Plans y' Oregon eati bt Air Conditioning Dr Thanik Permit # MEC2011 -00561 Additional Scope of Work- Fireplace Oregon Heating and Air Conditioning will perform the following scope of work: 1. Provide direct vent 5/8 piping thru roof for exhaust. 2. New gas line from meter. Equipment Schedule • Fireplace - Montigo 38,000 Btu • Gas • Per OMSC Tabel C402.4(2) Standard pressure @ 0.5 Psi pressure drop Load — Fireplace @ 38,000 Btu 250' developed length 3 /+" pipe adequate for 63,000 Btu k ctai City of Tigard Ap roved Plans Y B Date - Wee_ z - REVISION OFFICE COPY Page 1 of 1 • Oregon Heating & A/C, Inc. • Oregon_Pleating: l ` ,. : , a Ai. co�PGonuig . _ PHONE NUMBERS MAILING ADDRESS OPERATIONS CONTRACTOR LICENSE :i_.L . • : -_. O— 503 -691 -9699 • PO Box 241 19300 SW 118 Ave Oregon CCB 172126 1 800- Furnace �� 503 -691 -8556 (Fax) Dundee, OR 97115 Tualatin, OR 97062 Washington OREGOHC900BN " • ® • , ..Pm www.oregonheating.com , ..- /:- rr 4 i k- _ ` � I I In - II. r 1 I ' ^I L J . S ` Allii'7 I �•r� =i� �•i�:�� a/ ...ft •_/0"'HIL. ill I _ -- s CAS -t 00 i >‘ .1 i / / 'jA . 1 III I, '� ; _ .Irr.: 411)14 1 _ . 0 0 . iripm,„ror,.,‘,, .- Yf •^- r'- \ . -- : lIAf ' ., .:.,r .. ,.., •• Q .., ... I I • r. , ... �ry sriiraiiryii,.•iys r ^ ..., ,i„.....,, I WV 4 .0...,, Ds.. ihH` L in I 0 I,.0 '•' ., / t : [ • • il 15 L- D'".....i.-/ ....: , .. .....•,.., 030 lei. I ® i �i � or .... -1 :tier- r, / % t I:1i Q I % ® M I 1 i:5li asa�v�ISii ri% ' 1 i' . :i, I CD r� t., 3ti� ®'i� ; • I I ` rt := EY1C;:f•; I BJL`I..c _ . JI I , „ / I n��F't�c ® ® Itl ,�; 10.aw 1 .1 ma I ::Ahll:li �i �- .∎NO I � l r - r�w I f CiF7Er. LE ® ' ® . 111111 . 1 11 1 , j 1 0111•1111111111 ..ii. \ 5`i: '•.lI.II.IIi'•r7 ' P ill IMMI ■INII NORTH f i f 3 ri ---,„, F PLAN i _ foil .. ,,,, Ili Of TIGO www.montigo.com Installation Operation & Maintenance Manual Check local codes and read all instructions prior to installation. H38DF -PFC H38DF-PFC Series Gas Fireplace HL38DF -PFC TM s:;:.: HLS38DF -PFC AN D ip,f , - f 13 0 Warning: If the infor- ` ` ` .. . - mation in these instructions is not followed exactly, a fire or explosion may result causing property dam - .. i .Y age, personal injury or death. P Warning: WHAT TO DO IF YOU SMELL GAS Improper installation, adjustment, alteration, service or maintenance can cause • Do not try to light any appliance. injury or property damage. Refer to this manual. For assistance or additional • Do not touch any electrical information consult a qualified installer, service agency or the gas supplier. switch; do not use any phone in your building. • Immediately call your gas A Safety Notice: supplier from a neighbor's Glass doors on gas fireplaces are extremely hot while the fireplace is on and remain phone. Follow the gas supplier's hot even after the fireplace has been turned off. Safety screens are available and instructions. can reduce the risks of severe bums. Please keep children away from the fireplace • If you cannot reach your gas at all times. supplier, call the fire department Installation and service must be & For Your Safety: performed by a qualified installer, Do not store or use gasoline or other flammable vapors and liquids in the service agency or the gas supplier. vicinity of this or any other appliance. • Installer: Leave this manual - . „, % I with the appliance. ( :e ) a ) T Consumer. Retain this rraru31 for future reference. C US X80&16 Canadian Heating Products Inc. Langley, BC V4W 4A MYbntigo Del Ray Corp. Ferndale, WA 98248 100210 ° H *38DF PFC* Indoor Gas Fireplace Installation Section 2: Framing 1). Frame in the enclosure for the unit with framing materials. The Top Vent framed opening for the assembled fireplace is 23 3/4" wide, x 44" 1 " i` N Gating level high x 41° deep, see Figure 2. Non- combustible materials. Alcove Min.1 " -+ ---- over fireplace. NOTE: When constructing the framed opening, please ensure there is access to install the gas line when the unit is installed. See Figure 22. Combustible - 7• f Non - Combustible Header — Header Non - Combustible - 25" l / :;_L__----- -- "+ � Materials, with Low i /1104.0.11 s. 1. r ? profile mantel / Alcove over fireplace. See i figure 7. <11 23 cip 395/8° Y ......._______________ __/ . �41 ' • 35pe ling 4 Floor Figure 2. Framing dimensions. Figure 5. Non Combustible Framing with alcove above fireplace, Combustible Header — Right side. Combustible Framing above fireplace, Left side, see --1 12' Min. Combustible Shelf 7 figure 3. (Top Vent). � 1I I_ �t-__ l . - - 4' Naffing flange (supplied) Ly'r _ or use Non-combustible '" material. See figure 7. 44' 331/2' Exterior Wall Figure 2. Combustible Framing for shelves over the fireplace, Rear vent. Combustible Header Combustible Shea 77 2' Min. -- •-I -------------- C- Q t;I' Ii i - alil -- - - i1,12' I ' Min. PEL Short ' 4' Nailing flange (supplied) 90 elbow or use Non-combustible material, See figure 7. 46' Min 44° I Ex Waller Figure 3. Combustible Framing for shelves over the fireplace, Top vent. Page 6 Fart Na XG0816.100210 I H *38DF-PFC* Indoor Gas Fireplace ® Installation Section 3 -2: INSTALLING A ROOF MOUNTED DIRECT VENT - -- — • TERMINATION (PVTK -1) PVTK1 Termination -----_— T This section applies to installations where the direct vent termi- ' ; 2 min. Storm collar nation will be roof mounted. Roof flashing t _ — Section 3 -2 -1: VENTING LAYOUT . Support ring Selection of components and details of venting lay out should 32' I max. ' Support plate adhere to the following guidelines: Obstacle I A • The maximum termination point is 32' above the fireplace (NOTE: _� n if the maximum termination height is used, the flame pattern may be affected). ' lam_ Firestop • The Vertical termination must be a minimum 2' higher than where i. the termination exits the roofing materials, (asphault shingles, _ ' cedar shakes, etc). This distance should be measured from the t�� 7_ > ; high side of the roof slope where the flue flashing intersects the ' roofing materials. (see Figures 11 to 11c '). • Termination location must be a minimum 6' from a mechanical r air inlet. • Termination location must be a minimum 18" from a parapet wall. Figure 11a. Top vent, Roof mounted with 1 offset (1 offset = two 90° • A maximum of two offsets (each offset is made up of 2 -90° bends). bends) may be made. • Install a firestop at any location where venting passes through - PVTK1 ;;; " ""' combustible materials and construction. Termination T • Utilize support straps, or support plates, and rings (as required) Storm collar 1 2'min. to meet acceptable building practices. Roof flashing • Install all roof flashing and storm collars as shown. Support straps or ,a� suppo plate & ring Roof mounted Terminations A The following details are some possible configurations for Roof -_ ii r mounted terminations. See below. Firestop PVTK1 =; Termination T 32' max % %% Storm collar 2'min. �����7�/ Support plate Roof flashing # ®,� & r ing _ Support ring T 11 � � 0 32' max. Support plate _ll-- Obstacle Firestop 1■ I I I NI i Firesto l iii, ' , \ p F . _, F ttt. Figure 11. Top vent, Roof mounted termination with no offset in Figure 11b. Top vent; Roof mounted with 2 offsets (1 offset= two 90° vent run. bends). Part Na. XG0818.100210 Page 9 • Oregon Heating & Air Conditioning Dr Thanik Permit # MEC2011 -00561 Additional Scope'of Work- Fireplace Oregon Heating and Air Conditioning will perform the following scope of work: 1. Provide direct vent 5/8 piping thru roof for exhaust. 2. New gas line from meter. Equipment Schedule Fireplace- Montigo 38,000 Btu Gas Per OMSC Tabel C402.4(2) Standard pressure @ 0.5 Psi pressure drop Load — Fireplace @ 38;000 Btu 250' developed length 3/4" pipe adequate for 63,000 Btu Page 1 of 1 Oregon Heating & A/C, Inc. • ,Oregon .Heating PHONE NUMBERS MAILING ADDRESS OPERATIONS CONTRACTOR LICENSE ► - ;.: :: •: 503 - 691 -9699 PO Box 241 19300 SW 118`" Ave Oregon CCB 172126 = 1 -000 Furnace 503 - 691 -8556 (Fax) Dundee, OR 97115 Tualatin, OR 97062 Washington OREGOHC900BN " 0' .•,•, . www.oregonheating.com • • i (L - - - -- -- ' Z _... ._ . _ _. • + 7 r • �•.... a ! rt. I I I I 1 ! 1 /�� ry ��� �! ccI I l� . , �5 ) I *4L$ w�.i- • I. I I • 'I II�Pi / I \ I , Etk LC) tosara;:a ' . s. ____ It& Ilk 'x'�:`T ... •0j :.., • • s -� 64 MEZ=M1 �� �;' I t ID `� I ( iTh I - _ ® 1�iav —srn Eli -- '�� I - - 'e J 7.1. ® I � : . u,.UtHCt. L 1 e � I -s 1 ;�; i ® ISM ill _ , `� ®�. ' , I � $fit ! 11 $ , PAW % � _ ` , t � I i - I • 11111. 0.7 I! I • , •fin \ ®♦ — ' . 0 4 I \ 1_!'J 1 •viii 4 �.• `t -:i• f � .. 47.... i!1:®` . / . $.'r: I . /^�r((�� A� a Bt i1z : L/ ,:.„:,.. Y•r ® I In UII :, a ® \ O a a ® 1• c. ,I 1 A. A� 5- :: I I I. MS lam .1- �� © I II 11111111111131111111111 • NGRTI ( 1 ) FLOOR PLAN JAL' : coil vvI 3 www.montigo.com Installation Operation & Maintenance Manual Check local codes and read all instructions prior to installation. H38DF -PFC H38DF -PFC Series Gas Fireplace HL38DF -PFC HLS38DF -PFC • yw` M �... j . - t . r Q Warning: If the infor- mation in these instructions is not followed exactly, a fire or explosion may result causing property dam- age, personal injury or death. P Warning: WHAT TO DO IF YOU SMELL GAS Improper installation, adjustment, alteration, service ormaintenance can cause • Do not try to light any appliance. injury or property damage. Refer to this manual. For assistance or additional • Do not touch any electrical information consult a qualified installer, service agency or the gas supplier, switch; do not use any phone in your building. • Immediately call your gas A Safety Notice: supplier from a neighbor's Glass doors on gas fireplaces are extremely hot while the fireplace is on and remain phone. Follow the gas supplier's hot even after the fireplace has been turned off. Safety screens are available and instructions. can reduce the risks of severe burns. Please keep children away from the fireplace If you cannot reach your gas at all times. supplier, call the fire department. Installation and service must be For Your Safety: performed by a qualified installer, Do not store or use gasoline or other flammable vapors and liquids in the service agency or the gas supplier. vicinity of this or any other appliance. • Installer: Leave this manual � with the appliance ® I Consumer: Retain this �+ manual for. future reference.0 U S XGO&16 Canadian Heating Products Inc. Langley, BC V4W 4A Montigo Del Ray Corp. Ferndale, WA 98248 100210 • H *38DF PFC* Indoor Gas Fireplace Installation Section 2: Framing 1). Frame in the enclosure for the unit with framing materials. The Top Vent _ _ , framed opening for the assembled fireplace is 23 314" wide, x 44" 1 'Y \ Cieling level high x 41" deep, see Figure 2. Non - Combustible materials. Alcove MM.1 " -4 — -- over fireplace. NOTE: When constructing the framed opening, please ensure there is access to install the gas line when the unit is installed. See Figure 22. Combustible - 7• Non- Combustible • • Headers Header Non- Combustible 1/11111 z25 r � �� ` Materials, with Low S 2° profile mantelI Alcove � over fireplace. See � / T figure 7. 1 \) / 'I ► 11/ 23 3/\ 'I 44' Is.. 39 518" 41 I ' as "ng _l_ 44 Y..- 1___ __________,----- - , Floor Figure 2. Framing dimensions. Figure 5. Non Combustible Framing with alcove above fireplace, Combustible Header Right side. Combustible Framing above fireplace, Lett side, see --I 12' Min. -- Combustible Shelf figure 3. (Top Vent). 111•111111•1•111111111111111111111111M7 - 2, - - -_ I . INN 1 1 ' I 4' Nailing flange (supplied) a ff- i . or use Non-combustible ' ' material. See figure 7. 44' 33112" Exterior Wall Figure 2. Combustible Framing for shelves over the fireplace, Rear vent. Combustible Header Combustible Shelf 7 2' Min. ~I - --- - - -- - - Q 1 ff * III - -.= I 1 ; 1 T PEL Shor 4' Nailing flange (supplied) 90 elbow or use Non-combustible material. See figure 7 46' Min 44' Exterior Wall Figure 3. Combustible Framing for shelves over the fireplace, Top vent. Page 6 Part No. XG0816- 100210 H *38DF PFC* Indoor Gas Fireplace ® Installation Section 3 -2: INSTALLING A ROOF MOUNTED DIRECT VENT TERMINATION (PVTK -1) PVTKI II Termination' T This section applies to installations where the direct vent termi - ' 2' min. Storm collar i nation will be roof mounted. Roof flashing __________ � Section 3 -2 -1: VENTING LAYOUT 0 Support ring Selection of components and details of venting lay out should 32' max. y Support plate adhere to the following guidelines: Obstacle s s The maximum termination point is 32' above the fireplace (NOTE: - -- - n ` if the maximum termination height is used, the flame pattern Firestop may be affected). 1 t , N The Vertical termination must be a minimum 2' higher than where the termination exits the roofing materials, (asphault shingles, x KY cedar shakes, etc). This distance should be measured from the '' ti "` "` high side of the roof slope where the flue flashing intersects the ,` roofing materials. (see Figures 11 to 11c *). i • Termination location must be a minimum 6' from a mechanical 1 air inlet. • Termination location must be a minimum 18" from a parapet wall. Figure 11a. Top vent, Roof mounted with 1 offset (1 offset= two 90° • A maximum of two offsets (each offset is made up of 2 -90° bends). bends) may be made. N Install a firestop at any location where venting passes through PVTK1 combustible materials and construction. limn Termination T ■ Utilize support straps, or support plates, and rings (as required) Storm collar : 2' min. to meet acceptable building practices. Roof flashing N Install all roof flashing and storm collars as shown. Support straps or support plate & ring Roof mounted Terminations The following details are some possible configurations for Roof - — — I I I mounted terminations. See below. Firestop PVTKI = Termination T 32' max o %i ������ Storm collar 2' min. �i : Support plate Roof flashing ®, & I f n9 ._ Support ring 1 it _ ii 11 ii Obstacles T`-„ Firestop 32' max. Support plate 1, I I I In I/ Firestop Firestop 1:41 .�r. nii � :. Figure 11. Top vent, Roof mounted termination with no offset in Figure 11b. Top vent, Roof mounted with 2 offsets (1 offset= two 90° vent run. bends). Part No. xGO818 - 100210 Page 9