Series RFII — 5.6 K- factor
"Royal Flush II" Pendent Concealed Sprinklers
Quick & Standard Response, Standard Coverage
General Cap. The Protective Cap is temporarily
removed for installation, and then it
can be replaced to help protect the oft
Description sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro -
The Series RFII Quick Response tective Cap can also be used to mark
(3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas-
mm bulb), 5.6 K- Factor, "Royal Flush ter board, ceiling tiles, etc. by gently v.-°
II" Concealed Pendent Sprinklers are pushing the ceiling product against the
decorative sprinklers featuring a flat Protective Cap. When the ceiling in- — �_�
cover plate designed to conceal the stallation is complete the Protective
sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate
tecturally sensitive areas such as hotel Assembly installed.
lobbies, office buildings, churches, As an option, the Series RFII Standard
and restaurants. Response (5 mm bulb) "Royal Flush II"
Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be
sembly that conceals the sprinkler op- fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175
erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM.
The separable two -piece design of the intended for sensitive areas where it is
Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical
blies allows installation of the sprin- through the cover plate from the area
klers and pressure testing of the fire above the ceiling. Data
protection system prior to installation WARNINGS
of a suspended ceiling or application The Series RFII Concealed Pendent Approvals for Series RFII
' of the finish coating to a fixed ceiling. PP
They also permit removal of sus Sprinklers described herein must be UL and C -UL Listed. FM Approved.
pended ceiling panels for access to installed and maintained in compli- NYC under MEA 353 -01 -E. LPCB (Ref.
building service equipment without ance with this document, as well as No. 094a/09 for TY3551 & 094a/10 for
having to first shut down the fire pro wi the applicable standards of the TY3531) Approved.
tection system and remove sprinklers. N a t ion al F Protection Association, The approvals apply only to the serv-
Also, the separable two -piece design i addition to the standards of any ice conditions indicated in the Design
f the the Sprinkler wo-pe e other authorities having jurisdiction. Criteria section and maximum pres-
inch the th mm) of vertical provides for ign for adjustment, 2 Failure to do so may impair the per- sure ratings indicated in the
formance of these devices. Model/Sprinkler Identification Num-
to reduce the accuracy to which the res The owner is onsible for maintain- bers section.
length of fixed pipe drops to the sprin- p
klers must be cut. ing their fire protection system and de- Approvals for Air & Dust Seal
vices in proper operating condition. Part #10908100
The Series RFII Sprinklers are The installing contractor or sprinkler U L and C -UL Lis for use with the
shipped with a Disposable Protective manufacturer should be contacted RFII (TY3551 & TY3504) Standard Re-
with any questions. sponse Concealed Sprinkler.
IMPORTANT Temperature Ratings
Always refer to Technical Data Model /Sprinkler 155F/68C Sprinkler - 135F/57C Plate
Sheet TFP700 for the "INSTALLER 200F/93C Sprinkler - 165F/74C Plate
WARNING" that provides cautions Identification Discharge Coefficient
with respect to handling and instal- K = 5.6 GPM /psi / (80,6 LPM/bar /2 )
lation of sprinkler systems and corn- Numbers Adjustment
ponents. Improper handling and in- 1/2 inch (12,7 mm)
' stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm Finishes
a sprinkler system or its compo- bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass
nents and cause the sprinkler to fail UL, C -UL, FM, LPCB and NYC.
to operate in a fire situation or cause TY3504 (5 mm bulb) & TY3505 (3 mm Plated, or White Painted (Custom paint
it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by matches and colors other than white
are available on request.)
Page 1 of 4 JULY, 2004 TFP181
J _
Page 2 of 4 TFP181
Physical Characteristics 1/2• NPT t SEALING
Frame Bronze ASSEMBLY
- -- • — Support - Cup — Chrome Plated - Steel -- — - - -- / f - -- - •
Guide Pins Stainless Steel 4 1
. Deflector Bronze FRAME __ ` ` L
Compression Screw Brass i� % j 1 � �� - - CAP
Bulb Glass I '
�{+
Cap Bronze or Copper SUPPORT I' �l
Sealing Assembly CUP WITH BULB
Beryllium Nickel w/Teflon' ROLL FORMED ;
THREADS
Cover Plate Brass c _ I II
Retainer Brass s _ COMPRESSION
Ejection Spring . . . . Stainless Steel ,
GUIDE 1 f � u , � �
, / SCREW
Patents PINS (2) v
3
U.S.A. 4,014,388 � �/
I _
DEFLECTOR
(DROPPED
Operation DEFLECTOR 1 J
C7-;=._ l i ` r POSITION)
When exposed to heat from a fire, the 1 SPRINKLER/SUPPORT CUP
Cover Plate,. which is normally sol- I ASSEMBLY
dered to the Retainer at three points, •
falls away to expose the Sprinkler As- THREAD INTO I . RETAINER
SUPPORT CUP I WITH THREAD
sembly. At this point the Deflector sup- UNTIL MOUNTING ` 0 O � ` DIMPLES
ported by the Guide Pins drops down SURFACE IS
tO its operational position. FLUSH WITH • EJECTION
The glass Bulb contains a fluid that • CEILING SPRING
expands when exposed to heat. When
the rated temperature is reached, the •
fluid expands sufficiently to shatter the — ,.
glass Bulb, activating the sprinkler and
allowing water to flow. SOLDER COVER
TABS (3) COVER PLATE/RETAINER PLATE
Design ASSEMBLY
esi n
. FIGURE 1
Criteria SERIES RFII CONCEALED SPRINKLER
ASSEMBLY
The RFII (TY3551 & TY3504), 5 mm .
Bulb Type, Concealed Pendent Sprin- Step 1; The sprinkler must only be
klers are UL and C -UL Listed as stand- Installation installed in the pendent position and
and response - standard spray sprin- with the centerline of the sprinkler per-
klers for use in accordance with the The Series RFII must be installed in pendicular hi the mounting surface.
• current NFPA standard. They are FM accordance with the following instruc- Step 2. Remove the Protective Cap.
Approved as standard response - tions:
standard spray sprinklers for use in NOTES . Step 3. With pipe thread sealant ap-
accordance with the current FM Loss D not install any bulb type sprinkler if plied to the pipe threads, hand tighten
Prevention Data Sheets. Y tyP r
p the sprinkler into the sprinkler fitting.
The RFII (TY3531 & TY3505) ,3 mm the bulb is cracked or there is a loss of Step 4. Wrench tighten the sprinkler
Th T Concealed Pendent 3 rim liquid from the bulb: With the sprinkler using only the RFII Sprinkler Wrench
YP P held horizontally, a small air bubble
klers are UL and C -UL Listed as quick should be present. The diameter of the (Ref. Figure 3). The RFII Sprinkler
response - standard spray sprinklers air bubble is approximately 1/16 inch Wrench i s to be applied to the Sprin-
for use in accordance with the current kler as shown in Figure 3.
(1,6 mm) for the 155 °F /68 °C and 3/32
NFPA standard. They are FM Ap- inch (2,4 mm) for the 200 °F /93 °C tem- Step 5. Replace the Protective Cap
proved as standard response - stand- perature ratings. (Ref. Figure 4) by pushing it upwards
and spray sprinklers for use in accord- until it bottoms out against the Support
ante with the current FM Loss A leak tight 1/2 inch NPT sprinkler joint Cup. The Protective Cap helps prevent
Prevention Data Sheets. should be obtained with a torque of 7 damage to the Deflector and Arms dur-
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
The Series RFII Concealed Pendent ing ceiling installation and /or during
Sprinkle Seri s are onl listed and a - mum of 21 ft.lbs. (28,5 Nm) of torque application of the finish coating of the
nw the Series RFD Concealed is to be used to install sprinklers. g. It may also be used to locate
Higher levels of torque. may distort the ceiling.
Cover Plates having a metallic or white sprinkler inlet with consequent leak- the center of the clearance hole by
painted finish. age or impairment of the sprinkler. gently pushing the ceiling material up
against the center point of the Protec-
• The Series RFII must not be used in Do not attempt to compensate for in- Live Cap.
P
applications where the air pressure sufficient adjustment in the Sprinkler
above the ceiling is greater than that Assembly by under- or over - tightening • NOTE
below. Down drafts through the Sup- the Sprinkler /Support Cup Assembly. A.s long as the Protective Cap remains
• port Cup could delay sprinkler opera- Readjust the position of the sprinkler in place, the system is considered to
tion in a fire situation. fitting to suit. be "Out of Service ".
• Registered Trademark of DuPont
' TFP181 Page 3 of 4
FACE OF CLEARANCE HOLE CLEARANCE
`SPRINKLER DIAMETER - HOLE
— - - - -- \ -- FITTING - -- -- - - - - - i DIMENSION C j -- -- -- - - -- — — -
J ►=_i
• SPRINKLER
SUPPORT CUP ,
ASSEMBLY \ ii ! I; 1/2° (12,7 mm) THREADED D ADJUSTMENT
FACE OF CEILING 4
RETAINING RING I ' FIGURE 4
MOUNTING DISPOSABLE PROTECTIVE CAP
SURFACE
I ll
\ / I \ S tep 6. After the ceiling has been com-
pleted with the 2 -1/2 inch (63,5 mm)
-- • 1 diameter clearance hole and in prepa-
Y ration for installing the Cover Plate As-
_ ' ' 1 sembly, remove and discard the Pro -
tective Cap, and verify that the
3/16 °•to 11/16" MANUFACTURER DEFLECTOR COVER PLATE • Deflector moves up and down freely. If
(4,8 to 17,5 - mm) PRESET GAP IN DROPPED RETAINER the Sprinkler has been damaged and
REFERENCE 3/32° (2,4 mm) POSITION ASSEMBLY the Deflector does not move up and
down freely, replace the entire Sprin-
COVER PLATE COVER PLATE kler assembly: Do not attempt to mod-
- PROFILE DEPTH DIAMETER ify or repair a damaged sprinkler.
DIMENSION B DIMENSIONA Step 7. When installing an Air and .
Dust Seal, refer to Figure 5, otherwise
proceed to Step 8. To attach the Air and
A: 3 -1/4° (82,6 mm) C: 2 -3/8° to 2 -5/8" (60,3 to 66,7 mm) Dust Seal, verify the angle of the out -
B: 3/16" (4,8 mm) D: 1 -3/4° to 2 -1/4" (44,5 to 57,2 mm) side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
FIGURE the Retainer in the grooved slot of the
SERIES RFII CONCEALED SPRINKLER Air and Dust Seal and continue around
INSTALLATION DIMENSIONS the retainer until the entire Air and
Dust Seal is engaged.
NOTE
. The Air and Dust Seal is only to be
• ====== installed on the periphery of the Re-
•
-- I t' FRAME Jj =l. _ tainer.
ARM ir k Step 8. Screw on the Cover Plate /Re-
� � � �
tamer Assembly until the Retainer -
II ' • (� - ' - Figure 2 (or Air and Dust Seal - Figure
• j SUPPORT j i 1 1 5) contacts with the ceiling. Do not
- ; CUP j - I ; continue to screw on the Cover
< Plate /Retainer Assembly such that it
11111111 mai lifts a ceiling panel out of its normal
MI i �,7
% � position. If the Cover Plate /Retainer
� Assembly cannot be engaged with the
O Support Cup or the Cover Plate /Re-
7/8' (23 mm) tainer Assembly cannot be engaged
SQUARE sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
ALIGN __.-1-1...,,
ARROWS WITH \\ Care and
FRAME ARMS OE <'I
r Maintenance
ACCEPTS The Series RFII must be maintained
0 1/2° SOCKET and serviced in accordance with the
DRIVE following instructions:
NOTES
FIGURE 3 Absence of the Cover Plate Assembly
- RFII SPRINKLER WRENCH may delay sprinkler operation in a fire
situation.
Page 4 of 4 TFP181
When properly installed, there is a SUPPORT SPRINKLER FACE OF ORIENT
nominal 3/32 inch (2,4 mm) air gap CUP CEILING SEAL
__ .. _ - .__between- the•lip -of the- Cover -Plate -and — --
l — -- f — the ceilin , as shown in Fi ure 2. This SHOWN
air gap is necessary for p oper opera PLATE
tion of th e sprinkler. If the ceiling is to ` + `: R ETAINE R
be repainted after the installation of `i ;∎1 ASSEMBLY
the Sprinkler, care must be exercised " _
to ensure that the new paint does NOT � ' ��
seal off any of the air gap. ) I A CLEAN
Factory painted Cover Plates MUST / ,���, "'� ROOM
NOT be repainted. They should be re- �� �� LIP OF COVER SEAL
placed, if necessary, by factory RETAINER PLATE
painted units. FIGURE 5
Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504)
the Enclosure. Separation may result.
Before closing a fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT
main control valve for maintenance local requirements and /or national SHALL TYCO FIRE PRODUCTS' LI-
work on the fire protection system that codes. ABILITY EXCEED AN AMOUNT
it controls, permission to shut down the EQUAL TO THE SALES PRICE.
affected fire protection system must be THE FOREGOING WARRANTY IS
obtained from the proper authorities Limited THE IN LIEU OF ANY AND ALL
and all personnel who may be OTHER WARRANTIES EXPRESS OR
by this action must be notified. - arranty -IMPLIED. INCLUDING WARRANTIES
Sprinklers that are found to be leaking OF MERCHANTABILITY AND FIT -
or exhibiting visible signs of corrosion Products manufactured by Tyco Fire NESS FOR A PARTICULAR PUR-
must be replaced. Products are warranted solely to the POSE.
Automatic sprinklers must never be original Buyer for ten (10) years
against defects in material and work -
painted, plated, coated or otherwise manship when paid for and properly Ordering
altered after leaving the factory. Modi- installed and maintained under normal
fied sprinklers must be replaced.
Sprinklers that have been exposed to use and service. Ti warranty will ex- Procedure
ive products pire ten (10) years s from date of ship -
co os s not operated, should be replaced of combustion, but laced ment by Tyco Fire Products. No war- When placing an order, indicate the full
h they cannot be completely cleaned ranty is given for products or product name. Contact your local dis-
if by wiping the spr om le t a cloth or components manufactured by compa- tributor for availability.
by brushing it with a soft bristle brush. Hies not affiliated by ownership with Sprinkler Assembly:
Tyco Fire Products or for products and S ecif
age to the s nklers exercised - before, i dur nm components which have been subject rating) Semi s RFI Pen-
• 9 P 9, to misuse, improper installation, corro dent Sprinkler, P/N
and after installation. Sprinklers dam- sion, or which have not been installed, P (specify).
aged by dropping, striking, wrench maintained, modified or repaired in ac- • 155E /6ec 200F/93c
twist/slippage, or the like, must be re- cordance with applicable Standards of Ty3551 51- 790 -1 -155 51 -790 -1 -200
placed. Also, replace any sprinkler that the National Fire Protection Associa- TY3504 • 51-796-1-155 51- 796 -1 -200
has a cracked bulb or that -has lost tion, and /or the standards of any other TY3531 51- 792 -1 -155 51- 792 -1 -200
liquid from its bulb. (Ref. Installation Authorities Having Jurisdiction. Mate - TY3505 51- 797 -1 -155 51- 797 -1 -200
Section). rials found by Tyco Fire Products to be
If a sprinkler must be removed, do not defective shall be either repaired or Separately Ordered Cover Plate:
reinstall it or a replacement without replaced, at Tyco Fire Products' sole Specify: (specify temperature rating)
reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate
If a Cover Plate Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify).
dislodged during service, replace it im- assume for it, any other obligation in
mediately. connection with the sale of products or 135F/57C(a) 165F/74C•(b)
parts of products. Tyco Fire Products Brass 56- 792 -1 -135 56- 792 -1 -165
P P Y Bright Brass • 56- 792 -2 -135 56- 792 -2 -165
The owner is responsible for the in- shall not be responsible for sprinkler Chrome 56- 792 -9 -135 56- 792 -9 -165
spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome 56- 792 -8 -135 56- 2 -8-
their fire protection system and de incomplete information supplied by White 56- 792 -0-135 56
- 792 -0 -165 165
p y P pP y White (RAL9010)• 56- 792 -3 -135 56- 792 -3 -165
vices in compliance with this docu- Buyer or Buyer's representatives. Bright White 56- 792 -4 -135 56- 792 -4 -165
ment, as well as with the applicable IN NO EVENT SHALL TYCO FIRE Off White 56- 792 -5-135 56- 792 -5-165
standards of the National Fire Protec- PRODUCTS BE LIABLE, IN CON- Black 56- 792 -6-135 56- 792 -6-165
Custom 56- 792 -X -135 56- 792 -X -165
tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR (a) For use with 155F/68C sprinklers.
addition to the standards of any other UNDER ANY OTHER LEGAL THE- (b) For use with 200F/93C spr
authorities having jurisdiction. The in- ORY, FOR INCIDENTAL, INDIRECT, • Eastern Hemisphere sales only.
• stalling contractor or sprinkler manu- SPECIAL OR CONSEQUENTIAL
• facturer should be contacted relative to DAMAGES, INCLUDING BUT NOT Sprinkler Wrench:
any questions. LIMITED TO LABOR CHARGES, RE- Specify: RFII Sprinkler Wrench,
It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56-000-1-075.
sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal:
tested, and maintained by a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal,
P/N 56- 908 -1 -001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
•
Vico Fire & Building
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K- factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
tamed when exposed to corrosive at-
mospheres. Although corrosion resis- _—
__
Cant coated sprinklers have passed the - -
Description standard corrosion tests of the appli-
cable approval agencies, the testing is
The Tyco® Series TY -FRB, 2.8, 4.2, not representative of all possible cor- ;•I
5.6, and 8.0 K- factor, Upright and Pen- rosive atmospheres. Consequently, it i
dent Sprinklers described in this data is recommended that the end user be !
sheet are quick response - standard consulted with respect to the suitability I C j
coverage, decorative 3 mm glass bulb of these coatings for any given corro- :i .
type spray sprinklers designed for use sive environment. The effects of ambi-
in light or ordinary hazard, commercial ent temperature, concentration of — -- I
occupancies such as banks, hotels, chemicals, and gas /chemical velocity, '
shopping malls, etc. should be considered, as a minimum,
The recessed version of the Series along with the corrosive nature of the
TY -FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be ^`
plicable, is intended for use in areas exposed.
with a finished ceiling. It uses either a An intermediate level versions of the --
two -piece Style 10 (1/2 inch NPT) or Series TY -FRB Pendent Sprinklers • , r " +.N Nki
Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet r r•',
cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de-
recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780 l • :
(19,1 mm) of total adjustment from the , .: '
flush pendent position, or a two -piece WARNINGS
• Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY - FRB Sprinklers de \. ,, ,
inch NPT) Recessed Escutcheon with scribed herein must be installed and .-" .i
1/4 inch (6,4 mm) of recessed adjust- maintained in compliance with this
ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica-
total adjustment from the flush pen ble standards of the National Fire Pro -
dent position. The adjustment pro tection Association, in addition to the
vided by the Recessed Escutcheon re- standards of any other authorities hay- Model /Sprinkler
duces the accuracy to which the fixed ing jurisdiction. Failure to do so may
pipe drops to the sprinklers must be impair the performance of these de- Identification
cut. vices.
Corrosion resistant coatings, where The owner is responsible for maintain- Numbers
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2 "NPT
that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2 "NPT
manufacturer should be contacted TY2131 - Upright 4.2K, 1/2 "NPT
IMPORTANT with any questions. TY2231 - Pendent 4.2K, 1/2 "NPT
TY3131 - Upright 5.6K, 1/2 "NPT
Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2 "NPT
Sheet TFP700 for the "INSTALLER TY4131 - Upright 8.0K, 3/4 "NPT
WARNING" that provides cautions TY4231 - Pendent 8.0K, 3/4 "NPT
with respect to handling and instal - TY4831 Upright 8.0K, 1/2 "NPT
lation of sprinkler systems and com- TY4931 Pendent 8.0K, 1/2 "NPT
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 AUGUST, 2007 TFP171
Page 2 of 10 TFP171
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING 1/2 NOMINAL RECESSED * __ _ _ __ _ _ _
- -
-- -- -- - • - --- SURFACE MAKE=1N ""--- ESCUTCHEON -- -SSU
NPT _I DEFLECTOR
•
I 6
r 7/16" i vy
2-1/4" 5
/ w (1 1,1 mm) i q
(57,2 mm) loom
el NOMINA
1 14 �
2
1-9/16" I to! � MAKE -IN 2 3/16" '- 2 3 • (39,7 mm) FLATS _ (55,6 mm) 0 1
ii �N ir• �� 4Lf
•
SSP DEFLECTOR * --'— 2 -7/8" (73,0 mm) DIA. 1/2" NPT
} 7
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4-Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw .
• FIGURE 1
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND•PENDENT (TY1231) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED *
SURFACE
1/2" T M A MAKE-IN ESCUTCHEON DEFLECTOR
i == ;�_ � w • ' ri *il l
i am:. 6*
!; r_ 7/16" > 5
• 2 -3/16" � —� ���'! (11,1 mm)
(55,6 mm) AAA�� I I 4
t ��� NOMINAL � 1� I MAKE -IN II rf
1 -1/2" I �I / W RENCH , � I 2 3/16" to � 2
• (38,1 mm)
1 — (55,6 mm)
- -- - - -� - FLATS = I 3 0
SSP DEFLECTOR * f 2-7/8" (73,0 mm) DIA. - 1/2" NPT' } + Ii 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 2
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K- FACTOR, 1/2 INCH NPT
•
TFP171 Page 3 of 10
. ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL _ RECESSED _ *_ ___ ___-
- SURFACE -- NFT - MA KE -IN ESCUTCHEON DEFLECTOR
•
1.� 7/16"
�' 5
2- 3/16" -.m.--- -f- � olk. (11,1 mm) (55,6 mm) i 1 = A . � NOMINAL MAKE -IN ' 4
� WREN 1/2" I 11I/ I ` 2 3/16" � 2
(38,,1 mm) WRENCH
= (55,6 mm . 3
' / - JUL 4 FLATS SSP DEFLECTOR * f— 2 -7/8" (73,0�mm) DIA. 1/2" NPT f 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
•
•
. FIGURE 3
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40
PLATE SEATING NOMINAL RECESSED *
SURFACE
3/4" T MAKE-IN ESCUTCHEON DEFLECTOR
\ , _— = --_ _ . =— --:
6
1/2
1M1 5
ms
• 2 -5/16" ,�•u (12,7 mm) I
(58,7 mm) 1� I 11 4 0 •
i 1∎ ��NOMINAL
� rill MAKE -IN II r
1 -9/16" � l 2
• . (39,7 mm) WRENCH 0
• ° - II _- FLATS o 3 1 l et
—�+
SSP DEFLECTOR * f— 2 -7/8" (73,0 mm) DIA. 3/4" NPT t .
• PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
•
FIGURE 4
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
•
Page 4 of 10 TFP171 .
7/16" (11,1 mm)
1/2" NOMINAL SSU
NPT MAKE -IN DEFLECTOR __
__I *6
f t =. 5
2 -1/4" ,51-471-... -� 2 -3/16" (57,2 mm) l� 11 I (55,6 mm) II 4 --r-
1 If
1 -9/16" I WRENCH -111=1111111 p 0 '4 2
(39,7 mm) FLATS y
l _., f 3
P
SSP 1
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression . orifice seat on frame:
Screw •
FIGURE 5
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
• 8.0 K- FACTOR, 1/2 INCH NPT '
Technical Operation
Data The glass Bulb contains a fluid which
expands when exposed to heat. When
Approvals the rated temperature is .reached, the
UL and•C -UL Listed. fluid expands sufficiently to shatter the
•
FM, LPCB, and NYC Approved. glass Bulb, allowing, the • • sprinkler to
• • (Refer to Table A and B for complete activate and water to flow.
approval information including corro-
• sion resistant status.) De
• • Maximum Working Pressure
Refer to Table C. • Criteria •
Discharge Coefficient •
K = 2.8 GPM /psi (40,3 LPM /bar1/2) The Series TY -FRB Pendent and Up- •
' K = 4.2 GPM /psi /2 (60,5 LPM /bar1/2) right Sprinklers are intended for fire
K = 5.6 GPM /psi / (80,6 LPM /bar1/2 protection systems 'designed in ac-
• K = 8.0 GPM /psi / (115,2 LPM /bar cordance with the standard installation
rules recognized by the applicable
Temperature Ratings Listing or Approval agency (e.g., UL
Refer to Table A and B Listing is based on the requirements of
Finishes NFPA 13, and FM Approval is based
Sprinkler: Refer to Table A and B. on the requirements of FM's Loss Pre -
Recessed Escutcheon: White Coated, vention Data Sheets ). Only the Style
Chrome Plated, or Brass Plated. 10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations. Y
Physical Characteristics
Frame Bronze E
Button Brass /Copper -o
Sealing Assembly B
Beryllium Nickel w/Teflont
Bulb Glass E
Compression Screw Bronze
Deflector Copper /Bronze at
Bushing (K =2.8) Bronze
cr
0
a
0
4-
•
•
•
•
TFP171 Page 5 of 10
SPRINKLER FINISH (See Note 7)
_K_ - TYPE -- — TEMP.— — BULB -- - NATURAL- -CHROME - - WHITE*" - — - — - - — - • - - - -
LIQUID BRASS PLATED POLYESTER
135"F/57°C Orange
PENDENT 155"F168°C Red
(TY1231) 1, 2, 3, 5
and 175"F/79°C Yellow
UPRIGHT 200 °F /93 °C Green
2.8 (TY1131)
286 °F /141 °C Blue
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT
(TY1231)* 175 °F /79 °C Yellow
Figure 6 200"F/93°C Green 1, 2, 5
135"F/57°C Orange
RECESSED 155 °F /68 °C Red
• PENDENT
(TY1231)** 175"F/79°C Yellow
•
Figure 7 200 °F /93 °C Green
135 °F /57 °C Orange
PENDENT
155"F/68°C Red •
(TY2231)
and 175 °F /79 °C Yellow
UPRIGHT 200 °F /93 °C Green
4.2 (TY2131)
1/2" 286 °F /141 °C Blue 1 2
NPT 135 °F /57 °C, Orange
RECESSED 155"F/68°C Red
PENDENT
(TY2231)* 175 °F /79 °C Yellow
•
Figure 8 200 °F /93 °C Green
•
135 °F /57 °C Orange
•
RECESSED 155 °F /68 °C Red
•
•
PENDENT
•
(TY2231) ** 175 °F /79 °C Yellow
F igure 9 200 ° F /93 °C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc: (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Re-
sponse Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354 -01 -E.
7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin-
klers are UL and C -UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
*** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K- FACTOR SPRINKLERS
•
•
•
•
•
•
•
•
Page 6 of 10 TFP171
•
SPRINKLER FINISH (See Note 8)
_. • — K .. TYPE _ TEMP._ —BULB— _NATURAL- _CHROME— — WHITE"'" —"— —. - - - - - -- LEAD - - - -- - - - - -- - - - --
LIQUID BRASS PLATED POLYESTER COATED
135"F/57°C Orange
PENDENT 155 °F /68 °C Red
•
(TY3231) 1 2 3 4 5 6 7
and 175 °F /79 °C Yellow 1, 2, 3, 5
UPRIGHT 200"F/93°C Green
5.6 (TY3131)
286"F/141°C Blue
1/2"
NPT 135"F/57°C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 4, 5
(TY3231)' 175 °F /79 °C Yellow N/A
Figure 10 200"F/93°C Green
135"F/57°C Orange
•
RECESSED 155"F/68°C Red
• PENDENT 1, 2, 3, 4, 5 N/A
(TY3231)" 175 ° F /79 °C Yellow
Figure 11 200 °F /93 °C Green
135 °F /57 °C Orange
•
PENDENT 155"F/68°C Red'
(TY4231)
and 175 °F /79 °C Yellow 1, 2, 5
1, 2, 3, 4, 5, 6, 7
UPRIGHT 200 °F /93 °C Green •
•
8.0 (TY4131)
286 °F /141 °C Blue
3/4"
•
NPT 135 °F /57 °C Green
RECESSED 155 °F /68 °C Orange
PENDENT 1, 2, 4, 5 N/A
(TY4231)" 175"F/79°C Red
Figure 12 200 °F /93 °C Yellow
• 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red •
PENDENT 1, 2, 3, 4, 5 N/A
•
•
(TY4231)" 175"F/79°C • Yellow.
•
Figure 13 200 °F /93 °C Green
135 °F /57 °C Orange'
PENDENT 155 °F /68•C Red .
8.0 (TY4931)
1/2" and 175"F/79°C Yellow 1, 2, 5
1,2,4,5,6
NPT UPRIGHT 200 °F /93 °C Green
(TY4831)
286 °F /141 °C Blue •
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k104) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428 - 3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
"" Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K- FACTOR SPRINKLERS
TFP171 Page 7 of 10
SPRINKLER FINISH
TYPE _NATURAL_ _CHROME_ — _WHITE— — - -__ _ _— LEAD -. - - -- - -. – - -- -. -
BRASS PLATED POLYESTER COATED
PENDENT (TY3231)
and
2 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/2 RECESSED PENDENT
NPT (TY323)
PENDENT (TY4231)
and
4 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
3/4" RECESSED PENDENT
NPT (TY4231)
PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 UPRIGHT (TY3131) OR
1/2" RECESSED PENDENT 175 PSI (12,1 BAR)
NPT (TY3231)
(SEE NOTE 1) N/A
PENDENT (TY4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8 UPRIGHT (TY4131)
3/4" RECESSED PENDENT
NPT (TY4231)
N/A
8.0 PENDENT (TY4931)
1/2" and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4831)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
• Underwriters Laboratories, Inc. for use in Canada (C -UL); and , the Approval by the City of New York.
TABLE C, MAXIMUM WORKING PRESSURE
tained with a torque of 10 to 20 ft.lbs. the sprinkler into the sprinkler fitting.
Installation (13,4 to 26,8 Nm). A maximum of 30 Step 3. Tighten the sprinkler into the
ft.lbs. (40,7 Nm) of torque is to be used sprinkler fitting using only the W -Type
The Series TY -FRB Sprinklers must to install sprinklers with 3/4 NPT con-
sprinkler
Sprinkler Wrench (Ref. Figure 14
6 ). installed in accordance with the fol- nections. Higher levels of torque may
With 4
th reference to Figures 1, 2, 3, 4,
lowing instructions: distort the sprinkler inlet and cause and 5, the W -Type 6 Sprinkler Wrench
NOTES leakage or impairment of the sprinkler. is to be applied to the sprinkler wrench
Do not install any bulb type sprinkler if Do not attempt to make -up for insuffi- flats.
the bulb is cracked or there is a loss of cient adjustment in the escutcheon The Series TY -FRB Recessed Pen -
liquid from the bulb. With the sprinkler plate by under- or over - tightening the dent Sprinklers must be installed in
held horizontally, a small air bubble sprinkler. Readjust the position of the accordance with the following instruc-
should be present. The diameter of the sprinkler fitting to suit. tions.
air bubble is approximately 1/16 inch The Series TY -FRB Pendent and Up- Step A. After installing the Style 10.
(1,6 mm) for the 135F/57°C to 3/32 right Sprinklers must be installed in 20, 30, or 40 Mounting Plate, as appli-
inch (2,4 mm) for the 286 °F /141 °C accordance with the following instruc- cable, over the sprinkler threads and
temperature ratings. tions. with pipe thread sealant applied to the
A leak tight 1/2 inch NPT sprinklerjoint Step 1. Pendent sprinklers are to be
pipe threads, hand tighten the sprin
should be obtained with a torque of 7 installed in the pendent position, and kler into the sprinkler fitting.
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- upright sprinklers are to be installed in Step B. Tighten the sprinkler into the
mum of 21 ft. lbs. (28,5 Nm) of torque the upright position. sprinkler fitting using only the W -Type
may be used to install sprinklers with S te pipe Recessed Sprinkler Wrench (Ref.
1/2 NPT connections. A leak tight 3/4 p 2 2 . With r thread hth threads, hand tighten sealant a a Figure 15). With reference to Figure 1,
e
inch NPT sprinkler joint should be ob- plied the pipe pe g 2, 3, and 4, the W -Type 7 Recessed
•
•
•
•
•
Page 8 of 10 TFP171
2 -7/8" DIA. _ 2 -7/8" DIA.
5/8±1/4" (73,0 mm) 314' (19,1 mm) (73,0 mm)
-- - -- - - - - - - - - - - 1/2±1/8 " - - - 1/2_(12.7_mm) - - -
(15,916,4 n--1711)- 2 -1/4° DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2 -1/4° DIA. 1/4° (6,4 mm)
FACE OF (57,2 mm) .1 MOUNTING FACE OF (57,2 mm)
SPRINKLER PLATE SPRINKLER MOUNTING
PLATE
FITTING FITTING
1/8" 1/8"
- 11i��� ( 3,2 mm) i ltill (3,2 mm)
. \ ;�� Ea =J S TIN I
MOU FTING N I �■
SURFACE ,, .4• a. •
CLOSURE SERIES 1 -5/16° (33,3 mm) CLOSURE SERIES 1 -5/16° (33,3 mm)
TY -FRB 13/16" (20,6 mm) TY -FRB 1 -1/16" (27,0 mm)
FIGURE 6 FIGURE 7
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
- STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT
2 -7/8" DIA. 2 -7/8° DIA.
5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8° (73,0 mm) 1/2" (12,7 mm)
(15,916,4 mm) 2 -114° DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2 -1/4 " DIA. 1/4' (6,4 mm)
FACE OF 57,2 mm) (57,2 )
( ) MOUNTING FACE OF 57,2 mm MOUNTING
SPRINKLER
PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8'
II ( mm) •. ( 3 , 2 I m m)
� „ = � .�� t
\ - p III MOUNTING
MOUNTING � . SURFACE ■
SURFACE - - - - -- ■ _ - ---.
•
•
CLOSURE SERIES 1 -1/4" (31,8 mm) • CLOSURE SERIES , •1 -1/4° (31,8 mm)
TY-FRB 3/4" (19,1 mm) . TY -FRB 1' (25,4 mm)
• • FIGURE 8 • . - - FIGURE 9
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT . WITH -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON , . . STYLE 20 RECESSED ESCUTCHEON
4.2 K- FACTOR, .1/2 INCH NPT • 4.2 K- FACTOR, 1/2 INCH NPT
Sprinkler Wrench is to be applied to work on the fire protection system that altered after leaving the factory. Modi-
the sprinkler wrench flats. it controls, permission to shutdown the fied sprinklers must be replaced.
Step C. After the ceiling has been in- affected fire protection system must be Sprinklers that have been exposed to
stalled or the finish coat has been in- obtained from the proper authorities corrosive products of combustion, but
plied, slide on the Style 10, 20, 30, or and all personnel who may be affected have not operated, should be replaced
40 Closure over the Series TY-FRB by th act must be not if they cannot be completely cleaned -
Sprinkler and push the Closure over The owner must assure that the sprin by wi the sprinkler with a cloth or
the Mounting Plate until its flange klers are not used for hanging of any by brush i t w a soft br brush.
comes in contact with the ceiling. objects; otherwise, non - operation in Care must be exercised to avoid dam -
the event of a fire or inadvertent opera age to the sprinklers - before, during,
are and tion may result. and after installation. Sprinklers dam -
Absence of an escutcheon, which is aged by dropping, striking, wrench
Maintenance used to cover a clearance hole, may twist/slippage, or the like, must be re-
delay the time to sprinkler operation in placed. Also, replace any sprinkler
a fire situation. that has a cracked bulb or that has lost
The Series TY -FRB Sprinklers must liquid from its bulb. (Ref. Installation
be maintained and serviced in accord- Sprinklers that are found to be leaking Section).
ance with the following instructions: or exhibiting visible signs of corrosion
must be replaced. Frequent visual inspections are rec- •
NOTES ommended to be initially performed for
Before closing a fire protection system Automatic sprinklers must never be corrosion resistant coated sprinklers,
main control valve for maintenance painted, plated, coated or otherwise after the installation has been com-
•
•
TFP171 Page 9 of 10
2 -7/8' DIA. _ 2 -7/8" DIA. _
0 73
(73,0 mm) , mm
5/8±1/4' (19,1 mm) ( mm)
— _ — — - (1b,9±6,4 mm) -- — 112±1/8'_ " 7
1/2" (12 .. - .
2 -1/4 DIA. 1/4' (6,4 mm) — -- (12,7±3,2 mm) — 2 -1/4" DIA. — _ 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm)
SPRINKLER PLATE SPRINKLER MOUNTING
PLATE
FITTING FITTING
1/8° 1/8"
•�� (3,2 mm) •• (3,2 I mm)
uniMMs_IWit W AW ! 4ijl f
�,,,
} , MOUNTING IN 1
MOUNTING SURFAC
Pi
SURFACE = ! - �� •
CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm)
TY -FRB 3/4' (19,1 mm) TY -FRB 1" (25,4 mm)
FIGURE 10 FIGURE 11
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K- FACTOR, 1 /2'INCH NPT • 5.6 K- FACTOR, 1/2 INCH NPT
• 2 -7/8" DIA. 2 -7/8" DIA.
5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8" (73,0 mm) 1/2" (12,7 mm)
• (15,9±6,4 mm) 2 -1/4° DIA. 1 1/47(6,4 mm) (12,7±3,2 mm) ' 2 -1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING (57,2 mm)
FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER . PLATE
FITTING FITTING
1/8" I 1/8"
EIM X 711' r ���III .
411 Mill r
fil w i i .. i
I , ....,. ..__
, ' MOUNTING • � , }
MOUNTING . f SURFACE
SURFACE I I♦
- CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1 -5/16" (33,3 mm)
TY -FRB • 13/16" (20,6 mm) _ TY -FRB 1 -1/16° (27,0 mm)
FIGURE 12 ' FIGURE.13
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
• 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT
pleted, to verify the integrity of the cor WRENCH
rosion resistant coating. Thereafter, �� RECESS
annual inspections per NFPA 25
should suffice; however, instead of in- WRENCH RECESS 00131
specting from the floor level, a random (END ^A" USED FOR
sampling of close -up visual inspec- 1/2" NPT MODELS) *11111 .
tions should be made, so as to better �� ` I U f
determine the exact sprinkler condi-
tion and the long term integrity of the H RECESS �'�
WRENCH corrosion resistant coating, as it may
be affected by the corrosive conditions ( USED FOR PUSH WRENCH
3 /a ^END NC NPT MODELS) IN TO ENSURE •
present. ENGAGEMENT
The owner is responsible for the in- FIGURE 14 WITH SPRINKLER WRENCHING AREA
spection, testing, and maintenance of W -TYPE 6 SPRINKLER
their fire protection system and de- WRENCH FIGURE 15
vices in compliance with this docu- W -TYPE 7 RECESSED
ment, as well as with the applicable SPRINKLER WRENCH
standards of the National Fire Protec facturer should be contacted relative
tion Association (e.g., NFPA 25), in to any questions.
addition to the standards of any other It is recommended that automatic Inspection Service in accordance with
• authorities having jurisdiction. The in- sprinkler systems be inspected, local requirements and /or national
codes.
stalling contractor or sprinkler manu- tested, and maintained by a qualified
•
•
•
Page 10 of 10 TFP171
_ .. _ P/N 57 -XXX - X - XXX
I I
TEMPERATURE
MODEUSIN RATING
SPRINKLER
330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135 °F /57 °C
331 2.8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C
340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175F/79°C
341 4.2K PENDENT (1/2 "NPT) TY2231 3 WHITE (RAL9010)* 200 200 °F /93 °C
370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C
371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED
390 8.0K UPRIGHT (3/4 "NPT) TY4131
391 8.0K PENDENT (3/4 "NPT) TY4231 * Eastern Hemisphere sales only.
360 8.0K UPRIGHT (1/2 "NPT) TY4831* •
361 8.0K PENDENT (1/2 "NPT) TY4931*
TABLE D
PART NUMBER SELECTION
SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS
Limited In no event shall TFBP be liable, in
contract, tort, strict liability or under Ordering
Warranty any other legal theory, for incidental,
indirect, special or consequential dam- Procedure
ages, including but not limited to. labor
Products manufactured by Tyco Fire & charges,. regardless of whether TFBP When placing an order, indicate the
Building Products (TFBP) are war- was informed about the. possibility of full product name. Refer to the Price
ranted solely to the original Buyer for such damages; and in no event shall List for complete listing of Part Num-
. ten (10) years against defects in mate- TFBP's liability exceed an amount bers..
rial and workmanship when paid' for equal to the sales price. . Contact your local distributor for avail -
and properly installed and maintained y
under normal use and service. This The foregoing warranty is made in lieu ability.
• warranty will expire ten (10) years of any and all other warranties. ex -
• from date of shipment by TFBP. No • - • " • - • ' • " ! ' • -' Sprinkler Assemblies with NPT
warranty is given for products or corn- of merchantability and fitness for a par - Thread Connections:
ponents manufactured by companies ticular purpose. Specify: (Specify Model /SIN), Quick
not affiliated b Y P ownershi with TFBP This limited warranty sets forth the ex-
Response, (specify K- factor), (specify
or for products and components which clusive remedy for claims based on (smpera re ydyp t rating), Series pri FRB
have been subject to misuse, improper failure of or defect in products, materi- with ( sp ci y type of finish o or fins o r coating),
Sprinkler
installation, corrosion, or which have als or components, whether the claim P/N
/
� (specify from Table D).
not been installed, maintained, modi- is made in contract, tort, strict liability
fled or repaired in accordance with ap- or any other legal theory. Recessed Escutcheon:
plicable Standards of the National Fire
Protection Association, and /or the This warranty will apply to the full ex- Specify: Style (10, 20, 30, or 40) Re-
standards of any other Authorities tent permitted by law. The invalidity, in cessed Escutcheon with (specify *) fin -
Having Jurisdiction. Materials found whole or part, of any portion of this ish, P/N (specify *).
by TFBP to be defective shall be either warranty will not affect the remainder.
repaired or replaced, at TFBP's sole
• Refer to Technical Data Sheet TFP770.
option. TFBP neither assumes, nor Sprinkler Wrench:
authorizes any person to assume for it, Specify: W -Type 6 Sprinkler Wrench,
any other obligation in connection with P/N 56-000-6-387.
the sale of products or parts of prod-
. - ucts. TFBP shall not be responsible for Specify: W -Type 7 Sprinkler Wrench,
sprinkler system design errors or inac- P/N 56- 850 -4 -001.
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446