Loading...
Specifications FP52oto - col - .2_6 13 22 1 S t/✓'g au) y I CO tqco Fire & Building Products Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series EC -11 & EC -14 — 11.2 and 14.0 K- factor Extended Coverage (Light and Ordinary Hazard) Upright, Pendent, and Recessed Pendent Sprinklers Corrosion resistant coatings, where General applicable, are utilized to extend the life of copper alloy sprinklers beyond Description that which would otherwise be ob- tained when exposed to corrosive at- -' The Tyco® Series EC -11 and EC -14 mospheres. Although corrosion resis- u Extended Coverage Upright and Pen- tant coated sprinklers have passed the ' > dent Sprinklers are decorative glass standard corrosion tests of the appli- 1 ., 1 bulb sprinklers designed for use in cable approval agencies, the testing is > light or ordinary hazard occupancies. not representative of all possible cor- ` They are intended for use in automatic rosive atmospheres. Consequently, it .• ', sprinkler systems designed in accord- is recommended that the end user be _ +'`� = -" I ance with standard installation rules consulted with respect to the suitability' • (e.g., NFPA 13) for a maximum cover- of these corrosion resistant coatings • age area of 400 ft (37,2 m as corn- for any given corrosive environment. pared to the maximum coverage area The effects of ambient temperature, of 130 ft (12,1 m for standard cover- concentration of chemicals, and age sprinklers used in ordinary haz- gas /chemical velocity, should be con - and occupancies or 225 ft (20,6 m sidered, as a minimum, along with the for standard coverage sprinklers used corrosive nature of the chemical to in light hazard occupancies. which the sprinklers will be exposed. The Series EC -11 and EC -14 Sprin- klers feature a UL and C -UL Listing WARNINGS that permits their use with unob The Series EC -11 and EC -14 Ex- structed or non-combustible ob tended Coverage Sprinklers described structed ceiling construction as de- herein must be installed and main - fined and permitted by NFPA 13, as tained in compliance with this docu- well as a specific application listing for ment, as well as with the applicable use under concrete tees. standards of the National Fire Protec- tion Association, in addition to the The Series EC -11 and EC -14 Ex- standards of any otherauthorities hay- tended Coverage Sprinklers have ing jurisdiction. Failure to do so may been fire tested to compare their per- impair the performance of these de- formance to that of standard coverage vices. spray sprinklers. These tests have Model /Sprinkler shown that the protection provided is The owner is responsible for maintain - equal to or more effective than stand- ing their fire protection system and d e Identification and coverage spray sprinklers. vices in proper operating condition. The installing contractor or sprinkler Number manufacturer should be contacted with any questions. TY5137 - Upright, 11.2K IMPORTANT TY5237 - Pendent, 11.2K Always refer to Technical Data TY6137 - Upright, 14.0K Sheet TFP700 for the "INSTALLER TY6237 - Pendent,14.0K WARNING" that provides cautions TY5137 is a redesignation for C5137, • with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- TY5237 is a redesignation for C5237, stallation can permanently damage G1893, and S2511. a sprinkler system or its compo- nents and cause the sprinkler to fail TY6137 is a redesignation for C6137, to operate in a fire situation or cause 01896, and S2610. it to operate prematurely. TY6237 is a redesignation for C6237, G1895, and S2611. Page 1 of 8 DECEMBER, 2007 TFP220 • . 1 . Page 2 of 8 TFP22O - WRENCH 3/4" ** ESCUTCHEON PLATE FLAT NPT SEATING SURFACE _1 1 - Frame 2 - Button fir't 1 % Q • 3 - Bugling Assembly 2 . 4 -Bulb Il k 5 - Compression Screw B pi 1 Aks 6 - Defloctor' 1 2- 7/16" . _., 3 • Loikii (6 1,9 mm) r � ' Temperature rating is I UPRIGHT & . indicated on deflector MINI PENDENT ' 1- 11/16" r 4 • •• Pipe thread = + c (42,7 mm) ) connections per ISO ' 5 7/1 can be provided ,s �� on special request. -• - -- — — — - - -.• __ „Alp I 1/2" (12,7 mm) j 6* NOMINAL MAKE -IN CROSS UPRIGHT PENDENT SECTION FIGURE 1 SERIES EC -11 AND EC -14 EXTENDED COVERAGE SPRINKLERS 11.2 K- FACTOR (TY5137) UPRIGHT AND (TY5237) PENDENT 14.0 K- FACTOR (TY6137) UPRIGHT AND (TY6237) PENDENT SPRINKLER FINISH (See Note 5) HAZARD TYPE TEMP. BULB NATURAL CHROME WHITE' LEAD LIQUID BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange UPRIGHT 155 °F /68 °C • Red 1, 2, 3", 4 LIGHT K =11.2 (TY5137) PENDENT 175 °F /79 °C Yellow K =11.2 (TY5237) 200 °F /93 °C Green 1, 2, 4 1, 2, 4 Refer to Table B for K =14.0 (TY6237) UL and C - UL 286 °F /141 °C Blue Sensitivity Rating 135 °F /57 °C Orange and REC. PENDENT 1, 2, 3, 4 Refer to Table C for K =11.2 (TY5237) 155'F/68°C Red N/A • FM K =14.0 (TY6237) • 175 °F /79 °C Yellow - Sensitivity Rating With Style 30 1, 2, 4 Escutcheon 200 °F /93 °C Green 286 °F /141 °C Blue UPRIGHT 135 °F /57 °C Orange K =11.2 (TY5137) 155 °F /68 °C Red 1, 2, 3, 4 ORDINARY K =14.0 (TY6137) _ 1, 2, 3, 4 — and 175 °F /79 °C Yellow Refer to Table B for PENDENT 200 °F /93 °C Green 1, 2, 4 UL and C -UL K =11.2 (TY5237) Sensitivity Rating K =14.0 (TY6237) 286'F/141°C Blue and REC. PENDENT 135 °F /57 °C Orange Refer to Table C for K =11.2 (TY5237) 155'F/68°C Red FM K =14.0 (TY6237) 1, 2, 4 N/A Sensitivity Rating With Style 40 175 °F /79 °C Yellow Escutcheon 200 °F /93 °C Green NOTES: 1.Listed by Underwriters Laboratories, Inc. (UL). . 2.Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL). 3. Approved by Factory Mutual Research Corporation (FM). 4. Approved by the City of New York under MEA 177 -03 -E. 5. Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as - Corrosion Resistant Sprinklers. 'Frame and Deflector only. Listings and approvals apply to color (Special Order). ' Pendent Only. N /A: Not Available TABLE A, LABORATORY LISTINGS AND APPROVALS • TFP22O Page 3 of 8 LIGHT HAZARD ORDINARY HAZARD 135 °F 155 °F 175 °F 200 °F 286 °F 135 °F 155 °F 175 °F 200 °F 286 °F AREA STYLE 14 x 14 Up. or Pend. — — — — — OR OR QR OR SR 14 x 14 Style 30 Recessed — — — — — QR OR QR QR N/A 14 x 14 Style 40 Recessed — — — — — QR OR QR QR N/A 16 x 16 Up. or Pend. QR' OR' OR* OR' OR' SR SR SR SR SR 16 x 16 Style 30 Recessed OR' OR' OR' OR' OR' SR SR SR SR N/A 16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR N/A 18 x 18 Up. or Pend. OR' OR' OR' OR' OR' SR SR SR SR SR 18 x 18 Style 30 Recessed OR' OR' OR' OR' OR' SR SR SR SR N/A 18 x 18 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR N/A 20 x 20 Up. or Pend. OR' OR' OR' SR' SR' SR SR SR SR SR 20 x 20 Style 30 Recessed OR'. SR' OR' SR' SR' SR SR SR SR N/A 20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR N/A QR: Quick Response • SR: Standard Response N /A: Not Applicable ' Does not apply to Upright K = 14.0 TABLE B SENSITIVITY RATING FOR UL AND C -UL LISTING OF SERIES EC -11 OR EC -14 SPRINKLERS (SEE TABLE D FOR PERMITTED K- FACTOR /AREA COMBINATIONS) LIGHT HAZARD ORDINARY HAZARD 135 °F 155 °F 175 °F 200 °F 286 °F 135 °F 155 °F 175 °F 200 °F 286 °F AREA STYLE • 14 x 14 Up. or Pend. — — — — — SR SR SR SR SR 14 x 14 Style 30 Recessed — — — — — N/A N/A N/A N/A N/A 14 x 14 Style 40 Recessed — — — — — N/A N/A N/A N/A N/A 16 x 16 Up. or Pend. OR' OR' N/A N/A N/A SR SR SR SR SR 16 x 16 Style 30 Recessed OR QR N/A N/A N/A N/A N/A N/A N/A N/A 16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 18 x 18 Up. or Pend. OR' OR' N/A N/A N/A SR SR SR SR SR 18 x 18 Style 30 Recessed QR QR N/A N/A N/A N/A N/A N/A N/A N/A 18 x 18 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 20 x 20 Up. or Pend. OR OR' N/A N/A N/A SR SR SR SR SR 20 x 20 Style 30 Recessed QR QR N/A N/A N/A N/A N/A N/A N/A N/A 20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A QR: Quick Response SR: Standard Response N /A: Not Applicable ' Pendent Only TABLE C SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC -11 OR EC -14 SPRINKLERS (SEE FM LOSS PREVENTION DATA SHEET 2 -8N FOR PERMITTED K- FACTOR /AREA COMBINATIONS) Page 4 of 8 TFP22O Sprinklers, to prevent cold solder - Technical Operation ing, is 8 feet (2,4 m) for upright sprin- --klers-and-9-feet-(Z7-m)-for-pendent •__ D ata The glass bulb contains a fluid which sprinklers. . expands when exposed to heat. When Approvals the rated temperature is reached, the 5. The Series EC -11 and EC -14 Sprin- The Series EC -1 1 and EC -14 Ex- fluid expands sufficiently to shatter the klers are to be installed in accord - tended Coverage Upright, Pendent, glass bulb, which then allows the ance with all other requirements of and Recessed Pendent Sprinklers are sprinkler to activate and flow water. NFPA 13 for extended coverage up- UL and C -UL Listed. (Refer to Table A right and pendent sprinklers. For ex- for complete sprinkler approval infor- ample: obstructions to sprinkler dis- mation including corrosion resistant Design charge, obstructions to sprinkler status. The approvals apply to the /+ pattern development, obstructions service conditions indicated in the De- Criteria to prevent sprinkler discharge from sign Criteria section.) The Tyco Series EC 11 and EC 14 reaching hazard, clearance to stor- The Series EC -11 and EC -14 Ex- Extended Coverage Sprinklers must age, etc. tended Coverage Upright and Pendent only be installed in accordance with UL Sprinklers are FM Approved. (Refer to the applicable UL and C -UL Listing or and Specific As For Table A for complete sprinkler ap- FM Approval requirements as indi- Lsting Reequiqui r ement proval information including corrosion cated below. Only the Style 30 or 40 Ins tallation Under Concrete Tees resistant status. The approvals apply Recessed Escutcheon is to be used for Th e Se Ender 1 and EC 14 Ex- • to the service conditions indicated in recessed installation, as applicable tended Coverage Upright and Pendent the Design Criteria section.) (Ref. Table A, B, and C).. Sprinklers ( h a , TY5237, TY6137 & TY6237) have a UL and C -UL Spe- The Style 60 Two -Piece Flush Es- UL and C -UL Listing cific Application Listing for use under cutcheon (Ref. Figure 4) is UL Listed Requirements concrete tees when installed as fol- and FM Approved for use with the Se- lows: . ries EC -11 and EC -14 Pendent Sprin- 1. The Series EC -11 and EC -14 Sprin- klers. klers may be used for the coverage 1. The stems of the concrete tee con - Maximum Working Pressure areas shown in Table D, based on struction must spaced at less than 175 psi (12,1 bar) maintaining the minimum specified 7.5 feet (2,3 m) on center but more flow rate as a function of coverage than 3 feet (0,9 m) on center. The Pipe Thread Connection area and hazard group for all of the depth of the concrete tees must not 3/4 inch NPT sprinklers in the design area. exceed 30 inches (762 mm). The Discharge Coefficients maximum permitted concrete tee K = 11.2 GPM /psi112 2. The Series EC -11 and EC -14 Sprin- length is 32 feet (9,8 m); however, • (161,3 LPM /bar1'2) klers are permitted to be used with where the concrete tee length ex- K = 14.0 GPM /psi112 unobstructed or non - combustible ceeds 32 feet (9,8 m), non- combus- (201,6 LPM /bar1/2) obstructed ceiling construction as tible baffles, equal in height to the defined and permitted by NFPA 13. depth of the tees, can be installed so Temperature Ratings For example: that the space between the tees 135 °F /57 °C to 286 °F /141 °C does not exceed 32 feet (9,8 m) in Finish Unobstructed, combustible or non- length. Sprinkler: Refer to Table A combustible, ceiling construction • Recessed or Flush Escutcheon: White with a deflector to ceiling /roof deck 2. The sprinkler deflectors are to be Coated, Chrome Plated, and Brass distance of 1 to 12 inches (25 to 300 located in a horizontal plane at or Plated mm). above 1 inch (25,4 mm) below the bottom of the concrete tee stems. Physical Characteristics Obstructed, non - combustible, ceil- Frame Bronze ing construction with a deflector lo- 3. When the sprinkler deflectors are Button Bronze cation below structural members of located higher than a horizontal Sealing Assembly 1 to 6 inches (25 to 150 mm) and a plane 1 inch (251,4 mm) beneath the Beryllium Nickel w/Teflon t maximum deflector to ceiling /roof bottom of the concrete tee stems, Bulb Glass (3 mm dia.) deck distance of 22 inches (550 the obstruction to sprinkler dis- Compression Screw mm). charge criteria requirements of Bronze NFPA 13 for extended coverage up- Deflector Brass 3. The Series EC -11 and EC -14 Sprin- right sprinklers applies. klers having been specifically tested and listed for non - combustible ob- FM Approval Patents structed construction are permitted Requirements U.S.A. Patent Numbers 5,366,022; to be used within trussesorbarjoists The Series EC -11 and EC -14 Ex- 5,579,846; 5,584,344; 5,609,211; having non - combustible web mem- tended Coverage Sprinklers are to be 5,862,994; and 5,865,256. bers greater than 1 inch (25.4 mm) installed in accordance with the appli- when applying the 4 times obstruc- cable Factory Mutual Loss Prevention tion criteria rule defined under "Ob- Data Sheet for limited use in buildings structions to Sprinkler Discharge of specific roof construction and for the Pattern Development ". protection of certain specific ordinary hazard (non- storage and /or non -flam- 4. The minimum allowable spacing be- mable or combustible liquid) occupan- tween the Series EC -11 and EC -14 cies. Information provided in the FM TFP22O Page 5 of 8 Loss Prevention Data Sheets relate to, but are not limited to, hydraulic design, _ ceiling slope and obstructions, mini- 1/2±1/8" (73,0 mm) 1/2" (12,7 mm) mum and maximum allowable spac- (12,713,2 mm) F 2 - 1/4" DIA. 1/4" (6,4 mm) ing, and deflector -to ceiling distance. • FACE OF (57 mm) These criteria may differ from UL SPRINKLER 1/8" and /or NFPA criteria, therefore the de- FITTING (3,2 mm) signer should review and become fa- miliar with Factory Mutual require - ments before proceeding with design. = i = — MOUNTING � j f Installation SURFACE lip � MOUNTING I The Series EC - 11 and EC - 14 Sprin PLATE CLOSURE klers must be installed in accordance - - -_ - - -• with the following instructions: 1 - 3/8" (34,9 mm) NOTES 1 - 1/8" (28,6 mm) Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler FIGURE 2 held horizontally, a small air bubble SERIES EC -11 AND EC -14 RECESSED PENDENT SPRINKLER ASSEMBLY should be present. The diameter of the WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT air bubble is approximately 1/16 inch inch mm) for the for 28 /1 1 STYLE 30 RECESSED ESCUTCHEON °C inch (2,4 mm) for the 286 °F /141 °C temperature ratings. A 3/4 inch NPT sprinkler joint should be obtained with a minimum to maxi- mum torque of 10 to 20 ft.lbs. (13,4 to 26,8 Nm). Higher levels of torque may 2 - 7/8" DIA. distort the sprinkler inlet with conse- 5/8t1/4" (73,0 mm) 3!4" (19,1 mm) quent leakage or impairment of the sprinkler. (15,916,4 mm) 2 - 1/4" DIA. y 1/4" (6,4 mm) FACE OF (57,2 mm) Do not attempt to compensate for in- SPRINKLER 1/8" sufficient adjustment in an Escutcheon FITTING (3,2 mm) Plate by under- or over- tightening the Sprinkler. Readjust the position of the sprinkler fitting to suit. Oh 1ti�' Step1. The sprinkler must be installed I � with the deflector parallel to the mount - �• L( ing surface. Pendent sprinklers must I be installed in the pendent position, MOUNTING �� MOUNTING and upright sprinklers must be in- SURFACE PLATE stalled in the upright position. CLOSURE Step 2. After installing the Style 30, 40, 1 - 3/8" (34,9 mm) or 60 mounting plate (or other escutch- 7l8" (22 2 mm) eon, as applicable) over the sprinkler pipe threads and with pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the FIGURE 3 sprinkler fitting. SERIES EC -11 AND EC -14 RECESSED PENDENT SPRINKLER ASSEMBLY Step 3. Wrench tighten upright or pen - WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT dent sprinklers using only the W -Type STYLE 40 RECESSED ESCUTCHEON 3 (End A) Sprinkler Wrench. When in- stalling the pendent sprinkler with Style 30, 40, or 60 Escutcheon, wrench tighten the sprinkler using only the W -Type 22 Sprinkler Wrench. The wrench recess of the applicable sprin- kler wrench (Ref. Figure 5 and 6) is to be applied to the sprinkler wrench flats (Ref. Figure 1). Page 6 of 8 TFP22O • "FITTING SIDE" 2-7/8" DIA. - _.. TOWARDS - SPRINKLER -- (73;0 mm) INTERNAL FITTING 2 -1/4" DIA. y DIMENSIONS OF • (57,2 mm) STYLE 60 ESCUTCHEON ill _ ACCOMMODATE — CLASS 150 MALLEABLE FACE OF IRON REDUCING SPRINKLER FITTING: SPRINKLER FITTING 3/8" (9,5 mm) ABOVE WRENCH TO 1/8" (3,2 mm) BELOW MOUNTING MOUNTING SURFACE I 7 1/8^ SURFACE RECESS ( 3,2 mm) /� (END "A ") �L __ �- 1 ....- ESCUTCHEON PLATE �� i- � - FIGURE 5 SEATING SURFACE: IF CLOSURE W - TYPE 3 SPRINKLER 1/4" (6,4 mm) ABOVE 2- 5/16" (58,7 mm) WRENCH TO 1/2" (12,7 mm) BELOW 3/4 NPT MOUNTING SURFACE; 0 MOUNTING 1-13/16" (46,0 mm) 3/4" (19,1 mm) TOTAL MI PLATE WRENCH ADJUSTMENT "' —� "'" RECESS ii - t !� FIGURE 4 • SERIES EC -11 AND EC -14 PENDENT SPRINKLER ASSEMBLY "' 4 1 ) WITH 3/4 INCH TOTAL ADJUSTMENT - I � �� STYLE 60 TWO -PIECE FLUSH ESCUTCHEON !� , U O ; �li a 0 twist/slippage, or the like, must be re- i 1 MI Care and placed. Also, replace any sprinkler that WRENCH p�/� has a cracked bulb or that has lost HEX Maintenance liquid from its bulb. (Ref. Installation Section). FIGURE 6 The Tyco® Series EC -11 and EC -14 W -TYPE 22 RECESSED - Sprinklers must be maintained and Frequent visual inspections are rec- SPRINKLER WRENCH serviced in accordance with the follow- ommended to be initially Performed for ing instructions: • corrosion resistant coated• sprinklers, after the installation has been com- NOTE pleted, to verify the integrity of the cor- ante with local requirements and /or a protection system rosion resistant coating. Thereafter, . Before closing p y annual inspections per NFPA 25 national codes. main control valve for maintenance' work on the fire protection system that should suffice; however, instead of in- . it controls, permission to shut down the specting from the floor level, a random affected fire protection systems must sampling of close -up visual inspec be obtained from the proper authori- tions should be made, so as to better ties and all personnel who may be determine the exact sprinkler condi- affected by this action must be notified. tion and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions Sprinklers that are found to be leaking present. or exhibiting visible signs of corrosion must be replaced. The owner is responsible for the in- spection, testing, and maintenance of Automatic sprinklers must never be their fire protection system and de- painted, plated, coated, or otherwise vices in compliance with this docu- altered after leaving the factory. Modi- ment, as well as with the applicable fied sprinklers must be replaced. standards of the National Fire Protec- Sprinklers that have been exposed to tion Association (e.g., NFPA 25), in . corrosive products of combustion, but addition to the standards of any other have not operated, should be replaced authorities having jurisdiction. The in- if they cannot be completely cleaned stalling contractor or sprinkler manu- by wiping the sprinkler with a cloth or facturer should be contacted relative • by brushing it with a soft bristle brush. to any questions. Care must be exercised to avoid dam- Automatic sprinkler systems should be age to the sprinklers - before, during, inspected, tested, and maintained by a and after installation. Sprinklers dam- qualified Inspection Service in accord - aged by dropping, striking, wrench TFP22O Page 7 of 8 GROUP I GROUP II LIGHT-HAZARD ORDINARY ORDINARY 0.10 GPM /FT 0.15 GPM /FT 0.20 GPM /FT DESCRIPTION AREA GPM PSI GPM PSI GPM PSI TY5137 (K =11.2) UPRIGHT 14 x 14 - - 30 7.2 39 12.1 16 x 16 30 7.2 39 12.1 51 20.7 18 x 18 33 8.7 49 19.1 65 33.7 20 x 20 40 12.8 60 28.7 80 51.0 TY5237 (K =11.2) PENDENT 14 x 14 - - 30 7.2 39 12.1 16 x 16 30 7.2 39 12.1 51 20.7 18 x 18 33 8.7 49 19.1 65 33.7 20 x 20 40 12.8 60 28.7 80 51.0 TY6137 (K =14.0) UPRIGHT 14 x 14 N/A N/A - - - - 16 x 16 N/A N/A 39 7.8 51 13.3 18 x 18 N/A N/A 49 12.3 65 21.6 20 x 20 N/A N/A 60 18.4 80 32.7 TY6237 (K =14.0) PENDENT 14 x 14 - - - - - - 16 x 16 37 7.0 39 7.8 51 13.3 18 x 18 37 7.0 49 12.3 65 21.6 20 x 20 40 8.2 60 18.4 80 32.7 1 ft. = 0.3048 m 1 ft = 0.093 m 1 gpm = 3.785 Ipm 1 psi = 0.06895 bar 1 gpm /ft = 40.74 mm /min TABLE D FLOW CRITERIA FOR UL AND C -UL LISTING OF SERIES EC -11 AND EC -14 SPRINKLERS sprinkler system design errors or inac- ._ Limited curate or incomplete information sup - WarraWarra plied by Buyer or Buyer's repre- nty sentatives. Products manufactured by Tyco Fire & In no event shall TFBP be liable, in Building Products (TFBP) are war- contract, tort, strict liability or under ranted solely to the original Buyer for any other legal theory, for incidental, ten (10) years against defects in mate- indirect, special or consequential darn - rial and workmanship when paid for ages, including but not limited to labor and properly installed and maintained charges, regardless of whether TFBP under normal use and service. This was informed about the possibility of warranty will expire ten (10) years such damages, and in no event shall from date of shipment by TFBP. No TFBP's liability exceed an amount warranty is given for products or corn- equal to the sales price. ponents manufactured by companies The foregoing warranty is made in lieu not affiliated by ownership with TFBP of any and all other warranties. ex- or for products and components which , - • '... ' -. . .... , _ ,1 have been subject to misuse, improper of merchantability and fitness for a par - installation, corrosion, or which have ticular purpose . not been installed, maintained, modi- fied or repaired in accordance with ap- This limited warranty sets forth the ex- plicable Standards of the National Fire clusive remedy for claims based on Protection Association, and /or the failure of or defect in products, materi standards of any other Authorities als or components, whether the claim Having Jurisdiction. Materials found is made in contract, tort, strict liability by TFBP to be defective shall be either or any other legal theory. repaired or replaced, at TFBP's sole This warranty will apply to the full ex- option. TFBP neither assumes, nor tent permitted by law. The invalidity, in authorizes any person to assume for it, whole or part, of any portion of this any other obligation in connection with warranty will not affect the remainder. the sale of products or parts of prod- ucts. TFBP shall not be responsible for • Page 8 of 8 TFP220 Ordering P/N 51 - AAA - B -CCC Procedure AAA = 893 (for TY5237 When placing an order, indicate the full K11.2 Pendent) product name. Please specify the AAA = 894 (for TY5137 Sprinkler Identification Number (SIN), K11.2 Upright) quantity, and temperature rating. Re- AAA = 895 (for TY6237 • • fer to the Price List for complete listing K14.0 Pendent) of Part Numbers. AM = 896 (for TY6137 Contact your local distributor for avail- K14.0 Upright) ability. Sprinkler Assemblies with NPT B = 1 (for Natural Brass) Thread Connections: B = 3 (for White [RAL9010])* Specify: (specify SIN), (specify K -Fac- B = 4 (for White Polyester) tor), (specify. temperature rating), B = 7 (for Lead Coated (specify Pendent or Upright) Extended B = 9 (for Chrome Plated) Coverage Sprinkler with (specify fin- ish), P/N (specify - from Table E, where applicable). CCC = 135 (for 135 ° F /57 °C) CCC = 155.(for 155 °F /68 °C) Recessed Escutcheon, Two -Piece : CCC = 175 (for 175 °F /79 °C) Specify: Style (30 or 40) Two -Piece CCC = 200 (for 200 °F /93 °C) Recessed Escutcheon with (specify material or finish *), P/N (specify). *Eastern Hemisphere sales only. 'Refer to Technical Data Sheet TFP770. TABLE E PART NUMBERS FOR Flush Escutcheon, Two -Piece : EC -11 AND EC -14 SPRINKLERS Specify: Style 60 Two -Piece Flush Es- cutcheon with (specify finish'), P/N (specify). *Refer to Technical Data Sheet TFP778. Sprinkler Wrench: Specify: W -Type 3 Sprinkler Wrench, P/N 56- 895 -1 -001 Specify: W -Type 22 Recessed Sprin- kler Wrench, P/N 56- 665 -7 -001 © 2007 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 FPS2c(o -o©(2 tqco Fire Suppression - & Building Products Technical Services 800-381-93121+1-401-781-8220 www.tyco - fire.com Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K- Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Corrosion - resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond .3•Z: �' ' "'��": Description that which would otherwise be obtained - . s !‘" 1 . when exposed to co rrosive atmo- I fill' The TYCO Series TY -FRB, 2.8, 4.2, 5.6, p ° ; . .'7: and 8.0 K- factor, Upright and Pendent spheres. Although corrosion- resistant ;j a te, t. , i . I f coated sprinklers have passed the �I I L �.1 Sprinklers described in this data sheet ��, i , standard corrosion tests of the appli- mo t . : ,":: t-. are quick response, standard coverage, ; . <•.,,.i;.;;3! decorative 3 mm glass bulb -type spray cable approval agencies, the testing is j not representative of all possible cor- " . '• — -- sprinklers designed for use in light or ,.,. -r. ordinary hazard, commercial occupan- rosive atmospheres. Consequently,�:;•., cies such as banks, hotels, and shop- it is recommended that the end user - ping malls. be consulted with respect to the suit- ability of these coatings for any given . The recessed version of the Series TY- corrosive environment. The effects of FRB Pendent Sprinkler, where applica- ambient temperature, concentration of ble, is intended for use in areas with a chemicals, and gas /chemical velocity, V finished ceiling. This recessed pendent should be considered, as a minimum, - ge sprinkler uses one of the following, along with the corrosive nature of the x : • A two-piece Style 10 (1/2 inch NPT) chemical to which the sprinklers will be / + ,� or Style 40 (3/4 inch NPT) Recessed exposed. '�. . I'; Escutcheon with 1/2 inch (12,7 mm) of An intermediate level of the Series TY- !I:.,-.' recessed adjustment or up to 3/4 inch FRB Pendent Sprinklers is detailed ` - (19,1 mm) of total adjustment from the in Technical Data Sheet TFP356, and ` = flush pendent position, or a Sprinkler Guards are detailed in Tech- . , o • A two -piece Style 20 (1/2 inch NPT) nical Data Sheet TFP780. or Style 30 (3/4 inch NPT) Recessed Escutcheon with 1/4 inch (6,4 mm) of NOTICE recessed adjustment or up to 1/2 inch The Series TY -FRB Concealed Pendent Model /Sprinkler (12,7 mm) of total adjustment from the Sprinklers described herein must be flush pendent position. installed and maintained in compliance Identification The adjustment provided by the with this document and with the appli Number (SIN) Recessed Escutcheon reduces the cable standards of the National Fire accuracy to which the fixed pipe drops Protection Association, in addition to to the sprinklers must be cut. the standards of any authorities having TY1131: Upright 2.8K, 1/2"" NPT jurisdiction. Failure to do so may impair TY1231: Pendent 2.8K, 1/2" NPT the performance of these devices. TY2131: Upright 4.2K, 1/2 NPT Owners are responsible for maintaining TY2231: Pendent 4.2K, 1/2 NPT their fire protection system and devices TY3131: Upright 5.6K, 1/2 " NPT in proper operating condition. The TY3231: Pendent 5.6K, 1/2"" NPT IMPORTANT installing contractor or sprinkler manu- TY4131: Upright 8.0K, 3/4•" NPT Always refer to Technical Data facturer should be contacted with any TY4231: Pendent 8.0K, 3/4" NPT Sheet TFP700 for the "INSTALLER questions. TY4831: Upright* 8.0K, 1/2" NPT WARNING" that provides cautions TY4931: Pendent' 8.0K, 1/2" NPT with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. 'Eastern Hemisphere Sales Only Page 1 of 10 JULY 2010 TFP171 • TFP171 Page 2 of 10 7/ -16° (11 -1 -mm) ESCUTCHEON STYLE * NOMINAL PLATE SEATING RECESSED SSU MAKE -IN 1/2 SURFACE ESCUTCHEON DEFLECTOR I NPT ______ s= i 5 `�{ ( 7/16 ") �- . 4 I (11,1 mm) - 2 -1/4" 1111" l I NOMINAL i 'i I �� =A (57,2 mm) �� �— 2 w MAKE -IN 1 J v I I / 1 -9/16" � 2 -3/16 3 1,6 (55,6 mm) ) WRENCH (39,7 mm) l FLATS II II 7 1 1/2° NPT SSP DEFLECTOR - 2 -7/8° (73.0 mm) DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector • Temperature rating is indicated on deflector or adjacent to Assembly 5 - Compression orifice seat on frame. 2 - Button Screw 7 - Bushing FIGURE 1 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT 7/16° (11,1 mm) ESCUTCHEON STYLE 10 or 20 * NOMINAL PLATE SEATING RECESSED SSU 1/2° MAKE -IN SURFACE ESCUTCHEON DEFLECTOR J NPT 6* .........V141,..,........ i;,nrT1���1Tr�.�� /jk 5 '�' 7/16" (11,1 mm) 2 -3/16" 2 NOMINAL = A (55,6 mm) �� — • MAKE -IN q " r 1 -1/2 (55,6 m -3/16 j _ WRENCH I (38,1 mm) Ir 3 FLATS i . 1 1/2° NPT SSP DEFLECTOR F— 2-7/8" (73,0 mm) DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector • Temperature rating is indicated on deflector or adjacent to Assembly 5 - Compression orifice seat on frame. 2 - Button Screw FIGURE 2 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT TFP171 Page 3 of 10 7/161.(1.1,1_mm) ESCUTCHEON - -- STYLE- 10.or -20 — * NOMINAL PLATE SEATING RECESSED SSU 1/2" MAKE -IN SURFACE ESCUTCHEON DEFLECTOR O NPT I 6 * } 5 7 /,s to • (11,1 mm) 2 -3/16" 4 lir NOMINAL I 41= (55,6 mm) .I � MAKE -IN i 2 2 (55 3/16" 6 mm) � � I 1 - 1/2" II" , _ — WRENCH (38,1 r 3 I =IEEE FLATS � - 1 � � � 1/2° NPT SSP DEFLECTOR — 2 -7/8" (73,0 mm) DIA. - CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector • Temperature rating is indicated on deflector or adjacent to Assembly 5 - Compression orifice seat on frame. 2 - Button Screw FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT 1/2° (12.7 mm) ESCUTCHEON STYLE 30 or 40 SSU * NOMINAL 3/4 PLATE SEATING RECESSED DEFLECTOR MAKE-IN NPT SURFACE ESCUTCHEON 6* I — 5 ,M 1/2° � (12,7 mm) 2 -5/16° 4 ; ' 1 NOMINAL Li � mm) �� . MAKE -IN `s 2 i -1/4° 1 - 9/16° c 3 t � (57,2 mm) j � (39,7 mm) 3 7 j ° — - - - - -.. I - - - - II -- -.. } 3/4" NPT SSP DEFLECTOR ---i— 2 - 7/8' (73,0 mm) DIA. -- CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly ' Temperature rating is indicated on deflector or adjacent to 2 - Button 5 - Compression orifice seat on frame. Screw FIGURE 4 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT . TFP171 Page 4 of 10 • 7/16" (11,1 mm) SSU NOMINAL -- -- — — ° — DEFLECTOR MAKE -IN 1/2 NPT 5 �_ t °' 7/16" • I (11,1 mm) f 2-1/4' 4 NOMINAL ' (57,2 mm) IR IF MAKE -IN gli ti 2 ` 2- 3/16" I I 1 9/16° (55,6 mm) + WRENCH (39,7 mm) 3 i 4 FLATS SSP* 1 CROSS 1/2 NPT DEFLECTOR . SECTION UPRIGHT PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector • Temperature rating is indicated on deflector or adjacent to Assembly 5 - Compression 2 - Button orifice seat on frame. Screw FIGURE 5 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS 8.0 K- FACTOR, 1/2 INCH NPT Technical Operation inch (1,6 mm) for the 135 °F /57 °C and f� 3/32 inch (2,4 mm) for the 286 °F /141 °C D ata The glass Bulb contains a fluid that temperature ratings. expands when exposed to heat. When Obtain a leak -tight 1/2 inch NPT sprin- Approvals the rated temperature is reached, the kler joint by applying a minimum to UL and C -UL Listed fluid expands sufficiently to shatter the maximum torque of 7 to 14 ft.lbs. (9,5 FM, LPCB, and NYC Approved glass Bulb, allowing the sprinkler to to 19,0 Nm). Higher levels' of torque Refer to Table A and B for complete activate and water to, flow. can distort the sprinkler Inlet with con - approval information including sequent leakage or impairment of the corrosion resistant status. D sprinkler. - Maximum Working Pressure • Do not attempt to compensate for Refer to Table C. Criteria insufficient adjustment in the Escutch- • eon Plate by under- or over - tightening Discharge Coefficient The TYCO Series TY -FRB Pendent the sprinkler. Re- adjust the position of K =2.8 GPM /psi (40,3 LPM /bars / 2) and Upright Sprinklers are intended the sprinkler fitting to suit. . K =4.2 GPM /psi (60,5 LPM /bar1/2) for fire protection nc e systems designed in The Series TY -FRB Pendent and accordance with the standard installa- K=5.6 GPM /psi (80,6 LPM /bar1/2) tion rules recognized by the applicable Upright Sprinklers must be installed K =8.0 GPM /psi (115,2 LPM /bar1/2) Listing or Approval agency (such as, UL in accordance with the following Listing is based on the requirements of instructions. Temperature Rating NFPA 13, and FM Approval is based on Refer to Table A and B. pp 1. Install Pendent sprinklers in the the requirements of FM's Loss Preven- pendent position. Install upright Finishes tion Data Sheets). Only the Style 10, sprinklers in the upright position. Sprinkler: Refer to Table A and B. 20, 30, or 40 Recessed Escutcheon, as Recessed Escutcheon: White Coated, applicable, is to be used for recessed 2. With pipe thread sealant applied to the pipe threads, hand - tighten the Chrome Plated, or Brass Plated. pendent installations. sprinkler into the sprinkler fitting. Physical Characteristics Installation 3. Tighten the sprinkler into the sprin- Frame Bronze kler fitting using only the W -Type 6 Button Brass /Copper The TYCO Series TY -FRB Sprinklers Sprinkler Wrench (Figure 14). With Sealing Assembly Beryllium must be installed in accordance with reference to Figures 1 through Nickel w/Teflonf the following instructions. 5, apply the W -Type 6 Sprinkler . Bulb Glass Wrench to the sprinkler wrench Compression Screw Bronze `N OTICE:: flats. Deflector Copper /Bronze Bushing (K =2.8) Bronze Do not install any bulb -type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bub- ble should be present. The diameter t Registered Trademark of Dupont of the air bubble is approximately 1/16 • • TFP171 Page 5 of 10 SPRINKLER FINISH (See Note 5) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME WHITE * ** • FACTOR COLOR BRASS PLATED POLYESTER 135 "F /57 "C Orange PENDENT 155 °F /68 "C Red (TY1231) and 175 °F /79 °C Yellow 1, 2, 3, 4 UPRIGHT (TY1131) 200 °F /93 °C Green • 286 °F /141 °C Blue 135 °F /57 °C Orange 2.8 RECESSED 155 °F /68 °C Red 1/2" NPT PENDENT (TY1231)* 175 °F /79 °C Yellow Figure 6 200 °F /93 °C Green 1.2.4 135 °F /57 °C Orange RECESSED PENDENT 155 °F /68 °C Red (TY1231) ** 175 °F /79 °C Yellow Figure 7 200 °F /93 °C Green 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY2231) and 175 °F /79 °C Yellow UPRIGHT (TY2131) 200 °F /93 °C Green 286 °F /141 °C Blue 135 °F /57 °C Orange 4.2 RECESSED 1/2" NPT PENDENT 155 °F /68 °C Red 1, 2 (TY2231)* 175 °F /79 °C Yellow Figure 8 200 °F /93 °C Green 135 °F /57 °C Orange RECESSED C 6 Red 1 55'F/8 PENDENT ° (TY2231) ** 175F/79°C Yellow Figure 9 200 °F /93 °C Green NOTES: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C -UL) as Quick Response Sprinklers. • 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354 -01 -E. 5. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion- Resistant Sprinklers. • Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. '•' Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K- FACTOR SPRINKLERS • • TFP171 Page 6 of 10 SPRINKLER FINISH (See Note 8) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME WHITE * ** LEAD • FACTOR COLOR BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY3231) and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 UPRIGHT 200 °F /93 °C Green (TY3131) 286 °F /141 °C Blue 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red 5.6 PENDENT 175 °F /79 °C Yellow 1, 2, 4, 5 N/A 1/2" NPT (TY3231)' Figure 10 200 °F /93 °C Green • 286 °F /141. °C Blue 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 175 °F /79 "C Yellow 1, 2, 3, 4, 5 N/A (TY3231)" Figure 11 200!F/93°C Green • 286 °F /141 °C Blue 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY4231) and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7 1, 2, 5 UPRIGHT 200 °F /93 °C Green (TY4131) 286 °F /141 °C Blue 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red 8.0 PENDENT 175 °F /79 °C Yellow 1. 2, 5 N/A 3/4" NPT (TY4231)• Figure 12 200 °F /93 °C Green 286 °F /141 °C Blue 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 175 °F /79 °C Yellow 1, 2, 3, 5 N/A (TY4231)` • Figure 13 200 °F /93 °C Green 286 "F /141 °C Blue • • 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red 8 0 (TY4931) 1/2 "NPT and 175°,F/79°C Yellow 1, 2, 4, 5, 6 1, 2, 5 UPRIGHT 200 °F /93 °C Green (TY4831) 286 °F /141 °C Blue NOTES: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However. LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details, contact Tyco Fire Suppression & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53 -428- 3377.) 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead - Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion- Resistant Sprinklers. Where Lead - Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion- Resistant Sprinklers. Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. " Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE B • LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K- FACTOR SPRINKLERS • • • TFP171 Page 7 of 10 SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD FACTOR BRASS PLATED POLYESTER COATED PENDENT (TY1231) and 2 8 UPRIGHT (TY1131) 75 PSI (12,1 BAR) N/A 1/2" NPT RECESSED PENDENT (TY1231) PENDENT (TY2231) and 4 2 UPRIGHT (TY2131) 1/2" NPT 175 PSI (12,1 BAR) N/A RECESSED PENDENT (TY2231) PENDENT (TY3231) 175 PSI and (12.1 BAR) 5.6 UPRIGHT (TY3131) 250 PSI (17,2 BAR) 1/2" NPT OR 175 PSI (12,1 BAR) RECESSED (SEE NOTE 1) N/A PENDENT (TY3231) PENDENT (TY4231) 175 PSI and (12.1 BAR) 8 0 UPRIGHT (TY4131) 3/4" NPT 175 PSI (12,1 BAR) RECESSED N/A PENDENT (TY4231) 8.0 PENDENT (TY4931) 175 PSI and 1/2" NPT UPRIGHT (TY4831) 175 PSI (12 BAR) (12,1 BAR) NOTES: 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C -UL); and, the Approval by the City of New York. TABLE C MAXIMUM WORKING PRESSURE The Series TY -FRB Recessed Pendent Care and Exercise care to avoid damage to Sprinklers must be installed in accor- sprinklers before, during, and after dance with the following instructions. Maintenance installation. Never paint, plate, coat, 1. After installing the Style 10, 20, 30, or otherwise alter automatic sprinklers or 40 Mounting Plate, as applica- The TYCO Series TY -FRB must be after they leave the factory. ble, over the sprinkler threads and maintained and serviced in accordance Replace sprinklers that: with pipe- thread sealant applied to with the following instructions. • were modified or over - heated. the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. '`NOTICE" • were damaged by dropping, striking, wrench twisting, wrench slippage, or 2. Tighten the sprinkler into the sprin- Before closing a fire protection system the like. kler fitting using only the W-Type 7 main control valve for maintenance Recessed Sprinkler Wrench (Fig- work on the fire protection system • are leaking or exhibiting visible signs ure 15). With reference to Figures 1 of corrosion. 9 that it controls, obtain permission to to 4, apply the W -Type 7 Recessed shut down the affected fire protection • were exposed to corrosive products Sprinkler Wrench to the sprinkler systems from the proper authorities of combustion but have not oper- wrench flats. and notify all personnel who may be ated, if you cannot easily remove • 3. After ceiling installation and finish- affected by this action, combustion by- products with a cloth. ing, slide on the Style 10, 20, 30, or Absence of the outer piece of an • have a cracked bulb or have lost liq- 40 Closure over the Series TY -FRB escutcheon, which is used to cover uid from the bulb. Refer to the Instal- Sprinkler and push the Closure over a clearance hole, can delay sprinkler lation section in this data sheet. the Mounting Plate until its flange operation in a fire situation. comes in contact with the ceiling. TFP171 Page 8 of 10 2 -7/8" DIA. _ 2 -7/8" DIA. - - - - - — --- --- - - - - - - - -- (73;0 mm)- - -- - (73,0 -mm) 5/8±1/4" 3/4" (19;1 mm) — _ 1/2 ±1/8" 1/2" (12.7 mm) - (15,9±6,4 mm) 2 1/4° DIA. 1/4° (6,4 mm) (12,7±3,2 mm) p_1 /4' DIA. 1/4" (6.4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57.2 mm) MOUNTING • SPRINKLER PLATE SPRINKLER ■ PLATE FITTING FITTING 1/8" 1/8" _ u (3,2 mm) .. (3,2 mm) i =_.----iiiii 1 \ A MMARIC w , MOUNTING 1i' 1 MOUNTING SURFACE SURFACE .4.17e/7-, � .491r CLOSURE SERIES 1 -5/16' (33,3 mm) CLOSURE SERIES 1- 5/16" (33,3 mm) TY -FRB 13/16" (20.6 mm) TY -FRB 1- 1/16" (27,0 mm) FIGURE 6 FIGURE 7 SERIES TY-FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT _ 2 -7/8" DIA. 2 -7/8" DIA. (73,0 mm) 3/4" (19.1 mm) (73,0 mm) " 1/2' (12,7 mm 5/8±1/4" _ 1/2±1/8" ( mm) (15,9 ±6.4 mm) 2 1/4" DIA 1/4' (6,4 mm) (12,7±3.2 mm) 2 -1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8° 1/8" ... (3,2 mm) I .. (3,2 mm) 1 \ r M--m w..- ......,■■■ i : \ I ML;13 MOUNTING ,1' MOUNTING SURFACE SURFACE . - - -- CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm) TY-FRB 3/4" (19,1 mm) TY -FRB 1" (25,4 mm) FIGURE 8 FIGURE 9 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT Initial and frequent visual inspections of Responsibility lies with the owner for Care must be exercised to avoid dam - random samples are recommended for the inspection, testing, and mainte- age to the sprinklers - before, during, corrosion - resistant sprinklers to verify nance of their fire protection system and after installation. Sprinklers dam - the integrity of the corrosion - resistant and devices in compliance with this aged by dropping, striking, wrench material of construction. Thereafter, document, as well as with the appli- twist /slippage, or the like, must be annual inspections per NFPA 25 should cable standards of the National Fire replaced. Also, replace any sprinkler suffice. Protection Association (for example, that has a cracked bulb or that has lost Inspections of corrosion resistant NFPA 25), in addition to the standards liquid from its bulb. (Ref. Installation sprinklers are recommended at close of any other authorities having jurisdic- Section). range, instead of from the floor level lion. Contact the installing contractor or Initial and frequent visual inspections of per NFPA. Inspection at close range sprinkler manufacturer regarding any random samples are recommended for • can better determine the exact sprin- questions. corrosion - resistant sprinklers to verify kler condition and the long -term integ- Automatic sprinkler systems are rec- the integrity of the corrosion - resistant rity of the corrosion - resistant material, ommended to be inspected, tested, material of construction. Thereafter, which can be affected by the corrosive and maintained by a qualified Inspec- annual inspections per NFPA 25 should conditions present. tion Service in accordance with local suffice. requirements and /or national codes. a. ' • TFP171 Page 9 of 10 2 -7/8" DIA. 2 -7/8' DIA. . -_ ..... - - - -_. -- (73,0 -mm) - 3/4° (19;1 mm) - - - (73,0-mm) - 5/8t1/4" - - 1/2±1/8° 1/2" (12.7 mm) - (15,9 ±6,4 mm) 2 1/4" DIA. 1/4° (6,4 mm) (12.7 ±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) • FACE OF (57,2 mm) ~ MOUNTING FACE OF (57,2 mm) 1 MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" imp (3,2 mm) u (3,2 mm) w IM W.' i ' fA ANIIIIIIIIN , MOUNTING 110 1 MOUNTING I SURFACE SURFACE � A. �_. A = CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4° (31,8 mm) TY -FRB 3/4° (19,1 mm) TY -FRB 1" (25,4 mm) FIGURE 10 • FIGURE 11 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT 5:6 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA. 2 -7/8° DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/211/8° (73,0 mm) 1/2° (12,7 mm) (15,9±6,4 mm) 2 -1/4" DIA. 1/4° (6,4 mm) - (12,7 ±3,2 mm) 2 -1/4° DIA. 1/4° (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) 1 MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8° i� (3,2 mm) n 1 (3,2 mm) A te a %' L ■ ' i . MOUNTING 1I1 MOUNTING . SURFACE . SURFACE ° CLOSURE SERIES 1 -5/16° (33,3 mm) CLOSURE SERIES 1- 5/16" (33,3 mm) TY-FRB 13/16" (20,6 mm) TY -FRB, 1- 1/16" (27,0 mm) FIGURE 12 FIGURE 13 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT Inspections of corrosion - resistant sprinklers are recommended at close e, WRENCH range, instead of from -the floor level RECESS per NFPA. Inspection at close range WRENCH RECESS can better determine the exact sprin- (END "A" USED FOR to-Tl kler condition and the long -term integ- 1/2" NPT MODELS) rity of the corrosion resistant material, which can be affected by the corrosive conditions present. WRENCH RECESS ' (END "B" USED FOR %-..' 3/4" NPT MODELS) PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH • FIGURE 14 SPRINKLER WRENCHING AREA W -TYPE 6 SPRINKLER FIGURE 15 WRENCH W -TYPE 7 RECESSED SPRINKLER WRENCH • TFP171 Page 10 of 10 • P/N 57 - XXX - X - XXX j _ I MODEL/SIN SPRINKLER TEMPERATURE FINISH RATINGS • 330 2.8K UPRIGHT (1/2 "NPT) TY1131 1 NATURAL BRASS 135 135 °F (57 °C) • 331 2.8K PENDENT (1/2 "NPT) TY1231 4 WHITE POLYESTER 155 155 °F (68 °C) • 340 4.2K UPRIGHT (1/2 "NPT) TY2131 3 WHITE (RAL9010)' 175 175 °F (79 °C) 341 4.2K PENDENT (1/2 "NPT) TY2231 9 CHROME PLATED 200 200 °F (93 °C) 370 5.6K UPRIGHT (1/2 "NPT) TY3131 7 LEAD COATED 286 286 °F (141 °C) 371 5.6K PENDENT (1/2 "NPT) TY3231 . 390 8.0K UPRIGHT (3/4 "NPT) TY4131 391 8.0K PENDENT (3/4 "NPT) TY4231 360 8.0K UPRIGHT (1/2 "NPT) TY4831' ° Eastern Hemisphere sales only. 361 8.0K PENDENT (1/2 "NPT) TY4931' TABLE D PART NUMBER SELECTION SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS Limited responsible for sprinkler system design Ordering errors or inaccurate or incomplete infor- • Warranty mation supplied by Buyer or Buyer's Procedure y representatives. ' Products manufactured by Tyco Fire In no event shall TFSBP be liable, in Contact your local distributor for Suppression & Building Products contract, tort, strict liability or under availability. When placing an order, • (TFSBP) are warranted solely to the any other legal theory, for incidental, indicate the full product name and Part original Buyer for ten (10) years against indirect, special or consequential dam- Number (P /N). defects in material and workmanship ages, including but not limited to labor when paid for and properly installed charges, regardless of whether TFSBP Sprinkler Assemblies with NPT and maintained under normal use and was informed about the possibility of Thread Connections service. This warranty will expire ten such damages, and in no event shall Specify: (Specify Model /SIN), Quick (10) years from date of shipment by TFSBP's liability exceed an amount Response, (specify K factor), (specify TFSBP. No warranty is given for prod- equal to the sales price. temperature rating), Series TY -FRB ucts or components manufactured by companies not affiliated by ownership The foregoing warranty is made in lieu (specify Pendent or Upright) Sprinkler with TFSBP or for products and corn- of any and all other warranties, express with (specify type of finish or coating), ponents which have been subject to or implied. including warranties of mer- P/N (specify from Table D). misuse, improper installation, corro- chantabilitv and fitness for a particular Recessed Escutcheon: sion, or which have not been installed, purpose. Specify: Style (10, 20, 30, or 40) maintained, modified or repaired in This limited warranty sets forth the Recessed Escutcheon with (specify') accordance with applicable Standards exclusive remedy for claims based on finish, P/N (specify'). of the National Fire Protection Associa- failure of or defect in products, materi- tion, and /or the standards of any other als or components, whether the claim is Sprinkler Wrench Authorities Having Jurisdiction. Mate- made in contract, tort, strict liability or Specify: W -Type 6 Sprinkler Wrench, rials found by TFSBP to be defective any other legal theory. P/N 56- 000 -6 -387. • shall be either repaired or replaced, at . TFSBP's sole option. TFSBP neither This warranty will apply to the full Specify: W -Type 7 Sprinkler Wrench, assumes, nor authorizes any person extent permitted by law. The invalidity, P/N 56- 850 -4 -001. to assume for it, any other obligation in in whole or part, of any portion of this ' Refer to Technical Data Sheet TFP770. • connection with the sale of products or warranty will not affect the remainder. parts of products. TFSBP shall not be • Copyright © 2007 -2010 Tyco Fire Suppression & Building Products. All rights reserved. • �,,r.: °.r *; LISTED e[' � . � • I. L � + j:�: C SERIES AQB BRAIDED FLEXIBLE HOSE ASSEMBLIES — r — SERIES AQU UNBRAIDED FLEXIBLE HOSE ASSEMBLIES AquaFlex Stainless Steel sprinkler Fittings provide fast, easy sprinkler installation in a drop ceiling grid with a flexible, stainless steel hose. System Options: • Braided and unbraided flexible stainless steel hose in lengths: 31, 48, 60, 727790, 1220, 1525, 1830mm • Branch line nipples for attaching to rigid pipe • • i/ and 3 /4712.7 - 19.05mm straight and 90° reducers for connecting sprinklers. • FM Approved patent - pending, light- weight pre - assembled, ready -to- install 1 -Bee mounting bracket available in 24 and 48' widths. 24° width bracket is also cULus Listed. • Institutional bracket for wall or ceiling installations also available AquaFlex Stainless Steel Flexible Drop 1 -Bee bracket allows complete lateral alignment of PATENT PENDING sprinklers during installation. The bracket provides center points and reference marks 6° and 12 °/152 mm and 304 mm from the tile edge (on the 24' bracket) for ease of positioning without need for measuring. The system requires no welding for assembly. _r-,0,5 2O O - c' 9 1 2 The braided 1" nominal diameter system is FM Approved for T -Bar Grid commercial suspended ceilings and metal or wood frame sheetrock suspended ceilings.. The unbraided N nominal diameter system is UL 2443 Listed. TECHNICAL SPECIFICATIONS Maximum temperature: 225 ° F /107.2 ° C Maximum Working Pressure: • 200 psi /1375kPa (FM Approval for braided system) • 175 psi/1206 kPa (UL Listing for unbraided system) Connections: To branch line (inlet) via 1725.4 mm NPT male thread To sprinkler head (outlet) via W or 3 4712.7mm or 19.05mm NPT female thread Minimum Bend Radius: • 77178mm (FM Approval for braided system) • 47102 mm for (UL Listing for unbraided system) Maximum Number of Bends per Flexible Drop: See friction loss charts later in this document • Du not bend within 21/2763.5mni from connection nut. JO B /OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. •CtaLJI.C* REVD 10.85._.3 FIRE PROTECTION PRODUCTS - ACCESSORIES 10.85 i ,.. , ...., ,.... ::::......• ' . i,"..1-7 _ . • `'` . '•1 l l,' • 1::- I . FRICTION LOSS DATA Standard Straight Reducer - 5.5' Maximum number of 90° bends Length - Outlet (at 4" bend radius) Equivalent Length of 1' Schedule 40 pipe � � . .1 • 31 h 3 9.6/2.9 27/8.2 O.d.11 , r• AIL I: 790 3 3 8.2/2.5 33/10.0 Ci 1 1q ( 1' 'I ti. I I ) Oti,l,mi 48 V• 3 17.1/5.21 53/16.1 1220 3 3 16.5/5.0 55/16.7 60 Y2 3 21.4/6.5 68/20.7 1525 3 3 20.1/6.1 63/19.2 72 / 3 27.3/8.3 73/22.2 1830 3/4 3 26.2/8.0 76/23.1 This product has been tested and Approved by FM Global for use in wet, dry and preaction systems per NFPA 13, 13R and 13D. FM 1637 standards for safety include, but are not limited to, pressure cycling, corrosion resistance, flow characteristics, vibration resistance, leakage, mechanical and hydrostatic strength. • Series AQB, at 7' minimum bend radius and straight reducers, where C =]00. + Series AQU, at 4' minimum bend radius and straight reducers, where C =120. Note: Differences of equivalent lengths are due to the different test methods per UL 2443 and FM 1637 standards. Please refer to these standards for further details of their respective friction loss test Standard 90° Elbow Reducer - Short lifi Length Outlet Equivalent Length of 1' Schedule 40 Pipe 31 V 64/1.9 790 48 1220 60 � 5.9/1.8 10.2/3.1 t, 10.3/3.1 h 12.5/3.8 1525 >/ 13.1/4.0 • 72 1x 16.7/5.0 1830 94 17.0/5.2 Standard 90° Elbow Reducer - Long Length . Outlet Equivalent Length of 1' Schedule 40 Pipe 31 790 48 1220 60 1525 lLl�yu w; p L I]ir r,> >:. .. ttrtul Y2 6.8/2.1 >/ 6.3/1.9 V2 10.6/3.3 3 10.7/3.3 h 12.9/3.9 34 13.5/4.1 iiiiii 72 % 17.1/5.2 1 830 >. 174/5.3 NOTE: Elbow reducer friction loss values based upon FM testing of Series AQB Braided Hose only. www.victaulic.com \iCtauliC VICTAULIC IS A REGISTERED TRADEMARK Or VICTAULIC COMPANY. C 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. --=»m 10.85_2 REV._D ° FIRE PROTECTION PRODUCTS ACCESSORIES 10.85 Aqua ex Sta6riless steel, Sprinkler Fittings gs PRODUCT DETAILS 11 II1f ll 11111 5.5' straight reducer 1 � 1 n � , � 1 r , I;�) p ! I - itemL. . .. Description;. 7- to 0 0 O h , 111 �[� r , 17F III����i , 7 Hose 1 2 _ Adapter Ring . 9.0' straight reducer 3 Seal — .111111111111H11111111111111 IIIlhIIIIIIIIII1.111.11j11.11111111.11 4 Nut .I.II1IIIE'j. :. :;; >:. Z;Z 1.;. :::> : Z.'...t1uII 5 Nipple I ..... _ . . 4.— 2'/ --N 0 6 Braid 7 Collar Series AQB Flexible Hose - Braided (1" nominal diameter) ,��. 11 it lgi � tltltl111 I ,14air 13.0' straight reducer u • :. Item:_'. ;. % :;∎ •' �1 O 0 ... I ii= 511: ' Adapter p ose ! �n�l miltil � itit,itil►I1 ` ►il i III I I I IM� 1 1 � tn iiliti►i1 ` uu ■ n 3 SealRing P II I 4 Nut L-21/4 5 Ni le Series AQU Flexible Hose - Unbraided we nominal diameter) Short 90° elbow reducer [1: Long 90° elbow reducer NOTE: 9 and 13' straight reducers are not FM Approved. Short and long elbow reducers are not cULus Listed. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 02010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. ICtaUI1L1 REV _D 10.85_3 • FIRE PROTECTION PRODUCTS ACCESSORIES 10.85 AquaF' ee' "tain6ess Steer Sprinkler Fittings COMMERCIAL DROP CEILING INSTALLATION - 1 -BEE? BRACKET 0 1 X' or 48' Square Bar el 2 Center Bracket Assembly. Square Bar End Bracket Assembly e Sheet Metal Screw '01. 0 :,,,, 0 0 1 -BEE One-piece bracket with center open -gate assembly www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. jctaulIc' 10 .85 4 REV__D . FIRE PROTECTION PRODUCTS - ACCE SSORIES 10.85 Aqua ie.. Sta r le s Steel Sprinkler Fittings FLEXIBLE DROP ASSEMBLY WITH RECESSED SPRINKLER - 1 /i" ADJUSTMENT, T -BAR INSTALLATION /• R / \ 11/27 17t' 39mm�38mm 21/2764 mm B I mint. straight section See Chart I before bending 1/2722.2 mm or En 1'/25.4 mm Nom. ID I. IM TT iTT� En .n. MINIM= _ — 2h760 mm r — _ max. hole 2' /51m y - __� ♦ lour � i ® _ • Ye% min. hole • O _ = = == _— 80 mm 27a'/ = == ` -- 3 , 4 ./ ' 60 mm =- I (o) Cto■ 11 H1I* � � 98 mm *1.101111 �= 1 I •• I II •• I 10 ∎ `� a:::=. . ii ai ' 1'1%38 mm x + '1'/13 mm I P/.'/32 mm ^;+ rr -, . --41- �ii� 1'k' /45 mm I s'? Typical ceiling - - �'. tile Typical finished ceiling face WARNING: TypicalT -bar grid and ceiling tile 247610 mm or try % shown. Variations ofT -bar and tile 50'/1270 mm O.C. 74 mm may be used but may result in dimensional changes from '1" MAX. RECESS MAX. EXTENSION layouts depicted in this submittal. NOTE: Hose is permitted to be bent in alternative configurations. What is shown is a typical T -Bar installation and the corresponding clearance dimensions if one 90° bend is imparted to the hose. ,--.• -..a - l Hose Clearance 4. Chart - J::.'= : r> -.> -: F ,•,a -cam I.V,k, ; Y Win+ !c��, ,r „ v• - . - - rlilie'. — : 6InChes P . Minimum • e 7 Bend Radius 102 178 Min. t2 1434 323 373 Max. 13'/. 151. 5 7. 337 387 www.victaulic.com VICIAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 02010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. ICtaLJIICi" REV.. 0 10.85_5 • • FIRE PROTECTION PRODUCTS • • ACCESSORIES 10.85. d ia.2l u a � +�h, ,: Lc :infe J s St-,ear'I. .. Sprinkler Fittings FLEXIBLE DROP ASSEMBLY WITH'CONCEALED SPRINKLER – r/" ADJUSTMENT, T -BAR INSTALLATION / \ R 1 1 • 1y:'/ 1'h' / 2yi /64mm — i 39 mm 38 mm min.. straight section • . I before bending W/22.2 mm or 1.111 1'125.4 mm Nom. ID B IBM 1111. See Chart r_r_ r_r_ N =NEM MONO WARNING: MONO Typical T -bar grid and ceiling tile minem t■■shown. Variations of T -bar and tile !!!_ !_ may be used but may result in = dimensional changes from =_ layouts depicted in this submittal. —_ =m = - _ 2% 768 mm max. hole _ 2W/60 mm 1_ min. hole -` °� ° '3` lS MIS t= = ' a '� i == • O ` U —L 3W/ d y r•— mum :0 mm — - M . -' I '- 27 L� 1 r — - - / ' •• , .0 mm �� 1 (o) 11 wll• ` ii i •I Ili 1 -- ! V ,. I I r. dos l _ � -a I -`___' 1/2' /13 mm Typical finished Typical ceiling tile {I 31V/ 4'/ 2610 mm or ceiling face 78 mm 5071270 mm O.C. `A" MAX. RECESS MAX. EXTENSION NOTE: Hose is permitted to be bent in alternative configurations. What is shown is a typical T -Bar installation and the corresponding clearance dimensions if one 90° bend is imparted to the hose. c -- Hose - Clearance Chary- `r''- - --`•,', ' -. '`?. x „ ..'l S"T t?d - Inchesemm} Lam.' ii R Minimum 4 7 Bend Radius 102 178 Min. 14 161/4 B 323 373 Max. 14 16% 386 437 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 02010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. ictaulie 10.85 6 REV -_D • FIRE. PROTECTION PRODUCTS ACCESSORIES 10.85 1. -... .:.:I. .. ,..c.: 1 i t.:v' "i; FLEXIBLE DROP ASSEMBLY WITH TYPICAL INSTITUTIONAL SPRINKLER - BLOCK WALL OR CEILING INSTALLATION AquaFlex Series AQB and Series AQU systems can be installed in institutional pendent or sidewall .��� applications in block walls or ceilings ranging from 3 - 12' in thickness. See the tables below to select the correct flexible hose reducer for the required wall thickness. /ilo 8 toll q..)l'® '/ O AOUAFLEX INSTITUTIONAL BRACKET 5r STRAIGHT REDUCER 3° NOMINAL BLOCK WALL 4° NOMINAL BLOCK WALL ... • , Hose Clearances' '• - ' r iL yc ,_, I' ... .. ' R' Minimum 4/102 7/178 Bend Radius Lt 9 1/8 / 232 12 1/8 / 308 r\ R R L2 . 10 1/8 / 257 13 1/8 / 333 \ L3 8 5/8 / 219 11 5/8 / 295 1 t 4 10 5/8 / 270 13 5/8 346 A A L1 ASR IMMO B = B See C O O Note 1 _ See ;__ e l Note 1 7 �• L " 4r CU Ira _ _ / / / //. E I % /. E j t 1r;12 t 5.5" Straight Reducer . 5.5' Straight Reducer. _ 9' Straight Reducer - - 9' Straight Reducer=: . 13' Straight Reducer 13' Straight Reducer imliTa�!tttj, ;,Tel -a mil) ! rifbllv n3Mt al_ . svrfmiim n) ,; orrri -cti ). ..I ` . A 21/2 2K 215 21 2'h 21 . B 31 3'h 3V 3' 3' 3 C 5th 5V 9 9 13 13 D - 3sh 2 Vs 7 5 •-- 5 /e 11 s h 3% E 1 _ 1 _ 1 1 ; 1 F ... 1K 1V 11/2 1 1V• 1 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. jctaulic* REVD 10.857 . . FIRE PROTECTION PRODUCTS - ACCESSORIES 10.85 _. ® c - ... ....,.. ; ,, ,.. i- i , `),. ... ._,- Li ; ,1 ,...,.. , .., i,..; , . r---. ;— r. c ..,.. ...., ,.,,, . L.,1-...i 1. ..,;,,..,,,.- .-...} 9" STRAIGHT REDUCER 6" NOMINAL BLOCK WALL 8' NOMINAL BLOCK WALL Hose Clearances R I 4/102 7/178 1 / R 13 . 7 4 C'''-' L4 I 11 i all9=ill 'R' Minimum Bend Radius LI L2 9 1/8 / 232 12 1/8 / 308 10 1/8 / 257 13 1/8 / 333 13 8 5/8/219 11 5/8 /295 I 10 5/8 / 270 13 5/8 / 346 I= A 1.111 A L4 —......... DECO 1:12;113 B LW Wail _ See I, Note 1 NOP (4) C=2 II = B _____„_____ — • ii) c= Note 1 7 II% ..7_,P5 V 11 re aNg c 1 r ill 11/ , • / • ' .. or" . E .4: VA ___ E Lt-F-1: t . . , - 5.5 Straight Reducer, 5.5" Straight Reck 9" Straight Reducer 9" Straight Reducer, 13" Straight Reducer 13' Straight Reducer th LUIIJ _; i.. _ (' !Pin_ m 1 8 1 . 1 , lUiilitte 1 - {1;ictii) 11 ■IiiinftIV A 2½ 2 Y2 2½ 2½ 2½ 2½ B 3½ - Y2 3 3½ 3½ 3 V2 - C 5½ 5/2 9 9 13 13 3 sle D 2¼ 7% 5% 11%6 3 Ye E 1 I 1 1 1 1 F 1½ 116 1 'h 1 Y2 I Y, 1 • www.victaulic.com I VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. CI 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED jctau ic' 10.85_ ES REV ..D . .. FIRE PROTECTION PRODUCTS - ACCESSORIES 10.85 I ..J,., , ' I L'71. .... 13" STRAIGHT REDUCER 10' NOMINAL BLOCK WALL 12" NOMINAL BLOCK WALL Hose Clearances 11 = , kHz ,! ii =.' ,/ - P. Minimum 4/102 7/178 Bend Radius • LI 91/8/232 121/8/308 / / / R R L2 10 1/8 / 257 13 1/8 / 333 85/8/219 115/8/295 I t N I t \ L4 L3 10 5/8 / 270 13 5/8 / 346 , I I i I L3 A fliZt9 L4 A 11=1 1 OMNI =la B NaV r ..... , See .) /Note 1 EME —.LI!._., ..,, r , r WA , /see , .. ,,,, Note i t .._ P..-=,- v _ff 11 ,.... i Ma A .—. r — - 1 -1–___1 i t —.I F . • . - 5.5' Straight Reducer 5.5' Straight Reducer 9" Straight Reducer 9' Straight ReduCer 13' Straight ReduCer 13 Straight Reducer I Viti ■IA ; i Tadtarrnda J ' Emt-ITAN 11 •, ,, fritit 1 Lrouvratlii13 A 2½ 2½ 2½ 2½ 2½ 2 B 3½ 3½ 3½ 3 1/2 3 1/2 3 C - 5½ 5½ 9 9 13 13 - D 3% 2% 7% 5% 11 % 3 • E 1 I 1 1 1 1 F 1½ 1½ 1 1 V2 1½ www.victaulic.com ictaulic* VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV D 10.85_ 9 ` y FIRL PROTECTION PRODUCTS •••• ACCESSORIES 10.85 A quaRe Sthinies Ste el ` pronakwr F itte 6gs FLEXIBLE HOSE IN -PLANE BEND CHARACTERISTICS ONE BEND TWO BENDS THREE BENDS zx. zr. • Minimum Minimum Minimum I Minimum bend radius • bend radius I I bend radius bend radius • 9� I OR OR Minimum ' Minimum bend radius I bend radius i Minimum • Minimum bentl radius bend radius Minimum I bend radius Note: For out -of -plane (three - dimensional) bends, care must be taken to avoid imparting torque on the hose. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. C 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. ictaulic* 10.85_10 REV- -D Q C FIRE PROTECTION PRODUCTS •- ACCESSORIES 10.85 AquaFlex Stainless Ste& Sprinkler Fittings MATERIAL SPECIFICATIONS Corrugated Flexible Hose: SS304 Adapter Ring: SS304 (for r ID); Nylon (tor ' /e' ID) Seal: EPDM Nut and Nipple: Zinc - Plated Carbon Steel Reducer ('h or ' /4 ): Zinc- Plated Carbon Steel 90° Reducer (1 or 3 /0: Zinc - Plated Carbon Steel Braid and Collar: SS304 Bracket Stock Bar: Zinc - Plated Carbon Steel End and Center Brackets: Zinc - Plated Carbon Steel Staked Center Bracket Wing Nut: Zinc - Plated Carbon Steel End Bracket Screw: Zinc - Plated Steel Optional Tamper- Resistant Screw: Zinc - Plated Steel www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. O 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED. rlctaUlic' REV __D 10.65._11 I ,.fir; ter. r (; r .. 1 o� l-.�. -.ill' ie�.r -I 1. ;.;..,1;;: WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation /assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. For complete contact information, visit www.victaulic.com 10.85 5839 REV D UPDATED 1/2010 jctaauIIc VIC1AULIC IS A REGISIERLU TRADEMARK. of VIC1AULIC COMPANY. 0 2010 VIC [AMC COMPANY. ALL 910111S RESERVED. 10.85