Series RFII — 5.6 K- factor
"Royal Flush II" Pendent Concealed Sprinklers
Quick & Standard Response, Standard Coverage
General Cap. The Protective Cap is temporarily
removed for installation, and then it
can be replaced to help protect the Allik
Description sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro
The Series RFII Quick Response tective Cap can also be used to mark
(3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas- ' _ _ _
mm bulb), 5.6 K- Factor, "Royal Flush ter board, ceiling tiles, etc. by gently __ -
II" Concealed Pendent Sprinklers are pushing the ceiling product against the
decorative sprinklers featuring a flat Protective Cap. When the ceiling in- °ter ~�
cover plate designed to conceal the stallation is complete the Protective
sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate
tecturally sensitive areas such as hotel Assembly installed.
lobbies, office buildings, churches, As an option, the Series RFII Standard
and restaurants. Response (5 mm bulb) "Royal Flush II"
Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be
sembly that conceals the sprinkler op- fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175
erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM.
The separable two -piece design of the intended for sensitive areas where it is
Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical
blies allows installation of the sprin- through the cover plate from the area
klers and pressure testing of the fire above the ceiling. Data
protection system prior to installation WARNINGS
of a suspended ceiling or application The Series RFII Concealed Pendent Approvals for Series RFII
of the finish coating to a fixed ceiling. PP
They also permit removal of sus Sprinklers described herein must be UL and C -UL Listed. FM Approved.
pended ceiling panels for access to installed and maintained in compli- NYC under MEA 353 -01 -E. LPCB (Ref.
ance with this
building service equipment without document, as well as No. 094a/09 for TY3551 & 094a/10 for
having to first shut down the fire pro- w ith the applicable standards of the TY3531) Approved.
tection system and remove sprinklers. N atio nal F Protection Association, The approvals apply only to the serv-
Also, the separable two wo -p piece design in addition to the standards of any ice conditions indicated in the Design
f the the Sprinkler other authorities having jurisdiction. Criteria section and maximum pres-
inch a th mm) of vertical p provides deju for ign for 1/2 Failure to do so may impair the per- sure ratings indicated in the
formance of these devices. Model/Sprinkler Identification Num-
to reduce the accuracy to which the The owner is responsible for maintain- bers section.
length of fixed pipe drops to the sprin- p
klers must be cut. i ng their fire protection system and de Approvals for Air & Dust Seal
vices in proper operating condition. Part #10908100
The Series RFII Sprinklers are The installing contractor or sprinkler U L and C -UL Lis for use with the
shipped with a Disposable Protective manufacturer should be contacted RFII (TY3551 & TY3504) Standard Re-
with any questions. sponse Concealed Sprinkler.
IMPORTANT Temperature Ratings
Always refer to Technical Data Model /Sprinkler 155F/68C Sprinkler - 135F/57C Plate
Sheet TFP700 for the "INSTALLER 200F/93C Sprinkler - 165F/74C Plate
WARNING" that provides cautions Identification Discharge Coefficient
with respect to handling and instal- K = 5.6 GPM /psi (80,6 LPM /bar
lation of sprinkler systems and com- Numbers Adjustment
ponents. Improper handling and in- 1/2 inch (12,7 mm)
stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm Finishes
a sprinkler system or its compo- bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass
nents and cause the sprinkler to fail UL, C -UL, FM, LPCB and NYC. Plated, or White Painted (Custom paint
. to operate in a fire situation or cause TY3504 (5 mm bulb) & TY3505 (3 mm matches and colors other than white
it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by are available on request.)
Page 1 of 4 JULY, 2004 TFP181
•
Page 2 of 4 TFP181
Physical Characteristics 1/2' NPT SEALING
Frame Bronze / ASSEMBLY
Support Cup . Chrome Plated Steel
' Guide Pins Stainless Steel �.. 1 `
Deflector Bronze FRAME �j/ j ��
Compression Screw Brass �� 1 n, _J 1 CAP
Bulb Glass I `� {
Cap Bronze or Copper SUPPORT i
Sealing Assembly CUP WITH ( BULB
Beryllium Nickel w/Teflon' ROLL FORMED ) I
Cover Plate Brass THREADS
Retainer Brass fill COMPRESSION
Ejection Spring . .Stainless Steel GUIDE 1111 Iiii I / ai ��� s SCREW
Patents PINS (2) MI
� %`� l
U.S.A. 4,014,388 I S
�_ = 1 DEFLECTOR
Operation DEFLECTOR ti i (DROPPED
_. POSITION)
G- ti
When exposed to heat from a fire, the SPRINKLER/SUPPORT CUP
Cover Plate, which is normally s01 I ASSEMBLY
dered to the Retainer at three points,
falls away to expose the Sprinkler As- THREAD INTO I RETAINER
sembly. At this point the Deflector sup- SUPPORT CUP O �` WITH THREAD
ported by the Guide Pins drops down UNTIL MOUNTING O DIMPLES
p Y P SURFACE IS
to its operational position. FLUSH WITH • EJECTION
The glass Bulb contains a fluid that CEILING SPRING
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the - ■aii-c
glass Bulb, activating the sprinkler and /
allowing water to flow. SOLDER J COVER
TABS (3) COVER PLATE/RETAINER PLATE
Design ASSEMBLY
esi n
FIGURE 1
Criteria SERIES RFII CONCEALED SPRINKLER
ASSEMBLY -
The RFII (TY3551 & TY3504), 5 mm
. Bulb Type, Concealed Pendent Sprin- Step 1. The sprinkler must only be
klers are UL and C -UL Listed as stand- Installation installed in the pendent position and
and response - standard spray sprin- with the centerline of the sprinkler per -
klers for use in accordance with the The Series RFII must be installed in pendicular to the mounting surface.
current NFPA standard. They are FM accordance with the following instruc- Step 2. Remove the Protective Cap.
Approved as standard response - tions:
standard spray sprinklers for use in NOTES Step 3. With pipe thread sealant ap-
accordance with the current FM Loss plied to the pipe threads, hand tighten
Prevention Data Sheets. Do not install any bulb type sprinkler if the sprinkler into the sprinkler fitting.
The RFII (TY3531 & TY3505) 3 mm the bulb is cracked or there is a loss of Step 4. Wrench tighten the sprinkler
Bulb Type, Concealed Pendent Sprin- liquid from the bulb. With the sprinkler using only the RFII Sprinkler Wrench
yp p held horizontally, a small air bubble
klers are UL and C -UL Listed as quick should be present. The diameter of the (Ref Figure 3). The RFII Sprinkler
response - standard spray sprinklers air bubble is approximately 1/16 inch Wrench i s to be applied to the Sprin-
for use in accordance with the current (1,6 mm) for the 155 °F /68 °C and 3/32 kler as shown in Figure 3.
NFPA standard. They are FM Ap- inch (2,4 mm) for the 200 °F /93 °C tem- Step 5. Replace the Protective Cap
proved as standard response - stand- perature ratings. (Ref. Figure 4) by pushing it upwards
and spray sprinklers for use in accord- until it bottoms out against the Support
ante with the current FM Loss A leak tight 1/2 inch NPTsprinkler joi Cup. The Protective Cap helps prevent
Prevention Data Sheets. should be obtained with a torque o 7 damage to the Deflector and Arms dur-
The Series RFII Concealed Pendent to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- ing ceiling installation and /or during
Sprinklers are only listed and ap- mum of 21 ft.lbs. (28,5 Nm) of torque application of the finish coating of the
proved with the Series RFII Concealed is to be used to install sprinklers. ceiling. It may also be used to locate
Higher levels of torque may distort the t he cente of the clearance hole b
Cover Plates having a metallic or white by
painted finish. spr i w consequent leak- gently pushing the ceiling material up
age or impairment of the sprinkler. against the center point of the Protec-
The Series RFII must not be used in Do not attempt to compensate for in- tive Cap.
applications where the air pressure sufficient adjustment in the Sprinkler
above the ceiling is greater than that Assembly by under- or over - tightening NOTE
•
below. Down drafts through the Sup- t S prinkler /Support Cup Assembly. A long as the Protective Cap remains
port Cup could delay sprinkler opera- Readjust the position of the sprinkler in place, the system is considered to
tion in a fire situation. fitting to suit. be "Out of Service ".
' Registered Trademark of DuPont
TFP181 Page 3 of 4 .
E OF CLEARAN HOLE F C LEARANCE -
SPRI L► DIAMETER - HO
- -- \_FFAIITC
IN G - \ DIMENSION C J " —" - `
► =
SPRINKLER ,.
SINKL Y S PP 1I
ASSEMBLY 1
I
I
1/2 (12,7 mm) _I.I-
• THREADED 4
D ADJUSTMENT l� ,...._.
. ,,At gag iiv
FACE OF CEILING,
•
RETAINING RING � FIGURE 4
MOUNTING '
U DISPOSABLE PROTECTIVE CAP
SURFACE T r, .
\ / / Step 6. After the ceiling has been corn-
`r � � p l e ted with the 2 -1/2 inch (63,5 mm)
• �1e diameter clearance hole and in prepa-
V ration for installing the Cover Plate As-
I I , _ I sembly, • remove and discard the Pro
C_ j __ _
T
• tective Cap, and verify that the
•
3/16° to 11/16° • MANUFACTURER DEFLECTOR COVER PLATE Deflector moves up and down freely. If
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER the Sprinkler has been damaged and
REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY the Deflector does not move up and
down freely, replace the entire Sprin-
COVER PLATE COVER PLATE • kler assembly. Do not attempt to mod-
.
— PROFILE DEPTH • DIAMETER ify or repair a damaged sprinkler. -
DIMENSION B DIMENSION A • Step 7. When installing an Air and
Dust Seal, refer to Figure 5, otherwise
. proceed to Step 8. To attach the Air and
A: 3 -1/4" (82,6 mm) C: 2 -3/8" to 2 -5/8" (60,3 to 66,7 mm) Dust Seal, verify the angle of the out -
B: 3/16" (4,8 mm) D: 1 -3/4" to 2 -1/4" (44,5 to 57,2 mm) side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
FIGURE 2 the Retainer in the grooved slot of the
SERIES RFII CONCEALED SPRINKLER Air and Dust Seal and continue around
INSTALLATION DIMENSIONS the retainer until the entire Air and
Dust Seal is engaged.
- NOTE •
• • • The Air and Dust Seal is only to be
installed on the periphery of the Re -,. •
_ — FRAME . ,bpi tamer. ARM it r Step 8. Screw on the Cover Plate /Re-
— I, • — "
tamer Assembly until the Retainer -
( ' —' — , Figure 2 (or Air and Dust Seal - Figure
j SUPPORT 5) contacts with the ceiling. Do not
I i!P I CuP i I continue to screw on the Cover
< Plate /Retainer Assembly such that it
���� ��������� lifts a ceiling panel out of its normal
i / � � ��„ mII 1 position. If the Cover Plate /Retainer
i ii / /�% Assembly cannot be engaged with the
O Support Cup or the Cover Plate /Re-
7/8° (23 mm) tainer Assembly cannot be engaged
SQUARE sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
ALIGN
O
ARROWS WITH Care and
FRAME ARMS
Maintenance
ACCEPTS The Series RFII must be maintained
O 1/2° SOCKET and serviced in accordance with the
DRIVE following instructions:
NOTES
FIGURE 3 Absence of the Cover Plate Assembly
RFII SPRINKLER WRENCH may delay sprinkler operation in a fire
situation.
Page 4 of 4 TFP181
When properly installed, there is a SUPPORT SPRINKLER FACE OF ORIENT
nominal 3/32 inch (2,4 mm) air gap CUP CEILING SEAL
between the lip of the Cover Plate and I eevELAs
• the ceiling, as shown in Figure 2. This lam`` COVER ., / SHOWN
air gap is necessary for proper opera- PLATE A
tion of the sprinkler. If the ceiling is to RETAINER -
be repainted after the installation of ?J I; ASSEMBLY '��
the Sprinkler, care must be exercised ,' '� -- v l
to ensure that the new paint does NOT % A §
seal off any of the air gap. 4L Al ai l w
I CLEAN
Factory painted Cover Plates MUST ' 1- . . __ ROOM
NOT be repainted. They should be re- �r LIP OF COVER SEAL
. placed, if necessary, by factory
RETAINER PLATE
painted units. FIGURE 5
Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504)
the Enclosure. Separation may result. .
Before closinga fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT
main control valve for maintenance local requirements and /or national SHALL TYCO FIRE PRODUCTS' LI-
work on the fire protection system that codes. ABILITY EXCEED AN AMOUNT
it controls, permission to shut down the EQUAL TO THE SALES PRICE.
affected fire protection system must be L imited THE FOREGOING WARRANTY IS
obtained from the proper authorities MADE IN LIEU OF ANY AND ALL
and all personnel who may be OTHER WARRANTIES EXPRESS OR
by this action must be notified. arranty IMPLIED. INCLUDING WARRANTIES
Sprinklers that are found to be leaking OF MERCHANTABILITY AND FIT -
or exhibiting visible signs of corrosion Products manufactured by Tyco Fire NESS FOR A PARTICULAR PUR- •
must be replaced. Products are warranted solely to the POSE,
Automatic sprinklers must never be original Buyer for ten (10) years
against defects in material and work -
painted, plated, coated or otherwise manship when paid for and properly
altered after leaving the factory. Modi- installed and maintained under normal Ordering
fled sprinklers must be replaced. use and service. This warranty will ex- Procedure
Sprinklers that have been exposed to pire ten (10) years from date of ship -
corrosive products of combustion, but ment by Tyco Fire Products. No war - When lacin an order, indicate the full
have not operated, should be replaced rant is iven for roducts or P g
if they cannot be completely cleaned y g P product name. Contact your local dis
components manufactured by compa- tributor for availability.
' by wiping the sprinkler with a cloth or nies not affiliated by ownership with
by brushing it with a soft bristle brush. Sprinkler Assembly:
Tyco Fire Products or for products and
a a ge to the sprinklers a before Iduring components which have been subject
rating) y Seri s (specify temperature
Pen-
9 P during, to misuse, improper installation, corro dent eci Sprinkler, P/N s
and after installation. Sprinklers dam- sion, or which have not been installed, p (P ty).
aged by dropping, striking, wrench maintained, modified or repaired in ac-
applicable Standards of 1 79 0 - 1-1 200F/93C
twist/slippage, or the like, must be re- cordance with a 1-2
PP TY3551 51- 790 -1 -155 51- 790 -1 -200
placed. Also, replace any sprinkler that the National Fire Protection Associa- TY35o4 51- 796 -1 -155 51- 796 -1 -200
has a cracked bulb or that has lost tion, and /or the standards of any other TY3531 51- 792 -1 -155 51 -792 -1 -200
liquid from its bulb. (Ref. Installation Authorities Having Jurisdiction. Mate - TY3505 51- 797 -1 -155 51- 797 -1 -200
Section). rials found by Tyco Fire Products to be
If a sprinkler must be removed, do not defective shall be either repaired or Separately Ordered Cover Plate:
reinstall it or a replacement without replaced, at Tyco Fire Products' sole Specify: (specify temperature rating)
reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate
If a Cover Plate Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify).
dislodged during service, replace it im- assume for it, any other obligation in
mediately. connection with the sale of products or 135F/57C(a) 165F/74C•(b)
parts of products. Tyco Fire Products Brass 56- 792 -1 -135 56- 792 -1 -165
P P Y Bright Brass 56- 792 -2 -135 56- 792 -2 -165
The owner is responsible for the in- shall not be responsible for sprinkler Chrome 56- 792 -9-135 56- 792 -9 -165
spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome 56- 792 -8 -135 56- 792 -8 -165
their fire protection system and de- incomplete information supplied by White 56- 792 -3-135 56- 792.3 -165
P y P PP Y White (RAL9010)' 56- 792 -3-135 56- 792 -3 -165
vices in compliance with this docu- Buyer or Buyer's representatives. Bright White 56- 792 -4 -135 56- 792 -4 -165
ment, as well as with the applicable IN NO EVENT SHALL TYCO FIRE Oft White 56-792-5-135 56- 792 -5 -165
standards of the National Fire Protec- PRODUCTS BE LIABLE, IN CON- Cu C 56- 792 -6-135 56- 792 -6-165
Custom 56- 792 -X -135 56- 792 -X -165
tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR
addition to the standards of any other UNDER ANY OTHER LEGAL THE- (a) For use with 155F/68C sprinklers.
jurisdiction. The in- (b) For use with 200F/93C
sales sprinklers.
authorities having J ORY, FOR INCIDENTAL, INDIRECT, • Eastern Hemisphere sales only.
• stalling contractor or sprinkler manu- SPECIAL OR CONSEQUENTIAL
facturer should be contacted relative to DAMAGES, INCLUDING BUT NOT Sprinkler Wrench:
any questions. LIMITED TO LABOR CHARGES, RE- Specify: RFII Sprinkler Wrench,
It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56- 000 -1 -075.
' sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal:
tested, and maintained by a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal,
P/N 56- 908 -1 -001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
tyro I Fire & Building
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series TY -FRB — Z8, 4.2, 5.6, and 8.0 K- factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General mospheres. Although corrosion resis-
tant coated sprinklers have passed the .�
standard corrosion tests of the appli- r ~ �: - .
Description cable approval agencies, the testing is `. ; ' •
not representative of all possible cor- , 7;
The Series TY -FRB, 2.8, 4.2, 5.6, and rosive atmospheres. Consequently, it . 1
8.0 K- factor, Upright and Pendent is recommended that the end user be I
Sprinklers described in this data sheet consulted with respect to the suitability C f
are quick response - standard cover- of these coatings for any given corro- •
age, decorative 3 mm glass bulb type sive environment. The effects of ambi- _
spray sprinklers designed for use in ent temperature, concentration of z
light or ordinary hazard, commercial chemicals, and gas /chemical velocity, —
occupancies such as banks, hotels, should be considered, as a minimum, — - . ^' _
shopping malls, etc. along with the corrosive nature of the
The recessed version of the Series chemical to which the sprinklers will be
TY-FRB Pendent Sprinkler, where ap- exposed. i��.......„
plicable, is intended for use in areas An intermediate level versions of the ____ \
with a finished ceiling. It uses either a Series TY-FRB Pendent Sprinklers are
two -piece Style 10 (1/2 inch NPT) or detailed in Technical Data Sheet +
Style 40 (3/4 inch NPT) Recessed Es- TFP356, and Sprinkler Guards are de- j
cutcheon with 1/2 inch (12,7 mm) of tailed in Technical Data Sheet TFP780 4
recessed adjustment or up to 3/4 inch / ;
(19,1 mm) of total adjustment from the WARNINGS �1- +s
flush pendent position, or a two -piece The Series TY -FRB Sprinklers de- t
Style 20 (1/2 inch NPT) or Style 30 (3/4 scribed herein must be installed and "'�.,
inch NPT) Recessed Escutcheon with maintained in compliance with this -.ter rr.w.
1/4 inch (6,4 mm) of recessed adjust- document, as well as with the applica-
ment or up to 1/2 inch (12,7 mm) of ble standards of the National Fire Pro TY3231 - Pendent 5.6K
total adjustment from the flush pen- tection Association, in addition to the enen ,1/2' NPT
dent position. The adjustment provided standards of any other authorities hay- TY4131 - Upright 8.0K, 3/4 "NPT
by the Recessed Escutcheon reduces ing jurisdiction. Failure to do so may TY4231 - Pendent 8.0K, 3/4 "NPT
the accuracy to which the fixed pipe impair the performance of these de-
drops to the sprinklers must be cut. vices. Technical
Corrosion resistant coatings, where The owner is responsible for maintain -
applicable, are utilized to extend the ing their fire protection system and de- Data
life of copper alloy sprinklers beyond vices in proper operating condition.
that which would otherwise be ob- The installing contractor or sprinkler Approvals
tained when exposed to corrosive at- manufacturer should be contacted UL and C -UL Listed.
with any questions. FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
IMPORTANT information including corrosion resis-
Always refer to Technical Data tant status.)
Sheet TFP700 for the "INSTALLER Model/Sprinkler
WARNING" that provides cautions p Maximum Working Pressure
with respect to handling and instal- Identification 175 psi (12,1 bar)
lation of sprinkler systems and com- Discharge Coefficient
ponents. Improper handling and in- Numbers K = 2.8 GPM /psili (40,3 LPM/barli
stallation can permanently damage K = 4.2 GPM /psi / (60,5 LPM /barli
a sprinkler system or its compo- TY1131 - Upright 2.8K, 1/2 "NPT K = 5.6 GPM /psi (80,6 LPM /barlI
nents and cause the sprinkler to fail TY1231 - Pendent 2.8K, 1/2"NPT K = 8.0 GPM /psi (115,2 LPM /bar
• to operate in a fire situation or cause TY2131 - Upright 4.2K, 1/2"NPT Temperature Ratings
it to operate prematurely. TY2231 - Pendent 4.2K, 1/2"NPT Refer to Table A and B
TY3131 - Upright 5.6K, 1/2"NPT
Page 1 of 8 JULY, 2004 TFP171
Page 2 of 8 TFP171
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING „ ** NOMINAL RECESSED
*
SURFACE 1/2 MAKE -IN ESCUTCHEON SSU
1 NPT .DEFLECTOR
T �= fir r — — i *';TTr. 6
MS- 7/16” � S
2 1/4" } � (11,1 mm) i 4
(57,2 mm) ��� �- I NOMINAL
i � 7 1� MAKE IN 2
1- 9/16" I
4IP I r� 2- 3 3
(39,7 mm) WRENCH 1 (55,6 mm) p v ��
FLATS �!� 1
l = /1!� /%rim 111174 7
SSP DEFLECTOR ' 2 -7/8° (73,0 mm) DIA. 1/2" NPT 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16° (11,1 mm) STYLE 10 or 20
PLATE SEATING * * NOMINAL RECESSED
SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR
I - -_ 1 6*
M= W r 7/16 �� 5
2 -3/16° } O, (11,1 mm) I
(55,6 mm) A =� � NOMINAL ; 4
�i, MAKE -IN 1 -1/2" te I 2 -3/16° rie 2
(38,1 mm) I I P 1 v WRENCH 1 (55,6 mm)
II II F LATS = '1 �� 3
SSP DEFLECTOR * — 2 -7/8° (73,0 mm) DIA. 1/2° NPT ** I
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw ** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K- FACTOR, 1/2 INCH NPT
CO
Finishes Bulb Glass v
Sprinkler: Refer to Table A and B Compression Screw Bronze Operation
Recessed Escutcheon: White Coated, Deflector Copper /Bronze a
Chrome Plated, or Brass Plated Bushing (K =2.8) Bronze The glass Bulb contains a fluid which 2
expands when exposed to heat. When y
the rated temperature is reached, the 0)
Physical Characteristics fluid expands sufficiently to shatter the
F
cr
rame Bronze glass Bulb, allowing the sprinkler to =
. Button Brass /Copper o
activate and water to flow. a
Sealing Assembly o
Beryllium Nickel w/Teflont
TFP171 Page 3 of 8
ESCUTCHEON 7/16° (11,1 mm) STYLE 10 or 20
PLATE SEATING *. NOMINAL RECESSED
. SURFACE MAKE-IN ESCUTCHEON DEFLECTOR
6
IMEI_ IM� aFilifilplpir
2 -3/16° —7- 1�� 7/16"
X11 �� I (11,1 mm)
(55,6 mm) li NOMINAL' 4
411 MAKE -IN
(38,1 / mm) I WREN I H 11/11 55,6 mm V r 2
FLATS ( ) 3
1
SSP DEFLECTOR — 2-7/8 (73,0 mm) DIA. 1/2" NPT **
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
. FIGURE 3
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2° (12,7 mm) STYLE 30 or 40
PLATE SEATING ** NOMINAL RECESSED
•
SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR
it rat t''i riE P1 1 7-
f " 5
6
1/2° 2
2 5/16° 11 (12,7 mm
(58,7 mm) ��� � NOMINAL
� I i 4
. i `��� Ilk MAKE -IN I 1 -9/16° I �I � WRENCH 1 2 -1/4" V �
(39,7 mm) ' 2
= (57,2 mm)
b
II . FLATS 7 3
1 1 111 df 1
SSP DEFLECTOR * - 2 -7/8° (73,0 mm) DIA. 3/4° NPT f
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
* * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
Listing is based on the requirements of
Design NFPA 13, and FM Approval is based Installation
on the requirements of FM's Loss Pre-
Criteria vention Data Sheets ). Only the Style The Series TY -FRB Sprinklers must be
• 10, 20, 30, or 40 Recessed Escutch- installed in accordance with the follow -
The Series TY -FRB Pendent and Up- eon, as applicable, is to be used for ing instructions:
right Sprinklers are intended for fire recessed pendent installations.
protection systems designed in ac- NOTES
cordance with the standard installation Do not install any bulb type sprinkler if
rules recognized by the applicable the bulb is cracked or there is a loss of
Listing or Approval agency (e.g., UL liquid from the bulb. With the sprinkler
Page 4 of 8 TFP171
SPRINKLER FINISH (See Note 7) inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
K TYPE TEMP. BULB NATURAL CHROME WHITE "'
LIQUID BRASS PLATED POLYESTER (13,4 to 26,8 Nm). A maximum of 30
•
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con -
135°F/57°C Orange nections. Higher levels of torque may
PENDENT 155 °F /68 °C Red distort the sprinkler inlet and cause
(TY1231) 1, 2, 3, 5 leakage or impairment of the sprinkler.
and 175 °F /79 °C Yellow
UPRIGHT Do not attempt to make -up for insuffi-
200 °F /93 °C Green cient adjustment in the escutcheon
(TY1131)
2.8 286°F/141°C Blue plate by under- or over - tightening the
1/2" sprinkler. Readjust the position of the
NPT 135 °F /57 °C Orange sprinkler fitting to suit.
RECESSED 155 °F /68 °C Red
PENDENT The Series TY -FRB Pendent and Up-
•
(TY1231)• 175 °F /79 °C Yellow right Sprinklers must be installed in
Figure 5 accordance with the following instruc-
g ure 200 °F /93 °C Green 1, 2, 5 tions.
135 °F /57 °C Orange Step 1. Pendent sprinklers are to be
RECESSED Red installed in the pendent position, and
PENDENT upright sprinklers are to be installed in
(TY1231)•• 175 °F /79 °C Yellow the upright position.
Figure 6 200 °F /93 °C Green Step 2. With pipe thread sealant ap-
135 °F /57 °C Orange plied to the pipe threads, hand tighten
PENDENT the sprinkler into the sprinkler fitting.
(TY2231) 155 °F /68 °C Red Step 3. Tighten the sprinkler into the
and 175 °F /79 °C Yellow sprinkler fitting using only the W - Type
UPRIGHT 200F/93°C Green 6 Sprinkler Wrench (Ref. Figure 13).
(TY2131) With reference to Figures 1, 2, 3, and
4.2 286 °F /141 °C Blue 2 4, the W -Type 6 Sprinkler Wrench is to
1/2" be applied to the sprinkler wrench
NPT 135 °F /57 °C Orange flats.
RECESSED 155 °F /68 °C Red
PENDENT
(TY2231)* 175 °F /79 °C Yellow The Series TY -FRB Recessed Pen-
Figure 7 200 °F /93 °C Green dent Sprinklers must be installed in
accordance with the following instruc-
135°F/57°C Orange Lions.
RECESSED 155 °F /68 °C Red Step A. After installing the Style 10.
PENDENT 20, 30, or40 Mounting Plate, as appli-
(TY2231)** 175 °F /79 °C Yellow cable, over the sprinkler threads and
Figure 8 200 °F /93 °C Green with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
NOTES: kler into the sprinkler fitting.
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. Step B. Tighten the sprinkler into the
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response sprinkler fitting using only the W - Type
Sprinklers. 7 Recessed Sprinkler Wrench (Ref.
klers.proved by Factory Mutual Research Corporation (FM) as Quick Response Sprin- Figure 14). With reference to Figure 1,
5. Approved by the City of New York under MEA 354 -01 -E. 2, 3, and 4, the W - Type 7 Recessed
7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- Sprinkler Wrench is to be applied to
klers are UL and C -UL Listed as Corrosion Resistant Sprinklers. the sprinkler wrench flats.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Step C. After the ceiling has been in-
Recessed Escutcheon, as applicable. stalled or the finish coat has been ap-
Installed with Style 20 (1/2" NPT) or Style 30 (3/4° NPT) 1/2" Total Adjustment
plied, slide on lied, slid the Style 10, 20, 30, or
Recessed Escutcheon, as applicable. tY
°-° Frame and Deflector only. Listings and approvals apply to color (Special Order). 40 Closure over the Series TY
N /A: Not Available Sprinkler and push the Closure over
the Mounting Plate until its flange
TABLE A comes in contact with the ceiling.
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K- FACTOR SPRINKLERS
held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint
should be present. The diameter of the should be obtained with a torque of 7
air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi -
• (1,6 mm) for the 135 °F /57 °C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque
inch (2,4 mm) for the 286°F/141°C may be used to install sprinklers with
temperature ratings. 1/2 NPT connections. A leak tight 3/4
TFP171 Page 5 of 8
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL CHROME WHITE "' LEAD
LIQUID BRASS PLATED POLYESTER COATED
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY3231) 1,2,3,4,5,6,7 1,2,3,5
and 175 °F /79 °C Yellow
UPRIGHT 200 °F /93 °C Green
5.6 (TY3131) 286°F/141°C Blue
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 4, 5 N/A
(TY3231)* 175 °F /79 °C Yellow
Figure 9 200 °F /93 °C Green
135 °F /57 °C Orange
RECESSED
PENDENT 155 °F /68 °C Red
1, 2, 3, 4, 5 1, 2, 4, 5 N/A
(TY3231)" 175 °F /79 °C Yellow
•
Figure 10 200 °F /93 °C Green
135 °F /57 °C Orange
•
PENDENT 155 °F /68 °C Red
(TY4231)
1, 2, 5
and 175 °F /79 °C Yellow
1, 2, 3, 4, 5, 6, 7
UPRIGHT 200 °F /93 °C Green •
8.0 (TY4131)
286°F/141°C Blue
3/4"
NPT 135 °F /57 °C Green
RECESSED 155 °F /68 °C Orange
PENDENT 1, 2, 4, 5 N/A
(TY4231)* 175 °F /79 °C Red
Figure 11 200 °F /93 °C Yellow
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4231) ** 175 °F /79 °C Yellow
Figure 12 200 °F /93 °C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
• LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428 - 3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
• Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
• Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
"" Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K- FACTOR SPRINKLERS
Page 6 of 8 TFP171 •
•
' 2 -7/8° DIA. _ 2 -7/8° DIA.
(73,0 mm) . 3/4° (19,1 mm) 1/ 1/8 - - -^ .(73,0 mm) 1/2" (12,7 mm)
- — 5/8x1/4 ° —
• (15,9±6,4 mm) 2 -1/4° DIA. 1/4' (6,4 mm) (12,7x3,2 mm) 2 -1/4' DIA. 1/4° (6,4 mm)
FACE OF (57,2 mm) FACE OF (57,2 mm) MOUNTING
MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8' 1/8°
•�i (3 mm) •. (3,2 mm)
� 1 0 11i i llvl %/'
:1_
yr Mt i % _ } \
;, � %� MOUNTING IN
MOUNTING SURFACE � .
SURFACE � — . 'y'" =��
• SERIES 1 -5/16' (33,3 mm) CLOSURE SERIES 1 -5/16' (33,3 mm)
• CLOSURE Ty -FRB 13/16' (20,6 mm) TY -FRB 1 -1/16' (27,0 mm)
FIGURE 5 • FIGURE 6
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WIT H TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT • • WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
' STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
• 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT
• 2 -7/8° DIA. 2- 7 /8' - . •
•
5/8x1/4° (73,0 mm) 3/4° (19,1.mm) 1/2x1/8° (73,0 mm) 1/2° (12,7 mm)
(15,936,4 mm) 2 -1/4° DIA. 1 1/4" (6,4 mm) (12,7x3,2 mm) 2 -1/4° DIA. 1/4° (6,4 mm)
(57,2 mm) ' • FACE OF (57,2 mm) MOUNTING
FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE .
FITTING FITTING •
1/8' 1/8°
1111 Will
(3,2 mm) lltV�i ( 3,2 mm ) ::
yal
Al I f 11
, r MOUN
MOUNTING �i . SURFACE _
• • SURFACE - —
. SERIES 1 -1/4' (31,8 mm) • CLOSURE SERIES 1 -1/4' (31,8 mm)
CLOSURE Ty -FRB 3/4' (19,1 mm) TY -FRB 1' (25,4 mm)
FIGURE 7 • FIGURE 8 •
SERIES TY-FRB RECESSED PENDENT '• SERIES TY -FRB RECESSED PENDENT •
• WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT
used to cover a clearance hole, may a after installation. Sprinklers dam -
Care and delay the time to sprinkler operation in aged by dropping, striking, wrench
a fire situation. twist/slippage, or the like, must be re-
Maintenance Sprinklers that are found to be leaking has a cracked bulb or replace has lost
The Series TY-FRB Sprinklers must be or exhibiting visible signs of corrosion liquid from its bulb. (Ref. Installation
maintained and serviced in accord- must be replaced. Section).
ance with the following instructions: Automatic sprinklers must never be Frequent visual inspections are rec-
painted, plated, coated or otherwise omquent visual
to be initially performed for
NOTES altered after leaving the factory. Modi- corrosion resistant coated sprinklers,
Before closing a fire protection system fied sprinklers must be replaced. after the installation has been com-
main control valve for maintenance Sprinklers that have been exposed to plated, to verify the integrity of the cor-
work on the fire protection system that corrosive products of combustion, but rosion resistant coating. Thereafter,
it controls, permission to shut down the have not operated, should be replaced annual inspections per NFPA 25
affected fire protection system must be if they cannot be completely cleaned should suffice; however, instead of in-
obtained from the proper authorities by wiping the sprinkler with a cloth or specting from the floor level, a random
and all personnel who may be affected by brushing it with a soft bristle brush. sampling of close-up visual inspec
• by this action must be notified. Care must be exercised to avoid dam- tions should be made, so as to better
Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi-
•
TFP171 Page 7 of 8
• 2 -7/8' DIA. 2 -7/8' DIA.
(73,0 mm) (73,0 mm)
_ .. __ _ _5/8±1/4__ _ 3/4' (19,1 mm) __- -,_ __ - 1/2' (12,7 mm)
(15,9x6,4 mm) 2 -1/4' DIA. 1/4' (6,4 mm) (12,7 ±3,2 mm) •
2 -1/4' DIA. 1/4' (6,4 mm)
• FACE OF (57,2 mm) (57,2 mm)
MOUNTING FACE OF MOUNTING
SPRINKLER
FITTING PLATE S FITTING NG R PLATE
1/8' I 1 /8' •
•ai (3,2 mm) •. (3,2 mm)
PI
ltlli r ltivf ��'
,,A . �� I i[ } \
� }
S , ' O URFACE �'
MOUNTING 1�
•
SURFACE - - -- - = PI
-,•- • CLOSURE SERIES 1 -1/4' (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm)
TY -FRB 3/4' (19,1 mm) TY -FRB 1' (25,4 mm)
. FIGURE 9 FIGURE 10
- SERIES TY -FRB RECESSED PENDENT - SERIES TY-FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT • WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON • STYLE 20 RECESSED ESCUTCHEON
5.6 K- FACTOR, 1/2 INCH NPT • 5.6 K- FACTOR, 1/2 INCH NPT
2 -7/8' DIA. • 2 -7/8' DIA.
• (73,0 mm) 3/4' (19,1 mm) (73,0 mm) 1/2' (12,7 mm)
5/8±1/4' 1/2x1/8'
(15,9x6,4 mm) 2 -1/4' DIA. �. I 1/4' (6,4 mm) (12,7 ±3,2 mm) 2 -1/4' DIA. - 1/4' (6,4 mm)
(57,2 mm) ( m • FACE OF MOUNTING FACE OF � MOUNTING •
SPRINKLER • PLATE SPRINKLER -- PLATE
FITTING • FITTING '
1/8' 1/8'
"
(3,2 mm) n
EIM___-_. r)�I ( ) (3,2 mm)
, Mmir" w' I '
- t -
MOUNTING VP f
MOUNTING �I SURFACE
•
SURFACE , ,
CLOSURE SERIES • - . 1 -5/16' (33,3 mm) CLOSURE SERIES 1 -5/16' (33,3 mm)
TY-FRB 13/16' (20,6 mm) TY-FRB 1 -1/16' (27,0 mm)
• FIGURE 11 FIGURE 12
. SERIES TY -FRB RECESSED PENDENT. • ' SERIES TY-FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT ,' WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT • '
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
• 8.0 K- FACTOR, 3/4 INCH NPT . 8.0 K- FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may WRENCH •
be affected by the corrosive conditions ' RECESS
present.
WRENCH RECESS �w�
The owner is responsible for the in- (END °A° USED FOR '
spection, testing, and maintenance of ^ 1/2° NPT MODELS) /�
their fire protection system and de- ......-0 �iU(
vices in compliance with this docu-
ment, as well as with the applicable ` ,
standards of the National Fire Protec- WRENCH RECESS PUSH WRENCH
tion Association (e.g., NFPA 25), in (END "B" USED FOR
g ' 3/4° NPT MODELS) IN TO ENSURE
addition to the standards of any other ENGAGEMENT
authorities having jurisdiction. The in- WITH SPRINKLER
stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA
. facturer should be contacted relative to W - TYPE 6 SPRINKLER
any questions. WRENCH
It is recommended that automatic FIGURE 14
sprinkler systems be inspected, local requirements and /or national W - TYPE? RECESSED
tested, and maintained by a qualified codes. SPRINKLER WRENCH
Inspection Service in accordance with
•
•
•
Page8of8 TFP171
•
•
• - - -- P/N 57- XXX - -X- - XXX-
TEMPERATURE •
MODEL/SIN RATING
SPRINKLER - .
330 2.8K UPRIGHT (1 /2 "NPT) TY1131 135 135 °F /57 °C
331 2.8K PENDENT (1 /2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C
340 4.2K UPRIGHT (1 /2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C •
341 4.2K PENDENT (1 /2 "NPT) TY2231 3 WHITE (RAL9010)• 200 200 °F /93 °C
370 5.6K UPRIGHT (1 /2 "NPT) TY3131 9 CHROME PLATED - 286 286 °F /141 °C
371 5.6K PENDENT (1 /2 "NPT) TY3231 7 LEAD COATED
390 8.OK UPRIGHT (3 /4 "NPT) TY4131
391 8.0K PENDENT (3 /4 "NPT) • •TY4231 • Eastern Hemisphere sales only.
. TABLE C
: PART NUMBER SELECTION --
SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS ' • •
ORY, FOR INCIDENTAL, INDIRECT, Recessed Escutcheon:
Limited SPECIAL OR CONSEQUENTIAL Specify: Style (specify) Recessed Es-
DAMAGES, INCLUDING BUT NOT cutcheon with (specify finish), P/N
Warranty LIMITED TO LABOR CHARGES, RE- (specify).
• GARDLESS OF WHETHER TYCO
Products manufactured by Tyco Fire FIRE PRODUCTS WAS INFORMED 1/2 ".(15mm)
Products are warranted solely to the ABOUT THE POSSIBILITY OF SUCH Style 10
original Buyer for ten (10) years DAMAGES, AND IN NO EVENT Chrome Plated P/N 56- 701 -9 -010
• against defects in material and work- SHALL TYCO FIRE PRODUCTS' LI- White Coated P/N 56- 701 -4 -010
manship when paid for and properly ABILITY EXCEED AN AMOUNT Br a s s Plated 0• P/N 56- 701 -3 -010
installed and maintained under normal Brass Plated P/N 56-701-2-010
EQUAL TO THE SALES PRICE.
use and service. This warranty will ex- THE FOREGOING WARRANTY IS 1/2° (15 mm) •
' pire ten (10) years from date of ship- Style 20 .
ment by Tyco Fire Products. No war- MADE IN LIEU OF ANY AND ALL Chrome Plated P/N 56 -705 -9 -010
ranty is given for products or OTHER WARRANTIES EXPRESS OR White Coated P/N 56 -705 -4 -010 .
components manufactured by compa IMPLIED. INCLUDING WARRANTIES - White RAL9010• P/N 56- 705 -3 -010
Hies not affiliated by ownership with OF MERCHANTABILITY AND FIT- . Brass Plated P/N 56- 705 -2 -010
Tyco Fire Products or for products and NESS FOR A PARTICULAR PUR- • 3/4° (20 mm)
components which have been subject POSE, Style 30
to misuse, improper installation, corro- Chrome Plated ' P/N 56- 705 -9 -011
sion, or which have not been installed, White Coated P/N 56- 705 -4 -011
maintained, modified or repaired in ac- White Plated 0• P/N 56- 705 -3 -011
cordance with applicable Standards of r der�ng Brass Plated P/N 56- 705 -2 -011
the National Fire Protection Associa- Procedure . 3/4° (20 mm)
tion, and /or the standards of any other Style 40 .
Authorities Having Jurisdiction. Mate- Otatarabygun Emcal distributor for avail- Chrome Plated P/N 56- 700 -9 -010
rials found by Tyco Fire Products to be abpltv .indicate the White Coated P/N 56- 700 -4 -010
defective shall be either repaired or fulrproduct White RAL9010• P/N 56 -700 -3 -010
re replaced, at Tyco Fire Products' sole name. Refer to Brass Plated P/N 56 -700 -2 -010
p y the Price List for
option. Tyco Fire Products neither as- complete listing • Eastern Hemisphere sales only.
sumes, nor authorizes any person to of Part Numbers.
assume for it, any other obligation in Sprinkler Wrench:
connection with the sale of products or Sprinkler Assemblies with NPT Specify: W -Type 6 Sprinkler Wrench,
parts of products. Tyco Fire Products Thread Connections: P/N 56- 000 -6 -387.
shall not be responsible for sprinkler Specify: (Specify Model /SIN), Quick
• system design errors or inaccurate or Response, (specify K- factor), (specify Specify: W -Type 7 Sprinkler Wrench,
incomplete information supplied by temperature rating), Series TY-FRB P/N 56- 850 -4 -001.
• Buyer or Buyer's representatives. (specify Pendent or Upright) Sprinkler
IN NO EVENT SHALL TYCO FIRE with (specify type of finish or coating),
• PRODUCTS BE LIABLE, IN CON P/N (specify from Table C).
TRACT, TORT, STRICT LIABILITY OR '
UNDER ANY OTHER LEGAL THE -