Fire Protection by Computer Design '
C" 110 101:\J
HYDRO TECH FIRE PROTECTION INC
P.O. BOX 40
15218 NE CAPLES
BRUSH PRAIRIE, WA 98606
360- 256 -2816
• Job Name : DARTMOUTH
Building : REMOTE AREA 1
Location : THIRD FLOOR
System :
Contract :
Data File : DARTMOUT.WX1
r
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
•
HYDRO TECH FIRE PROTECTION INC Page 1
H. DARTMOUTH Date 110407
Hydraulic Design Information Sheet
Name - DARTMOUTH SQUARE OFFICE BUILDING Date - 11 -28 -07
Location - THIRD FLOOR _ _
Building - REMOTE AREA — 1 System No. -
Contractor - HYDRO TECH FIRE PROTECTION INC. Contract No. -
Calculated By - JCSMITH Drawing No. -
Construction: ( ) Combustible (X) Non - Combustible Ceiling Height -
occupancy -
S. (X) NFPA 13 (X) Lt. Haz. Ord.Haz.Gp. ( ) 1 ( ) 2 ( ) 3 ( ) Ex.Haz.
Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve .
S. Other
T Specific Ruling Made By Date
• E •
M Area of Sprinkler Operation - 1500 System Type Sprinkler /Nozzle
Density - .1000 (X) Wet Make RELIABLE
D Area Per Sprinkler - 400.00 ( ) Dry Model J112
E Elevation at Highest Outlet.- 40.75 ( ) Deluge Size 3/4 QR EC
S Hose Allowance - Inside - 100 ( ) Preaction K- Factor 11.2
I Rack Sprinkler Allowance - ( ) Other Temp.Rat.155
G Hose Allowance - Outside -
N
Note
Calculation Flow Required - 229.2 Press Required - 82.9 BASE
Summary C- Factor Used: 120 Overhead 140 Underground
- W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - 10 -8 -2007 Cap. -
T Time of Test - 11:40 Rated Cap.- Elev.-
E Static Press - 98 @ Press -
R Residual Press - 20 Elev. - Well
Flow - 4920 Proof Flow
S Elevation - 0
U
P Location - SW 69TH & DARTMOUTH ST.
P
L Source of Information - TUALITIN VALLEY WATER DISTRICT
Y
C , Commodity Class Location
O Storage Ht. Area Aisle W.
M- Storage Method: Solid Piled o Palletized $ Rack
M
( ) Single Row ( ) Conven. Pallet ( ) Auto. Storage ( ) Encap.
S R ( ) Double Row ( ) Slave Pallet ( ) Solid Shelf ( ) Non
T A ( ) Mult. Row ( ) Open Shelf
O C
R K , Flue Spacing Clearance:Storage to Ceiling
A Longitudinal Transverse
G
E Horizontal Barriers Provided:
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
•
Water Supply Curve (C)
•
HYDRO TECH FIRE PROTECTION INC Page 2
DARTMOUTH • - Date 110407
•
City Water Supply: • Demand:
C1 - Static Pressure : 98 D1 Elevation 1 17.649
C2 - Residual Pressure: 20 D2 - System Flow ; 329.169
C2 - Residual Flow • : 4920 • ,D2 - S stem Pressure 88.331
Hose: Adj City )
• Hose Demand )
D3 - System Demand 329.169
• Safety Margin 9.145
•
150 •
140
130
p120 • •
R110 :
E 100 C1 •
S 90 in D •
S 80
U 70
R
E 50
40
30 C2
20
D1
10
•
500 1000 1500 2000 2500 3000 3500 4000 4500 .
FLOW(NA1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
•
Fittings Used Summary
HYDRO TECH FIRE PROTECTION INC • - • Page 3
DARTMOUTH Date 110407
Fitting Legend -
Abbrev. Name Y '/. 1 1 1 Y2 2 2% 3 3 4 5 6 8 10 12 14 16 I 18 20 24
B Generic Butterfly Valve 0 0•. 0 0 0 0 7 10 0 12 9 10 12 19 21 0 0 0 0 0
G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
L Long Turn Elbow 1 1 2 2 2 3 4 5 5 6 8 9 13 . - 16 18 24 27 I 30 34 40
T 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101
121
•
•
•
•
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD .
HYDRO TECH FIRE PROTECTION INC Page 4
DARTMOUTH Date .110407
Node Elevation K -Fact Pt Pn Flow Density Area Press
No. Actual Actual Req.
104 40.75 11.2 19.77 na 49.8 0.1 400 12.8
105 40.75 11.2 21.14 na 51.49 0.1 400 12.8
101 40.75 11.2 12.8 na 40.07 0.1 400 12.8
102 40.75 11.2 13.71 na 41.47 0.1 400 12.8
, • 103 40.75 11.2 17.11 na 46.33 0.1 400 12.8
1 38.92 48.29 na
2 38.92 • 49.14 na
TOR 11.25 73.7 na
• BASE 0.0 82.96 na 100.0
. TEST 0.0 88.33 na
•
The maximum velocity is 18.46 and it occurs in the pipe between nodes 103 and 1
•
•
•
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations = "Hazen - Williams " . -
.HYDRO TECH FIRE PROTECTION INC Page 5
DARTMOUTH Date 110407
Hyd. • Qa Dia. Fitting Pipe Pt Pt
• Ref. "C" or • Ftng's Pe Pv Notes
Point Qt Pf /Ft Eqv. Ln. Total Pf Pn
•
104 49.80 1.682 0.0 19.330 19.773 K Factor = 11.20
to . 120 0.0 0.0 0.0
105 49.8 0.0706 0.0 19.330 1.365 Vel = 7.19
105 51.50 1.682 2L 4.95 78.870 21.138 K Factor = 11.20
to 120 2T 19.799 24.749 0.793
2 101.3 0.2625 0.0 103.619 27.205 Vel = 14.63
.0.0
• 101.30 49.136 K Factor = 14.45
_ 101 40.07 1.682 0.0 19.330 12.800 K Factor = 11.20
. to . 120 0:0 0.0 . 0.0
_ 102 40.07 0.0472 0.0 19.330 0.913 Vel = 5.79
• 1,02 41.47 1:682. 0.0 19.330 13.713 • K Factor = 11.20
to ' • • 120 0.0 0.0 0.0
• 103 - 81.54 . 0.1.757 • 0.0 19.330 • 3.397 Vel. = 11.77
103 46.33 1.682 : 2T 19.799 55.410 17.110 K Factor = 11.20
to ' 120 0.0. 19:799 0.793
"1 127.87 0.4040 0:0 ' 75.209 30.387 • - Vel = 18.46
1 0.0 2.635 0.0 18.625 48.290
_ to 120 0.0 0.0 0.0
.2 ••• 127.87 0.0454 0.0 18.625 0.846 Vel = 7.52
2: 101.30 2.635 3L 16.474 61.250 49.136
to • 120 1T 16.474. 32.948 11.984
• TOR 229.17 0.1336 0.0 94.198 12.583 Vel = 13.48
- . TOR. 0.0' 2.635 2L 10.983 12.250 73.703
to - 120 1B 9.61 " 20.593 4.872
BASE 229.17 0.1336 0.0 32.843 • 4.387 . Vel = 13.48
BASE 100.00 6.16 • '• 3L 38.734 350.000 82.962 • Qa = 100.00
" to - 140. 1T 43.037 86.075 4.000 * Fixed loss = 4
- TEST 329.17 0.003.1 1G 4.304 436.075 1.369 Vel = 3.54
0.0 --
329.17 ' 88.331 ' K Factor = 35.02
•
. --
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Bulletin 172 Rev.A
CO •
• Model JL112 & J112 - Pendent c
® ECLH - Extended Coverage Light Hazard
_ ri EC - Extended Coverage Ordinary Hazard
ECOH - Exte nded Coverage Ordinary
Do
Hazard - Quick Response <
D
Model JL112 & J112 ECLH /ECOH
Pendent & Recessed Pendent
(SIN R7216 - Link and RA7216 - Bulb) SIN RA 7216 is Corrosion Resistant with White
Polyester Coating.
• Quick Response for Light Hazard
(20' x 20' - 12' x 12' Room sizes) -
• Quick Response for Ordinary Hazard %
( 14' x 14' - 12' x 12' Room sizes) - � '
• Standard Response for Ordinary Hazard ..t �. -� - : -'1,
(20' x 20' - 12' x 12' Room sizes) .'. y
11L - ` .:.:'.:G. �- t
Features ,► - "!
1. Extended Coverage Ordinary Hazard and Light ; ,
Hazard protection to 400 ft (37.2m per sprinkler. .''_
2. Nominal K = 11.2 (160). '
3. Available in Pendent or Recessed Pendent styles. -4- t
4. Recessed pendent version provides 3 /4" (19mm) '
adjustment to flush pendent position see _ ' ':; - . .
adjustment table). - "
5. Available in brass, chrome and polyester coated __
Model JL112 Pendent Model J112 Pendent
finishes. (R 7216) (RA 7216)
6. For applications as per NFPA 13.
Approvals Organizations
1. Underwriters Laboratories, Inc. (UL) Design Criteria
2. Underwriters Laboratories of Canada (cULus) Reliable Model JL112 & J112 ECLH /ECOH sprinklers
UL Listing Category shall only be used in systems designed and installed in
9 g ry accordance with NFPA 13 and all other local codes
Sprinklers, Automatic and Open Extended Coverage and ordinances. The following design criteria also
Sprinklers- Ordinary Hazard Occupancy UL Guide apply:
Number - VNIV. • Minimum sprinkler spacing is 8 ft.
The Reliable Model JL112 and J112 sprinkler are • Sprinklers have a minimum flow requirement for each
Extended Coverage Sprinklers for use in both Light spacing as shown in the Flow Requirements Table on
and Ordinary Hazard 1 and 2 occupancies with a the reverse side.
coverage area of up to 400 square feet per sprinkler.
For ordinary hazard applications it is a Standard • ECOH sprinklers are only to be used in system
Response Sprinkler. For light hazard applications it is hydraulically designed per NFPA 13 for a minimum
Quick Response Sprinkler. area of 1500 ft or 5 sprinklers, whichever is greater.
The use of ECLH /ECOH sprinklers can provide lower • Deflector to commodity clearance shall be a
installation costs by requiring fewer sprinklers, less minimum of 18 in (457mm).
piping and reduced labor. • ECOH sprinklers shall be installed in unobstructed
ECLH /ECOH sprinklers are to be installed according constructions as defined in NFPA 13. For open web
to the design criteria shown in this bulletin, NFPA 13,
and all other local codes and ordinances. Flows and truss construction web thickness is not to exceed 1
pressures as shown on pages 2 and 3 of this bulletin, inch.
must be used for the appropriate spacing and for the • ECOH sprinklers which are installed above the
designated hazard classifications. bottom of a horizontal obstruction, shall have their
This ECLH /ECOH sprinkler is available in various deflectors located as shown in the Obstruction Table
. finishes, which includes a white polyester corrosion on page 3.
• resistant finish. • Sprinklers can be installed under a sloping ceiling not
ECLH /ECOH sprinklers are available in a pendent or
an attractive recessed pendent type which provides exceeding 2 inches of rise in 12 inches.
up to 3 /4" (19mm) of escutcheon adjustment. • Maximum working pressure is 175 psi at the sprinkler.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford NY 10523
1
Sprinkler Model Specifications
Temperature Rating Max. Ceiling Temp. Maximum Maximum I
Sprinkler Model Type Sprinkler Coverage I THD Size Approvals
°F °C °F °C Spacing Area
JL112 ECLH/ECOH- R7216 Link/Pendent 165 74 100 38
20' 400 ft
' JL112 ECLH/ECOH- R7216 Link/Recessed 212 100 150 66 I 3/4
1,2
J112 ECLH 155 68 100 38
ECLH/ECOH- RA7216 Bulb/Pendent NPT
J112 ECLH/ECOH- RA7216 Bulb/Recessed
200 93 150 66 20' 400 ft
Flow Requirements - Ordinary Hazard - Standard Response
Ordinary Hazard 1 Ordinary Hazard 2
"K" Factor
Spacing Coverage Area 0.15 gpmfft Density 0.20 gpmlft Density
*Flow `Pressure 'Flow 1 `Pressure US f Metric
14' x 14' 196 ft 30 7.2 39 12.1
and less
16' x 16' 256 ft 39 12.1 51 20.7 11.2 160.0
18' x 18' 324 ft 49 19.1 65 33.7
20' x 20' 400 ft 60 I 28.7 80 I 51.0
' Flow is in gpm and pressure is in psi
Recess Escutcheons Recessed Pendent ECLH /ECOH Adjustments
F1 /F2 FP Escutcheon ECLH ECOH
7 - .. R7216 RA7216 R7216 RA7216
_r FP 3 A 3 /7 3 A 3 /4
_' " 1� '� �` Fl n/a n/a 3 A '/a
. F2 1/2 / rVa n/a
/; F '. • Adjustments in inches.
Finishes
Sprinkler Finishes
Model J1 Model J112 Sprinkler Escutcheon
Sprinkler Wrench Sprinkler Wrench Bronze Brass
Use Model J1 Wrench for Use Model J112 Wrench for
JL112 & J112 ECLH/ECOH JL112 & J112 ECLH/ECOH Chrome Chrome
Pendent Sprinkler Removal Recessed Sprinkler Removal White Polyester Coated White Painted
and Installation and Installation — — — ._._..... ....._....__ ............................._...--- .— .._._.._..- ....-- ---- .._... — .................
Ordering Information
J1 Wrench J112 Wrench 1. Sprinkler Model
2. Temperature Rating
3. Finish
�' 4. Escutcheon and finish (where applicable)
.«ct Oh�Y >;.tlFtC
A
`" ^" Corrosion Resistant
Bulb
J112 ECLH/ECOH °F °C
• 155 68
200 93
2.
. . .. .
. . .
. . . • .
. _. •
• • . .
. . • . , • • . ,
. . .
.. . ,
. ..
'' ..
. .
. . .
•
• Minimum Flow, Requirements For Earlier Editions of NFPA 13 -FOR REFERENCE ONLY
. .
, .. ., . NFPA13 - 1991 Requirements NFPA13 -1989 Requirements 1 "K" Factor
• Ordinary Hazard 1 Ordinary Hazard 2 Ordinary Hazard 1 Ordinary Hazard 210rdinary Hazard 3
Coverage
_ i
bpacing 0.15 gpm/ft 0.20 gpm/ft 0.16 gpm/ft 0.19 gpm/ft 1 0.21 gpmfft I ..
..._ _us__ .Metric
• • - - - ----'"-`°-•-• ---- ------ - - -- -- - - - - - -
Density Density Deiiiitir - Density 1 .
'Flow 'Pressure 'Flow 'Pressure 'Flow 'Pressure I 'Flow I 'Pressure! 'Row I 'Pressure
• •
14 x 14'
196 ft 30.2 7.0 39.2 11.9 31.4 7.6 37.3 10.7 41.2 13.0
and less I ,
• • 16x 16' 256 ft 38.4 11.4 51.2- • 20.2 41.0 12.9 48.7 18.2 53.8 22.3 11.4 164.4
I
. •• , _ , 18' x 18' 324 ft .48.6 18.2 64.8 32.3 51.9 20.7 1 61.6 29.2 68.0 35.7
20 . x 20' 400 ft - 60.0 .27.7 80.0 49.3 64.0 31.5 76.0 44.5 84.0 54.3
•
. .
•
. : . *Flow is in gpm and pressure is in psi
• Flow Requirements •- Light Hazard - Quick Response
• • I .
-. Flow Pressure "K" Factor
Spac
• . ing . • Coverage Area
(gpin) (psi) US Metric
• • . • ----- --1 -
• . .
16' x 16' ...256 tt . 30 • 7.2
•
18' x 18' 324 ft . 33 8.7- 11.2 160
20' x 20' 400 ft 40 ' 12.8
. ..
•
. .
.
• Location of Deflector to Horizontal Obstruction
•
• •• . Maximum Allowable Distance ._, y5/16" Du --'
Distance from Sprinkler
-• Deflector Above Bottom of
- ' • •• to Side of Obstruction Obstruction
Less than 1' 0' aPh. COtorl Drini. '. 1 i i 7
nr..FIT Ar....ear 1 .
1 to less than 1' - 6' 0', _ pro:10„ssii p,, I i
.. - ." • 1. - 6 to less than 2' 1' • :-• ,,ii 7 .V1I (mi..") . .
ReCOuldrnfOrD
: CC.VG NOLL Du,
, .
.' . . 2: to.less than 2' - 6' 1' I:;',":',A NiEftWgil .
-!.
.f....zz_z.s .F
/16
' 1 --- ' 1.5 Pi 8
. ,
2 6° to less than 3' • 1' .
- " .( g=7 4 ' glf!9A ;., Ala' Or ririe:C.
. . • ro Criz.NG
. •
. . 3 10 less than a -6' 3' . 0 :!-1,; 1 k' t
"; IL -
4 - 6' to less than 5 7
•. 4' toless than 4' - e
, -
' ' , /5-
\
• 5' to less than 5 - 6' 7' --
. -
5 76 to less than 6' • . 7' I 1
•
6' tales'than 6' -6' • 9' .
6' - 6' to less than 7' 11'
:, ,7/.1: Du.
V I 2,,,,,, 1
7' and greater 14'
1 I . ----------------- _....
• Fig. 1 - Fl Escutcheon
, .
Solder Link Bulb •
Classification °F °C Classification °F °C Bulb Color
Ordinary 165 74 Ordinary 155 68 Red
Intermediate 212 100 Intermediate 200 93 Green
. .
•
• • .
. .
3.
. .
. .
• . •
. ,
. :•
. . . . . , •
- 'Reliable...For Complete Protection • . • Reliable offers a wide selection of sprinkler components. Following are some of the many
precision -made Reliable products that guard life and property from fire around the clock.
• Automatic sprinklers • Deluge valves
• Flush automatic sprinklers • Detector check valves
• • Recessed automatic sprinklers • Check valves
• • • Concealed automatic sprinklers • Supertrol electrical system
• • Adjustable automatic sprinklers • Sprinkler emergency cabinets
• Dry automatic sprinklers • Sprinkler wrenches
• Intermediate level sprinklers • Sprinkler escutcheons and guards
••• Open sprinklers • • Inspectors test connections
• Spray nozzles • Sight drains
• Alarm valves • Ball drips and drum drips
• • Retarding chambers • Control valve seals
■ Dry pipe valves • Air maintenance devices
•• -Accelerators for dry pipe valves • Air.compressors
. • 'Mechanical sprinkler alarms • Pressure gauges
. • Electrical sprinkler. alarm switches • Identification signs
. Water flow detectors • Fire department connection
•
•
The equipment presented in this bulletin is to be installed' in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances. whenever applicable.
Products manufactured and distributed by RELIABLE have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and
reputable sprinkler contractors located throughout the United States. Canada and foreign countries.
• Manufactured by
The Reliable Automatic Sprinkler Co., Inc. ® Recycled Paper
(800) 431 -1588
llellabld (800) 848-6051 Coles Fax
(914) 829 22 Sales Offices
042 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 8/07 P/N 9999970310
Bulletin 136K
Model F1FR to
c
® Mod
Quick Response F1 FR Recessed
Q S a)
Model Fl FR Sprinkler Types ., w
Standard Upright
Standard Pendent I 1 � Conventional _ :
Vertical Sidewall
Horizontal Sidewall ��'� ',
— HSW 1 Deflector . - -
M odel Fl FR Recessed Sprinkler Types
Recessed Pendent Upright Pendent
Recessed Horizontal Sidewall -
— HSW 1 Deflector ,l T -! s 1 � , rr `
'7,4
P
1 k
e. _
1 1 �
Product Description r °`' _''`y . •
Reli able Mod els F1FR and F1FR Recessed Sprinklersare - - _
.
quick response sprinklers which combine the durability of a I I I
standard sprin klerwith the attractive low profileof a deco ra-
tive sprinkler. Vertical Sidewall Conventional
The Models F1FR and F1FR Recessed automatic sprin-
klers utilize a 3.0 mm frangible glass bulb. These sprinklers
have demonstrated response times in labo ra tory tests which
are five to ten times faster than standard response sprin-
klers. This quick response enables the Model F1FR and .ra r ,.:-
F1FR Recessed sprinklers to apply water to a fire much R = a , ,
faster than standard sprinklers of the same temperature rat - 11 l w
ing. .� � 4
The glass bulb consists of an accurately controlled .
amount of special fluid hermetically sealed inside a pre-
cisely manufactured glass capsule. This glass bulb is spe-
cially constructed to provide fast thermal response. The
balance of parts are made of brass, copper and beryllium Horizontal Sidewall Recessed Pendent
nickel. HSW 1 Deflector
At normal temperatures, the glass bulb contains the fluid Application
in both the liquid and vapor phases. The vapor phase can pp
be seen as a small bubble. As heat is ap plied, the liquid ex- Quick response sprinklers are used in fixed fire protec-
pands, forcing the bubble smaller and smaller as the liquid tion systems: Wet, Dry, Del ugeor Preaction. Care must be
pressure increases. Continued heating forces the liquid to ex ercised thattheori fice size, tern perature rat ing, deflector
push out against the bulb, causing the glass to shatter, style and sprinkler type are in accordance with the latest
opening the waterway and allowing the deflector to distrib- published standards of the National Fire Protection Asso-
ute the discharging water. nation or the approving Authority Having Jurisdiction.
The temperature rating of the sprinkler is identified by the Quick response sprinklers are intended for installation as
color of the glass bulb. specified in NFPA 13. Quick re sponse sprin klers and stan-
dard response sprinklers should not be intermixed.
The Reliable Automatic Sprinkler Co., Inc. 525 North MacQuesten Parkway, Mount Vernon, New York 10552
•
Model Fl FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Spnn klerType " K" Factor Sprinkler Identification • Stan dards .lpright(SSU)andPendent(SSP) Sprinkler Approval Number(SIN)
Deflectors MarkedtolndicatePosition - -- -US_ _ ._- Metric_._ _ -__ Heigh_ ___Organization... _. SSU - - ' SSP -
y2( 15mm )StandardOrificewith %'NPT(R1) Thread 5.62 81.0 2.2'(56mm) 1,2,3,4,5,6,7 R3625 R3615
i '( 20mm) Large
7/Orificewith % " NPT(R 3 /4)Thread 8.0 115.3 2.3"(58rrm) 12,3,4,7,8 R3622 R3612
• 7 /, F'(17mm)SmallOrifice with y2'NPT( Thread (1) 4.24 61.0 2.54 "(65rrm) 1,2,8 R3623 R3613
. y (lomm) email Ori y" NPT (RY) Thread trf 2.82 40.6 2.54" (66rrm) 1,2,8 R3621 R3611
10mmOrifice XLH with RV Thread • 4.10 59.1 56.1mm 4,6,7 R3624 R3614
Conventional - Install in Up right or Pen dent Posi tion
1ommOrifice XLH with R % Thread 4.10 59.1 56.1mm - R3674
15mm Stan dardOrificewith " NPT (RY)Thread 5.6 81.0 56.1mm 4,6,7 R3675
20mm Large Or i fice with 3 /e NPT (R 8.0 _ 115.3 58.4mm _ 4, 7 P3672
' Identified by a pintle ex tending beyond the de flec tor.
4 ,
1,,.„.
.. i
,....
,,,,_,..,,,... „.: ' .,.•
. (Ille
I.
Uprig Pendent Upri - ght ' Conventional
Model Fl FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model RC1 Sprinkler Wrench
Installation Data:
Nominal Thread "K" Factor Sprinkler Approval (2) Sprinkler Identification
Orifice Size US Metric Height Organizations Number (SIN)
yz' (15mn) y" NPT (R1/2) 5.62 81.0 2.2' (561m) 1,2,3,4,5,7,8 R3615
"1/22" (26 % " NPT(R 3 /4) 8.0 115.3 2.3'(58rrii) 1,2,3 R3612
X6" (1) (11mn) • y" NPT (R1/2) 4.24 61.0 2.54" (65mm) 1,2,8 R3613
%" (1) (10 rrn) . y NPT (R'/z) 2.82 40.6 2.54" (65rrrn) 1,2,8 R3611
10mm ' ' Rae 4.10 59.1 56.1mm 4,7 R3614
L Identified by a pintle. extending beyond the deflector.
(`) Re fer to es cutch eon data table for ap prov als and di men sions.
-- 5.�• Or.
, V ,d• U4
_
L --1-.1.-=:,1 J
r i& ee
sM M.,N
"'I' - C" .
r „r S4
w
11rnCl sass- •
\I /
7- _ _ L - Ji� I _. :. d r,r, 4 r0 �•
_ ) -
,'.,, j rw. ' JYGGI:
2.
. Model Fl FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
-. "K" Factor_ _ .... .. - - Approval -- - -- — Sprinkler-Identification - - - • •
Nominal Orifice Threa S ize US Size Sprinkler Height Organizations Number (SIN)
'/" ' /2 " NPT (R'h) 5.62 81.0 2.2 " (56mm) 1,2,3,6,8
R3685
15mm 1/2" NPT (R'/2) 5.62 81.0 2.2" (56mm) 4 (')
(1) LPC Approval is Pen dent only.
� •;-1 Orientatio Deflector to Ceiling
1/4..,,-7"="7, .' : : :: Dimension (Min. - Max.)
: ..• 1 Upright 4" - 12" (102mm - 305mm)
L n ".
_ Pendent 6" - 12" (152mm - 305mm)
; r
7 ' '
Vertical Sidewall
• Model Fl FR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
: Installation Wrench: Model D Sprinkler Wrench
Installation Data:
ApprovalOrganizations Sprinkler
"K" Factor and Type of Approval Identification Num-
Nominal Thread Sprinkler Length Light Ordinary ber
Orifice Size US Metric Hazard Hazard (SIN)
(15mm) )'" NPT(R1/2) 5.62 81.0 2.63" (67mm) 1,2,3,5,8 1,2,5,8 R3635
NOTE UL and ULC Listing permits use with Fl or F2 recessed escutcheon.
f' k•
•
il # - , ..11111111W--;'
1
ii l - - 4I1i
, .
% J 1%\ •
Horizontal Sidewall
3.
•
.
. 0.
Installation Maintenance
▪ Quick response sprinklers are intended for installation The Models F1FR and F1FR Recessed Sprinklers
as specified in NFPA 13. Quick response sprinklers and should be inspected quarterly and the sprinkler system •
standard response sprinklers should not be intermixed. maintained in accordance with NFPA 25. Do not clean
• The Model Fl FR Recessed Quick Response Sprinklers sprinklers with soap and water, ammonia or any other
are to be installed as shown. The Model Fl or F2 Escutch- cleaning flu ids. Re move dust by using a soft brush or gen-
. eons - illustrated - are - the - only - recessed - escutcheons - to be - -tie• vacuuming- Remove any sprinkler -which has -been
used with the Model F1FR Sprinklers. The use of any other painted (other than factory applied) or damaged in any
recessedescutcheonwillvoidallapprovalsandnegateall way. A stock of spare sprinklers should be maintained to
warranties. allow quick replacement of damaged or operated sprin-
When in stall ing Model Fl FR Sprin klers, use the Model D klers. Prior to installation, sprinklers should be maintained
. Sprinkler Wrench. When installing Model Fl FR Recessed in the original cartons and packaging until used to mini- 1
Sidewall Sprinklers, use the Model GFR1 Sprinkler mize the potential for damage to sprinklers that would
Wrench. Use the Model RC1 Wrench for installing Fl FR cause improper operation or non -operation.
Recessed Pendent Sprinklers. Any other type of wrench
may damage these sprinklers.
Approval Organizations Sprinkler Types
1. Underwriters Laboratories, Inc. Standard Upright
2. Underwriters' Laboratories of Canada Standard Pendent
3. Factory Mutual Research Corporation Conventional
4. Loss Prevention Council Sidewall (Vertical, Horizontal HSW1)
5. NYC BS&A No. 587 -75 -SA Recessed Pendent
6. Meets MIL- S -901C and MIL -STD 167 -1 Recessed Horizontal Sidewall HSW1
7. Verband der Schadenversicherer
8. NYC MEA 258 -93 -E Finishes (1) `2'
ULI Listing Category Standard Finishes
Sprinklers, Automatic & Open Sprinkler Escutcheon
Quick Response Sprinkler Bronze Brass
ULI Guide Number Chrome Plated Chrome Plated
VNIV White Polyester Coated White Painted
Special Application Finishes
Temperature Ratings Sprinkler Escutcheon
Sprinkler Max. Ambient Bulb Bright Brass Bright Brass
Classification Temperature Temp. Cob' Black Plated Black Plated
• °C °F Black Paint Black Paint
Ordinary 57 135 100°F(38°C) Orange Off White Off White
Ordinary 65 155 100°F (38°C) Red
. Intermediate 79 175 150°F (66'q Yellow Satin Chrome Satin Chrome
Intermediate 93 200 150°F Green
High (1) 141 286 225°F (107°q Blue (1) Other finishes and col ors are avail able on spe cial or der.
Consult the factory for details.
(1) Not available for recessed sprinklers. (2) FM Approval is lim ited to bronze and brass, chrome or black
Escutcheon Data plated finishes only.
Face ofFimngto Ordering Information
E Approvals Adten A f Specify:
Model t Dimension pia, 1. 1 Sprikler Model
F1 1,2,4 y,,, r4" X." -' %' 2. Sprinkler Type
(19mm) (19mm) (5rrm- 24nttn) 3. Orifice Size
4. Deflector Type •
F2 1,2,3,4,5,7,8 1 /2" 1 /2" y 1" 776,-'X6' 5. Temperature Rating
(13mm) (25mm) (5rrrn -24nm) 6. Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
Note: When Model F1FR Recessed sprinklers are
ordered, the sprinklers and escutcheons are packaged
separately.
The equip ment presented in this bul le tin is to be in stalled in ac cor dance with the latest per ti nentStandardsof the National Fire Protec tionAssoci ation, Factory Mutual Re search
Corpora Lion, or other similar or ga ni za lions and also with the pro vi sionsof gov em mental codes or or di nanceswhen ever applicable.
Prod uctsmanufactured anddistributed by Reliable have been protecting lifeand property for over 80 years, and are in stalled and serviced by the most highly qual i tied and rep uta-
ble sprin kler con trac tors located through out the United States, Can ada and for eign coun tries
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. ® Recycled
Paper
. e
(800)431 -1588 Sales Offices
' (800)848 - 6051 Sales Fax Revision lines indicate updated or new data
(914)668-3470 Corporate Offices
www.reliabtesprinkler .com Internet rn Address EG. Printed in U.S.A. 12/00 P/N9999970027
dd