FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Lockwood Engineering LLC 503 - 546 -0628 503 -445 -6388 Fax
FIRESTOP CO. Pa•e 2
General Project Data Report
General Data_
Project Title: FIRESTOP CO.
Designed By: Dee Lockwood Date: June 12, 2008
Code Reference: Approving Agency:
Client Name: Broadway Rose Phone: Project No. 2008 -122
Address: 12850 SW Grant City, State Zip Code: Tigard, OR
Company Name: Representative:
Company Address: City And State:
Phone:
Building Name: Building Owner:
Contact at Building: Phone at Building:
Project Data —
Description Of Hazard: light Sprinkler System Type: WET
Design Area Of Water Application: 2160 ft Maximum Area Per Sprinkler: 180 ft
Default Sprinkler K- Factor: 5.30 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 0.00 gpm Outside Hose Stream Allowance: 100.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm
Sprinkler Specifications
Make: Model:
Size: Temperature Rating: 165 F
i = atS ,
. Source Of Information:
Test Hydrant ID: Date Of Test:
Hydrant Elevation: 0 ft Static Pressure: 107.00 psi
Test Flow Rate: 2434.00 gpm Test Residual Pressure: 95.00 psi
Calculated System Flow Rate: 325.40 gpm Calculated Inflow Residual Pressure: 55.72 psi
Available Inflow Residual Pressure: 106.71 psi
.am : ja mro
Calculation Mode: Demand
HMD Minimum Residual Pressure: 7.00 psi Minimum Desired Flow Density: 0.10 gpm /ft
Number Of Active Nodes: 33
Number Of Active Pipes: 38 Number Of Inactive Pipes: 0
Number Of Active Sprinklers: 12 Number Of Inactive Sprinklers: 0
t
Active Version 200 Pipe Capacity Thursday, June 12, 2008
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
LockwooSTOd P ngi Eneeage ring L LC 503 - 546 -0628 503 - 445 -6388 Fax
FIRE CO P
Fire Sprinkler Input Data
ndelnput Data __ --
S Pressure Node Non - Sprinkler
Node No. Node Description Area Group Elevation Discharge
KFactor (K) Estimate (psi) (feet) (gpm)
1 No Discharge N/A 55.72 0.00 0.00
2 Non - Sprinkler N/A 55.68 0.00 100.00
3 No Discharge N/A 55.45 0.00 0.00
4 No Discharge N/A 50.44 0.00 0.00
5 No Discharge N/A 47.47 1.00 0.00
6 No Discharge N/A 40.00 7.70 0.00
7 No Discharge N/A 28.24 16.30 0.00
8 No Discharge N/A 21.50 20.30 0.00
10 No Discharge N/A 14.24 20.30 0.00
11 No Discharge N/A 14.46 20.30 0.00
12 No Discharge N/A 14.86 20.30 0.00
13 No Discharge N/A 15.10 18.40 0.00
14 No Discharge N/A 15.51 18.40 0.00
15 No Discharge N/A 18.99 20.30 0.00
16 No Discharge N/A 26.26 20.30 0.00
20 No Discharge N/A 11.96 20.30 0.00
4 21 No Discharge N/A 11.98 20.30 0.00
22 No Discharge N/A 13.90 20.30 0.00
23 No Discharge N/A 14.11 20.30 0.00
24 No Discharge N/A 15.68 20.30 0.00
25 No Discharge N/A 15.83 20.30 0.00
• 201 Sprinkler 5.30 13.78 20.00 0.00
202 Sprinkler 5.30 13.78 20.00 0.00
203 Sprinkler 5.30 13.00 20.00 0.00
204 Sprinkler 5.30 12.77 20.00 0.00
• 205 Sprinkler 5.30 12.80 20.00 0.00
Active Version 200 Pipe Capacity Thursday, June 12, 2008
AFIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Lockwood Engineering LLC 503 - 546 -0628 503 -445 -6388 Fax
. I FIRESTOP CO. Page 4
[ Fire Sprinkler Input Data
._Node-_ln-put Data4cont'c__y
Sprinkler Pressure Node Non - Sprinkler
Node No. Node Description Area Group Elevation Discharge
KFactor (K) Estimate (psi)
(feet) (gpm)
206 Sprinkler 5.30 12.61 20.00 0.00
207 Sprinkler 5.30 11.69 20.00 0.00
208 Sprinkler 5.30 11.53 20.00 0.00
209 Sprinkler 5.30 11.60 20.00 0.00
210 Sprinkler 5.30 12.97 20.00 0.00
211 Sprinkler 5.30 12.29 20.00 0.00
212 Sprinkler 5.30 12.03 20.00 0.00
Active Version 200 Pipe Capacity Thursday, June 12, 2008
IRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
ockwood Engineering LLC 503 -546 -0628 503 -445 -6388 Fax
IRESTOP CO. Pa•e 5
Fire Sprinkler Input Data
Nominal Nominal Fitting Total CFactor
Beg. End. Pipe Description Diameter Type Fitting Length Length Length (gpm /inch-
Node Node (inch) Group Data (feet) (feet) (feet) psi)
1 2 CAST IRON, CEMENT 8.000 0 T 1.00 46.60 47.60 140
2 3 CAST IRON, CEMENT 4.000 0 15.00 0.00 15.00 140
3 4 Backflo Prey 5.000 Loss
4 5 PVC, CLASS 200 4.000 0 4ET 156.00 90.60 246.60 150
5 6 SCHED 10 WET STEEL 2.500 0 ETG 10.25 25.00 35.25 120
6 7 SCHED 10 WET STEEL 2.500 0 ETG 37.00 25.00 62.00 120
7 8 SCHED 10 WET STEEL 2.000 0 ET 3.20 18.00 21.20 120
8 15 SCHED 10 WET STEEL 2.000 0 2E 2.80 12.00 14.80 120
15 12 SCHED 10 WET STEEL 2.000 0 2E 30.60 12.00 42.60 120
15 14 SCHED 40 WET STEEL 1.250 0 ET 25.70 9.00 34.70 120
12 11 SCHED 10 WET STEEL 2.000 0 5.30 0.00 5.30 120
11 10 SCHED 10 WET STEEL 2.000 0 9.50 0.00 9.50 120
14 13 SCHED 40 WET STEEL 1.250 0 12.80 0.00 12.80 120
13 12 SCHED 40 WET STEEL 1.250 0 ET 24.30 9.00 33.30 120
20 21 SCHED 40 WET STEEL 1.250 0 9.50 0.00 9.50 120
21 22 SCHED 40 WET STEEL 1.250 0 2E 22.00 6.00 28.00 120
22 23 SCHED 10 WET STEEL 2.000 0 9.00 0.00 9.00 120
. 23 24 SCHED 10 WET STEEL 2.000 0 ET 20.00 18.00 38.00 120
24 25 SCHED 10 WET STEEL 2.000 0 10.50 0.00 10.50 120
16 7 SCHED 10 WET STEEL 2.000 0 T 4.40 12.00 16.40 120
25 16 SCHED 40 WET STEEL 1.250 0 2T 67.00 12.00 79.00 120
24 8 SCHED 40 WET STEEL 1.250 0 2T 68.00 12.00 80.00 120
23 202 SCHED 40 WET STEEL 1.250 0 T 9.80 6.00 15.80 120
202 201 SCHED 40 WET STEEL 1.250 0 11.90 0.00 11.90 120
201 14 SCHED 40 WET STEEL 1.250 0 ET 19.10 9.00 28.10 120
22 205 SCHED 40 WET STEEL 1.250 0 2ET 13.70 12.00 25.70 120
Active Version 200 Pipe Capacity Thursday, June 12, 2008
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Lockwood Engineering LLC 503 -546 -0628 503 - 445 -6388 Fax
FIRESTOP CO Page 6
. Fire Sprinkler Input Data
' e_lnput Data (t ont'd)
Nominal Nominal Fitting Total CFactor
Beg. End. Pipe Description Diameter T ype Fitting Length Length Length (gpm /inch-
Node Node (inch) Group Data (feet) (feet) (feet) psi)
205 204 SCHED 40 WET STEEL 1.250 0 12.75 0.00 12.75 120
204 203 SCHED 40 WET STEEL 1.250 0 12.75 0.00 12.75 120
203 13 SCHED 40 WET STEEL 1.250 0 ET 7.30 9.00 16.30 120
21 209 SCHED 40 WET STEEL 1.250 0 T 4.00 6.00 10.00 120
209 208 SCHED 40 WET STEEL 1.250 0 13.40 0.00 13.40 120
208 207 SCHED 40 WET STEEL 1.250 0 13.40 0.00 13.40 120
207 206 SCHED 40 WET STEEL 1.250 0 13.40 0.00 13.40 120
206 11 SCHED 40 WET STEEL 1.250 0 T 5.40 6.00 11.40 120
20 212 SCHED 40 WET STEEL 1.250 0 T 26.00 6.00 32.00 120
212 211 SCHED 40 WET STEEL 1.250 0 14.00 0.00 14.00 120
. 211 210 SCHED 40 WET STEEL 1.250 0 8.00 0.00 8.00 120
210 10 SCHED 40 WET STEEL 1.250 0 T 1.00 6.00 7.00 120
Active Version 200 Pipe Capacity Thursday, June 12, 2008
IRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
ockwood Engineering LLC 503 - 546 -0628 503 - 445-6388 Fax
IRESTOP CO. Page 7
•
Fire Sprinkler Output Data
ti. �u�'.a� ..
Nom. Dia. F. Lift Pipe -Len.
Beg. Nodal Spk/Hose Residual
Inside Dia. Q ( gpm ) PF -
Eleva (psi /ft) Fit -Len.
End. KFactor (feet) Discharge Pressure C -Value Velocity Fittings Tot -Len PE -(psi)
Node (K) (gpm) (psi)
(fps (ft) PV -(psi)
1 0.00 0.00 0.00 55.72 8.00 325.40 0.00087 1.00 0.041
2 0.00 0.00 100.00 55.68 7.980 2.09 T 46.60 0.000
CAST IRON, CEMENT 140 0 47.60 0.000
2 0.00 0.00 100.00 55.68 4.00 225.40 0.01538 15.00 0.231
3 0.00 0.00 0.00 55.45 3.850 6.21 0.00 0.000
CAST IRON, CEMENT 140 0 15.00 0.001
Backflo
3 0.00 55.45 225.57
Prey
4 5.00 psi 0.00 50.44 21.57
4 0.00 0.00 0.00 50.44 4.00 225.40 0.01030 156.00 2.540
5 0.00 1.00 0.00 47.47 4.072 5.55 4ET 90.60 0.433
PVC, CLASS 200 150 0 246.60 0.001
5 0.00 1.00 0.00 47.47 2.50 225.40 0.12965 10.25 4.570
6 0.00 7.70 0.00 40.00 2.635 13.26 ETG 25.00 2.901
SCHED 10 WET STEEL 120 0 35.25 0.005
6 0.00 7.70 0.00 40.00 2.50 225.40 0.12965 37.00 8.038
7 0.00 16.30 0.00 28.24 2.635 13.26 ETG 25.00 3.724
SCHED 10 WET STEEL 120 0 62.00 0.005
7 0.00 16.30 0.00 28.24 2.00 183.94 0.23592 3.20 5.001
8 0.00 20.30 0.00 21.50 2.157 16.15 ET 18.00 1.732
SCHED 10 WET STEEL 120 0 21.20 0.010
16 0.00 20.30 0.00 26.26 2.00 41.47 0.01499 4.40 0.246
7 0.00 16.30 0.00 28.24 2.157 3.64 T 12.00 1.732
SCHED 10 WET STEEL 120 0 16.40 0.002
8 0.00 20.30 0.00 21.50 2.00 153.87 0.16956 2.80 2.509
15 0.00 20.30 0.00 18.99 2.157 13.51 2E 12.00 0.000
SCHED 10 WET STEEL 120 0 14.80 0.008
24 0.00 20.30 0.00 15.68 1.25 30.07 0.07282 68.00 5.826
8 0.00 20.30 0.00 21.50 1.380 6.45 2T 12.00 0.000
SCHED 40 WET STEEL 120 0 80.00 0.009
• 210 5.30 20.00 19.09 12.97 1.25 51.88 0.19973 1.00 1.398
10 0.00 20.30 0.00 14.24 1.380 11.13 T 6.00 -0.130
SCHED 40 WET STEEL 120 0 7.00 0.016
11 0.00 20.30 0.00 14.46 2.00 51.88 0.02269 9.50 0.216
10 0.00 20.30 0.00 14.24 2.157 4.56 0.00 0.000
SCHED 10 WET STEEL 120 0 9.50 0.003
206 5.30 20.00 18.82 12.61 1.25 48.03 0.17315 5.40 1.974
Active Version 200 Pipe Capacity Thursday, June 12, 2008
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Lockwood Engineering LLC 503 -546 -0628 503 -445 -6388 Fax
FIRESTOP CO. Page 8
Fire Sprinkler Output Data
Nom. Dia. F. L. /ft Pipe -Len.
Beg. Nodal Residual Q (gpm) PF -(psi)
End. KFactor Elevation Discharge pressure Inside Dia. Velocity (psi /ft) Fit -Len. pE -(psi)
Node (K) (feet) (gpm) (psi) C -Value (fps) Fittings Tot -Len. PV -(psi)
Type -Grp (ft)
11 0.00 20.30 0.00 14.46 1.380 10.30 T 6.00 -0.130
SCHED 40 WET STEEL 120 0 11.40 0.015
12 0.00 20.30 0.00 14.86 2.00 99.91 0.07627 5.30 0.404
11 0.00 20.30 0.00 14.46 2.157 8.77 0.00 0.000
SCHED 10 WET STEEL 120 0 5.30 0.005
13 0.00 18.40 0.00 15.10 1.25 13.86 0.01737 24.30 0.579
12 0.00 20.30 0.00 14.86 1.380 2.97 ET 9.00 -0.823
SCHED 40 WET STEEL 120 0 33.30 0.004
203 5.30 20.00 19.11 13.00 1.25 33.08 0.08686 7.30 1.416
13 0.00 18.40 0.00 15.10 1.380 7.10 ET 9.00 0.693
SCHED 40 WET STEEL 120 0 16.30 0.010
14 0.00 18.40 0.00 15.51 1.25 19.22 0.03181 12.80 0.407
13 0.00 18.40 0.00 15.10 1.380 4.12 0.00 0.000
SCHED 40 WET STEEL 120 0 12.80 0.006
• 201 5.30 20.00 19.67 13.78 1.25 20.88 0.03707 19.10 1.042
- 14 0.00 18.40 0.00 15.51 1.380 4.48 ET 9.00 0.693
SCHED 40 WET STEEL 120 0 28.10 0.006
15 0.00 20.30 0.00 18.99 2.00 113.77 0.09699 30.60 4.132
12 0.00 20.30 0.00 14.86 2.157 9.99 2E 12.00 0.000
SCHED 10 WET STEEL 120 0 42.60 0.006
15 0.00 20.30 0.00 18.99 1.25 40.10 0.12401 25.70 4.303
14 0.00 18.40 0.00 15.51 1.380 8.60 ET 9.00 -0.823
SCHED 40 WET STEEL 120 0 34.70 0.012
25 0.00 20.30 0.00 15.83 1.25 41.47 0.13195 67.00 10.424
16 0.00 20.30 0.00 26.26 1.380 8.89 2T 12.00 0.000
SCHED 40 WET STEEL 120 0 79.00 0.013
•
20 0.00 20.30 0.00 11.96 1.25 4.17 0.00189 26.00 0.060
212 5.30 20.00 18.39 12.03 1.380 0.90 T 6.00 -0.130
SCHED 40 WET STEEL 120 0 32.00 0.001
20 0.00 20.30 0.00 11.96 1.25 4.17 0.00189 9.50 0.018
21 0.00 20.30 0.00 11.98 1.380 0.90 0.00 0.000
SCHED 40 WET STEEL 120 0 9.50 0.001
21 0.00 20.30 0.00 11.98 1.25 24.93 0.05146 4.00 0.515
209 5.30 20.00 18.05 11.60 1.380 5.35 T 6.00 -0.130
SCHED 40 WET STEEL 120 0 10.00 0.008
21 0.00 20.30 0.00 11.98 1.25 29.10 0.06852 22.00 1.919
22 0.00 20.30 0.00 13.90 1.380 6.24 2E 6.00 0.000
SCHED 40 WET STEEL 120 0 28.00 0.009
Active Version 200 Pipe Capacity Thursday, June 12, 2008
IRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Lockwood Engineering LLC 503 - 546 -0628 503 - 445 -6388 Fax
IRESTOP CO. Page 9
Fire Sprinkler Output Data
Nom. Dia. F. L. /ft Pipe -Len.
Beg. Nodal Residual Q (gpm) PF -(psi)
End. KFactor Elevation Discharge pressure Inside Dia. Velocity (psi /ft) Fit -Len. PE -(psi)
Node (K) (feet) (gpm) (psi) C -Value (fps) Fittings Tot -Len. PV -(psi)
Type -Grp (ft)
22 0.00 20.30 0.00 13.90 1.25 23.93 0.04773 13.70 1.227
205 5.30 20.00 18.97 12.80 1.380 5.13 2ET 12.00 -0.130
SCHED 40 WET STEEL 120 0 25.70 0.007
22 0.00 20.30 0.00 13.90 2.00 53.03 0.02363 9.00 0.213
23 0.00 20.30 0.00 14.11 2.157 4.66 0.00 0.000
SCHED 10 WET STEEL 120 0 9.00 0.003
23 0.00 20.30 0.00 14.11 1.25 18.51 0.02954 9.80 0.467
202 5.30 20.00 19.67 13.78 1.380 3.97 T 6.00 -0.130
SCHED 40 WET STEEL 120 0 15.80 0.006
23 0.00 20.30 0.00 14.11 2.00 71.54 0.04111 20.00 1.562
24 0.00 20.30 0.00 15.68 2.157 6.28 ET 18.00 0.000
SCHED 10 WET STEEL 120 0 38.00 0.004
24 0.00 20.30 0.00 15.68 2.00 41.47 0.01499 10.50 0.157
25 0.00 20.30 0.00 15.83 2.157 3.64 0.00 0.000
SCHED 10 WET STEEL 120 0 10.50 0.002
•
202 5.30 20.00 19.67 13.78 1.25 1.21 0.00003 11.90 0.000
. 201 5.30 20.00 19.67 13.78 1.380 0.26 0.00 0.000
SCHED 40 WET STEEL 120 0 11.90 0.000
204 5.30 20.00 18.94 12.77 1.25 13.97 0.01764 12.75 0.225
203 5.30 20.00 19.11 13.00 1.380 3.00 0.00 0.000
SCHED 40 WET STEEL 120 0 12.75 0.004
205 5.30 20.00 18.97 12.80 1.25 4.97 0.00260 12.75 0.033
204 5.30 20.00 18.94 12.77 1.380 1.07 0.00 0.000
SCHED 40 WET STEEL 120 0 12.75 0.002
207 5.30 20.00 18.12 11.69 1.25 29.20 0.06898 13.40 0.924
206 5.30 20.00 18.82 12.61 1.380 6.26 0.00 0.000
SCHED 40 WET STEEL 120 0 13.40 0.009
208 5.30 20.00 18.00 11.53 1.25 11.08 0.01149 13.40 0.154
207 5.30 20.00 18.12 11.69 1.380 2.38 0.00 0.000
SCHED 40 WET STEEL 120 0 13.40 0.003
• 209 5.30 20.00 18.05 11.60 1.25 6.88 0.00475 13.40 0.064
208 5.30 20.00 18.00 11.53 1.380 1.47 0.00 0.000
SCHED 40 WET STEEL 120 0 13.40 0.002
211 5.30 20.00 18.58 12.29 1.25 32.79 0.08547 8.00 0.684
210 5.30 20.00 19.09 12.97 1.380 7.03 0.00 0.000
SCHED 40 WET STEEL 120 0 8.00 0.010
• 212 5.30 20.00 18.39 12.03 1.25 14.21 0.01820 14.00 0.255
Active Version 200 Pipe Capacity Thursday, June 12, 2008
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Lockwood Engineering LLC 503 -546 -0628 503 - 445 -6388 Fax
FIRESTOP CO. Page 10
ANN
Fire Sprinkler Output Data
_OveralLPipe Output Data 1cont'd)
Nom. Dia. F. L. /ft Pipe -Len.
Beg. Nodal Residual Q (gpm) PF -(psi)
End. KFactor Elevation Discharge pressure Inside Dia. Velocity (Psi /ft) Fit -Len. PE -(psi)
Node (K) (feet) (9Pm) (psi} C -Value (fps) Fittings Tot -Len. PV -(psi)
Type -Grp (ft)
211 5.30 20.00 18.58 12.29 1.380 3.05 0.00 0.000
SCHED 40 WET STEEL 120 0 14.00 0.004
Active Version 200 Pipe Capacity Thursday, June 12, 2008
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Lockwood Engineering LLC 503 -546 -0628 503 -445 -6388 Fax
FIRESTOP CO. Page 11
[Fire Sprinkler Output Data
'Overall SprinklerO
Flowing Area Group Sprinkler Sprinkler Residual Flowing Area Flowing Sprinkler
Sprinkler Elevation Pressure z Density Discharge
Node No. Code KFactor (K) (feet) (psi) (ft) (gpm /ft (gpm)
201 5.30 20.00 13.78 180.00 0.109 19.67
Sub Totals For Non -Group 180.00 0.109 19.67
202 5.30 20.00 13.78 180.00 0.109 19.67
Sub Totals For Non -Group 180.00 0.109 19.67
203 5.30 20.00 13.00 180.00 0.106 19.11
Sub Totals For Non -Group 180.00 0.106 19.11
204 5.30 20.00 12.77 180.00 0.105 18.94
Sub Totals For Non -Group 180.00 0.105 18.94
205 5.30 20.00 12.80 180.00 0.105 18.97
Sub Totals For Non -Group 180.00 0.105 18.97
206 5.30 20.00 12.61 180.00 0.105 18.82
Sub Totals For Non -Group 180.00 0.105 18.82
207 5.30 20.00 11.69 180.00 0.101 18.12
Sub Totals For Non -Group 180.00 0.101 18.12
208 5.30 20.00 11.53 180.00 0.100 18.00
Sub Totals For Non -Group 180.00 0.100 18.00
209 5.30 20.00 11.60 180.00 0.100 18.05
Sub Totals For Non -Group 180.00 0.100 18.05
210 5.30 20.00 12.97 180.00 0.106 19.09
Sub Totals For Non -Group 180.00 0.106 19.09
211 5.30 20.00 12.29 180.00 0.103 18.58
Sub Totals For Non -Group 180.00 0.103 18.58
212 5.30 20.00 12.03 180.00 0.102 18.39
Sub Totals For Non -Group 180.00 0.102 18.39
Totals For All Groups 2160.00 0.102 225.40
Active Version 200 Pipe Capacity Thursday, June 12, 2008
FIRE Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Lockwood Engineering LLC 503 - 546 -0628 503 - 445 -6388 Fax
FIRESTOP CO. Page 12
Fire Sprinkler Output Summary
Hydraulically_ Most Demanding Sprinkler Node
HMD Sprinkler Node Number: 208
HMD Actual Residual Pressure: 11.53 psi
HMD Actual GPM: 18.00 gpm
Sprinkler Summary _
Sprinkler System Type: WET
Specified Area Of Application: 2160.00 ft
Minimum Desired Density: 0.100 gpm /ft
Application Average Density: 0.104 gpm /ft
Application Average Area Per Sprinkler: 180.00 ft
Sprinkler Flow: 225.40 gpm
Average Sprinkler Flow: 18.78 gpm
Flow Velocity And Imbalance Summary
Maximum Flow Velocity (In Pipe 7 - 8) 16.15 ft/sec
Maximum Velocity Pressure (In Pipe 10 - 210) 0.02 psi
Allowable Maximum Nodal Pressure Imbalance: 0.0100 psi
Actual Maximum Nodal Pressure Imbalance: 0.0065 psi
Actual Average Nodal Pressure Imbalance: 0.0006 psi
_ Actual Maximum Nodal Flow Imbalance: 18.0397 gpm
. Actual Average Nodal Flow Imbalance: 0.5564 gpm
• OveralLNetwork Summary
•
Number Of Unique Pipe Sections: 38
Number Of Flowing Sprinklers: 12
Pipe System Water Volume: 57.60 gal
Sprinkler Flow: 225.40 gpm
Non- Sprinkler Flow: 100.00 gpm
Total System Demand Flow: 325.40 gpm
Minimum Required Residual Pressure At System Inflow 55.72 psi
Node:
Demand Flow At System Inflow Node: 325.40 gpm
Active Version 200 Pipe Capacity Thursday, June 12, 2008
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
Lockwood Engineering LLC 503 - 546 -0628 503 - 445 -6388 Fax
_ I FIRESTOP CO Page 13
•
- Fire Sprinkler Output Data
.draulic Supply /Demand Graph --
200
180
160
N
140
Q
120
107
co
100 95
5o • •
80 ,
60 •
40
20
0 •
3 6 9 12 15 18 21 24 27 30
Flowrate(x100) gpm
Adjusted Hydrant Data f r cotauc7rt q Iz22o sc,3-6klmr !r
Static Pressure: 107 psi ECEVAT?onl CW4,I&E €s, _ f hb. 12gSD SO- GQ,d,JT
Test Residual Pressure: 95 psi
Test Flow Rate: 2434 gpm
. Demand Point Data
Calculated Residual Pressure: 55.72 psi
Calculated Flow Rate. 325.40 gpm
Excess Available Inflow Residual Pressure: 50.99 psi
Active Version 200 Pipe Capacity Thursday, June 12, 2008
Nor' Fire & Building
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series TY -FRB — 2.8, 4.2 5.6 and 8.0 K- factor
Upright, Pendent, and Rec sed Pendent Sprinklers
Quick Response, Standard Coverage
tained when exposed to corrosive at-
G eneral mospheres. Although corrosion resis- f.
tant coated sprinklers have passed the
Description standard corrosion tests of the appli-
cable approval agencies, the testing is
The Tyco® Series TY -FRB, 2.8, 4.2, not representative of all possible cor-
5.6, and 8.0 K- factor, Upright and Pen- rosive atmospheres. Consequently, it
dent Sprinklers described in this data is recommended that the end user be ,
sheet are quick response - standard consulted with respect to the suitability
coverage, decorative 3 mm glass bulb of these coatings for any given corro-
type spray sprinklers designed for use sive environment. The effects of ambi-
in light or ordinary hazard, commercial ent temperature, concentration of
occupancies such as banks, hotels, chemicals, and gas /chemical velocity, —
shopping malls, etc. should be considered, as a minimum,
The recessed version of the Series along with the corrosive nature of the
TY -FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be
plicable, is intended for use in areas exposed.
with a finished ceiling. It uses either a An intermediate level versions of the •
Style 10 (1/2 inch NPT) or Series TY -FRB Pendent Sprinklers ` f •-•'\
Style 40 (3/4 inch NPT) Recessed Es - are detailed in Technical Data Sheet ,/
cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de-
. recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780
(19,1 mm) of total adjustment from the +-64i
flush pendent position, or a two -piece WARNINGS r ,
Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY -FRB Sprinklers de-
inch NPT) Recessed Escutcheon with scribed herein must be installed and
114 inch (6,4 mm) of recessed adjust- maintained in compliance with this
ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica-
total adjustment from the flush pen- ble standards of the National Fire Pro -
dent position. The adjustment pro- tection Association, in addition to the
vided by the Recessed Escutcheon re- standards of any other authorities hay- Model/Sprinkler
duces the accuracy to which the fixed ing jurisdiction. Failure to do so may
pipe drops to the sprinklers must be impair the performance of these de- Identification
cut. vices.
Corrosion resistant coatings, where The owner is responsible for maintain- Numbers
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2 "NPT
that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2"NPT
manufacturer should be contacted TY2131 - Upright 4.2K, 1/2"NPT
with any questions. TY2231 - Pendent 4.2K, 1/2 "NPT
IMPORTANT TY3131 - Upright 5.6K, 1/2"NPT
Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2"NPT
Sheet TFP700 for the "INSTALLER TY4131 - Upright 8.0K, 3/4"NPT
WARNING" that provides cautions TY4231 - Pendent 8.0K, 3/4"NPT
• with respect to handling and instal- TY4831- Upright 8.0K, 1/2 "NPT
lation of sprinkler systems and corn- TY4931- Pendent 8.0K, 1/2"NPT
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
• to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 AUGUST, 2007 TFP171
Page 2 of 10 TFP171
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED
SURFACE NFT MAKE -IN ESCUTCHEON DEFECTOR
ice' 5
� ■r = � 1 m
1/4 ) " `� � 7/16"
I (11,1 mm) I 4
(57 - ,2 mm I f _� � NOMINAL
- `�1� MAKE -IN ill � 2
1 9/16" r _ I 2-3/16" yr 3 (39,7 mm) I I' WRENCH t (55,6 mm) : LATS _ �.jf 1
me
oeetorirlt 7
SSP DEFLECTOR * --*-- 2-7/8" (73,0 mm) DIA. 1/2" NPT t
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw
FIGURE 1
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED
SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR
1 7/16" 5
6
2 -3/16" ,1 ■f =
- } I (11,1 mm) I
• (55,6 mm) 4 A�N � - F
NOMINAMAKE -IN L 1 4
1 1 /2" I 11011 �� 2-3/16" 2
(38,1 mm)
WREN (55,6 mm) 4 y s
. __ _ 11 - FLATS r 1 I 3
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 1 1/2" NPT
1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
. Screw
FIGURE 2
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K- FACTOR, 1/2 INCH NPT
tLJCfJ I Fire & Building
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series TV -B — 2.8 5.6, and 8.0 K- factor
Upright, Pendent, an : Recessed Pendent Sprinklers
Standard Response, Standard Coverage
General cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
Description is recommended that the end user be
consulted with respect to the suitabilit
The Series TY -B, 2.8, 5.6, and 8.0 of these coatings for any given corro -
K- factor, Upright and Pendent Sprin- sive environment. The effects of ambi- r
klers described in this data sheet are ent temperature, concentration of
standard response - standard cover- chemicals, and gas /chemical velocity,
age, decorative 5 mm glass bulb type should be considered, as a minimum, t
spray sprinklers designed for use in along with the corrosive nature of the , ` '
light,
ordinary, or extra hazard, corn- chemical to which the sprinklers will be
mercial occupancies such as banks, exposed. w ,
hotels, shopping malls, factories, refin-
An intermediate level version of the
eries, chemical plants, etc. Series TY -B Pendent Sprinkler can be
The recessed version of the Series obtained by utilizing the Series TY -B
TY-B Pendent Sprinkler, where appli- Pendent Sprinkler in combination with
cable, is intended for use in areas with the Model S2 Shield. � R
a finished ceiling. It uses a two -piece
• Style 10 (1/2 inch NPT) or Style 40 (3/4 WARNINGS , """" �
• inch NPT) Recessed Escutcheon. The The Series TY-B Sprinklers described I
• Recessed Escutcheon provides 1/2 herein must be installed and main- if
inch (12,7 mm) of recessed adjust- tained in compliance with this docu- ,..
ment or up to 3/4 inch (19,1 mm) of meet as well as with the applicable
total adjustment from the flush pen- standards of the National Fire Protec-
dent position. The adjustment pro- tion Association, in addition to the
vided by the Recessed Escutcheon re- standards of any other authorities hay- ..
duces the accuracy to which the fixed ing jurisdiction. Failure to do so may
pipe drops to the sprinklers must be impair the performance of these de-
cut. vices.
Corrosion resistant coatings, where The owner is responsible for maintain-
.
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition.
that which would otherwise be ob- The installing contractor or sprinkler
tained when exposed to corrosive at- manufacturer should be contacted
mospheres. Although corrosion resis- with any questions.
tant coated sprinklers have passed the
standard corrosion tests of the appli-
Model/Sprinkler
IMPORTANT Identification
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER Numbers
WARNING" that provides cautions
with respect to handling and instal- TY1151 - Upright 2.8K, 1/2 "NPT
lation of sprinkler systems and corn- TY1251 - Pendent 2.8K, 1/2 "NPT
ponents. Improper handling and in- TY3151 - Upright 5.6K, 1/2 "NPT
stallation can permanently damage TY3251 - Pendent 5.6K, 1/2 "NPT
• a sprinkler system or its compo- TY4151 - Upright 8.0K, 3/4 "NPT
nents and cause the sprinkler to fail TY4251 - Pendent 8.0K, 3/4 "NPT
. to operate in a fire situation or cause TY4851 - Upright 8.0K, 1/2 "NPT
it to operate prematurely. TY4951 - Pendent 8.0K, 1/2 "NPT
Page 1 of 8 DECEMBER, 2007 TFP151
Page 2 of 8 TFP151
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING 112„ ** NOMINAL SSU
SURFACE NPT MAKE -IN DEFLECTOR
i __,--
r� itf?TT FTb�r :.rf'T1; *7RTTs� 6
i�0 5
2-1/4" ` } ' 2-3/16" 4
(57,2 mm) 1 W =W1 (55,6 mm)
— 2
1 -9/16" WRENCH r� � � 3
(39,7 mm) FLATS k 1 k r III
/% ?!r% SSP 7
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
STANDARD RESPONSE SERIES TY -8 UPRIGHT (TY1151) AND PENDENT (TY1251) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm) STYLE 10
PLATE SEATING ** NOMINAL RECESSED
SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR
6
f -- r —
m ° 7/16" �'� 5
• 2 -3/16" + ( mm)
• (55,6 mm) O NOMINAL MAKE -IN
ir
(3 /m, p 1 `_, 2 -3 g V �� 2
(55,6 mm) r 0 3
WRENCH a=
1 -��� i�-r• -�� �^ FLATS 0 0
1
SSP DEFLECTOR* 2 -718" (73,0 mm) DIA. - -1 1/2 "NPT ** 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY3151) AND PENDENT (TY3251) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
. .....
_....
..
tqco/ F/ow Control Tyco Fire
Products CENTRAL
Customer Service /Sales:
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Tel: (215) 362 -0700 / (800) 523 -6512
Fax: (215) 362 -5385
Series TY -B — 5.6 K- factor
Horizontal and Vertical Sidewall Sprinklers
3 mm QUICK Response, Standard Coverage
General sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers will be exposed. i
Description �` (-
WARNINGS ' . �- • .. ,
The Series TY -B, 5.6 K- factor, Horizon- The Series TY -8 Sprinklers described ./ '- -. w i
tal and Vertical Sidewall Sprinklers de- herein must be installed and main- '' Jl 1
scribed in this data sheet are standard tained in compliance with this docu- k
response - standard coverage, deco- ment, as well as with the applicable -
rative 5 mm glass bulb type spra standards of the National Fire Protec- .-4 / /
sprinklers designed for use in light and tion Association, in addition to the w
ordinary hazard, commercial occupan- standards of any other authorities ha v-
cies such as banks, hotels, shopping ing jurisdiction. Failure to do so may
malls, etc. They are designed for instal- impair the integrity of these devices.
lation along a wall or the side of a beam
and just beneath a smooth ceiling. The owner is responsible for maintain-
Sidewall sprinklers are commonly ing their fire protection system and de- r.
used instead of pendent or upright vices in proper operating condition.
sprinklers because of aesthetics or The installing contractor or sprinkler -
building construction considerations, ma should be contacted
where piping across the ceiling is not relat to any questions. I
• desirable.
itb.
The recessed version of the Series ( .
TY -B Horizontal Sidewall Sprinkler is Model /Sprinkler � ;,- -.--
intended for use in areas with a fin -
ished wall. It uses a two -piece Style 10 Identification
Recessed Escutcheon. The Recessed
Escutcheon provides 1/2 inch (12,7 Numbers
mm) of recessed adjustment or up to
3/4 inch (19,1 mm) of total adjustment TY3351 - Horizontal
• from the flush sidewall position. The TY3451 - Vertical Finishes
adjustment provided by the Recessed Sprinkler: Refer to Table A
Escutcheon reduces the accuracy to Recessed Escutcheon: White Coated
which the fixed pipe nipples to the or Chrome Plated. (Other colors are
sprinklers must be cut. Technical available on request.)
Corrosion resistant coatings, where Physical Characteristics
applicable, are utilized to extend the Data Frame Bronze
life of copper alloy sprinklers beyond Button Brass /Copper
that which would otherwise be ob- Approvals Sealing Assembly
tained when exposed to corrosive at- UL and C -UL Listed. Beryllium Nickel w/Teflont
mospheres. Although corrosion resis- FM, LPCB, and NYC Approved. Bulb Glass
tant coated sprinklers have passed the (Refer to Table A for complete approval Compression Screw Bronze
• standard corrosion tests of the appli- information including corrosion resis- HSW Deflector Bronze
cable approval agencies, the testing is tant status) VSW Deflector Copper
not representative of all possible cor- Maximum Working Pressure
rosive atmospheres. Consequently, it 175 psi (12,1 bar) Patents
is recommended that the end user be U.S.A. Patent Number 5,810,263 and
consulted with respect to the suitability Discharge Coefficient UK Patent Number 2,347,624 may be
of these corrosion resistant coatings K = 5.6 GPM /psi (80,6 LPM /bar applicable to the Series TY B Horizon-
- for any given corrosive environment. Temperature Ratings tal Sidewall Sprinkler.
The effects of ambient temperature, Refer to Table A
. concentration of chemicals, and
gas /chemical velocity, should be con -
Page 1 of 6 FEBRUARY, 2002 - TFP161 (1.6.1)
tqco Fl ow Control Tyco Fire
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Model DS -1 — 5.6 K- factor
Dry Type Sprinklers
Standard Response, Standard Coverage
General Sprinkler
Description Identification
The Model DS -1, 5.6 K- factor, Stand- Numbers ,
and Response, Standard Coverage,.
Dry Type Sprinklers are decorative SIN TY3255 - (Pendent) 4
5 mm glass bulb automatic sprinklers SIN TY3155 - (Upright)
designed for the following typical uses: SIN TY3355 - (Horizontal Sidewall)
• where pendent sprinklers are re-
quired on dry pipe systems that ;' ;;
are exposed to freezing tempera-
tures (e.g. sprinkler drops from un-
heated portions of buildings)
• where sprinklers and /or a portion
of the connecting piping may be Technical „! •
- exposed to freezing temperatures
(e.g. sprinkler drops from wet sys- Data
tems into freezers, sprinkler '
sprigs from wet systems into un- Approvals
heated attics, or horizontal piping UL and C -UL Listed. FM Approved.
extensions through a wall to pro- (Refer to Table A) tr.
tect an unheated area of a build-
ing) Maximum Working Pressure
175 psi (12,1 bar)
• where sprinklers are used on sys Inlet Thread Connection Aak
tems that are seasonably drained
to avoid freezing (e.g. vacation re- 1 inch NPT (Standard Order)
sort areas) ISO 7-R1
3/4 inch NPT
WARNINGS 1- 1/4 -14UNC Bulb Glass
- The Model DS -1 Dry Type Sprinklers Discharge Coefficient Compression Screw Bronze
described herein must be installed and K = 5.6 GPM /psi 112 Deflector Bronze
maintained in compliance with this (80,6 LPM /barl'2) Frame Bronze
document, as well as with the applica Guide Tube Stainless Steel
ble standards of the National Fire Pro- Temperature Ratings Water Tube Stainless Steel
tection Association, in addition to the Refer to Table A Spring Stainless Steel
standards of any other authorities hav- Finishes Sealing Assembly
ing jurisdiction. Failure to do so may Sprinkler: Natural Brass, Chrome Beryllium Nickel w/Teflon
impair the integrity of these devices. Plated, White Polyester Escutcheon Carbon Steel
The owner is responsible for maintain- Escutcheon: White Coated or Chrom Patents
ing their fire protection system and de- Plat
g p y (Colors other than white are available U.S.A. Patent Number 5,188,185 is ap
vices in proper operating condition. on request.) plicable to the Model DS -1, 5.6 K -fac-
. The installing contractor or sprinkler tor, Standard Response, Standard
manufacturer should be contacted Physical Characteristics Coverage, Dry Type Sprinklers.
relative to any questions. Inlet Copper
The Model DS -1 Dry Type Sprinklers Plug Copper
must only be installed in fittings that Yoke Stainless Steel
meet the requirements of the Design Casing
Criteria section. Galvanized Carbon Steel
Insert Bronze
Bulb Seat Stainless Steel
Page 1 of 6 JULY, 2001 TFP500
Page 2 of 6 -
SPRINKLER FINISH
SIN TY3255 Pendent SIN TY3255 Pendent SIN TY3355 Hor. Sidewall
w/ Standard w/ Std. Escutcheon w/ Std. Escutcheon
Recessed Escutcheon (Ref. Fig. 5) and a top of
(Ref. Fig. 3) Deflector -to- Ceiling
SIN TY3255 Pendent distance of
SIN TY3255 Pendent w/ Deep Escutcheon 4 to 12 inches
w/ Wide Flange (Ref. Fig. 6) (100 to 300 mm)
Recessed Escutcheon
(Ref. Fig. 4) SIN TY3155 Upright (Ref. Fig. 8)
w/o Escutcheon
(Ref. Fig. 7)
Temperature Bulb Natural Chrome Polyester Natural Chrome Polyester Natural Chrome Polyester
Rating Color Code Brass Plated (All Brass Plated (All Brass Plated (All
Colors) Colors) Colors)
135 °F /57 °C Orange 1 , 2, 3 1 , 2 1 , 2, 3 1 , 2 1 " , 2 ", 3"" 1 *, 2"
155 °F /68 °C Red 1,2,3 1,2 1,2,3 1,2 1 ",2 *,3 "" 1",2"
175 °F /79 °C Yellow 1 , 2, 3 1 , 2 1 , 2, 3 1 , 2 1 " , 2`, 3 ** 1 ", 2"
200 °F /93 °C Green 1 , 2, 3 1 , 2 1 , 2, 3 1 , 2 1 " , 2 ", 3 ** 1 ", 2"
286 °F /141 °C Blue N/A 1 , 2, 3 1 , 2 1 " , 2 ", 3 "" 1 ", 2*
360 °F /182 °C Mauve N/A 1 , 2, 3 1 , 2 1 " , 2" 1 *, 2*
Notes:
1. Listed by Underwriters Laboratories, Inc (Maximum order length of 48 inches).
2. Listed by Underwriters Laboratories for use in Canada (Maximum order length of 48 inches).
3. Approved by Factory Mutual Research Corporation (Maximum order length of 48 inches).
* Light and Ordinary Hazard Occupancies Only.
'" Light Hazard Occupancies Only.
N/A - Not Available.
TABLE A
MODEL DS -1, STANDARD RESPONSE - STANDARD COVERAGE, DRY TYPE SPRINKLERS _
LABORATORY LISTINGS AND APPROVALS _
PLUG WITH a ; �, INLET WRENCH
RECESS
GASKETED SPRING lir
PLATE SEAL _ " - _,
S._.
YO KE
SPRING — 1 N
�� r
i_i ;
- CASING
WATER - PUSH WRENCH IN TO _
TUBE ENSURE ENGAGEMENT WITH
INSERT SPRINKLER WRENCHING AREA
GUIDE - FIGURE 2
TUBE — _ - BULB W -TYPE 7 SPRINKLER WRENCH
SEAT
FRAME —
I® - 5 mm
BULB
VENT HOLE
4 , 4 COMPRESSION
DEFLECTOR -- -- SCREW
FIGURE 1
MODEL DS -1 STANDARD RESPONSE
DRY TYPE SPRINKLER ASSEMBLY
9/94
• P :O. Box 3365 SOUTH EL \ •NTE • CA 91733 . (818) 444 -0541 • FAx (818) 444 -3887
300 RING HANGER (21 FM
• PIPE ROD PRICE/EA BOX WEIGHT /C .
SIZE SIZE P. GALV. QUANT. (APPROX.)
i l 1/2' , ' 3/8" $1.52 100 9
3/4 318" 1.52 100 9
1" 3/8" 1.52 100 10
1 1 /4" 3/8" 1.52 100 11
1 1 /2" 3/8" 1.52 100 11
2" 3/8" 1.52 100 14
2 1/2" 3/8" 3.04 50 28
3" 3/8" 3.14 50 30
` 3 1/2" 3/8" 5,85 50 32
-
4" 3/8" 5.85 25 40
5" 1/2" 7.65 20 65
-
6" 1/2" 8.93 20 110
8" 1/2" 10.20 10 130 303 RING HANGER _I EXTRA HEAVY
PIPE ROD PRICE /EA BOX WEIGHT /C
140.*: SIZE SIZE P. GALV. QUANT. (APPROX.)
2 1/2" 1/2" $10.60 50 55
• 3" 1!2" 11.65 50 60
4" 1/2" 13.40 25 100
305 RING HANGER WITHOUT SWIVEL NUT
PIPE ROD PRICE /EA BOX WEIGHT /C
o a SIZE SIZE P. GAL' /. QUANT. (APPROX.)
.
/ 1/2" 1/2" $1.37 100 8
3/4" 1/2" 1.37 100 8
1" 1/2" 1 37 100 9
11/4" 1/2" 1.37 100 10
1 1/2" 1/2" 1.37 100 10
2" 1/2" 1.37 100 13
2 1/2" 1/2" 5.02 50 27
3" 1/2" 5.61 50 29
3 1/2" 1/2" 8.97 50 31
4" 1/2" 8.97 25 49
5" 5/8" 10.04 20 64
6" 5/8" 16.09 20 108
8" 5/8" 19.70 10 128
* = NON - CANCELABLE NON - RETURNABLE ITEM
.aia/gg
P.O. Box 3365 Soum EL MONTE • CA 91733. (818) 444 -0541 • FAX (818) 444 -3887
001/020
SWAY BRACE MODEL E
• SIZE
Pipe size to be braced: 1" through 8" SCH 10 and SCH 40.
Pipe size used for bracing: 1" and 1 1/4" SCH 40 IPS.
MATERIAL
Carbon Steel.
FINISH
Plain, Electro- Galvanized and H.D.G.
APPROVALS
* Patented. `
* UL and cUL Listed. - `
* Must be used with AFCON listed Attachment Ends.
FUNCTION
For bracing fire sprinkler pipe against sway and seismic disturbances.
The pipe attachment component used to secure the fire sprinkler piping to the brace pipe.
INSTALLATION
* Place assembly over sprinkler pipe to be braced. -
* Insert bracing pipe through MODEL "E" under channel bracket.
* Tighten both hex nuts until gage spring lays flat.
FEATURES
* Can be used to brace SCH'10 and SCH 40 pipe.
* Field adjustable - Eliminates pre- engineering of brace pipe length.
* Requires no threading.
* Can be used as a 4 -way riser brace.
* Gage spring allows easy verification of necessary minimum torque. (5LB/FT)
ORDERING
Part N, Pipe size to be braced, Braced Pipe size and Finish.
d 9 z7
P.O. Box 3365 SOUTH EL MONTE • CA 91733 • (818) 444 -0541 • FAx (818) 444 -3887
077
LOCKING ATTACHMENT END
1 0 N
awl
tr) aprons Bead
■111
•
-s-
SIZE o
1 and 1 1 %4 inch bracing pipe. 11"
D
/ t
MATERIAL
Carbon Steel.
SIZE A B C D
FINISH
•
Plain, Electro- Galvanized and H.D.G. 1" 1" 2" 21/x2" 1"
1 1/4" 1 1/8" 2 1/4" 2 9/16" 1 3/16"
APPROVALS
* Patented.
* Underwriters Laboratories Listed
FUNCTION
The building attachment component used to secure brace pipe to the structure of this sway
bracing system.
INSTALLATION
* Insert brace pipe into fitting and against swivel bolt..
* Tighten set screw until it contacts tightly against the fitting.
FEATURES
* To be used with plain end pipe.
* Swivel design allows attachment at any angle.
* Visual inspection, proper torque when set screw head contacts bracket.
* May be ordered with larger hole. - Consult factory.
ORDERING
Part #, pipe size and finish.