BP 201 -440 9 Go
•
•
• -
•
15201 NW Greenbrier Parkway Suite A-4
Beaverton, Oregon 97006
•
Phone: (503) 207-1900
Fax: (503) 207 -1901
.
01
• FIRE . ALARM SUBMITTAL
WASHINGTON SQUARE
TESLA • MOTORS
Submittal Version Date Siemens Job Number
440P- 112616
RevO 06115112
Siemens Project Manager
Charls Hughes
•
Siemens Project Engineer
Mohsin Malik
Proprietary document for approval only
Table of Contents SIEMENS
Il. BILL OF MATERIAL &
COMPONENT SPECIFICATIONS
2 FUNCTIONAL MATRIX
3
4
5
9
•
•
•
BILL OF MATERIALS SIEMENS
Washington Square
Testa Motors
440P- 112248 Fire Alarm System
Item Part # Qty Mfg Description
1 FP -11 4 Siemens Fire Print Intelligent Detector
2 DB -11 4 Siemens Detector Base Standard
3 AD2 -XHR 2 Siemens Duct Detector Housing w /Relay
4 STA -50 2 Siemens Sample Tube for Duct Widths 3' to 5'
5 RSAW -11 2 Siemens Remote Lamp Indicator
•
•
•
•
'PROPRIETARY DOCUMENT FOR APPROVAL ONLY 3 6/15/2012
SIEMENS Data Sheet
Fire Safety & Security Products
MXL Panel I
FACP
Advanced Fire Protection System
ARCHITECT AND ENGINEER SPECIFICATIONS
• i`irePrint "" application - specific detection •Logic controlledoutputfurtctions
• More than 2000 intelligent inpuMlevicecapacity • Multiple levels of password protection
• • Automatic environmental compensation
Oynamcsupeivisionof intefligentdevices SIEMENS for smoke detectors
• Multiple command stations
• Security - device monitoring • One-person 'vraIk test' via 'loop; 'zone'
• Sprinkler supervision
• Detectorsensitivity readout/ printout, _ _ • ,4fa r m t verification by'device'or zone'
per NFPA 72 Chapter 7 '
• Time-base controlled output functions
• City Tie / Lease Line
• Intelligent /analog detection circuits: • Coded outputs
Style 6 (aassA) or Style 4(Oass B)
• Conventional initiating circuits: • Supervised serial annunciator
Style D (ClassA) or Style B (Class B) d river / input Interface
• Notif icatio n appliance circuits INA111: • 1 &gauge steel enclosure
Style Z (Class A)orStylev (Class El) • Multi language display
• Degrade -mode operation • Intelligent interface to building /
• Distil buted processing process - management systems
• Bache racter backlit, alphanumericdisplay • Operates as an interactive peer with
• 32- charactercustom messages other MXL. MXL -IQsor MXLVsystems
• Thermal-strip printer in a Ufe LINK Network
• Supervised remote printer • Pre -alarm operation
• Co mpare system software • NCCgraphics
• Fully fed program mable , via laptop PC • NEC 760 power-limited circuits
• Menu- drivenoperatorcommands - (AUL8649 ^ Edition compliant)
• Central &distributed architecture • Sinorix^' NFPA Approval (2001)
• Up to 800event history log with online • UUKL Usted for Smoke Contro l
• and off li ne reports • wUL 864 9 Edition Listed, OULC Listed;
• User help screens CSFM, NYC Fire Departmentand
• I-b liday schedule City of Chicago Approved
System Overview
The MXL fire panel is a microprocessor - based The MXL system is approved by CSFM, NYMEA and the aty
advanced protection system. The use of the MXL of Chicago for use in those specific locales.
system's unique multiprocessor 'network' design; as In addition to the standard fire applications, MXL is
well as its ability to utilize analog and conventional €UL Listed, under the category 'UUKL for Smoke Control.'
detection devices, makes the MXL panel a highly The MXL panel can be used as a listed fireman's smoke -
flexible and reliable fire-control system. control station in high-rise office buildings, malls and
The MXL panel is ideally suited for commercial, other multi -level or vast structures. The MXL
industrial and institutional fire - detection and system also complies with Uniform Building Code
notification applications. The MXL system Section 905 requirements for smoke control.
complies with the requirements of N Standard The MXL panel isPUL Listed for releasing SinorixNN
72, and is listed by ocU nderwriters Laboratories (UL), Engineered Fire SuSuppression System. MXL follows the
via its €4UL864 9" Edition. (AUnderwriter's' releasing requirements specified in the NFPA 2001.
Laboratories of Canada (ULC) also lists the MXL
panel for fire applications.
MXL Panel 5000
SIEMENS Industry, Inc.
Building Technologies Division
MXL Components
The basic MXL control unit consists of the following • [2) two - line, 80 character LCD display
sub - assemblies: MMB -3 Main Control Board; MPS-6 / • indicator LEDs
MPS -12 Power Supply; MKB -2 Annunciator and • display - control keys
Keyboard; MME -3, or MLE -6 Enclosures. Optional •numeric keypad
• 12 programmable function keys
modules — which can be installed with the MXL • all other keys necessary for operator control
System — include: MOM 214 Expansion Card Cage; These keys include but are not limited to: Acknowledge;
ALD 2I Analog Loop Driver; CRM-4 Controllable Relay Silence and Reset. Model MKB -2 also includes spaces
Module; NIM 1 W Network/Foreign Systems Interface for mounting the Model MMM -1 microphone module
Module; REP -1 Network Repeater Module; CSM-4 and the Model TMM -1 telephone. Model MKB -2 is
Controllable Signal Module; CZM -4 Conventional Zone supplied with two (2) blank plates for use when either
Module; PIM -1 Peripheral Interface Driver; CMI -300 the microphone or telephone is omitted.
NCC -WAN Modem Interface Module; PSR -1 Remote
Power Supply; NET -4 Style 4 Network Interface, and Display / Keyboard (MKB -5)
NET -7 Style 7 Network Interface.
Additionally, the MXL system includes option modules T .• `
MOI -7 System Interface, MOD -16 Output Driven and _
MID 16 Point Input Module. These option modules 1 7
can be used to drive graphic annunciators and 1
fireman's smoke control stations, or to monitor
foreign systems. MKB-5
The MXL is compatible with a full line of intelligent The MKB -5 display keyboard, which mounts on the inner
initiating devices highlighted by the FirePrintTM door of any MXL enclosure, provides:
application- specific detectors: Models FP -11 and FPT- • 6 - 114" VGA backlit, 80 character LCD display
11. The MXL panel is also compatible with FireFinder, • indicator LEDs
the NCC series of text and graphic command centers. • 12 programmable function keys
• numeric keypad
. MXL Enhanced Main Board (MMB - 3)
'�l 74,4.j.,: user - programmable function keys
• all other keys necessary for operator control
bo Th keys include but are not limited to: Acknowledge;
- f - 4 14 , — It'`: Silence and Reset. Multiple Model MKB -5 modules can be
°a ; .. used; each providing full control of the MXL system. Up to
•
-' "`=� ` four (4) Model MKB -5 can operate in a fully supervised
ls' . - f i , , R li mode; each with independent, built -in printer I driver
it, ,-
Ml capability.
MMB -3 Power Supply (MPS -6)
The function control of the MXL is contained on
the MMB -3 Main Control Board. Model MMB -3 • _.
offers a fast, integral microprocessor and " „
installation conveniences such as diagnostic LEDs . -_y
and removable terminal blocks for field wiring. -
Model MMB -3 acts as the central controller for the b i
system, and includes two (2) ALD circuits and two • - - • ' •
(2) notification appliance circuits. Model MMB-3
....
� •
mounts in the MXL enclosure back box.
• " •
Display / Keyboard (MKB -2) MPS -6
I Model MPS -6 is a fully supervised power supply that
• — - provides the MXL system with primary DC power. Model
`'
Y MPS -6 is rated at 6.5 Amps, and is unfiltered and
unregulated. Model MPS -6 supplies power to the MXL
T � � I , Control Unit, and supplies its expansion modules with
power required for normal operation. Model MPS -6
incorporates a circuit breaker on the primary input, and
MKB -2 includes a built -in AC -line filter for surge and noise
The Model MKB -2 display keyboard, which mounts suppression. Model MPS -6 mounts in the MXL enclosure
on the inner door of any MXL enclosure, provides: back box.
SIEMENS Industry, Inc.
Building Technologies Division
MXL Components — (continued) Analog Loop Driver (ALD -2I)
Power Supply (MPS -12)
• 11• • .� i y , r te
�. + I i 7 • ! awl
1111110111 -
• 11111111 • ALD -2I
' Model ALD -2I is a MXL network- option module that
• •
supplies two (2) intelligent analog circuits utilizing
Fire Safety "I ", "IL ", and FP series intelligent devices.
MPS -12 Model ALD -2I occupies two (2) addresses on the MXL
Model MPS -12 is a fully supervised power supply Network and through the use of unique
that provides the system with preliminary DC communication - protocol devices connected to the
power. Model MPS -12 is rated at 12 Amps, and circuits of Model ALD -2I. The circuits are dynamically
is unfiltered and unregulated. Model MPS -12 supervised by the MXL control panel. Up to 60
supplies power to Models PSR -1, MMB -3 and their programmable input and output devices may be
expansion modules with power required for connected to each of its two (2) circuits. Each circuit
normal operation. Model MPS -12 incorporates may be wired as Class B (Style 4) or Class A (Style 6).
a resettable circuit breaker on the primary input, Controllable Signal Module (CSM -4)
and includes a built -in AC -line filter for surge and
noise suppression. Model MPS -12 mounts in the ,m. •
MXL enclosure back box. - .: .f1-1+41 r}=r„
Network Optional Module Card Cage (MOM -4) • 11 Al, ' I.
�! j .fK1111* U1* 1f 111 _•1 rr�>-'!. y'.
"MI 177.111Mit • iJ
11
CSM-4
MTIVUlIttr
MOM -4 Model CSM -4 provides two (2) fully supervised,
programmable notification - appliance circuits.
The Model MOM -4 Card Cage provides the MXL Model CSM-4 supplies two (2) Class B (Style Y)
main unit or remote units with card slots for or Class A (Style Z) -type output circuits for the
option modules. Each Model MOM -4 supplies supervision and control of listed audible or visual
connection space for either two (2) full -width notification appliances such as: horns, bells,
option modules: (Models ALD -2I, CZM -4, NIM -1 R) strobes, etc.
or four (4) half -width option modules: (Models
CSM -4, CRM -4, CMI -300, NET -7, REP -1) or a Each circuit can provide up to 1.5 amps (24 VDC)
combination of one (1) full and two )2) half -width of current to power notification appliances. Model
modules. CSM -4 is also used for Sinorix. Leased line and
municipal -tie connections are also possible with
Network Optional Module Card Cage (MOM -2) Model CSM -4.
Controllable Relay Module (CRM -4)
40, t.
rir oee:.• tit '1 mill ...
m..:w..o +.
MOM - 2 I{� ". Si r
Model MOM -2 provides the MXL main unit,
remote units. Each Model MOM -2 provides space - •
for one (1) full width module (Models: ALD-21,
CZM -4, and NIM -1 R) or two (2) half -width
CRM -4
optional modules (Models: CSM -4, CRM -4, CMI-
300, NET -7, REP -1). Model CRM -4 is designed to provide auxiliary control
of building functions such as: door - holder release,
elevator capture, smoke control, lock release, etc.
Model CRM -4 provides four (4) fully programmable
relays. Each relay contains one (1) set of SPDT
contacts rated at 2 amps 30 VDC 1 120 VAC resistive.
SIEMENS Industry, Inc.
Building Technologies Division
MXL Components — (continued)
Communication Module (NET -4) Model REP -1 provides the ability to configure the
local or global networks of the MXL panel in a 'star'
, • _ or 'daisy-chain' configuration. Model REP -1 provides
t� q _ . . ` �.� two (2) Style 4 or one (1) Style 7 RS -485 network
}; g ; �-� `. ,: # . circuits. Through the use of Model REP -1, the MXL's
4 a -, *�- ` local network (MXL -MXLR) can be ex anded up to
• ` i� ; cattlI`� .1' ii - 64 nodes. P P
�.x *� . ,t s ja. 1 :� Remote Power Supply (PSR -1)
NET-4 !tea t '''1 i - c 1,. il • • .L -Er, _r„
Model NET -4 is a plug -in -type module used to 1 , st ' 1 ,' ,4 4 4 41 ,. - : :
tv N-t °4 L• Ilk'
�
provide communication between the Fire Safety 1- , ,
MXL panel and various other MXL remote 4 s ,• f t ,t ∎
- .
modules. Model NET -4 is designed to plug into * � '6�� • 1 ' i - '
an edge- connector -type slot on the Model PSR -1 . . ; . 1
Network Supply. Model NET -4 provides NFPA „ ._ i ri..
Style 4 -type communication: fully digital; PSR -1
RS -485 operating at 19.2K Baud rate. Model PSR -1 is a microprocessor - controlled remote
Style 7 Network Interface Card (NET -7) power supply and battery charger for use with the
MXL panel. Model PSR -1 operates in conjunction with
�� y 3 '. :. either a Model MPS -6 or MPS -12, providing 6 or 12
• _ ,,� Amps of power for use with various MXL modules.
.:;�� +r 7 •-3.,: When used with a Model NET -4 or Model NET -7 plug-
T 4�� •, — :» in communication module, Model PSR 1 becomes
• ..... r_ " i a part of the MXL panel's internal network. Model
lit , ,;, PSR -1 acts as an interface between remote - option
' modules and the MXL.
Peripheral Interface Driver (PIM -1)
NET -7
Model NET -7 is a microprocessor - controlled MXL x • -
network- interface module that allows the wiring ° � I .:
of the MXL RS 485 network in a NFPA Style 7 �' ,•,.t i - r •
configuration. Model NET -7 plugs into a half slot := �=
of the Models MOM -214 card cage at the MXL : ....1:
command center (MMB -2) and at the Model PSR -1 �kt+'s _�
or Model MOM -4 slot at the MXL remote units
(MXLR, MXLRV). PIM-1
Model NET -7 provides two (2) independent and Model PIM -1 is a MXL option module that provides
fully supervised communication paths, allowing a bidirectional, isolated RS -232 port for connection to
system operation through an open and short peripheral devices, such as: printers, CRTs, VDTs, color
circuit. Model NET -7 also isolates the power graphics, alphanumeric pagers and remote diagnostics
supplies at each remote unit, providing the ability hardware. Model PIM -1 mounts in the MXL enclosure,
to localize ground -fault conditions. The and connects to Model MMB -3, providing a screw -
communication for Model NET -7 operates at terminal block for connection of RS -232. A number of
19.2K Baud rate and is fully digital. supervised and non- supervised formats are available for
Model PIM -1.
Network Repeater Module (REP -1) Output / Input Module (MOI -7)
•• IV IfV" 4 44, a I
• T l� -• - L . 1 1 .. � t . . -
REP -1
MOI-7
SIEMENS Industry, Inc.
Building Technologies Division
MXL Components — (continued)
Model M01 -7 is a MXL RS -485 network module These inputs can be individually set for: Alarm,
that provides a fully programmable serial Supervisory, Trouble, Security or Status usage.
interface to Model MOD -16 output drivers and Further, the Model MID -16 inputs can also be
MID -16 input drivers. When used with Model configured to provide supervision for lamps driven by
MOD -16 drivers, Model M01 -7 provides a serial- Model MOD -16 outputs. Screw terminals and
annunciator output or relay driver. When used connectors are provided on the Model MID -16
with Model MID -16, Model M01 -7 provides modules for interface to monitored devices.
programmable inputs.
MXL / (V) Standard Size Enclosure (MME -3)
Each Model MOI -7 can operate up to eight (8)
Model MOD -16 drivers and eight (8) Model MID -
16 drivers simultaneously. Each Model MOD -16
output and Model MID -16 input is independently
programmable, via the MXL custom software.
Output Driver (MOD -16)
MME -3
The Model MME -3 enclosure set consists of a sheet -
x metal back box and door with key -lock. Model MME -3
can be used for the MXL System, MXLV Voice Command
�"`" Console, MXLR Transponder, MXLRV Voice Transponder
or Amplifier Equipment (via the Model MSR -1 Rail Kit).
To mount MXL I MXLV modules in Model MME -3, the
MOD -16 Model MBR -MP removable - module mounting plate is
Model MOD -16 is an output- driver module used in required.
conjunction with Model M01 -7, as a part of the Using the Model MBR -MP mounting plate — one (1)
Fire Safety MXL System. Up to eight (8) Model Model MMB, or one (1) Model PSR -1, and up to three (3)
MOD -16s can be connected to a Model M01 -7 expansion card cages (Model MOM or Model OMM) can
interface module. Each Model MOD -16 provides be mounted in the Model MME -3 enclosure. When used
16 open - collector, current - sinking outputs, which to mount MXL amplifiers (Model EL -410), the Model
are rated at 24 VDC, 50mA. Model MOD -16 MBR -MP module is not required. Instead, up to three (3)
outputs are programmable, via the MXL custom Model EL -410 amplifiers may be installed in Model MME -
software. 3, via three (3) Model MSR -1 Rail Kits. When amplifiers
are mounted in any enclosure, always install Model
Programmable Input Driver (MID -16) MDG -1 grills in the door for proper ventilation.
Model MME -3 is designed for surface of semi -flush
mounting, and includes various knockouts for wire and
conduit entry. The door in the Model MME -3 set has
two (2) cutouts for clear lenses, blank plates or grills —
depending on the application — and contains a key -lock.
MXL MME -3 and MLE -6 Modules
wow Mounting Plates (MBR -MP)
MID -16
Model MID -16 is an input module used in
conjunction with Model M01 -7, as a part of the
Fire Safety MXL System. Up to eight (8) Model
MID -16s can be connected to a single Model M01-
7, along with eight (8) Model MOD -16 output -
driver modules. Each Model MID -16 provides a MBR -MP
non - supervised input, which can monitor The MXL IV Module Mounting Plate (Model MBR -MP) is
normally open contact devices. required for use in both Models MME -3 and MLE -6
Each Model MID -16 input can be separately used enclosures in order to mount all MXL and MXLV
as a part of the MXL custom programming logic. equipment.
SIEMENS Industry, Inc.
Building Technologies Division
MXL Components — (continued)
Model MBR -MP is not necessary if Models MME -3 Model MBR -3MP allows mounting of an additional three
and MLE -6 enclosures are used only for mounting (3) Model MOM or Model OMM module expansion card
of amplifiers (Model EL- 410D). cages.
Model MBR -MP is a removable MXL IV module Various combinations of hardware can be installed in
mounting plate that allows the Model MME -3 or Model MLE -6. If only amplifiers are to be installed in
Model MLE -6 enclosure to be shipped to the job Model MLE -6, no Model MBR -MP or Model MBR -3MP
site for wiring and conduit installation, while the plates are required. Instead, up to five (5) Model EL-
system hardware (electronics) is mounted to the 410D amplifiers can be installed by using five (5) Model
studs on Model MBR-MP — pre-wired, MSR -1 rail kits.
programmed and tested — prior to delivery and Model MLE -6 can also be used to mount up to three (3)
installation at the job site. This process allows for MXL card cages and two (2) amplifiers. This
faster, more efficient system start -ups with less configuration would be typical of a remote, voice
chance of the sensitive electronics being transponder cabinet. In this configuration, one (1)
damaged while field wiring and conduit are Model MBR -MP would be used in the upper half of
connected to the system enclosure. Model MLE -6 to mount the MXL modules, while the
The Model MBR -MP mounting plate bolts to the lower half would use two (2) Model MSR -1 rail kits to
Model MME -3 or Model MLE -6 enclosures for easy mount up to two (2) Model EL -410D amplifiers.
installation on the job site. Model MBR -MP also Model MLE -6 is designed for surface or semi -flush
has handles to allow easy transport and Mounting, and includes various knockouts for wire and
mounting. Model The MBR -MP contains mounting conduit entry. The door supplied with the Model MLE -6
studs for one (1) Model MMB or Model PSR -1; one set has three (3) cutouts for either clear lenses, blank
(1) Model PIM -1; one (1) Model TBM -2, and up to plates or grills — depending on the application. The door
three (3) Model MOM or Model OMM card cages also contains twp (2) key - locks, which are keyed the
or two (2) card cages and one (1) TSP -40 Printer same.
(same mounting studs as the Model MBR-2 Various combinations of dead -front mounting
enclosures). plates are possible with the Model MLE -6 enclosure. A
Model MBR -MP is ordered and shipped separately typical MXLV installation would have one (1) Model
from the Models MME -3 and MLE -6 enclosures. MKB -2 at the top, and two (2) Model MHD -3 dead- front
MXL / (V) Large Size Enclosure (MLE -6) plates in the middle [for 14 VSM I VLM I VFM modules
per plate] and one (1) or two (2) Model MHD -2 lower
• dead -front plates.
MLE -6 Optional Card cage Mounting Plate
.�.1, (MBR -3MP)
MLE -6
The Model MLE -6 enclosure set consists of a sheet -
metal back box and door with two (2) key - locks.
Model MLE -6 can be used for the MXL system, MBR -3MP
MXLV Voice Command Console, MXLR Transponder, Model MBR -3MP is an optional MXL I MXLV card
MXLRV Voice Transponder or Amplifier Equipment cage mounting plate for use exclusively in the
(via the Model MSR -1 Rail Kit.) Model MLE -6 enclosure. When installed in the Model
To mount MXLIV modules in Model MLE -6, the MLE -6 back box, Model MBR -3MP adds the option of
Model MBR -MP removable module mounting plate mounting up to an additional three (3) Model MOM or
is required with the Model MBR -3MP option Model OMM expansion card cages.
available for use.
Using the Model MBR -MP mounting plate, one (1)
Clear Lens (MDL -1)
Model MMB or Model PSR -1 and up to three (3)
expansion card cages (Model MOM or Model OMM)
can be mounted in Model MLE -6. If additional card
cages are required, the Model MBR -3MP optional
card cage mounting plate can also be installed in
Model MLE -6, below Model MBR -MP. MDL -1
SIEMENS Industry, Inc.
Building Technologies Division
-
MXL Components — (continued)
Model MDL -1 is a clear Plexiglas® lens that fits in Middle Dead -Front Plate for Mounting Switch
one (1) of the two (2) openings in the Model MME- and LED / Fan - Control Modules (MHD -3)
3 enclosure door, or in one (1) of the three (3)
openings in the Model MLE -6 enclosure door.
One (1) lens is included in the Model MDL -1 package. • MI
Sheet Metal Blank Plate (MDB -1)
MHD -3
Model MHD -3 is a hinged sheet -metal panel that attaches to
the Model MME -3 or MLE -6 enclosure back box, and fits in
either the middle of the upper sections of the Model MME -3
MDB -1 or MLE -6 enclosures. Model MHD -3 has openings for two
(2) rows of Model VSM -1 Switch Modules; Model VLM -1 LED
Model MDB -1 is a sheet -metal blank plate that fits in Annunciator Modules; Model VFM -1 Fan Control Modules,
one (1) of the two (2) openings in the Model MME -3 or Model VSB -1 Blank Plates.
enclosure door, or in one (1) of the three (3) openings Model MHD -3 has openings for two (2) rows of Model
in the Model MLE-6 enclosure door. One (1) blank VSM -1 Switch Modules; Model VLM -1 LED Annunciator
plate is in the Model MDB -1 package. Modules; Model VFM -1 Fan Control Modules, or Model VSB -
Upper or Middle Dead -Front Panel (MHD -1) 1 Blank Plates. Each row can mount up to seven (7)
modules, totaling 14 modules for each Model
MHD -3. Model MHD -3 attaches to the backboxes with
screw fasteners, and is hinged for easy access to the
rear of the modules inside the enclosure.
Middle Dead Front Plate for the Switch /LED/
MHD -1 Fan - Control Modules with Printer Cutout (MHD -4)
Model MHD -1 is a hinged sheet -metal panel that
attaches to the Model MME -3 or the MLE -6 enclosure
back box, and fits in the upper or the middle section of
the Model MME -3 back box, or the upper or either of
the two (2) middle sections of the Model MLE -6 back
box. MHD -4
Model MHD -1 has an opening with a cover plate for Model MHD -4 is a hinged sheet -metal panel that attaches
the Model TSP -40 printer (when used), and attaches to the Model MME -3 or the MLE -6 enclosure back box, and
to the backboxes with screw fasteners. Once in place, fits in the middle section of both enclosures.
Model MHD -1 covers and protects modules and wiring; Model MHD -4 has openings for two (2) rows of Model
providing dead -front construction to that area. VSM -1 Switch Modules; Model VLM -1 LED Annunciator
Lower Dead -Front Panel (MHD -2) Modules; Model VFM -1 Fan Control Modules, or Model
VSB -1 Blank Plates. Each row has space to mount four (4)
modules, totaling eight (8) modules for each Model MHD -4.
Model MHD -4 also has a cutout to display the Model
TSP -40 Internal Thermal Strip Printer. Model MHD -4
mounts to the backboxes with screw fasteners, and is
MHD -2 hinged for easy access to the rear of the modules and
Model MHD -2 is a hinged sheet -metal panel that inside of the enclosure. When in place, Model MHD -4
attaches to the Model MME -3 or the MLE -6 enclosure covers and protects modules and wiring, providing dead -
back box, and fits in the lower section of the Model front construction to that area.
MME -3, and on the lower two (2) sections of the Model Rail Kit (MSR -1)
MLE -6 back box.
Model MHD -2 has no openings and attaches to the e�
backboxes with screw fasteners. Once in place, Model
MHD -2 covers and protects modules and wiring;
providing dead -front construction to that area.
MSR -1
SIEMENS Industry, Inc.
Building Technologies Division
MXL Components — (continued)
Model MSR -1 is a System 3Tm -type rail kit that fits into Model RCC -1 is a remotely located MXL annunciator display
either the Model MME -3 or MLE -6 enclosure back box. module. Model RCC -1 contains an 80- character LCD
Model MSR -1, which comes with a U- bracket and display and control keypad (MKB), as well as a PS -5N7
a Z- bracket, allows the following modules —or any network interface.
other System 3 -type module — to be mounted in Model RCC -1 modules can be located anywhere that
a Model MME -3 or Model MLE -6 enclosure: annunciation or control is required. Model RCC -1 can be
• Model EL - 410D amplifier programmed for display only, or can provide display and
• Model PS - 35 power supply system control. Remote printers, VDT, or graphics
• Model BC 35 battery charger computers can be located throughout a facility — provided
• Model M0I - 7 I / 0 interface
• Model MID - 16 input driver Model PIM -1 is added to Model RCC -1.
• Model MOD 16 output driver ® UL Listed Parallel Printer PAL -1
• Model PS -5A power supply ( )
• Model SYS3 -MPFO
[for mounting the D2300CP fiber -optic interface
modules]
When used in the Model MME -3 enclosure three (3) , x
Model MSR -1 Rail Kits can be installed to mount up
to three (3) rows for up to three (3) EL -410D
amplifiers. When used in the Model MLE -6, up to five PAL -1
(5) MSR -1 Rail Kit rows can be installed to allow
mounting for up to five (5) EL -410D amplifiers. Model PAL -1 is a ®UL Listed, supervised parallel- system
printer for the MXL panel. Model PAL -1 connects
When the Model MLE -6 enclosure is used with the to Model MKB -5 to provide the MXL panel with a
Model MBR -MP mounting plate for installation of MXL ®UL Listed, supervised parallel- system printer.
or MXLV equipment, up to two (2) Model MSR -1 Rail
Kit rows can also be installed in Model MLE -6 for B6 Intelligent Control Point (ICP -B6)
mounting of either two (2) Model EL -410 amplifiers or
some complement of System 3 -type mount modules.
MPS -12 transformer I supply, can accept NET -4 or NET
7 network interfaces, and includes diagnostic LEDs `' '
and two (2) system relays. Model PSR -1 mounts in the
upper section of the MXL enclosure back box. ,,, , , �` . "„
Thermal Strip Printer (TSP -40A) -
ICP -B6
• Model ICP -B6 is a field- mounted output module that is
4
arm capable of being programmed to either a remote bell or
horn — or to a speaker or telephone zone. Model ICP -B6
•
communicates with the MXL fire panel, via ALD loop.
I
TSP -40A Line - Isolator Module (LIM -1)
Model TSP -40A is a thermal strip printer, designed as
an event - logging device for the MXL panel, providing a
' `w LIM -1 of
permanent- history report of all system activity. Model „, ; •
TSP -40A mounts in the MXL enclosure, and its printout ;N ;
is visible through a window in the locked -door (
•. -
enclosure. Printouts are automatically spooled on a , �� ..tea
take -up reel for easy records storage.
Remote Command Console (RCC -1) LIM -1
Model LIM -1 is a short - circuit isolator module for use on the
analog loops of the MXL panel. Model LIM -1 is capable of
-- providing Style 4 or Style 6 wiring of the ALD loop. Multiple
s` , short- circuit isolators can be used on a single ALD loop to
prevent loss of protection in the event of a short circuit.
IUL
RCC -1
SIEMENS Industry, Inc.
Building Technologies Division
MXL Components — (continued) Details for Ordering
5 -Volt Power Supply / Network Interface (PS -5N7) Model Part
Number Number Description
t c- te n { . ' I i s: 1j • ,..
S: �'f Yz: ALD -2I 500 - 891618 [2] Two -Loop Analog Driver
4 '." °ir : oz, .4-+.r CRM-4 500-890401 Programmable Relay [94] Modules
o (� .. :.. I t ; _t "
. CSM -4 500-890402 Notification Appliance Circuits [2] Module
i_ 7-1,.r-11,,,,.. x '" "' ... ICP -B6 500- 895303 Intelligent Control Output [B6 chip]
. , F ® LIM -1 500- 892361 Short- circuit Line Isolator (ALD)
`�3 MBR -MP 500 - 694210 Module Mounting Plate [MME -3, MLE -6]
PS -5N7 MBR -3MP 500- 694532 Module Mounting Plate [MLE -6 use only]
Model PS -5N7 is a 5V power supply and MXL local- MDB -1 500- 692070 Blank Metal -Door Inserts
network interface module. Model PS -5N7 is an integral MDL -1 500- 692069 Plexiglas® Door Insert
part of Model RCC -1. Model PS -5N7 can be used to MHD -1 305- 092071 Middle 1 Dead Front 1 no openings
provide a Style 4 or Style 7 network interface for either MHD -2 305 - 092072 Bottom I Dead Front 1 no openings
a remote transponder for the MXLV panel (with either MHD -3 305 - 092073 Middle 1 Dead Front [w/ switch openings]
Model TBM -2, ACM -1 and VSM -1 I VLM -1 1 VFM -1), or MHD -4 305 - 092074 Middle / Dead Front [wl switch, printer openings]
to drive Model OMM -1 and associated MXLV cards. MID -16 500 - 891747 16 -Input Driver Module
MKB -2 500 - 892077 Hinged Display /Control Keyboard
5 -Volt Power Supply (PS -5A) MKB -5 500 - 648727 Multi -Line Display / Control Keyboard
Model PS -5A provides 5 Volts for powering Model MOI- MLE -6 500- 694530 Large Enclosure
7. Model PS -5A obtains its power from the 24 -Volt [holds up to six (6) Model OMM I MOM modules]
MMB -3 500 - 648860 MXL Main Board, Fast Processor
power supply in the MXL system. Models M01-7 and MME -3 500 - 694209 Medium Enclosure [holds up to 6 OMMsI MOMS]
PS -5A both mount on System 3 rails, and can also be MOD -16 500 - 890828 Programmable Output Driver
mounted externally to the MXL system. MOI -7 500- 892800 Network I 1 0 Interface [Style 4 or 7]
Models M01 -7 and PS -5A typically drive remote- MOM -2 500- 892766 Expansion Card Cage [2 slots]
graphics annunciators or monitor foreign systems and MOM-4 500 - 890269 Expansion Card Cage [4slotsl
devices. MPS -6 500 - 490357 MXL 6 -Amp Power Supply
MPS -12 500- 492209 MXL 12 -Amp Power Supply
Network Interface Module (NIM-1W) MSR -1 545 - 092415 Single -Row Rail Kit for Model MBR -2
NET 500 - 891181 Style 4 Communication Module
• . •44 r , t - h Z -_ NET -7 500 - 091914 Style 7Communication Module
,.• , -1 1 Y - ' �„ �.
•, ,: _ 1 i ,� }.._.:r ' ' 4 . NIM-1W 500 - 699103 Local and Wide -Area Network Interface Module
`�:_•.'- --- PAL -1 500- 692407 '•=)ULListed, Field- Mounted Parallel Printer
.`: ` ---s k- :f• < "' Std . PIM -1 500 - 691324 Peripheral Interface Module
MM -1W PS -5N7 500- 892728 Local Network Interface [Style 4 or 7]
PSR -1 500 - 891182 Remote Power Supply I Controller
Model NIM-1W allows for the interconnection or RCC -1 500 - 692533 Remote Command Display Console
networking of up to 63 MXL panels. Model NIM-1W REP -1 500 - 892954 RS -485 Network Repeater .
provides a RS -485 communications path in either Style TSP -40A 500- 634933 Thermal Strip Printer
4 or Style 7 wiring configurations. Model NIM-1W
allows MXL panels to have inter -panel logic, as well as
communicate in a peer -to -peer manner. Model Related Documentation
NIM-1W can be programmed via CSGM logic as a Product Data Sheet Number
foreign system interface to communicate with MXLV 5035
external - building management systems.
SIEMENS Industry, Inc.
Building Technologies Division
Installation and Operation Manual [IOM]
Model Part
Number Number Description
M -1 315- 090725 Conventional Zone Module
ILI -1 1 1H 11A 1 1AH 315- 092724 Intelligent Ion Detectors
ILP -1 1 IPLT -1 315- 092594 Intelligent Photo Detectors
ILT -1 315- 093336 Intelligent Heat Detectors
ILI -1 B I 1BH 315 - 093234 Intelligent Ion High Velocity Detectors
ILP -2 315- 095028 FirePrintTm Application-Specific Detection
MSI -10B 120B 315 - 093329 Intelligent Manual Station
MS -MI 315 - 092169 Intelligent Metal Manual Station
TRI -B6 I B6D / B6R 315 - 093315 Intelligent Monitor Module [single l dual with array]
TRI -B6M 315- 094547 Intelligent Mini - Monitoring Module
ICP -B6 315 - 092471 Intelligent Control Output [B6 chip]
UM -1 315 - 092135 Line - Isolator Module
FP -11 315- 095921 Intelligent FirePrintTM Detector
TRI -SIDIR 315 - 096242 Intelligent Monitor Module
Note: For further details, refer to MXL IOM manual: 315 - 092036.
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up -to -date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Femwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario November 2010
Building Technologies Division Tel: (973) 593 -2600 ISII - FS) L6T 5E4 / Canada
Supersedes sheet dated 3/10
FAX: (908) 547 -6877 Printed in U.S.A. Tel: (905) 799 -9937 (Re•. 2)
URL: www.SBT.Siemens.com /FIS FAX: (905) 799 -9858
SIEMENS Catalog Sheet
Fire Safety & Security Products
MXL, MXL -IQ and MXLV Panels
Intelligent FirePrint Detector
Model FP -11
ARCHITECT AND ENGINEER SPECIFICATIONS
• Most Sophisticated "Detector Intelligence" available in the Fire/ Life Safety market
• Multi- criteria fire detection for the price of a photoelectric detector - - -- ._...._.,.�
• FirePrintTM' technology to distinguish between deceptive
phenomena and an actual fire
• Easily programmed to match specific hazard profiles
from the fire -alarm control panel (FACP)
• Pre -Alarm reporting based upon fire profile selected
•
• Remote- sensitivity- measurement capability / ~
• System -logic activation based upon any of three (3) y
inputs from the detector (smoke, heat or 'neural network)
• Field- cleanable chamber with replaceable chamber parts
• Compatible with field programmer / tester (Model DPU) •
or FPI -32 Upgrade Kit
• Supports software - based, automatic environmental
compensation (EnviroLINK) • Multi- color, detector - status LED
• Backward compatible with older MXL systems
(Rev. 2 and above) • (2) Two -wire operation
• Optional fully programmable relay base, audible base • ®UL and ®ULC Listed;
and duct housing FM, CSFM & NYMEA Approved
• Product Overview
The Intelligent Fire Detector (Model FP -11) provides methods and reduces installation and service costs by
the most highly evolved detection system - electronically programming and testing the detector
including the most sophisticated level of protection; prior to installation.
as well as nuisance -alarm immunity.- currently
available in the Fire 1 Life Safety market. Specifications
Model FP -11 utilizes advanced detection Model FP -11 is a plug -in, two -wire, multi- sensor
technology that allows the detector to distinguish detector with photoelectric and thermal inputs that is
non - threatening deceptive phenomena (i.e. - compatible with the MXL family of FACPs. Each
cigarette smoke) from actual fire hazards, while detector consists of a dust - resistant, field - cleanable
optimizing detection for the area of its intended photo chamber; a solid- state, non - mechanical thermal
zone. Model FP -11 uses state -of- the -art sensor, and microprocessor -based electronics with a
microprocessor circuitry with error check, detector low- profile plastic cover and base.
self- diagnostics and supervision programs. Model FP -11 utilizes state -of- the -art ASIC and surface -
Model FP -11 is compatible with the Siemens mount technology for maximum reliability. Every
Industry, Inc. - Fire Safety division's FPI -32 upgrade Model FP -11 fire detector is shipped with a protective
kit or Siemens' field - programmer I tester (Model dust cover. Model FP -11 fire detector utilizes an
DPU), which is a compact, portable and menu- infrared light- emitting diode (IRLED), and light sensing
driven accessory for efficiently programming and photodiode. Under normal conditions, light transmitted
testing detectors electronically. Model DPU or by the LED is directed away from the photodiode and
FPI -32 upgrade kit eliminates the need for scattered through the smoke chamber in a controlled
cumbersome, unreliable mechanical programming pattern.
Intelligent FirePrint Detector 6175
SIEMENS Industry, Inc.
Building Technologies Division
•
Specifications — (continued)
The smoke chamber is designed to manage light sophisticated mathematical formulas or algorithms —
dissipation and extraneous reflections from dust comparing this input to characteristics of both
— particles or other non -smoke airborne contaminants threatening and deceptive phenomena that would
in such a way as to maintain stable, consistent deceive any ordinary detector. This technology was
detector operation. When smoke enters the developed over years of research and reviewing the
detector chamber, light emitted from the IRLED results of over 20 years of fire -test data in one of the
is scattered by the smoke particles, and is received world's most advanced fire research centers. The
by the photodiode. results of this research are the mathematical models
Model FP 11 also utilizes a modern, accurate and that form the algorithms used in FirePrint. No other fire
shock - resistant thermistor to sense temperature detector has this level of intelligence or this amount of
• changes. The 'on- board' FirePrint technology research and development supporting its design.
allows the detector to gather smoke and thermal The software of the microprocessor can identify and
data, analyzing this data in the detector's 'neural disregard false input caused by radio frequency (RFI)
network.' By comparing data received with the and electromagnetic (EMI) interference, and validates
common characteristics of fires, or fire fingerprints, all trouble conditions before annunciating or reporting
Model FP -11 can compare these 'fire prints' to to the control panel. The microprocessor for Model FP-
those of deceptive phenomena that cause other 11 uses an integral EEPROM to store the detector's
detectors to alarm. The advanced FirePrint address and other critical operating parameters, which
technology allows the Model FP -11 to accurately include the assigned program values for alarm and
determine a true fire hazard from non - threatening, trouble thresholds.
deceptive phenomena — without the need to use Communications within the detector; between Model
alarm delaying verification and confirmation FP -11 and the FACP; or with the field programmer 1
techniques, which can increase the probability tester (Model DPU), are supervised and safeguarded
of losses due to fire. against disruption by reliable, microprocessor -based
Model FP -11 provides the highest level of detector error checking routines. Additionally, the
intelligence available today with a detector I microprocessor supervises all EEPROM memory
control -panel link that allows the user to program locations and provides a high degree of EEPROM failure
the detector for the specific hazard profile. fault tolerance.
•
Detectors are optimized by selecting one (1) of In MXL 1 (V) applications, Model FP -11 determines its
the following applications: operating status to be in'normal, alarm, or trouble
• Office / Retail mode, depending on the difference between the alarm
• Lobby threshold values stored in the detector's memory and
• Computer room the detector's latest analog measurement. The detector
• Dormitory then communicates changes in its status to the FACP.
• Healthcare facility
• Parking garage In addition, the MXL I (V) FACP will sample the value of
•
• Utility 1 transformer room the analog signal for Model FP -11 over a period of time,
• Hostile environment in order to determine if those values indicate excessive
• Precious storage buildup in the photo chamber. In the event of
• Air duct excessive buildup, the MXL 1(V) FACP will accurately
• warehouse 1 light manufacturing indicate which detector shall require maintenance.
Once programmed, the software does the rest — Model FP -11 is listed as a self- testing device. The LED
no guessing on detector sensitivities or alarm for Model FP -11 flashes GREEN every four (4) seconds,
verification — the FACP programs Model FP -11 for indicating communication with the FACP, and that it
the protected area without any confirmation delays. has passed its self -test. Should the detector sense a
Once optimized for the hazards in the protected fault or failure within its systems, the LED will flash
area, Model FP -11 provides the utmost means in AMBER, and the detector will transmit that data to the
detection. Should the operator or installer forget FACP. A quick visual inspection is sufficient to indicate
to program the detector, Model FP -11 will revert the condition of the detector at any time. If more
to a default setting that, in turn, allows operation detailed information is required, a printed report can be
as a standard photoelectric or photothermal provided from the MXL panel, indicating the status and
detector. settings assigned to each individual detector.
The FP -1 l's FirePrint technology for Model FP -11 When Model FP -11 moves to the alarm mode, it will
monitors input from the photo chamber and the flash AMBER, and will transmit that data to the FACP.
thermal sensor, evaluating this information with When the MXL 1 (V) confirms the condition of the
detector, the FACP will instruct Model FP -11 to flash
SIEMENS Industry, Inc.
Building Technologies Division
•
Specifications — (continued)
RED — and to continue flashing RED, until the detector locks, as well as an installation tool, preventing
system is reset manually at the FACP. At that same unauthorized removal of the detector head. Model
time, any user - defined system alarm functions DB -11 has integral, decorative plugs to cover the outer
programmed into the system are activated. Each mounting screw holes.
Model FP -11 detector can operate one (1) remote Model FP -11 is electrically compatible with existing
alarm indicator; one (1) auxiliary relay, or one (1) MXL- detector accessories, including relays, remote
audible base. lamps, duct housings and audible bases. With duct
Detector sensitivity, calibration and identification housings, a base adapter and new detector housing
are dynamically supervised by the FACP. Detector cover are required (order AD -11 UK upgrade kit). To use
sensitivity and pre -alarm levels are a function of the existing Model DB -3S base or audible base, Model FP -11
application chosen at the FACP, and are controlled requires a base adapter (Model DB- ADPT).
by the panel. If an.alternate, non - FirePrint mode is All Model FP -11 detectors are approved for operation
selected, then the sensitivity can be changed from within the ®UL- specified temperature range of 32 °F
the FACP. (0 °C) to 100 °F (38 °C).
The Program l Test unit (Model DPU) or FPI -32
upgrade kit is used to program and verify the Application Data
detector's address. The technician selects the Installation of the Model FP -11 series of fire detectors
accessory's program mode to enter the desired requires a (2) two-wire circuit of 18 AWG (minimum)
address. In turn, Model DPU or FPI -32 automatically thermoplastic fixture wire enclosed in conduit, or 18
sets I verifies the address, and tests the detector. AWG (American Wire Gauge) limited energy, shielded
Model DPU also allows the user to change the cable without conduit, if permitted by local codes. Field
device ID from that of a Model FP -11 detector to an wiring should conform to local and national electric
older detector ID (such as: ILP -1, ILPT -1, ILP -2, ID- codes and the control panel wiring specifications.
60P or ID -60PT) to allow for easy replacement of
older detectors without the need of reprogramming "T- tapping " is permitted only for Style 4 (Class B) wiring.
the FACP. Model FP -11 fire detectors can be applied within the
The FPI -32 upgrade kit operates on AC power or maximum 30 -foot center spacing (900 sq. ft. areas), as
rechargeable batteries, providing flexibility and referenced in NFPA 72. This applications guideline is
convenience in programming and testing based upon ideal conditions — specifically — smooth
equipment from almost any location. When in test ceiling surfaces, minimal air movement, and no physical
mode, Model DPU or FPI- 32 kit will perform obstructions between potential fire sources and the
a series of diagnostic tests without altering the detector. Do not mount detectors in close proximity to
address or other stored data, allowing technicians ventilation or heating and air - conditioning outlets.
to determine if the detector is operating properly. Exposed joints or beamed ceilings May also affect safe
Model FP -11 may be installed on the same'initiating. spacing limitations for detectors. Should questions arise
circuit with IL or ID series detectors (Photoelectric, regarding detector placement, observe National Fire
thermal, or ionization), M51-series manual stations, Protection Association (NFPA) 72 guidelines.
TRI- series interfaces, ICP output control devices, or
CZM series of addressable, conventional -zone Dimensions
modules. Diameter Base
All Model FP -11 detectors can be cleaned in the 6"
field — when required — by simply removing the
detector cover and unsnapping the photo chamber. T WI PP-
There is also the option of cleaning the interior of Overall the detector with a clean, soft cloth or brush, or Height
replacing the labyrinth and bug screen included in
the detector maintenance kit, Model DMK -11. I>n'
Model FP -11 uses the low- profile, surface - mounting IV? df
base, Model DB -11. This base mounts on a 4 -inch
octagon, square, or a single -gang electrical box.
The base utilizes screw -clamp contacts for electrical
connections and self- wiping contacts for increased
reliability. The base can be used with the optional
Model LK -11 detector locking kit, which contains 50
SIEMENS Industry, Inc.
Building Technologies Division
Technical Data Details for Ordering
Environmental Model Part
Temperature: 32 °F (0 °C) to 100 °F (38 °C) Number Number Description
Humidity: Up to 93% RH, non - condensing
Air Pressure: No effect FP -11 500 - 095112 Addressable FirePrinUm Detector
Alarm Temperature: 135 °F (57 °C) DB-11 500-094151 Detector Mounting Base
For Series 11 Intelligent Detectors
Electrical DB -11 E 500-094151E Detector Base (Small)
Voltage: 16 -27 VDC Air -Duct Housing (for use with Models
Ripple: 3V peak -to -peak AD2 -P 500- 649706 FP -11, HFP -11,
HFPO -11 and PE -11 Detectors)
Supervisory Current: 110pA.max Air -Duct Housing (for use with Models
Alarm Current: • 33 -50 mA AD2 -XHR 500 - 649708 FP -11, HFP -11,
HFPO -11 Detectors with Relay)
ADBX -11 500 - 096181 Audible Base
DB -X11 RS 500 - 096125 Relay Base for Series 11
• Intelligent Detectors
RLI -1 500-390673 Remote Alarm Indicator:
4" Octagon Box Mount, Red
RLI-2 500 - 390674 - Remote Alarm Indicator:
Single -Gang Mount, Red
DMK 11 500-695338 Series 11' Maintenance Kit (replacement
. / labyrinth and bug screen)
DB -ADPT 500 -094187 Base Adapter to Model DB -3S Base
• LK -11 500 - 695350 Base Locking Kit for Series 11 Detectors
In Canada, please order:
•
Model Part •
•
Number Number • Description
135 °F Fixed Temperature, Plug -In
FP-11C 500-095112C Detector Addressable FirePrintIm
Detector IULC Listedl
Detector. Mounting Base
• • DB -11C 500- 095687 For Series 11 Intelligent Detectors
IOULC Listed] •
AD -.11 PC 500 - 095984 Air -Duct Housing IULC Listed]
DB X11 RSC 500 093125C -Relay Base for Series 11 Intelligent
Detectors I€ULC Listed]
•
ADBX-11C 500-096181C Audible Base for Series 11 Intelligent
• Detectors I €ULC Listed]
Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up -to -date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Femwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
Building Technologies Division Tel: (973) 593 -2600 su•FS L6T 5E4 / Canada August 2010
• FAX: (908) 547 -6877 Printed in U.S.A. Tel: (905) 799 -9937 Suvenedes sheet dated 5/06
)Rev.l)
URL: www.SBT.Siemens.com /FIS FAX: (905) 799 -9858
•
SIEMENS Catalog Sheet
Fire Safety & Security Products
Air -Duct Housings and Detectors
Air -Duct Housings — AD2 Series
Models AD2 -P, AD2 -PR, AD2 -XHR, AD2 -4W, ST(s): 10, 25, 50 and 100
ARCHITECT AND ENGINEER SPECIFICATIONS
• For use with Series 11 detectors
• Relay models available
• Design for air - velocity range of 100 to 4,000 fpm i ---
• Alarm LED visible from front
t „IM,h,
• Self- contained model available with t.
'on- board' power supply 1 1 �.... =- • _-
• Clear housing cover for quick f • ; 4 ,-Ardwis ---=
identification of detector type;
• removable with only four (4) captive screws
• ®UL and @ULC Listed;
FM, CSFM & NYMEA Approved
Product Overview
The Siemens Industry, Inc. — Fire Safety Air -Duct Notes - (cont.'d): With the MXL series of control panels, up to 60
Detector Housings are designed to be used with the detectors (per circuit) having relays may be used. The connection of
Series 11 detectors. Designed for installation a remote lamp or a remote relay is allowed for each detector, but not
simultaneously.
directly to heating, ventilating and air-conditioning With the FireFinder XLS series of control panels, up to 252
duct systems, they comply with National Fire detectors (per circuit) having relays may be used. The connection of an
Protection Association Standard No. 90A. When intelligent remote lamp (ILED) and a remote Relay is allowed for each
equipped, the air -duct detector housing will signal the detector simultaneously.
presence of smoke being carried through the duct Air -duct housings (see: Details for Ordering) are °Underwriters'
system. Air -duct detectors are not intended to be Laboratories, Inc. listed.
substituted for open -area detection. Specifications
Air -duct housings can be equipped with optional relays, The air duct housings are uniquely designed to use
which are utilized to operate any supplementary with the photoelectric detector. Sensitivity of PE -11
equipment when smoke is detected. detectors can be checked by viewing the LED or a
Notes: Most conventional time - control equipment guarantee RSAW- 11 or RSAC - multicolor remote lamp. A green
only one (1) detector per zone when the detector operated flash indicates the detector has passed its self test.
relay function is critical. The connection of a remote
lamp and a remote relay per detector is allowed with Amber indicates a 'Trouble' condition, and red indicates
PXL or System 3T'" only; other conventional systems may an 'Alarm' state. HFP -11, HFPO -11 and FP -11 sensitivity
use either a remote lamp or a relay. may be viewed from the multi -color LED on the detector
or, preferably, may be printed by command on an
optional printer from the MXL control panel.
Air -Duct Housings and Detectors 6185
SIEMENS Industry, Inc.
Building Technologies Division
Specifications — (continued)
The detector unit employs a cross - sectional sampling All that is necessary for installation of the air -duct
principle of operation. Inlet sampling tubes are detector is the cutting of three (3) small holes for the
available in four (4) lengths (see: Sampling Tube Sampling Tube installation (template included),
Selection Table). Outlet sampling tubes are one (1) and the drilling of two (2) holes for mounting the
common length and draw. A continuous, cross - sectional air -duct housing. The unit is then easily mounted in
sample of air moves through the duct. Stratification or place, and connection made to the existing wires
skin affect phenomenon that occurs in the duct can or terminals —if optional accessories are
prevent smoke (especially in large ducts) from reaching utilized.
a spot -type detector. (For full details, refer to installation instructions part number
In addition, the unique design of the sampling chamber 315-049708-4.)
insures uniform sensitivity in air velocities, ranging ST -50 and ST -100 require support. ST -100 is shipped in
from a low of 10- feet -per- minute to as high as 4,000- two (2) 5 -ft. (152 cm.) pieces with a coupling for field
feet -per- minute. Each housing comes with three (3) assembly.
wiring entry ports: Technical Data
• Two (2) 3/4" conduit knockouts
• One (1) 1/2" conduit opening Temperature Range: 32 °F (0 °C) - 100 °F (38 °C)
The inlet sampling tube length is determined by the Altitude Range: No Altitude Limitations
width of the air duct being protected. The inlet tube— Relative Humidity: 10 - 85%
greater than and nearest to the duct width — should be (non condensing I non - freezing)
used (see: Sampling Tube Selection Table). The inlet Air - Duct Velocity Range: 100 - 4,000 Ft. /Min.
tube can then be trimmed at the job site to the exact Sampling Tube Pressure Greater than 0.01 inches; less
width of the duct. The outlet sampling tube for all ducts Range of Differences: than 1.2 inches of water column
— irrespective of width — has a fixed length of Note to Architect: When building codes regulate the location of
approximately 5.5 inches (14cm.), and is supplied with detectors within ventilating systems, make sure the number and
the air -duct housing. locations of detectors is in accordance with the code regulations.
Note: When the use of a remote relay is required, order model D for Ordering
for conventional systems; AD2 -XHR for addressable g
systems. When required the WP - 2000 weatherproof enclosure Model Part
for duct housing is available. Description
(For full details, refer to installation instructions part number Number Number
315-049708.) AD2 P 500-649706 Air -Duct Housing for use with FP -11,
Note: When a self - contained duct detector with power HFP -11, HFPO -11 and PE 11
supply is required, order model AD2-4W. AD2 -PR 500 - 649707 Air -Duct Housing for use
(For full details, refer to installation instructions part number with PE 11 relay
315- 049708.) AD2 500 - 649708 Air -Duct Housing for use with FP -11,
Sampling Tube Selection Table HFP -11 and HFPO 11, with relay
AD2-4W 500-649709 Self- contained Air -Duct Housing with
Duct Width
Sampling Tube 'on board' power supply and relay
(Model No.) ST - 500 - 649710 Sampling tube for Ducts 6" to 1'
For duct widths 6" to 1' ST -10 ST -25 500 - 649711 Sampling tube for Ducts over 1' to 3'
For duct widths 1' to 3' ST -25 ST -50 500 - 649712 Sampling tube for Ducts 3" to 5'
For duct widths 3' to 5' ST 50 ST -100 500- 649713 Sampling tube for Ducts 5' to 10'
(requires support)
For duct widths 5' to 10' Product Includes:
(requires support) • ST -100
- (1) short - return (outlet) tube
Maintenance of the detector is easily accomplished - (1) stopper
by the removal of the Series 11 duct - housing - (2) #12 + 3/4" sheet screws
sampling chamber cover. The detector, which plugs - (1) mounting template
into the housing, is easily removed for cleaning by Note: Detector and sampling tube to be purchased separately.
a trained technician. Minimum hardware required is: one (1) air -duct housing
assembly; one (1) sampling tube and one (1) detector.
Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up -to -date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
Building Technologies Division Tel: (973) 593 -2600 SFS L6T 5E4 f Canada December 2009
FAX: (908) 547 -6877 Printed in U.S.A. Tel: (905) 799 -9937 Supersedes sheet dated 9/09
(Rem. 2 )
URL: www.SBT.Siemens.com /FIS FAX: (905) 799 -9858
FIRE SYSTEM FUNCTION MATRIX SIEMENS
Washington Square Revision: 0
Testa Motors •
440P- 112248
SYSTEM RESPONSE
0
O
O 0
O.
co
.0 _2 E al
c (i
v o m
c F- v m E
i2 c
o_ m
a( w a E
,e E
Cu C 2
co
0. a) Q it
(.0 co Q 2 D
C 2 it
0
O _
c O LL 0
V c al . , a) y
'5 co t m I 0 ` W 2 5 N O
O
Q O v
(] O 0 u) O 0
• : O O O N a 2 O a
a) a € 3 a E cl a)
o
INITIATION DEVICE ACTIVATED Q 3 ¢ 12 ('n ¢ 1- cnn .
Area Smoke /Heat Detector X X X
Air Handler Duct Smoke Detector X X X X
Waterflow Switch X X X
Valve Tamper Switch X X
Fire System Trouble _ X X
PROPRIETARY DOCUMENT FOR APPROVAL ONLY 4 6/15/2012
•