Loading...
Specifications /59/ 2 6 v/ 72. Ql Xv-e ,B /7 sa-u4 az, V ? X .- Bulletin 110 Rev.S Model G co cp . ° ® Automatic Sprinklers Spray Upright . H e1rn'le — -Spray- Pendent - -- . - - -- - - - -- ° - .. IRECE1 . I V A nd Conventional (',1T4 V I ON . Product Description 111G C The Reliable Model G Automatic Sprinkler utilizes the center strut solder in compression principle of :^'- -_ construction. The fusible alloy is captured in the •, , cylinder of the solder capsule by a stainless steel ball. 'a ~ T, When the fusible alloy melts, the ball moves into the - cylinder allowing the cylinder to fall away from the , Y ); sprinkler. When this happens, the lever is released to ,JI Jim. i spring free from the sprinkler so that all of the operating . ti. Pasc parts clear from the waterway allowing the deflector to '_ -; ; . distribute the discharging water. _ _ • _ Except for the parts in the cylinder as mentioned above, the sprinkler components are made from Upright . Pendent copper based alloys for maximum corrosion • protection. Lead plated, wax coated or wax over lead plated sprinklers are available for specially severe I environments. Chrome plated sprinklers are available i '�� ` , . for decorative purposes. ? i, • • All sprinklers are individually hydrostatically tested. ' ! ? r >, All sprinklers are identified as to their fusing point by ', ��! markings that appear on several of the operating parts r 1 G: : -. ,.. and by an identifying color that appears on the frame. ` Sprinkler Types Standard Upright - This deflector configuration is Small Orifice Upright Conventional normally used with exposed piping installations. Water is distributed laterally and downward in a wide pattern approximating a hemisphere which is completely. and uniformly filled with water in the form of small drops or spray. • Standard Pendent - This deflector configuration is Application and Installation normally used where the space above the piping is Standard sprinklers are used in fixed fire protection I limited or where a concealed piping installation is systems: Wet, Dry, Deluge or Preaction. Care must be employed. The discharge characteristics of the exercised that the orifice sizes, temperature ratings, standard pendent are virtually identical to the deflector styles and sprinkler spacings are in standard upright as described above. accordance with the latest published standards of the • National Fire Protection Association or the approving • Large and Small Orifice —By varying the orifice size, authority having jurisdiction. a large or small orifice sprinkler is created that will The sprinklers must be installed with the Reliable distribute as much as 40% more water or 65% less Model D Sprinkler Wrench. Any other type of wrench water than the normal 1/2" (15mm) orifice sprinkler. may damage the sprinkler. The approvals or listings of Reliable Automatic Conventional —This deflector configuration is used Sprinklers by major approving organizations are primarily in those countries where the LPC installation shown in the tabulated list provided on the back of this rules have precedence. The sprinkler is designed to bulletin. distribute a portion of its water discharge upward against the ceiling with the balance downward. It may be installed in either the upright or the pendent position. Sprinklers with conventional deflectors are available with orifice sizes corresponding to light, .Patent No. 4,440,234 ordinary and extra -high hazard installations. • The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552 • Technical Data • "K" Factor Sprinkler Identification Sprinkler Number (SIN) • Sprinkler Type US Metric Height Approvals SSU SSP • Standard= Upright (SSU) and Pendent (SSP) -- — --- —. — - -- -- - — - --- - - -- -- — -- Deflectors Marked to Indicate Position / (15 mm) Standard Orifice with y" NPT (R/ Thread 5.62 81.0 2 Ye" (73 mm) 1, 2, 3, 4, 5, 6, 7 R1025 R1015 %' (11 mm) Small Orifice with y" NPT (Ry) Thread 4.24 61.0 2 Yee" (73 mm) 1, 3, 7 R1023 R1013 B" (10 mm) Small Orifice with y" NPT (Ry) Thread 2.82 40.6 2 Ye" (73 mm) 1, 2, 3, 7 R1021 R1011 X,3" (8 mm) Small Orifice with y" NPT (R}2) Thread 1.98 28.5 2 Ye" (73 mm) 1, 3, 7 R1022 R1012 ' %z' (20 mm) Large Orifice with y" NPT (Ry) Thread 7.96 114.7 2 Ye" (73 mm) 1, 2, 3, 7 R1026 R1016 '332 (20 mm) Large Orifice with 3;" NPT (RX)Thread 8.20 118.2 2'3 e" (75 mm) 1, 2, 3, 7 R1027 R1017 20 mm XHH with 20 mm Thread 8.20 118.2 75.4 mm 4, 5, 6 R1027 R1017 10 mm XLH with 10 mm Thread 4.10 59.1 73 mm 4, 5, 6 R1024 R1014 Conventional—Installed in Upright or Pendent Position 10mm XLH with 10mm Thread 4.10 59.1 73 mm 5 R1074 15mm Standard Orifice with (Ry) Thread 5.62 81.0 73 mm 4, 5, 6 R1075 20mm XHH with (R3;) Thread 8.20 118.2 75.4 mm 4, 5 R1077 . Temperature Ratings Maintenance Maximum Model G Sprinklers should be inspected quarterly and the Sprinkler Ambient sprinkler system maintained in accordance with NFPA 25. Do Rating Temperature Frame ('), not clean sprinklers with soap and water, ammonia or any other Classification °F °C °F 1 °C Color cleaning fluids. Remove any sprinkler that has been painted Ordinary 135 57 100 38 Black (other than factory applied) or damaged in any way. A stock of Ordinary 165 74 100 38 Uncolored spare sprinklers should be maintained to allow quick replace - Intermediate 212 100 150 66 White ment of damaged or operated 'sprinklers. Prior to installation, High 286 141 225 107 Blue sprinklers should be maintained in the original cartons and . - packaging until used to minimize the potential for damage to I Frame color does not apply to painted or plated sprinklers sprinklers that would cause improper operation or -Use sprinkler rating as identified on operating parts. non -operation. Use only the Model D Sprinkler Wrench for sprinkler removal and installation. Any other type of wrench may damage the sprinkler. Finishes Standard Finishes Approval Organizations Bronze —All Temperature Ratings 1. Underwriters Laboratories, Inc. Chronw —All Temperature Ratings 2. Factory Mutual Research Corporation White ( —All Temperature Ratings . 3. Underwriters' Laboratories of Canada Only Frame and Deflector are Painted 4. Loss Prevention Council Special Application Finishes 5. Pleniere Assemblee Bright Brass Plated —Only frame, deflector and cap are plated. 135 °F (57 °C), 165 °F 6. VdS S BS&A No. 5 8 rig g (74°C), N.Y.C. MEA ), 212 °F (100°C) Temp. Rating. 7. N 7-75—SA or • N.Y.C. MEA 258-93-E 93 3-- E . Black Plated —Only frame, deflector and cap are plated. All Temp. Ratings. • Polyester Coated (2) —Only frame and deflector are coated: Lead Plated —165 °F (74 °C), 212 °F (100 °C) and 286 °F (141 °C) Temp. Ratings. Ordering Information Wax- Coated (3) —165 °F (74 °C) Clear Wax, 212 °F (100 °C) Brown Wax. Specify Wax- Coated Over 1. Model G l Lead Plated (3) —165 °F (74 °C) Clear Wax, 212 °F (100 °C) Brown Wax. 2. Deflector • Upright (l) Other colors and finishes are available. Consult factory for details. • Pendent (2) UL listed and NYC MEA Approved only. • Conventional (3) 212 °F (100 °C) brown wax may be used on 286 °F (141 °C) 3. Nominal Orifice sprinklers when maximum ambient temperatures do not exceed 150 °F 4. Inlet Thread (66 °C). UL Listed, FM Approved, NYC MEA 258 -93 -E. 5. Temperature Rating 6. Finish The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association. Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 80 years. and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States. Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co., Inc. Re l i a b i e (800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 668 - 3470 Corporate Offices Revision lines indicate updated or new data. www.reliablesprinkler.com I nternet Address EG.PrinetlinUSA not P/N 9939970005 • • 0x' 5 —ar- 9�f • Bulletin 117Rev.Q • !tellable ® Model Fl RECEIVED Model F1 Recessed 2 6 ;05 _ _ Standard Res o Sprinklers `p CITY OFTI M } • o o, Hopi The Designer Model Fl Sprinkler -:,•_: :- • Standard Upright .u. Standard Pendent th, , Extended Coverage Pendent ` -. Conventional Vertical Sidewall Horizontal Sidewall Upright Pendent - HSW 1 Deflector - Horizontal Sidewall Extended Coverage k - EC-6 Deflector t , ! a ti The D Model Fl Recessed Sprinkler ' t - ir Recessed Pendent ' ' . ; Recessed Extended Coverage Pendent t . • Recessed Extended Coverage Horizontal Sidewal Vertical Sidewall Conventional Approval Organizations • 1. Underwriters Laboratories Inc. s :;-----1?---- - � , - , rt 2. Underwriters' Laboratories of Canada f A , I'Sr r` t 3. Factory Mutual Research Corp. 4. Loss Prevention Council �' 5. NYC BS &A No. 587 -75 -SA Horizontal Sidewall Recessed Pendent 6. Pleniere Assemblee 7. Verband der Schadenversicherer 8. NYC MEA 258 -93 -E r ',' '5l' UL Listing Category vj ,, Sprinklers, Automatic & Open (VNIV) ► • Product Description Extended Coverage Recessed Extended The Fl Glass Bulb Sprinkler combines the durability of a Horizontal Sidewall . Coverage Horizontal standard sprinkler with the attractive low profile of a decora- Sidewall tive sprinkler. Whether installed on exposed piping or in an office ceiling, it is functional and attractive. The Horizontal ., = • � and Vertical Sidewall Sprinklers provide an equally attractive _ _ I� , appearance when ceiling piping cannot be used. + L. .� Beautifully versatile is the description for the Reliable 4 0 °;° Model Fl Rec Designer glass bulb sprinkler. Re- `.., . '. - cessing The Designer enhances its already low profile dec- orative appearance, and facilitates a rapid and perfect Pendent Coverage Pendent installation. Model Fl Recessed Designer's escutcheon is highly ad- At normal temperatures, the glass bulb contains the fluid in justable. The two piece construction makes field installation a both the liquid phase and in the vapor phase. The vapor very easy and rapid task. This also allows ceiling panels to phase can be seen as a small bubble. As heat is applied, the later be removed without shutting down the fire protection liquid expands forcing the bubble smaller and smaller as the system, thus facilitating maintenance of above ceiling ser- liquid pressure increases. Continued heating forces the liq- vices. uid to push out against the bulb, causing the glass to shatter, The Designer Automatic Sprinkler utilizes a frangible opening the waterway and allowing the deflector to distribute glass bulb. The glass bulb consists of an accurately con- the discharging water. trolled amount of special fluid hermetically sealed inside of a The Fl Sprinkler temperature rating is identified by the precisely manufactured glass capsule. This glass bulb is color of the glass bulb capsule as well as frame color where - specially constructed to provide fast thermal response. applicable. The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552 . • -Model Fl Upright, Pendent & Conventional Sprinklers Installation Wrench: Model D Sprinkler Wrench t f :. : - . ... fit' I It i ^` _..'� ` *fir. Sao �� ; ! ' ; r . Upright . Pendent Conventional Upright (2) • Installa Data: Nominal Sprinkler • Nominal Thread Sprinkler Approval identification Orifice Size K Factor . Height Organization Numbers (SIN) US I Metric Upright I Pendent Standard - Upright (SSU) and Pendent (SSP) Deflectors Marked to Indicate Position 1/2" (15mm) //' NPT (R' /2) • 5.6 80 2.2" (56mm) 1,2,3,4,5,6,7 R1725 R1715 ' %z' (20mm) 3 /4" NPT (R' /4) (') 8.0 115 2.3" (58mm) 1,2,3,4,7,8 R1722 R1712 1/2" (15mm)t 1 /2" NPT (R'h) 5.6 80 2.2" (56mm) 7 R1795 • R1705 ' %2" (20mm)t 3 4" NPT (R 8.0 115 2.3" (58mm) 7 R1792 R1702 6" (11mm) h" NPT (R1/2) (2) 4.2 60 2.54" (65mm) 1,2,8 R1723 R1713 3A" (lomm) /z" NPT (R1/2) (2) (3) 2.8 40 2.54" (65mm) 1;2,8 R1721 R1711 lomm XLH R 3 %e 4.2 60 56.1mm 4,6,7 I R1724 R1714 Conventional - Install in Upright or Pendent Position 1Omm XLH R 3 /a 4.2 60 56.1mm — • I • R1774 15mm 'h" NPT (R1/2) 5.6 • 80 56.1mm 4,6,7 I R1775 20mm 3 /4" NPT (R 8.0 115 58.1mm 4,7 R1772 • (') LPC Approval up 286 °F (141 °C) (2) Small Orifice identified by a pintle extending beyond the deflector. (3) FM Approval for SSU only, up to 200 °F (93 °C). (4) VdS Approval for Intermediate Response 155 °F (68 °C) only. 2. • Model Fl Recessed Pendent Sprinkler . Installation Wrench: Model RC1 Sprinkler Wrench -- 2 Vs' NYS (27.2"m/ . Iniir VA . (.9,2,aro/ • • r r= st�--C�2i � rCUXFI '' a rs 4 I J i' r n/ 4/2" a t2 [r �(?lr.. rEnm./ 240/ MUM v ( rai p i , • .• f * w h o , I, � n v-7.i [�." ' _ 1 — `ti �: .L. _.7 , i J6 l'93 i A i I2 t I • Fl Recessed I vm• i A (.x2"."/ 7• (•r 1171C01I 2 27/12' ON .. ( • (2) When installed directhj into a tee, the escutcheon dimension's • adjustment will be reduced. Installation Data: Nominal Sprinkler Nominal Thread K Factor Sprinkler Approval Orifice Size Height Organizations Identification US Metric Numbers (SIN) ," (15mm) Y" NPT (R);) 5.6 80 2.2" (56mm) .1,2,3 - R1715 1 7„," (20mm) r;" NPT (RX) 8.0 115 2.3" (58mm) 1,2,3 R1712 ,Y," (15mm) y," NPT (RY,) 5.6 80 2.2" (56mm) 7 • R1705 ," (20mm) Y," NPT (R3;) 8.0 115 2.3" (58mm) • 7 R1702 ' 74: (11mm) (2) y," NPT (RY) 4.2 60 2.54" (65mm) . 1,2,8 • . R1713 X" (10mm) (21 7," NPT (R1/2) • 2.8 40 2.54" (65mm) 1,2,8 R1711 • 10mm R g 4.2 60 56.1mm 4 R1714 (11 FM Approval • Light Hazard - No Limitations. • Ordinary Hazard - Groups 1 & 2, Wet Systems only. (2) Identified by a pintle extending beyond the deflector. . (3) LPC Approval is XLH,' OH! and OH!! Occupancies only, 57 °C through 93 °C ratings. (41 VdS Approval for Intermediate Response 155 °F (68 °C) only. • 3. • • • • • • Model Fl Vertical Sidewall Sprinkler Installation Wrench: Model D Sprinkler Wrench Installation Position: Upright or Pendent` Approval Type:. Light Hazard Occupancy _ _. _ _ __ .__ _ . ___ ____ _ _ • • Vertical Sidewall U.S. Patent No. 6,374,9201 Installation Data: Nominal Sprinkler Nominal Thread K Factor Sprinkler Approval Orifice Size Height Organizations Identification US Metric Numbers (SIN) / (15mm) y NPT(R/2 5.6 80 2.2" (56.1mm) 1,2,3,0 6,8 R1785 (') LPC Approval is pendent only, 57 °C through 93 °C ratings. • Sprinkler • Deflector to - Type Ceiling Distance (Min. - Max.) • Upright 4 "(102mm) - 121305mm) Pendent 4 "(102mm) - 12 "(305mm) Model Fl Horizontal Sidewall Sprinkler Deflector: HSW 1 _ • • Installation Wrench: Model D Sprinkler Wrench Horizontal Sidewall .Installation Data: Nominal Approval Organizations PP 9 Sprinkler Nominal Thread K Factor Sprinkler Identification Orifice Size Length Light Ordinary Numbers (SIN) US Metric Hazard Hazard 1/2" (15mm) 1/2" NPT (R'h) 5.6 80 2.63" (67mm) 1,2,3,5 12,5 R1735 Note: UL and ULC Listing permits use with Fl escutcheons, light hazard only. 4. Model Fl Extended Coverage Pendent Sprinkler • Deflector: EC Pendent Installation Wrench: Model D Sprinkler Wrench r.- • Approval Type: Extended Coverage - Light Hazard Occupancy ,-,;' . Installation Data: . 1 Nominal Thread Nominal Sprinkler Approval T R�ure Sprinkler = , K Factor g _ Identification Orifice Size US Metric Height Organizations °F °C Numbers (SIN) • "r /,," (20mm) X" NPT (R /a) 8.0 115 2.2" (56mm) 1,2,8 135; 155 57; 68 R1742 Extended Coverage y," (15mm) y," NPT (R'/) 5.6 80 2.2" (56mm) 1,2,8 135; 1551 57; 68 R1745 Pendent • COVERAGE AREA Pressure Flow Rate Nominal Max. Area Width x Length K =8.0 (115) K =5.6 (80) qpm Umin , psi bar psi bar ft. x ft. m x m 26 98.4 10.6 0,7 21.6 1,5 16 x 16 4.9 x 4.9 33 125.0 17.0 1,2 34.7 2,4 18 x 18 5.5 x 5.5 40 151.4 25.0 1,7 51.0 3,5 20 x 20 6.0 x 6.0 Model Fl Recessed Extended Coverage Pendent Sprinkler Deflector: EC Pendent , . Installation Wrench: Model RC1 Sprinkler Wrench -, I I Approval Type: Extended Coverage - Light Hazard Occupancy ( ° "'°/ p 1 I A/,0 . CM (4o/ , � ' � - I ,• u• • 7 J (sx x l .ran) 11/8V COLLAR 1 1 X ,/7 REDUCER WA TIGHT 1 (MATH, X 12.7.....') • .rye! 7 1.1 I • .T,;.; " ` , . , : is '.: J J / / %/ J ' J 1i JJ� uwsiu r 1'1 '�� (:ASl.n/ ' N . 7 • 12:7' J /. - Extended Coverage . • A ot.,mmf Recessed IING 2A M 77 /I7 DA ( . f" When installed directly into a tee, the escutcheon dimension's adjustment will be reduced. . Installation Data: • Nominal Temperature Sprinkler Nominal Thread K Factor Sprinkler Approval Rating Identification Orifice Size US Metric Height Organizations °F °C ( ) Numbers SIN " /,," (20mm) X" NPT (R3/4) 8.0 115 2.2" (56mm) 1,2,8 135; 155 57; 68 R1742 /," (15mm) I y," NPT (R'/z) 5.6 80 1 2.2" (56mm) 1,2,8 135; 155 57; 68 R1745 COVERAGE AREA Pressure Flow Rate Nominal Max. Area Width x Length K =8.0 (115) K =5.6 (80) gpm , Umin psi bar psi bar ft. x ft. m x m 26 98.4 10.6 0,7 21.6 1,5 16 x 16 4.9 x 4.9 _ 33 125.0 17.0 1,2 34.7 2,4 18 x 18 5.5 x 5.5 40 151.4 25.0 1,7 51.0 3,5 20 x 20 6.0 x 6.0 5. Model Fl Extended Coverage Horizontal Sidewall Sprinkler Deflector: EC -6 • Glass Bulb: 3mm 155 °F (68 °C) Standard, Unless 5mm 135 °F (57 °C) is Specified Installation D Sprinkler Wrench - -- - --- - - - - - - -- Approval Type: Extended Coverage — Light Hazard Occupancy I Y t � `C� 6ta�•:, • I �f f7,q Extended Coverage Horizontal Sidewall Installation Data: Temperature Sprinkler Nominal Thread K Factor Sprinkler Approval Rating Identification Orifice Size US Metric Height Organizations °F °C Numbers (SIN) %2 (20mm) ?;" NPT (R' /.) 8.0 115.3 2.75" (70mm) 1,2,8 135 (5mm bulb) 57 155 (3mm bulb) 68 R1762 COVERAGE AREA Max. Area Deflector to Flow Rate Pressure Width x Length Ceiling Dimensions (Min. - Max.) gpm L/min psi bar ft. x ft. m x m . 36 136.3 20.3 1,4 16 x 22 4.9.x 6.7 4"(102mm) - 6 "(152mm) 39 147.6 23.8 1,6 16 x 24 4.9 x 7.3 4 "(102mm) - 6 "(152mm) • 6. Model Fl Recessed Extended Coverage Horizontal Sidewall Sprinkler . • Deflector: EC -6 Glass Bulb: 3mm 155 °F (68 °C) Only • Installation Wrench: Model GFR1 Sprinkler Wrench Approval - Type:Extended Coverage =Light Hazard - Occupancy " " • - • - " 1. • , Nne - - -. ' /e• 1. 2.. +l 1.22161,74 I NI . 10 e (IOt.em,,' t0 152.4.77ff+1 F ) \I 17.777N SWING COLOR SAVOUR 117906:77 �._ .\,; ' ;IV IVIV . '', it v./ T : i 1/4 . 722m„, -,: -...,.. - ,+..,.,...-,i1-5; , _, -71 . W 4 Recessed Extended Coverage ] 1 L L Horizontal Sidewall L,` WA I A LE 1."J 2 I ' ow C beZ (5724r1 f 0 i .J / IQ/UMW . r 19. r,,,,,,/ "' When installed directly into a tee, the escutcheon dimension's adjustment will be reduced. Installation Data: Temperature Sprinkler Nominal Thread K Factor Sprinkler Approval Rating Identification Orifice Size US Metric Height Organizations , eF oC Numbers (SIN) '%32" (20mm) %" NPT (R 8.0 115.3 2.75" (70mm) 1,2,8 155 68 R1762 • COVERAGE AREA Max. Area Deflector to Ceiling Flow Rate Pressure Width x Length Dimensions (Min. - Max.) gpm L/min psi bar ft. x ft. m x m " 36 • • 136.3 . • 20.3 1,4 16 x 22 4.9 x 6.7 4 "(102mm) - 6 "(152mm) 39 147.6 23.8 1,6 16 x 24 4.9 x 7.3 4 "(102mm) - 6 "(152mm) 7. • Model Fl & Fl Recessed Sprinklers Maintenance Application The Models Fl and Fl Recessed Sprinklers should • Model Fl and Fl Recessed sprinklers are used in fixed be inspected quarterly and the sprinkler system main- • fire protection systems: Wet, Dry, Deluge or Preaction. tained in accordance with NFPA 25. Do not clean sprin- klers with soap and water,_ ammonia or any, other... . - . Care - must - exercised - that - the-orifice-size, temperature-rat - cleaning fluid. Remove any sprinkler which has been ing, deflector style and sprinkler type are in accordance painted (other than factory applied) or damaged in any • with the latest published standards ofthe National Fire Pro- way. A stock of spare sprinklers should be maintained • tection Association or the approving Authority Having to allow quick replacement of damaged or operated Jurisdiction. sprinklers. Prior to installation, sprinklers should be Installation maintained in the original cartons and packaging until • Model F1 sprinklers are standard response sprinklers in- used to minimize the potential for damage to sprinklers tended for installation as specified in NFPA 13. They must that would cause improper operation or non -operation. also be installed with the Model D Sprinkler Wrench specifi- . cally designed by Reliable for use with these sprinklers. The Model Fl Recessed Sprinklers are to be installed Temperature Ratings with a maximum recess of 3 /4 inch (19mm). The Model Fl Sprinkler Maximum Ambient Escutcheon illustrated is the only recessed escutcheon to Classification Temperature Temperature Bulb be used with the Model Fl Pendent and EC Sprinklers. The °F °c °F °C Color use of any other recessed escutcheon will void all approv- Ordinary 135 57 100 38 Orange als and negate all warranties. When installing Model Fl Re- Ordinary 155 68 100 38 Red cessed Pendent, EC Pendent, and EC HSW Sprinklers, use Intermediate 175 79 150 66 Yellow the Model GFR1 Sprinkler Wrench. Any other type of Intermediate 200 93 150 66 Green . High 286 141 225 107 Blue wrench may damage these sprinklers. Extra High (I) 360 182 300 149 Mauve • Glass bulb sprinklers have orange covers to protect the bulb during the installation process. REMOVE THIS PRO- "' Not Available For Fl Recessed TECTION ONLY AFTER THE SYSTEM HAS BEEN HYDRO- Patents: U.S. Patent No. 6,374,920 • STATICALLY TESTED AND, WHEN APPLICABLE, THE Applies to Model Fl Vertical Sidewall Sprinklers. • ESCUTCHEONS HAVE BEEN INSTALLED. RASCO . wrenches are designed to install sprinklers when covers Finishes (t) • are in place. Standard Finishes Sprinkler Escutcheon Bronze Brass Chrome Chrome • Ordering Information White Polyester Coated"' White Painted Specify: Special Application Finishes 1. Sprinkler Model Sprinkler Escutcheon 2. Sprinkler Type Bright Brass'� , Bright Brass Black Plated (6) Black Plated 3. Orifice Size Black Paint ° ' Black Paint. 4. Deflector Type Off White " Off White. 5. Temperature Rating: Satin Chrome Satin Chrome P 9 Lead Plated (' Specify Bulb Size when ordering Wax Coated 3 5j Wax Over Lead " " " Model. Fl EC HSW Sprinkler. 6. Sprinkler Finish ( "Other colors and finishes are available on special order. Consult factory for details. 7. Escutcheon Finish (where applicable) "' 200 °F (93 °C) maximum. "' UL and ULC Listed, and NYC Approved Only. . . .. - "' 155 °F to 200 °F (68 °C to 93 °C) ratings only. (51 286°F (141 °C) Sprinklers may be coated for ambient conditions not exceeding 150 °F (66 °C). j8j LPC approved for 10mm and 15mm sprinklers only. The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Proaucts manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries Manufactured by The Reliable Automatic Sprinkler Co., Inc. Rel (800) 431-1588 Sales Offices ® e d aa (800) 848-6051 Sales Fax Revision lines indicate updated or new data. (914) 668 -3470 Corporate Offices www. reIiablesprinkler.com Internet Address EG printed in USA. 12/03 P/N 9999970011