irinPaD Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 pactiyi
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
tamed when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
Description standard corrosion tests of the appli- '
cable approval agencies, the testing is _
The Tyco® Series TY -FRB, 2.8, 4.2, not representative of all possible cor-
5.6, and 8.0 K- factor, Upright and Pen- rosive atmospheres. Consequently, it .
dent Sprinklers described in this data is recommended that the end user be I I lip
•
sheet are quick response - standard consulted with respect to the suitability
coverage, decorative 3 mm glass bulb of these coatings for any given corro-
type spray sprinklers designed for use sive environment. The effects of ambi-
in light or ordinary hazard, commercial ent temperature, concentration of
o
tz.
ccupancies such as banks, hotels, chemicals, and gas /chemical velocity,
—
shopping malls, etc. should be considered, as a minimum,
The recessed version of the Series along with the corrosive nature of the
TY -FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be exposed.
^`
plicable, is intended for use in areas p
with a finished ceiling. It uses either a An intermediate level versions of the ..-;
two -piece Style 10 (1/2 inch NPT) or Series TY -FRB Pendent Sprinklers ,' , .\ \
• Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet t •
• cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de-
1 recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780 1 ,
(19,1 mm) of total adjustment from the t
flush pendent position, or a two -piece WARNINGS
Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY -FRB Sprinklers de- "`
inch NPT) Recessed Escutcheon with scribed herein must be installed and , '
1/4 inch (6,4 mm) of recessed adjust- maintained in compliance with this
ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica-
total adjustment from the flush pen- ble standards of the National Fire Pro -
dent position. The adjustment pro- tection Association, in addition to the
vided by the Recessed Escutcheon re- standards of any other authorities hav- Model/Sprinkler
duces the accuracy to which the fixed ing jurisdiction. Failure to do so may
pipe drops to the sprinklers must be impair the performance of these de- Identification
cut. vices.
Corrosion resistant coatings, where The owner is responsible for maintain- Numbers
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2 "NPT
that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2 "NPT
manufacturer should be contacted TY2131 - Upright 4.2K, 1/2 "NPT
IMPORTANT with any questions. Pendent
TY3131 - Upright 5.6K, 1/2 "NPT
Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2 "NPT
Sheet TFP700 for the "INSTALLER TY4131 - Upright 8.0K, 3/4 "NPT
WARNING" that provides cautions TY4231 - Pendent 8.0K, 3/4 "NPT
with respect to handling and instal- TY4831- Upright 8.0K, 1/2 "NPT
lation of sprinkler systems and com- TY4931- Pendent 8.0K, 1/2 "NPT
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
• nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 AUGUST, 2007 TFP171