Correspondence (585) •
City of Tigard, Oregon ° 13125 SW Hall Blvd. e Tigard, OR 97223
August 12, 2008 j`b = ®O
'ry
RE: RACK STORAGE Z::g:A
Building Permit: BUP2008 -00260 Construction Type: 2B
Tenant Name: Winco Occupancy Type: M
Address: 7501 SW Dartmouth Occupant Load: 2269
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2007 edition; and the Oregon Fire Code (OFC) 2007 Edition.
Fire Extinguishers: Provide 2 -A rated fire extinguishers as required per table 906.3 (1)
of OFC the extinguisher shall be located so that no usable space has a distance greater
than 75 feet to the extinguishers. OFC 906.3
Clearance: The clearance between the sprinkler deflector and the top of storage shall
be 18 in. or greater. NFPA 13 8.5.6.1
Loads Posted: The racks shall display in one or more conspicuous locations a
permanent plaque not less than 50 square inches in area, showing the maximum
permissible unit load in clear legible print. OSSC 1603
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp,
shall be maintained on the jobsite. The plans shall be available to the Building Division
inspectors throughout all phases of construction. 106.4.2 OSSC
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectfully,
1
Dan Nelson,
Senior Plans Examiner
(503)718 -2436
dann @tigard -or.gov
Phone: 503.639.4171 • Fax: 503.684.7297 a www.tigard- or.gov • TTY Relay: 503.684.2772