.- Bulletin 110 Rev.S
Model G co cp
. ° ® Automatic Sprinklers
Spray Upright
.
H e1rn'le — -Spray- Pendent - -- . - - -- - - - -- ° - ..
IRECE1 . I
V A nd Conventional
(',1T4 V I ON
. Product Description 111G C
The Reliable Model G Automatic Sprinkler utilizes the
center strut solder in compression principle of :^'- -_
construction. The fusible alloy is captured in the •, ,
cylinder of the solder capsule by a stainless steel ball. 'a ~ T,
When the fusible alloy melts, the ball moves into the -
cylinder allowing the cylinder to fall away from the , Y );
sprinkler. When this happens, the lever is released to ,JI
Jim. i
spring free from the sprinkler so that all of the operating . ti. Pasc
parts clear from the waterway allowing the deflector to '_ -; ;
. distribute the discharging water. _ _ • _
Except for the parts in the cylinder as mentioned
above, the sprinkler components are made from Upright . Pendent
copper based alloys for maximum corrosion
• protection. Lead plated, wax coated or wax over lead
plated sprinklers are available for specially severe
I environments. Chrome plated sprinklers are available i '�� ` , .
for decorative purposes. ? i, •
• All sprinklers are individually hydrostatically tested. ' ! ? r >,
All sprinklers are identified as to their fusing point by ', ��!
markings that appear on several of the operating parts r 1 G: : -. ,..
and by an identifying color that appears on the frame. `
Sprinkler Types
Standard Upright - This deflector configuration is Small Orifice Upright Conventional
normally used with exposed piping installations. Water
is distributed laterally and downward in a wide pattern
approximating a hemisphere which is completely. and
uniformly filled with water in the form of small drops or
spray. •
Standard Pendent - This deflector configuration is Application and Installation
normally used where the space above the piping is Standard sprinklers are used in fixed fire protection
I limited or where a concealed piping installation is systems: Wet, Dry, Deluge or Preaction. Care must be
employed. The discharge characteristics of the exercised that the orifice sizes, temperature ratings,
standard pendent are virtually identical to the deflector styles and sprinkler spacings are in
standard upright as described above. accordance with the latest published standards of the
• National Fire Protection Association or the approving •
Large and Small Orifice —By varying the orifice size, authority having jurisdiction.
a large or small orifice sprinkler is created that will The sprinklers must be installed with the Reliable
distribute as much as 40% more water or 65% less Model D Sprinkler Wrench. Any other type of wrench
water than the normal 1/2" (15mm) orifice sprinkler. may damage the sprinkler.
The approvals or listings of Reliable Automatic
Conventional —This deflector configuration is used Sprinklers by major approving organizations are
primarily in those countries where the LPC installation shown in the tabulated list provided on the back of this
rules have precedence. The sprinkler is designed to bulletin.
distribute a portion of its water discharge upward
against the ceiling with the balance downward. It may
be installed in either the upright or the pendent
position. Sprinklers with conventional deflectors are
available with orifice sizes corresponding to light, .Patent No. 4,440,234
ordinary and extra -high hazard installations.
•
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
•
Technical Data
• "K" Factor Sprinkler Identification
Sprinkler Number (SIN)
• Sprinkler Type US Metric Height Approvals SSU SSP
• Standard= Upright (SSU) and Pendent (SSP) -- — --- —. — - -- -- - — - --- - - -- -- — --
Deflectors Marked to Indicate Position
/ (15 mm) Standard Orifice with y" NPT (R/ Thread 5.62 81.0 2 Ye" (73 mm) 1, 2, 3, 4, 5, 6, 7 R1025 R1015
%' (11 mm) Small Orifice with y" NPT (Ry) Thread 4.24 61.0 2 Yee" (73 mm) 1, 3, 7 R1023 R1013
B" (10 mm) Small Orifice with y" NPT (Ry) Thread 2.82 40.6 2 Ye" (73 mm) 1, 2, 3, 7 R1021 R1011
X,3" (8 mm) Small Orifice with y" NPT (R}2) Thread 1.98 28.5 2 Ye" (73 mm) 1, 3, 7 R1022 R1012
' %z' (20 mm) Large Orifice with y" NPT (Ry) Thread 7.96 114.7 2 Ye" (73 mm) 1, 2, 3, 7 R1026 R1016
'332 (20 mm) Large Orifice with 3;" NPT (RX)Thread 8.20 118.2 2'3 e" (75 mm) 1, 2, 3, 7 R1027 R1017
20 mm XHH with 20 mm Thread 8.20 118.2 75.4 mm 4, 5, 6 R1027 R1017
10 mm XLH with 10 mm Thread 4.10 59.1 73 mm 4, 5, 6 R1024 R1014
Conventional—Installed in Upright or Pendent Position
10mm XLH with 10mm Thread 4.10 59.1 73 mm 5 R1074
15mm Standard Orifice with (Ry) Thread 5.62 81.0 73 mm 4, 5, 6 R1075
20mm XHH with (R3;) Thread 8.20 118.2 75.4 mm 4, 5 R1077 .
Temperature Ratings Maintenance
Maximum Model G Sprinklers should be inspected quarterly and the
Sprinkler Ambient sprinkler system maintained in accordance with NFPA 25. Do
Rating Temperature Frame ('), not clean sprinklers with soap and water, ammonia or any other
Classification °F °C °F 1 °C Color cleaning fluids. Remove any sprinkler that has been painted
Ordinary 135 57 100 38 Black (other than factory applied) or damaged in any way. A stock of
Ordinary 165 74 100 38 Uncolored spare sprinklers should be maintained to allow quick replace -
Intermediate 212 100 150 66 White ment of damaged or operated 'sprinklers. Prior to installation,
High 286 141 225 107 Blue sprinklers should be maintained in the original cartons and .
- packaging until used to minimize the potential for damage to
I Frame color does not apply to painted or plated sprinklers sprinklers that would cause improper operation or
-Use sprinkler rating as identified on operating parts. non -operation. Use only the Model D Sprinkler Wrench for
sprinkler removal and installation. Any other type of wrench may
damage the sprinkler.
Finishes
Standard Finishes Approval Organizations
Bronze —All Temperature Ratings 1. Underwriters Laboratories, Inc.
Chronw —All Temperature Ratings 2. Factory Mutual Research Corporation
White ( —All Temperature Ratings . 3. Underwriters' Laboratories of Canada
Only Frame and Deflector are Painted 4. Loss Prevention Council
Special Application Finishes 5. Pleniere Assemblee
Bright Brass Plated —Only frame, deflector and cap are plated. 135 °F (57 °C), 165 °F 6.
VdS S BS&A No. 5 8 rig
g (74°C), N.Y.C. MEA
), 212 °F (100°C) Temp. Rating. 7. N 7-75—SA or • N.Y.C. MEA 258-93-E
93 3-- E
. Black Plated —Only frame, deflector and cap are plated. All Temp. Ratings. •
Polyester Coated (2) —Only frame and deflector are coated:
Lead Plated —165 °F (74 °C), 212 °F (100 °C) and 286 °F (141 °C) Temp. Ratings. Ordering Information
Wax- Coated (3) —165 °F (74 °C) Clear Wax, 212 °F (100 °C) Brown Wax. Specify
Wax- Coated Over 1. Model G
l Lead Plated (3) —165 °F (74 °C) Clear Wax, 212 °F (100 °C) Brown Wax. 2. Deflector
• Upright
(l) Other colors and finishes are available. Consult factory for details. • Pendent
(2) UL listed and NYC MEA Approved only. • Conventional
(3) 212 °F (100 °C) brown wax may be used on 286 °F (141 °C) 3. Nominal Orifice
sprinklers when maximum ambient temperatures do not exceed 150 °F 4. Inlet Thread
(66 °C). UL Listed, FM Approved, NYC MEA 258 -93 -E. 5. Temperature Rating
6. Finish
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association. Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years. and are installed and serviced by the most highly qualified and
reputable sprinkler contractors located throughout the United States. Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
Re l i a b i e (800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 668 - 3470 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com I nternet Address EG.PrinetlinUSA not P/N 9939970005
•
• 0x' 5 —ar- 9�f
• Bulletin 117Rev.Q •
!tellable ® Model Fl RECEIVED
Model F1 Recessed 2 6 ;05
_ _ Standard Res o
Sprinklers `p CITY OFTI M
}
• o o, Hopi
The Designer Model Fl Sprinkler -:,•_: :- •
Standard Upright .u.
Standard Pendent th, ,
Extended Coverage Pendent ` -.
Conventional
Vertical Sidewall
Horizontal Sidewall Upright Pendent
- HSW 1 Deflector -
Horizontal Sidewall Extended Coverage k
- EC-6 Deflector t
,
!
a
ti
The D Model Fl Recessed Sprinkler ' t -
ir
Recessed Pendent ' '
. ;
Recessed Extended Coverage Pendent t . •
Recessed Extended Coverage Horizontal Sidewal Vertical Sidewall Conventional
Approval Organizations •
1. Underwriters Laboratories Inc. s :;-----1?---- -
� , - , rt
2. Underwriters' Laboratories of Canada f
A , I'Sr r` t
3. Factory Mutual Research Corp.
4. Loss Prevention Council �'
5. NYC BS &A No. 587 -75 -SA Horizontal Sidewall Recessed Pendent
6. Pleniere Assemblee
7. Verband der Schadenversicherer
8. NYC MEA 258 -93 -E r ',' '5l'
UL Listing Category vj ,,
Sprinklers, Automatic & Open (VNIV) ►
• Product Description Extended Coverage Recessed Extended
The Fl Glass Bulb Sprinkler combines the durability of a Horizontal Sidewall . Coverage Horizontal
standard sprinkler with the attractive low profile of a decora- Sidewall
tive sprinkler. Whether installed on exposed piping or in an
office ceiling, it is functional and attractive. The Horizontal ., = • �
and Vertical Sidewall Sprinklers provide an equally attractive _ _ I� ,
appearance when ceiling piping cannot be used. + L. .�
Beautifully versatile is the description for the Reliable 4 0 °;°
Model Fl Rec Designer glass bulb sprinkler. Re- `.., . '. -
cessing The Designer enhances its already low profile dec-
orative appearance, and facilitates a rapid and perfect Pendent Coverage Pendent
installation.
Model Fl Recessed Designer's escutcheon is highly ad- At normal temperatures, the glass bulb contains the fluid in
justable. The two piece construction makes field installation a both the liquid phase and in the vapor phase. The vapor
very easy and rapid task. This also allows ceiling panels to phase can be seen as a small bubble. As heat is applied, the
later be removed without shutting down the fire protection liquid expands forcing the bubble smaller and smaller as the
system, thus facilitating maintenance of above ceiling ser- liquid pressure increases. Continued heating forces the liq-
vices. uid to push out against the bulb, causing the glass to shatter,
The Designer Automatic Sprinkler utilizes a frangible opening the waterway and allowing the deflector to distribute
glass bulb. The glass bulb consists of an accurately con- the discharging water.
trolled amount of special fluid hermetically sealed inside of a The Fl Sprinkler temperature rating is identified by the
precisely manufactured glass capsule. This glass bulb is color of the glass bulb capsule as well as frame color where -
specially constructed to provide fast thermal response. applicable.
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552 . •
-Model Fl Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
t f :. : - . ...
fit' I It i
^` _..'� `
*fir.
Sao
�� ; ! ' ; r .
Upright . Pendent Conventional Upright (2)
•
Installa Data:
Nominal Sprinkler
•
Nominal Thread Sprinkler Approval identification
Orifice Size K Factor . Height Organization Numbers (SIN)
US I Metric Upright I Pendent
Standard - Upright (SSU) and Pendent (SSP) Deflectors Marked to Indicate Position
1/2" (15mm) //' NPT (R' /2) • 5.6 80 2.2" (56mm) 1,2,3,4,5,6,7 R1725 R1715
' %z' (20mm) 3 /4" NPT (R' /4) (') 8.0 115 2.3" (58mm) 1,2,3,4,7,8 R1722 R1712
1/2" (15mm)t 1 /2" NPT (R'h) 5.6 80 2.2" (56mm) 7 R1795 • R1705
' %2" (20mm)t 3 4" NPT (R 8.0 115 2.3" (58mm) 7 R1792 R1702
6" (11mm) h" NPT (R1/2) (2) 4.2 60 2.54" (65mm) 1,2,8 R1723 R1713
3A" (lomm) /z" NPT (R1/2) (2) (3) 2.8 40 2.54" (65mm) 1;2,8 R1721 R1711
lomm XLH R 3 %e 4.2 60 56.1mm 4,6,7 I R1724 R1714
Conventional - Install in Upright or Pendent Position
1Omm XLH R 3 /a 4.2 60 56.1mm — • I • R1774
15mm 'h" NPT (R1/2) 5.6 • 80 56.1mm 4,6,7 I R1775
20mm 3 /4" NPT (R 8.0 115 58.1mm 4,7 R1772
•
(') LPC Approval up 286 °F (141 °C)
(2) Small Orifice identified by a pintle extending beyond the deflector.
(3) FM Approval for SSU only, up to 200 °F (93 °C).
(4) VdS Approval for Intermediate Response 155 °F (68 °C) only.
2.
•
Model Fl Recessed Pendent Sprinkler .
Installation Wrench: Model RC1 Sprinkler Wrench
-- 2 Vs' NYS
(27.2"m/ .
Iniir VA
. (.9,2,aro/
•
• r r= st�--C�2i � rCUXFI
'' a rs 4 I J i' r n/ 4/2" a t2
[r �(?lr.. rEnm./
240/ MUM
v ( rai p i , • .• f * w h o , I, � n
v-7.i [�." ' _
1 — `ti �: .L. _.7 , i J6
l'93 i A i I2 t I
•
Fl Recessed I
vm• i
A (.x2"."/ 7• (•r
1171C01I 2 27/12' ON ..
(
•
(2) When installed directhj into a tee, the escutcheon dimension's
• adjustment will be reduced.
Installation Data:
Nominal Sprinkler
Nominal Thread K Factor Sprinkler Approval
Orifice Size Height Organizations Identification
US Metric Numbers (SIN)
," (15mm) Y" NPT (R);) 5.6 80 2.2" (56mm) .1,2,3 - R1715
1 7„," (20mm) r;" NPT (RX) 8.0 115 2.3" (58mm) 1,2,3 R1712
,Y," (15mm) y," NPT (RY,) 5.6 80 2.2" (56mm) 7 • R1705
," (20mm) Y," NPT (R3;) 8.0 115 2.3" (58mm) • 7 R1702 '
74: (11mm) (2) y," NPT (RY) 4.2 60 2.54" (65mm) . 1,2,8 • . R1713
X" (10mm) (21 7," NPT (R1/2) • 2.8 40 2.54" (65mm) 1,2,8 R1711
•
10mm R g 4.2 60 56.1mm 4 R1714
(11 FM Approval
• Light Hazard - No Limitations.
• Ordinary Hazard - Groups 1 & 2, Wet Systems only.
(2) Identified by a pintle extending beyond the deflector. .
(3) LPC Approval is XLH,' OH! and OH!! Occupancies only,
57 °C through 93 °C ratings.
(41 VdS Approval for Intermediate Response 155 °F (68 °C) only.
•
3. •
•
•
•
•
•
Model Fl Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent`
Approval Type:. Light Hazard Occupancy _ _. _ _ __ .__ _ . ___ ____ _ _
•
•
Vertical Sidewall
U.S. Patent No. 6,374,9201
Installation Data:
Nominal Sprinkler
Nominal Thread K Factor Sprinkler Approval
Orifice Size Height Organizations Identification
US Metric Numbers (SIN)
/ (15mm) y NPT(R/2 5.6 80 2.2" (56.1mm) 1,2,3,0 6,8 R1785
(') LPC Approval is pendent only, 57 °C through 93 °C ratings.
•
Sprinkler • Deflector to -
Type Ceiling Distance
(Min. - Max.) •
Upright 4 "(102mm) - 121305mm)
Pendent 4 "(102mm) - 12 "(305mm)
Model Fl Horizontal Sidewall Sprinkler
Deflector: HSW 1 _ • • Installation Wrench: Model D Sprinkler Wrench
Horizontal Sidewall
.Installation Data:
Nominal Approval Organizations PP 9 Sprinkler
Nominal Thread K Factor Sprinkler Identification
Orifice Size Length Light Ordinary Numbers (SIN)
US Metric Hazard Hazard
1/2" (15mm) 1/2" NPT (R'h) 5.6 80 2.63" (67mm) 1,2,3,5 12,5 R1735
Note: UL and ULC Listing permits use with Fl escutcheons, light hazard only.
4.
Model Fl Extended Coverage Pendent Sprinkler
• Deflector: EC Pendent
Installation Wrench: Model D Sprinkler Wrench r.-
• Approval Type: Extended Coverage - Light Hazard Occupancy ,-,;'
. Installation Data: . 1
Nominal Thread Nominal Sprinkler Approval T R�ure Sprinkler = ,
K Factor g _ Identification
Orifice Size US Metric Height Organizations °F °C Numbers (SIN) •
"r /,," (20mm) X" NPT (R /a) 8.0 115 2.2" (56mm) 1,2,8 135; 155 57; 68 R1742 Extended Coverage
y," (15mm) y," NPT (R'/) 5.6 80 2.2" (56mm) 1,2,8 135; 1551 57; 68 R1745 Pendent •
COVERAGE AREA
Pressure
Flow Rate Nominal Max. Area
Width x Length
K =8.0 (115) K =5.6 (80)
qpm Umin , psi bar psi bar ft. x ft. m x m
26 98.4 10.6 0,7 21.6 1,5 16 x 16 4.9 x 4.9
33 125.0 17.0 1,2 34.7 2,4 18 x 18 5.5 x 5.5
40 151.4 25.0 1,7 51.0 3,5 20 x 20 6.0 x 6.0
Model Fl Recessed Extended Coverage Pendent Sprinkler
Deflector: EC Pendent ,
. Installation Wrench: Model RC1 Sprinkler Wrench -, I I
Approval Type: Extended Coverage - Light Hazard Occupancy ( ° "'°/
p 1 I A/,0 . CM
(4o/
, � ' � - I ,• u• • 7 J (sx x l .ran)
11/8V COLLAR 1 1 X ,/7 REDUCER
WA TIGHT 1 (MATH, X 12.7.....')
• .rye! 7 1.1 I
•
.T,;.; " ` , . , :
is '.: J J / / %/ J ' J
1i JJ� uwsiu r 1'1 '�� (:ASl.n/
'
N . 7 • 12:7' J /. -
Extended Coverage . • A ot.,mmf
Recessed
IING 2A M 77 /I7 DA
(
. f" When installed directly into a tee, the escutcheon
dimension's adjustment will be reduced.
. Installation Data: •
Nominal Temperature Sprinkler
Nominal Thread K Factor Sprinkler Approval Rating Identification
Orifice Size US Metric Height Organizations °F °C ( )
Numbers SIN
" /,," (20mm) X" NPT (R3/4) 8.0 115 2.2" (56mm) 1,2,8 135; 155 57; 68 R1742
/," (15mm) I y," NPT (R'/z) 5.6 80 1 2.2" (56mm) 1,2,8 135; 155 57; 68 R1745
COVERAGE AREA
Pressure
Flow Rate Nominal Max. Area
Width x Length
K =8.0 (115) K =5.6 (80)
gpm , Umin psi bar psi bar ft. x ft. m x m
26 98.4 10.6 0,7 21.6 1,5 16 x 16 4.9 x 4.9 _
33 125.0 17.0 1,2 34.7 2,4 18 x 18 5.5 x 5.5
40 151.4 25.0 1,7 51.0 3,5 20 x 20 6.0 x 6.0
5.
Model Fl Extended Coverage Horizontal Sidewall Sprinkler
Deflector: EC -6
•
Glass Bulb: 3mm 155 °F (68 °C) Standard, Unless 5mm 135 °F (57 °C) is Specified
Installation D Sprinkler Wrench - -- - --- - - - - - - --
Approval Type: Extended Coverage — Light Hazard Occupancy
I Y
t � `C� 6ta�•:,
• I �f f7,q
Extended Coverage Horizontal Sidewall
Installation Data:
Temperature Sprinkler
Nominal Thread K Factor Sprinkler Approval Rating Identification
Orifice Size US Metric Height Organizations °F °C Numbers (SIN)
%2 (20mm) ?;" NPT (R' /.) 8.0 115.3 2.75" (70mm) 1,2,8 135 (5mm bulb) 57 155 (3mm bulb) 68 R1762
COVERAGE AREA
Max. Area Deflector to
Flow Rate Pressure Width x Length Ceiling Dimensions
(Min. - Max.)
gpm L/min psi bar ft. x ft. m x m .
36 136.3 20.3 1,4 16 x 22 4.9.x 6.7 4"(102mm) - 6 "(152mm)
39 147.6 23.8 1,6 16 x 24 4.9 x 7.3 4 "(102mm) - 6 "(152mm) •
6.
Model Fl Recessed Extended Coverage Horizontal Sidewall Sprinkler .
• Deflector: EC -6
Glass Bulb: 3mm 155 °F (68 °C) Only •
Installation Wrench: Model GFR1 Sprinkler Wrench
Approval - Type:Extended Coverage =Light Hazard - Occupancy " " • - • - "
1. •
, Nne - - -. ' /e• 1. 2.. +l
1.22161,74 I NI . 10 e
(IOt.em,,' t0 152.4.77ff+1
F ) \I 17.777N SWING COLOR
SAVOUR 117906:77
�._ .\,; ' ;IV IVIV
. '', it v./
T : i 1/4
. 722m„,
-,: -...,.. -
,+..,.,...-,i1-5;
, _, -71 .
W 4
Recessed Extended Coverage ] 1
L L
Horizontal Sidewall L,`
WA I A LE 1."J
2 I ' ow C beZ
(5724r1 f 0
i .J / IQ/UMW .
r 19. r,,,,,,/
"' When installed directly into a tee, the escutcheon dimension's
adjustment will be reduced.
Installation Data:
Temperature Sprinkler
Nominal Thread K Factor Sprinkler Approval Rating Identification
Orifice Size US Metric Height Organizations , eF oC Numbers (SIN)
'%32" (20mm) %" NPT (R 8.0 115.3 2.75" (70mm) 1,2,8 155 68 R1762
•
COVERAGE AREA
Max. Area Deflector to Ceiling
Flow Rate Pressure Width x Length Dimensions
(Min. - Max.)
gpm L/min psi bar ft. x ft. m x m
" 36 • • 136.3 . • 20.3 1,4 16 x 22 4.9 x 6.7 4 "(102mm) - 6 "(152mm)
39 147.6 23.8 1,6 16 x 24 4.9 x 7.3 4 "(102mm) - 6 "(152mm)
7.
•
Model Fl & Fl Recessed Sprinklers Maintenance
Application The Models Fl and Fl Recessed Sprinklers should •
Model Fl and Fl Recessed sprinklers are used in fixed be inspected quarterly and the sprinkler system main- •
fire protection systems: Wet, Dry, Deluge or Preaction. tained in accordance with NFPA 25. Do not clean sprin-
klers with soap and water,_ ammonia or any, other... . -
. Care - must - exercised - that - the-orifice-size, temperature-rat - cleaning fluid. Remove any sprinkler which has been
ing, deflector style and sprinkler type are in accordance painted (other than factory applied) or damaged in any
• with the latest published standards ofthe National Fire Pro- way. A stock of spare sprinklers should be maintained •
tection Association or the approving Authority Having to allow quick replacement of damaged or operated
Jurisdiction. sprinklers. Prior to installation, sprinklers should be
Installation maintained in the original cartons and packaging until •
Model F1 sprinklers are standard response sprinklers in- used to minimize the potential for damage to sprinklers
tended for installation as specified in NFPA 13. They must that would cause improper operation or non -operation.
also be installed with the Model D Sprinkler Wrench specifi-
. cally designed by Reliable for use with these sprinklers.
The Model Fl Recessed Sprinklers are to be installed Temperature Ratings
with a maximum recess of 3 /4 inch (19mm). The Model Fl Sprinkler Maximum Ambient
Escutcheon illustrated is the only recessed escutcheon to Classification Temperature Temperature Bulb
be used with the Model Fl Pendent and EC Sprinklers. The °F °c °F °C Color
use of any other recessed escutcheon will void all approv- Ordinary 135 57 100 38 Orange
als and negate all warranties. When installing Model Fl Re- Ordinary 155 68 100 38 Red
cessed Pendent, EC Pendent, and EC HSW Sprinklers, use Intermediate 175 79 150 66 Yellow
the Model GFR1 Sprinkler Wrench. Any other type of Intermediate 200 93 150 66 Green .
High 286 141 225 107 Blue
wrench may damage these sprinklers. Extra High (I) 360 182 300 149 Mauve •
Glass bulb sprinklers have orange covers to protect the
bulb during the installation process. REMOVE THIS PRO- "' Not Available For Fl Recessed
TECTION ONLY AFTER THE SYSTEM HAS BEEN HYDRO- Patents: U.S. Patent No. 6,374,920
• STATICALLY TESTED AND, WHEN APPLICABLE, THE Applies to Model Fl Vertical Sidewall Sprinklers.
• ESCUTCHEONS HAVE BEEN INSTALLED. RASCO .
wrenches are designed to install sprinklers when covers Finishes (t)
•
are in place.
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Chrome •
Ordering Information White Polyester Coated"' White Painted
Specify: Special Application Finishes
1. Sprinkler Model Sprinkler Escutcheon
2. Sprinkler Type Bright Brass'� , Bright Brass
Black Plated (6) Black Plated
3. Orifice Size Black Paint ° ' Black Paint.
4. Deflector Type Off White " Off White.
5. Temperature Rating: Satin Chrome Satin Chrome
P 9 Lead Plated ('
Specify Bulb Size when ordering Wax Coated 3 5j Wax Over Lead " " "
Model. Fl EC HSW Sprinkler.
6. Sprinkler Finish
( "Other colors and finishes are available on special order.
Consult factory for details.
7. Escutcheon Finish (where applicable) "' 200 °F (93 °C) maximum.
"' UL and ULC Listed, and NYC Approved Only.
. . .. - "' 155 °F to 200 °F (68 °C to 93 °C) ratings only.
(51 286°F (141 °C) Sprinklers may be coated for ambient conditions
not exceeding 150 °F (66 °C).
j8j LPC approved for 10mm and 15mm sprinklers only.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Proaucts manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. Rel (800) 431-1588 Sales Offices ® e d aa
(800) 848-6051 Sales Fax Revision lines indicate updated or new data.
(914) 668 -3470 Corporate Offices
www. reIiablesprinkler.com Internet Address EG printed in USA. 12/03 P/N 9999970011