 1.3 6.3 2.5
159.Omm 9.5 4.8 23.8 9.5
2.9 1.4 7.2 2.9
165.1 mm 9.5 4.8 23.8 9.5
2.9 1.4 7.2 2.9
6 9.9 5.0 24.8 9.9
168.3 3.0 1.5 7.6 3.0
216.3mm 13.1 6.6 32.8 13.1
4.0 2.0 10.0 4.0
8 13.1 6.6 32.8 13.1
219.1 4.0 2.0 10.0 4.0
10 16.5 8.3 41.3 16.5
273.0 5.0 2.5 12.6 5.0
12 19.9 9.9 49.7 19.9
323.4 6.1 3.0 15.1 6.1
For reducing tees and branches, use the value that is corrosponding
to the branch size. Example: for 8' x 8' x 2^ tee, the branch
value 2' is 8.0 feet.
• Friction resistance for all elbows and tees except Figures 5105
and 519S.
. Page 3 of 6 • TFP1810
Figures - 501, 510 519 and 510DE
•
c to ` t- ---C toE -1 F AI
�.. I ._...._.1._._._._ lit t
I t
CtoE CtoE i C I oE
L �j CtoE li
i- CtoE o� A- « - -CtoE
Figure 501 Figure 510 Figure 519 Figure 510DE
Figure 501 Figure 510 Figure 519 Figure 510DE
45° Elbow 90° Elbow Tee • 90° Drain Elbow
Nominal C to E Appx. Wt. C to E Appx. Wt. C to E Appx. Wt. C to E A B Appx. Wt.
Size Inches Lbs. Inches Lbs. Inches Lbs. Inches Inches Inches Lbs.
mm Kg. dim Kg. mm Kg. mm mm mm Kg.
1 /a" 1.75 0.9 2.75 1.0 2.75 1.4
44.5 0.4 69.9 0.5 69.9 0.6
1' /z" 1.75 1.1 2.75 1.2 2.75 1.8
44.5 0.5 69.9 0.5 69.9 0.8
2 „ 2.00 1.8. 3.25 2.0 3.25 . 2.7
50.8 0.8 82.6 0.9 82.6 1.2
2' /z" 2.25 2.2 3.75 3.0 3.75 5.8 3.75 2.00 2.75 2.7
57.2 1.0 , 95.3 1.4 95.3 2.6 . 95.3 • . 50.8 69.9 1.2
• 2.50 3.5 4.25 4.5 4.25 • 7.0 4.25 2.34 2.75 3.7
3 „
63.5 . 1.6 108.0 2.0 108.0 3.2 .108.0 59.4 69.9 1.7
4" 3.00 5.2 5.00 - 8.5 5.00 11.8 5.00 2.85 2.75 7.0
76.2 2.4 127.0 3.9 127.0. 5.4 127.0 72.4 69.9 3.2
5 „ 3.25 8.5 5.50 • 13.5 5.50. .17.0 5.50 3.38 2.75 13.0
82.6 • - 3.9 139.7 6.1 139.7 7.7 . 139.7 85.9 69.9 5.9 .
6 „ • 3.50 12.0 6.50 18.5 6.50 26.0 6.50 3.92 2.75 13.4
88.9 5.4 165.1 8.4 ' . 165.1 11.8 ' 165.1 99.6 69.9 6.1
8" 4.25 23.0 7.75 36.5 • 7.75 45.0 7.75 4.95 2.75 26.3
108.0 10.4 196.9 16.6 196.9 20.4 196:9 125.7 69.9 11.9 •
Figures 50IS, 510S and 519S
cto : •-CtoE_ 1
t
Ct _� CtoE
L L � E I1 CtoE
.12... - . { - - 1_
Figure 501S Figure 510S° Figure 519S° ,
Figure 501S Figure 510S Figure 519S
•
Friction Resistance 501S, 510S & 519S 45° Elbow 90 Elbow Tee
(Expressed as Equivalent Straight Pipe) Nominal C to E Appx Wt. C to E Appx. Wt. C to E Appx. Wt.
Elbow Tee Size Inches Lbs. Inches Lbs. Inches Lbs.
Size 90° 45° Branch Run mm Kg. mm Kg. mm Kg.
Inches Feet Feet Feet Feet 2° 2.00 1.8 2.75 1.5 2.75 2.1
mm Meters Meters Meters Meters 50.8 0.8 69.9 0.7 69.9 1.0
2 3.2 1.6 8.0 3.2 2, /2" 2.25 2.2 3.00 2.2 3.00 3.0
60.3 1.0 0.5 2.5 1.0 57.2, 1.0 76.2 1.0 76.2 1.4
2' /z 3.9 2.0 9.8 3.9 76 lmm 2.25 2.2 3.00 2.3 3.00 3.1
73.0 1.2 0.6 3.0 1.2 57.2 1.0 76.2 1.0 76.2 1.4
4.1 2.1 10.3 4.1 3 „ 2.50 3.5 3.38 3.0 3.38 4.1
76.1 mm 1.2 0.6 3.1 1.2 63.5 1.6 85.9 1.3 85.9 1.9
3 4.9 2.4 12.2 4.9 4" 3.00 5.2 4.00 5.6 4.00 7.7
88.9 1.5 0.7 3.7 1.5 76.2 2.4 101.6 2.6 101.6 3.5
4 6.5 3.3 16.3 6.5 139.7mm 3.25 7.7 4.88 8.6 4.88 12.0
114.3 2.0 1.0 5.0 2.0 82.6 3.5 124.0 3.9 124.0 5.4
8.0 4.1 20.0 8.0 5" 3.25 8.5 4.88 8.8 4.88 12.0
139.7mm 2.4 1.3 6.1 2.4 82.6 3.9 124.0 3.9 124.0 5.4
5 8.2 4.1 20.5 8.2 165.1 mm 3.50 12.0 5.50 11.00 5.50 15.0
141.3 2.5 1.3 6.3 2.5 88.9 5.4 139.7 5.0 139.7 6.8
9.5 4.8 23.8 9.5 6" 3.50 12.0 5.50 11.2 5.50 15.2
165.1. 2.9 1.4 7.2 2.9 88.9 5.4 139.7 5.1 139.7 6.9
6 9.9 5.0 24.8 9.9 8" 4.25 23.0 6.88 23.4 6.88 31.2
168.3 3.0 1.5 7.6 3.0 108.0 10.4 174.8 10.6 174.8 14.2
8 13.1 6.6 32.8 13.1 ' Note: Figure 510S and 519S fittings are special shoA rediuslittings with smaller center to end dimensions
than standard grooved fillings. Depending on the size and coupling used, there may he Interferences
219.1 4.0 2.0 10.0 4.0
al the boll pads which requires repositioning Mlle coupling orientation. The use o111ange adapters Is
not recommended with Figures 5105 and 519S fittings. Contact Tyco Fire Products for details.
.
•
Page 4 of 6 . . . TFP1810
Figures 250 and 350
.Figures 250 and 350 Concentric Reducer - Groove x Groove
Nominal E to E • Appx. Wt. Nominal E to E Appx. Wt. Nominal E to E Appx. Wt.
_E to E Size Inches Lbs. Size Inches Lbs. Size Inches Lbs.
I Inche mm Kg Inches mm Kg. Inches • mm Kg.
I 2.50 1 3.50 4.2 4.00 5.8
•2x /. 63.5 0 .5 •139.7mmx3 88.9
1.9 •6x5 101.6 2.6
2.50 1.3 3.50 4.4 5.00 12.2
• /z 63.5 0.6 •139.7mm%4 88.9 2.0 8 x 2 127.0 5.5
2
Figure 250 '2 /z % 2 2 .5 0 1.2 5 1 /z 3.50 4.6 /z 5.00 12.1
• 63.5 % 0.5 88.9. 2.1 8 % ' 127.0 5.5
Cast 2.50 1.5 3.50 4.6 5.00 12.0
•76.1mmx1' /z 63.5 0.7 5x2 88.9 2.1 8x 127.0 5.5
2.50 1.6 3.50 4.5 5.00 11.9
• 1--E to E-•{ '76.1mm is 2 63.5 0.8 5 x 2'/ 88.9 2.0 8 x 4 127.0 5.4
II 3 x 1' /< 2.50 1.3 5 X 3 3.50 4.4 8 % 5 5.00 11.3
-_
63.5 0.6 88.9 2.0 127.0 5.1
- ---- - - 3x1 /z • 2.50 • 1.3 . •54 3.50 4.5 86 5.00 10.8
�_ 63.5 0.6 x 88.9 2.0 x
127.0 4.9
•3X2 2.50 1.3 •165.1mmX3 4 .00 5.5. 10X4 6.00 21.9
Figure 350 63.5 0.6 101.6 2.5 152.4 10.0
Fabricated , - 3.00 1.5 •16 mm x 4 4.00 6.0 1 0 x 5 6.00 21.6
Sizes 3" to 6" 76.2 0.7 101.6 . 2.7 152.4 9.8
•3 X 76..1... 3.00 2.0 • • 4.00 5.6 • 10 6 6.00' 21.1
. 76.2 . 0.9 t . 101.6 2:5 x 152.4 9.6
I---E to E - { 3.00 . ' 2.2 4.00 •. 6.0 . 6.00 19.5
4X1 /4. 76.2' 1.0 •6 101 2:7 10x8 152.4 8.9 •
I 3.00 2.3 4.00 6.0 7.00 28.0
- 11 3.00 4 x 1 Yz 76.2 1.0, 6 x 2' /z 101.6 2.7 12 x 4 1778 12.
•4x2 3.00 • 2.3 •6x76.1mm 4.00 6.0 12 7.00 30.0
76.2 1.0 . 101.6 2.7 177.8 13.6
Figure 350
3.00 2.3 4.00 . 6.0 7.00 28.0
• Fabricated . • •4 x 21/2 76.2 1.0 . . 6 x 3 101.6 2.7 12 x 8 - 177.8 12.7
Sizes 8" to 12" 3.00 3.2 4.00 5.9 7.00 33.0
•4'x76.1mm 76.2 1.5 •6 101.6 2.7 12 x 10 177.8 _ 15.0
4 x 3 3.00 2.6 •6 X 139.7mm 4.00 6.3
76.2 1.2 101.6 2.9 .
•
Note: Sizes marked with on asterisk (•) are only available In Figure 250 Cast.
Sizes without an asterisk are only available in Figure 350 Fabricated. .
•
ADA CAP®
Patented
Pipe Nominal_ Dimensions
Size Outlet O Takeout Center to EDnd Net
Inches
NPT* Inches Inches Inches Inches Lbs.
D Inches mm mm mm mm Kg.
, 1.25 1.75 1.89 0.77
31.8 44.5 48.0 0.3
1'/z 3 1 .900 1.25 " 1.75 1.89 0.77
T r I c 48.3 31.8 44.5 48.0 0.3
I B
1 1.37 2.00 2.02 0.88
34.8 50.8 51.3 0.4
A - /Z 1.25 1.75 • 1.89 0.92
31.8 44.5 48.0 0.4
L 2 3/ � 2 1.25 1.75 1.89 0.92
60.3 31.8 44.5 48.0 0.4
• 1 1.37 2.00 2.02 1.06
34.8 50.8 51.3 0.5
, 1.47 1.97 1.89 1.28
37.3 50.0 48.0 0.6
2' /z 3/a 2.875 1.47 1.97 1.89 1.28
73.0 37.3 50.0 48.0 0.6
• 1 1.37 2.00 2.02 1.50
• 34.8 50.8 _ 51.3 0.7
• ISO -7 threaded outlets are available upon requesL '
•
Page 5 of 6 - TFP1810
• Figures 391, 392, 393, 312 and 313
1r-- E to E Figures 391, Figure 312 Figure 313
-- - - - 392 and 393 22+/2° Elbow 11'/4° Elbow
Adapter Nipples -
*. Figure E to E Appx. Wt. C to E Appx. Wt. C to E Appx. Wt.
Nominal Inches Lbs. Inches Lbs. Inches Lbs.
Size mm Kg. mm Kg. mm Kg.
• 4.00 0.8 1.75 0.4 1.38 0.4
Ir to E 1'h 101.6 0.4 44.5 0.2 35.1 0.2
1' /z° 4.00 0.9 1.75 0.5 1.38 0.5
Figure 101.6 0.4 44.5 0.2 35.1 0.2
2 „ 4.00 1.2 1.88 0.6 1.38 0.6
101.6 0.5 47.8 0.3 35.1 0.3
4.00 1.9 2.00 0.7 1.50 1.1
E to E --el - ^ " - . 21/2° 101.6 0.9 50.8 0.3 38.1 0.5
3 „ 4.00 2.5 2.25 1.4 1.50 1.2
• 101.6 1.1 . 57.2 0.6 38.1 0.5
H . Figure 6.00 5.5 2.63 . 2.4 1.75 2.2
393 4° 152.4 2.5 66.8 1.1 44.5 1.0
•
5 „ 6.00 7.4 ' 2.88 4.1 2.00 3.3
152.4 3.4 73.2 1.9 50.8 1.5
C to E 6" 6.00 9.5, 3.13' 5.6 2.00 4.6
152.4 4.3 79.5 2.5 50.8 2.1
Figure • ` 6.00 - 14.2 3.88. 11.1 2.00 8.7
312 8 152.4 6.4 98.6 5.0 50.8 3.9
Ct o E lla 8.00 27.0 4.38 • 14.0 2.13 9.1
� . 10° • 203.2 12.2 11.3' 6.4 54.1 4.1
C to E 12 „ 8.00 " 33.0 4.88 22.0 2.25 16.7
Figure 203.2 15.0 124.0 10.0 57.2 7.6
C to E 313
•
•
Figures 327 and 341 •
C to E Figure 341
Figure 327 150 lbs. •
Cross Flange Adapter
Nominal C to E Appx: Wt. E to E Appx. Wt.
- Size . nches • Lbs.. Inches Lbs..
• mm kg. mm kg.
•
• - .•... - - - -- : - f 1' /4" 2.75 2.0. • 4.00 2.8
69.6 • 0.9 101.6 1.3 .
CtoE 1 , /2 ° 2.75 . .2.2 4.00 3.2
69.9 2.0 101.6 1.5
2 � 3.25 2.7 4.0 5.2
Figure 327 82.6 1.2 101.6 2.4
2' /z„ 3.75 5.0 4.00 8.0
95.3 2.3 101.6 3.6
3 , 4.25 7.1 4.00 10.2
108.0 3.2 101.6 4:6
j. .j: 4° 5.00 11.9 6.00 17.2
127.0 5.4 152.4 7.8
Ijl • I j l l 5 , 5.50 17.1 6.00 21.4
EtoE 139.7 7.8 152.4 9.7
6.50 27.5 6.00 26.0
t t t I 6" 165.1 12.5 152.4 11.8
j l 8 , 7.75 47.0 6.00 38.4
Figure 341 196.9 21.3 152.4 17.4
10° 9.00 68.0 8.00 65.0
•
• 228.6 30.8 203.2 29.5
12° 10.00 107.0 8.00 91.0
254.0 48.5 • 203.2 41.3
•
Page 6 of 6 . TFP1810
•
Fi ' 321
• _ 1.._c t o E--- -1 Figure 321 Reducing Tee .
i - Nominal C to E Appx. Wt. Nominal C to E Appx. Wt.
_ Size Inches Lbs. Size Inches Lbs.
Inches' - mm Kg' • - - lnches mm Kg.
j 11/2x11/2x 1'/ 3.25 2.0 6 x.6 x 4 6.50 26.6
•
CtoE 82.6 0.9 165.1 12.1
• 3.25 2.7 6.50 27.0
( j I 2x2x1h 82.6 1.2 6x6x5 165.1 12.2
Figure 321 2'hx2'hx1'4 8x8x2
• 3.75 4.2 7.75 36.2
95.3 1.9 196.9 16.4
2' x2' x1' 3.75 4.2 8x 8x3 7.75 • 36.5
95.3 1.9 196.9 16.6
2' x21/2 x2 3.75 4.3 8x8x4 7.75 36.6
95.3 2.0 196.9 16.6
3x 3x 1'h 4.25 5.3 8x 8x5 7.75 36.8
108.0 2.4 196.9 16.7
3x3x2 4.25 .5.5 8x8x6 • 7.75 37.0
• 108.0 2.5 196.9 16.8
3x3x2' /. 4.25 5.8 .10x10x2 9.00 57.1
• 108.0 2.6 228.6 25.9
4x4x •1'/. 5.00 . . 9.8 10x 10x3 9.00 57.4
• 127.0 4.4. 228.6 26.0 - . 4x4xiv 5.00 •9.9 10x10x4 9.00 57.6
127.0 .4.5. 228.6 26.1
4'x422 5.00 ' 10.1 • 10x10x5 9.00 . 57.8
127.0 ' 4.6 .• • 228.6 26.2
- 4x4x2'h 5.00 . 10.3 10x10x 9.00 58.0
127.0 , 4.7. - '•.228.6. 26.3
• 4 x4x3 5.00 •• 10.5 10x10x8 9.00 58.4
127.0• 4.8 228.6 26.5
5x5x2 5.50 14.5 12x 12x3 10.00 80.2
139.7 6.6 • - • 254.0 36.4
5x5x21/2 5.50 14.8 12x12x4 10.00 80.5
139.7 6.7 254.0 36.5
5x5x3 5.50 15.2 12x12x5 10.00 80.7
139.7 6.9. 254.0 36.6
5x5x4 5.50 15.8 .12x12x6 10.00 80.9
139.7 7.2 254.0 36.7
' 6x6x2 6.50 26.5 12x12x8. 10.00 91.4 '
• 165.1 11.9 254. 41.5
' 6x6x2' /z 6.50 26.5 12x12x10 10.00 91.8
165.1 • 12.0 254.0 41.6
6x6x3 6.50 26.5 '
165.1 12.0
•
•
General Notes: It is the Designer's responsibility to select products suitable for the intended service and to ensure
• that pressure ratings and performance data is not exceeded. Always read and understand the installation instructions 900 r •
(I1-1- 1000). Never remove any piping component or correct or modify any piping deficiencies without first ill
depressurizing and draining the system. Material and gasket selection should be verified to be compatible for the
specific application. Certified Company
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19946 Printed U.S.A.
TOLCO
INCORPORATED
46 CORONA, CA • (714) 737.5599 (
FIG. 68
• WIDE THROAT TOP BEAM "C" CLAMP WITH LOCKNUT
. Size Range - 3/8 thru 7/8 inch rod.
Function - For attachment to structural shapes
requiring wider throat especially under roof with
-_..
bar joist construction. This clamp may be used in
the set screw down position only
Approvals - Conforms to Manufacturers Stand-
ardization Society SP -69, type 19.
Finish - Plain and Electro- Galvanized.
Order By - Figure number, rod size, and finish. ----`
Note - Do not overtighten set screw.
FIG. 69
BEAM CLAMP RETAINING STRAP
Size Range - 3/8 thru 7/8 inch rod by 4 thru 14 !
inch length.
Material - Carbon Steel
Function - To offer more secure fastening of beam
clamp to beam when danger of movement might be
expected.
Approvals - Underwriters' Laboratories listed
when used with Tolco U.L. Listed Fig. 65 and 66
Universal Beam Clamp.
Finish - Mil. Galvanized and Stainless Steel.
Order By - Figure number, type, length "A ", and
rod size being used with beam clamp.
Note - Minimum return on Strap: 1 ". A
ROD H STOCK
TYPE
SIZE
7/ SI SIZE A FINISH
1 3/16 16gax1 t Mil. Galv.
1/2. 9/16 16gax1 t M il. Galv.
2 5/8 11/16 14gax1 -1/4 t Mil. Galv.
3/ 13/16 14gax1 -1/4
3 3/8 7/8 specify 12gax1 1/4 t Mil. Galv.
•
.. k2r0) , ..
, .
. . .
: To LcO
INCORPORATED
•
ADJUSTABLE RING HANGER FIG.2
Size Range: 1/2" thru 6"
Approvals: Underwriters' Laboratories listed and Factory Mutual approved.
Conforms to Federal Specification WW -H -171 E (Type 10) and Manufac-
`. turers Standardization Society SP -69 (Type 10).
0 T E Service Application: For general piping 9 p p g purposes. Knurled swivel nut design
l permits hanger adjustment after installation. Spring tension on swivel nut
B holds it securely in hanger before installation. Swivel nut easily removed.
Special Note: Also available to accomodate the new rod schedule per the
National Fire Protection Association Pamphlet 13, 1973. i.e., 1/2" - 4"
A
Ikillk% ... 3/8" rod; 5 ", 6" and 8" ... 1/2" rod. Specify Fig. 2 NFPA and pipe
size.
Ordering: Specify pipe size and figure number.
PIPE ROD HOLE A B • MATERIAL MAX. I
SIZE SIZE SIZE C D •
E SIZE LOAD
FIG. 2 1/2 3/8 35/64 3.1/4 2 -7/8 , 2 15/16 1 -1/2 1 x 16ga 400
ADJUSTABLE RING HANGER 3/4 3/8 35/64 3 2-1/2 1-5/8 15/16 1.1/8 1 x 16ga 400
1 3/8 35/64 3 -1/4 2.5/8 1.7/8 15/16 1-1/4 1 x 16 ga 400
Carbon Steel - Plated or Galvanized 1.1/4 • 3/8 35/64 3-1/2 2-11/16 . 1.13/16 15/16 1 1 x 16 ga 400
1 -1/2 3/8 35/64 3-7/8 • 2-7/8 2 15/16 - 1 1 x 16 ga 400
2 3/8 35/64 4-1/2 3 -5/16 2-3/8 15/16 1-3/16 1 x 169a 400
2 1/2• 43/64 5.3/8 3-7/8 2 -13/16 1 1-5/16 1-3/16 x 14 ga 600
3. 1/2• 43/64 • 6 4-1/4 3.1/4. 1 1 -1/2 1.3/16 x 14 ga 600
3 -1/2 1/2• 43/64 7 5 4 1 2 1 -3/16 x 14 ga 600
4 5/8• 51/64 7-1/4 5 4-1/4 1-1/8 1-3/4 1.174 x 14 ga 1000
5 5/8•• 51/64 9 6-1/4 5-3/8 1-1/8 2-1/4 1 -1/4 x 12 ga 1250
6 3/4•• 63/64 9 -7 /B 6.5/8 5 1 -1/4 2-1/8 1-5/8 x 12 ga 1250 _
• 3/8" not it used when 1973 NFPA rod sizing Is requested.
•• 1/2" nut is used when 1973 NFPA rod sizing Is requested.
•
. PIPE FIG. FIG.2 FIG.2
.
SIZE WON NFPA
•
1/2 17 14 17
+, 3/4 17 14 17
1 18 16 18
• 1.1/4 19 17 19
WEIGHTS ON RING HANGERS 1 -1 /z 21 1e 21
2 23 20 23
_ NET PER HUNDRED 2-1/2 • 41 37 40
D 3 • 45 40 43
3.1/2 52 48 50
4 . 59 53 56
5 97 91 95
B C 6 ' 139 130 134
A RING HANGER LESS NUT FIG. 2 WON
,...
Made the same as Fig. 2 except without swivel nut. Generally hung using nuts
Q and washers, or spring type tension nuts. Conforms to Federal Spc- ification
WW -H -171 E (Type 7) and Manufacturers Standardization Society SP -69
(Type 7), 3/4" - 6 ". •
PIPE HOLE MATERIAL
FIG. 2 WON SIZE SIZE A B C D E
SIZE
RING HANGER LESS NUT 1/2 35/64 3-1/4 2 -7/8 2 15/16 1-1/2 1 x 16ga
3/4 35/64 3 2-1/2 1 -5/8 15/16 1.1/8 1 x 16 ga
Carbon Steel - Plated or Galvanized 1 35/64 3-1/4 2 -5 /8 1-7/8 15/16 1-1/4 1 x 16 ga
1 -1/4 35/64 3-1/2 2-11/16 1-13/16 15/16 1 • 1 x 16 ga
1-1/2 35/64 3-7/8 2-7/8 2 15/16 1 1 x 16 ga
2 35/64 4.1/2 3 -5/16 2 -3/8 15/16 1-3/16 1 x 16 ga
• 2 -1/2 43/64 5-3/8 3 -7/8 2-13/16 1 1.5/16 1-3/16 x 14 ga
3 43/64 6 4-1/4 3-1/4 1 1-1/2 1.3/16 x 14 ga
3 -1/2 43/64 7 5 4 1 2 1.3/16 x 14 ga
4 51/64 7-1/4 5 4-1/4 1-1/8 1.3/4 1-1/4 x 14 ga •
5 51/64 9 6-1/4 5-3/8 1-1/8 2.1/4 1-1/4 x 12 ga
6 63/64 9-7/8 6 -5/8 5 1-1/4 2-1/8
1-5/8 x 12 ga
TOLCO INCORPORATED / 601 W. LAMBERT ROAD / BREA, CALIFORNIA 92621
6 .. __... _
ti .r.
' 1 - 7 ir �~ �:.J %�i ^' .f4 ;. .i!1� _ -'l lG x - 1'+k '.' -': - _ : i`y :tt �;51'M.'r.;ii•n1 -
` _ lil�r � - - ; 'Iti .T..'�Y .kk .. :.:0.4. 1.:-. G t'r l err' =`.:
.[ .G =^ 4C 3- . . _:.h- 1 �r .+.rlf'al ::i �:: " .h: �`:.: ._.Z .�.j.. -T~T'. ••,._ ,� :.....� . ` _-..v'• 1 _.
' .i • Y_ •' .., ] +�i. \�4 =�=5 "'-• i `'�`y11 Sr•.ia- rv;. '_` f ? r .F`' j: � P
:•,��� * t :G _ �- :F_, ':ti: :,`l�. 4,.tr s =` y...:. e::- :f. s ...:.x 1 '%- `�:
■ . �� � ',F�, F " ti,. i, ��_� : r. _. .' rta' ', . r. s �= • " r:= - ;'
L -- s:�:j_._ s G' � f: r ,-, s A : c'cE : sso z 4 {_
: "ffaA7 . near..c,.x: , tv:�i: :t�'.3Aliti 4..ezw,, ..:._r= ; r__r::i - - ,,%;_ '.`' :-- •'•;:'
[;r. 'r-- TL; :i.r`L "i..- :.1:41?_ _ 2S' w: ='i ._ ::UJ: -._ .,: : ^4.`.'.V1'1:':w.' - ;•r_ ■.:.r1 : :: :•.. .n:. a.ti .
' � ° `. ; ,: ` i :: r - ' is FUNCTION: Desi use in i
:Y �` - _ =�. •.?'was : i ; t ; , :.- : • .:. ..:� - .._.::;:�•; maned for pipe hanger as
„ :- :, - .: ` aE 1; G_. P P assembly.
` ;" MATERIAL:
• ='•':: , F,�UI L Low carbon steel
_ - YnTIIRE7A�l7E�l)���
€ ? ;?- ;�„ _ a =: FIN ISH:
s & ' . . .-.: Plain
t: . _ '.r.:.;.' l J . ..� Vie: _`" ; i'� : . - =:' ;':,�`�
- ' ORDERING: Specify rod size, length (B) and figure number.
Max. Rec.
Rod Load /lbs. Wt. Per
Size Inch /lbs.
B 650 °F • 750 °F
111111
11111 3 /e x B 610 540 .02
1/2 x B 1130 1010 .04
1111111111111111111 5
1111 11 /exB 1810 1610 .07
% x B 2710 2420 .11
'A x B 3770 3360 .14 .
1S, , ! -.4 - `= `fm,.',._.a.: -.1 7. .<jy,1. ^e.,�_ ^::23. �*t-r :tkm, t:_in..•ri21xn. - s_rX '�_.. ..::v,� '
tf, IT `}, . . iF .. : tni. 1-::': , �':. eT�4V '::i.YT-:':'.3�_i:n:C•:.r �.YD_tYJ! %�_.•�- :u�.r:_, L rn.a l
1�' ,.e:.:. +~.... 1, ' ;1tee r; ';
�. �.:;t ,, lr FUNCTION:
-�; , '-a I ; ;_ ,'N , '_ ' Designed for use in pipe hanger asse
) r �' P P assembly.
;t��'��l�r'`ry5� `lY'`�!:�n71'.4 -, �n f ?�� fL:�,�� �i" %] ^.�
��. . �. , �44ii, MATERIAL L: L
^ {;�,- a .r, h ' : F'A'�� RIA
,�;'��; � Ih1Y E;;�T�RE- ,D f�: ;_.; Low carbon steel
?,�{ ;t; 'n ::�1iS•w, - . � i- X�fi��- .�GS�;:`:�;'9r • e ,�� r: •.
.; =:. T AaNG E R: tR: - FINISH:
-:niA ' 7.'-, xi. �..' �.. ... ^t °�.K.ti°..:1_;,�,3Si:;:k+.t �. -t S: r '.
Plain
Fig. 15 RIGHT -HAND THREADS ORDERING: Specify rod size, length (B) and figure number.
Fig. 15L RIGHT - AND LEFT -HAND
:
THREADS
Rods . =Thread• ...Wt,
Le - Load /Ibs.:::: _ Per_ .: \ Size:: - : n - , - :Lengths. ' :Inch %Ibs
C:.- 650 ° .F; -::7 50 ° F -
B \ 1111111111111 3 /exB 2 610 540
.03
1111 1 /2xB 2 1130 1010 .06
C��
3h 5 /ax6 2V2 1810 1610 .09
x 3
1111111111 2420
011111111 2710 .13
' /exB 3 3770 3360 .17
1 x B 4 4960 4420 .22
-.+_. g 1+ - 2' i. w?" .7..➢ 7.. 'rte iw. r,..::
s . r.' , ca..,s.:
;%jir i '� . r�PvS: !:9i.:;c . �t+1:��s' :� � :r '�r:.�
R•:t, , z- r' : s , {Efre �>.= FUNCTION:
, i �• r'<.' applications S r Y om',- Useful s her
1. , . &,_;: �„ FUNC in app on where stud lengths cannot b
� ` os:,,,,,. ' , r • *.r. �.k ; w +_v A.4 " redetermined. be
T,. =2 e11?- tJ:y.{11�`N,,. Ai..+cG. 71 +V :V' i ,-- 1 `/.' •kti .� •
J [" "F ,I .ru ✓e•••h. ,O4 .��'r
,, r:�r • ..
j E s) 1 n4 � %4At � r'1
•FT, i- add ^a
} ��,° � ,,; , �^ , ti , � � , -, � , MATERIAL: Low carbon steel
�st:: •:, ��!'.;: .? o` G' F.- F., 7.' 1`: SE:, �'i' 4V�in :Y:_ ?.�;:.f:. '�yg2i."z.
Fi 20 PLAIN ORDERING: Specify rod size, length and figure rnunber.
g•
Fig. 21 ELECTRO- GALVANIZED Packaging Max. Rec.
Rod . Feet Per Bundle Load /lbs. Wt. Per
Size
l
� 6 ft. 10 ft. 12 ft. • 650 °F 750 °F FOOtlibsr
��11�111 300 500 600 240 210 .12
���,� ` �lll /4 20 30
• �� 061. ,v- ,,.. �� - % -16 150 200 240 610 540 .29
.0,
, . ��� WW v ��0$ il .
N /z ' 13 72 120 144 1130 1010 .54
s`04,
0�;01�1111 % -11 48 80 96 1810 1610 .83 r
` ,;,,�11 .... A -10 30 50 60 2710 2420 1.25
' /a -9 24 40 48 3770 3360 1.65
1 -8 12 20 24 4960 4420 2.25
r.'ld4s:;n_a_LYF: {,, .: Vito- ' csS:l.;a: :' - =1:Y1 ::':F:__ ...f. ., . cv. .
._ -'Ma •:uh'•-_�,.: -,7 7.r ,, E :. ••; ',: .t:: .
12 PHD Manufacturing, Inc.
•
Az g7 f 2F i g §J)
P.O. Box 3365 SOUTH EL MoNTE, CA 91733 626.444.0541 FAx 626.444.3887 www.afcon.org
•
•
001/020
SWAY BRACE MODEL E
Part # 077
O
SIZE - Pipe to be braced: 1" tluu 8" Steel SCH 7 thru 40 IPS.
Pipe used for bracing: 1" and 1 1/4" SCH 40 IPS. •
MATERIAL - Carbon Steel.
FINISH - Plain, Electr•o- Galvanized, H.D.G. and Stainless Steel.
LISTING - UL in US and CANADA.
Only-for use with other AFCON bracing products.
APPROVAL - :OSHPD pending.
• • PATENT - No. 3,570,794
FUNCTION - For bracing pipe against sway and seismic
•
disturbances. The sprinkler pipe_attachinent component of a lateral
sway brace assembly, consisting additionally of AFCON 70 series
attachment end joined with brace pipe sized per N.F.P.A. ,, •
INSTALLATION - Place Model E over pipe to be braced. Insert
((n
brace pipe through MODEL "E" under channel bracket, leaving 1"
minimum extension beyond. Tighten but'•.; hex. nuts until gage •
spring lays flat. Minimum torque c.E.65 iii. -Ib. Install as a lateral
sway brace per N.F.P.A.
FEATURES
* UL Horizontal Load Ratings: 2015# Sch. 10 tluu 40, All Sizes
•
655/I Sch. 7 - 1" tluu 4"
150U/ Sch. 7 - 6"
* Can be used as a 4 -way sway brace.
* Visual inspection, proper installation when gage spring lays flat.
ORDERING - Part #, Pipe size to be braced, Brace pipe size and
• Finish.
•
•
03,02
•
•
g§§E
P.O. Box 3365 SOUTH EL MONTE, CA 91733 626.444.0541 FAX 626.444.3887 www.afcon.org
070
•
ATTACHMENT END THREADED
•
• O
•
•
•
SIZE - 1 tluu 2 inch bracing pipe.
Use in combination with 1 tuu 10 inch AFCON sway braces.
MATERIAL - Carbon Steel.
F INISH - Plain and Elcctro- Galvanized.
LISTING - UL in US and CANADA. V
•
Only for use with other AFCON bracing products. •
e APPROVAL - OSHPD pending.
FUNCTION - For bracing pipe against sway and seismic
disturbances. The building attachment component,
of a sway brace assembly, consisting additionally of AFCOK.001 •
thru 40 series sway brace joined with bracing pipe sized per N.F.P.A.
INSTALLATION - Make -On to brace pipe then secure to the
building structure with appropriate fastener.
FEATURES
* UL Horizontal Load Rating: 2765 #, All Sizes
* Swivel design allows attachment at any angle.
* To be used with threaded pipe.
* May be ordered with larger hole. - Consult Factory.
ORDERING - Part #, pipe size and finish.
02/01
•
•
[Page Too Large for OCR Processing]
[Page Too Large for OCR Processing]
[Page Too Large for OCR Processing]