Plans[Page Too Large for OCR Processing] FP5 12 - ono I I52E5 5 Svc 72► ,-vL - RECEIVED Vico Fire & Building JAN 0 3 2012 Products CITY OF TIGARD BUILDING DIVISION Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K- factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General tamed when exposed to corrosive at- mospheres. Although corrosion resis- tant coated sprinklers have passed the .' Description standard corrosion tests of the appli - - . ,' ' cable approval agencies, the testing is — �° The Tyco® Series TY -FRB, 2.8, 4.2, not representative of all possible cor- 5.6, and 8.0 K- factor, Upright and Pen- rosive atmospheres. Consequently, it I n i dent Sprinklers described in this data is recommended that the end user be 1 la sheet are quick response - standard consulted with respect to the suitability j coverage, decorative 3 mm glass bulb of these coatings for any given corro- , . • } type spray sprinklers designed for use sive environment. The effects of ambi- ,�„i.—,1i in light or ordinary hazard, commercial ent temperature, concentration of — r;:„ ,, occupancies such as banks, hotels, chemicals, and gas /chemical velocity, shopping malls, etc. should be considered, as a minimum, , The recessed version of the Series along with the corrosive nature of the TY -FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be �..1 plicable, is intended for use in areas exposed. with a finished ceiling. It uses either a An intermediate level versions of the `� two-piece Style 10 (1/2 inch NPT) or `� P Y ( ) Series TY -FRB Pendent Sprinklers " t •` '� Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet r cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de- j recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780 (19,1 mm) of total adjustment from the flush pendent position, or a two -piece WARNINGS y ' �� Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY -FRB Sprinklers de- ' �,., inch NPT) Recessed Escutcheon with scribed herein must be installed and y' 1/4 inch (6,4 mm) of recessed adjust- maintained in compliance with this ' ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica- total adjustment from the flush pen- ble standards of the National Fire Pro - dent position. The adjustment pro- tection Association, in addition to the vided by the Recessed Escutcheon re- standards of any other authorities hay- Model /Sprinkler duces the accuracy to which the fixed ing jurisdiction. Failure to do so may pipe drops to the sprinklers must be impair the performance of these de- Identification cut. vices. Corrosion resistant coatings, where The owner is responsible for maintain- Numbers applicable, are utilized to extend the ing their fire protection system and de- life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2 "NPT that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2 "NPT manufacturer should be contacted TY2131 - Upright 4.2K, 1/2 "NPT IMPORTANT with any questions. TY2231 - Pendent 4.2K, 1/2 "NPT TY3131 - Upright 5.6K, 1/2 "NPT Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2 "NPT Sheet TFP700 for the "INSTALLER TY4131 - Upright 8.0K, 3/4 "NPT WARNING" that provides cautions TY4231 - Pendent 8.0K, 3/4 "NPT with respect to handling and instal- TY4831- Upright 8.0K, 1/2 "NPT lation of sprinkler systems and com- TY4931- Pendent 8.0K, 1/2 "NPT ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 AUGUST, 2007 TFP171 • Page 2 of 10 TFP171 ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING NOMINAL RECESSED 1 SURFACE 1/2" MAKE -IN ESCUTCHEON SSU NPT DEFLECTOR i _ r a 5 6 -� 7/16" '' 2-1/4" f �� (57,2 mm) I � ��A �� t ( 11 mmOMINAL ) 4 p r MAKE -IN 2 1- 9/16" I � 2-3/16" 7 9 3 (39,7 mm) WRENCH 1 (55,6 mm) F ; FLATS _ ' .t 1 i l /r• \\ /mil• �\ 1 7iN SSP DEFLECTOR * — 2 -7/8" (73,0 mm) DIA. — 1 1/2" NPT f 7 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw FIGURE 1 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING NOMINAL RECESSED * SURFACE 1/2" T -IN ESCUTCHEON DEFLECTOR ° a Z 7/16" 5 2 - 3/16" 1 I I MAKE -IN ( 11,1 mm) I (5 5 , 6 mm) =� � 111 NOMINAL I 4 � lilir - 1 -1/2" I � ' 1� �, i 2 3/16" Yp 2 (38,1 mm) WRATSH (55,6 mm) � y p 3 SSP DEFLECTOR * — 2 -7/8" (73,0 mm) DIA. — —1 1/2" NPT I PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw FIGURE 2 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT • • • TFP171 • - Page 3 of 10 ESCUTCH 7/16" (11,1 mm) STYLE 10 or 20 • • PLATE- SEATIN . _-_ NOMINAL — _._RECESSED — _ * __ . _ __- - _-_ - -_ _ - -. _ __ - .— -_- SURFACE 1/2" MAKE -IN ESCUTCHEON EC NPT I DEFLECTOR F --- ----• • • - � � ii 0111 i iri TT1 � �S 2- 3/ ITru 6* 16" ��r 1 m !,' 5 (11,1 mm) (55,6 mm) =� � NOMINAL ; 4 • 71 MAKE-IN 11/2" Id � I/ I � 1 2-3/16" t i AS 2 • (38,1 mm) WRENCH 1 (55,6 mm) g 3 • i _,_.A _. _ ;.A FLATS =� • SSP DEFLECTOR 2 -7/8" (73,0 mm) DIA. - -1 1/2" NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION • • 1 - Frame - 3 - Sealing 4 - Bulb 6 - Deflector * • Temperature rating is indicated �n deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. • -' Screw . • • • F IGURE 3 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT,(TY3231) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT . • • ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40 • PLATE SEATING NOMINAL RECESSED * • 2 -5/16" • SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR °' 5 6 F --- . __--- .•.#, . `� IMES ;lir � (12,7 mm) I ' (58,7 mm) 7 � I NOMINAL ' 4 1 MAKE -IN ' A • ) 7 m m) (39,I I H ��r 1/2 4 V i; 2 2 -1/4 mm 7m C = (57,) � ' i --e -- - • S I 3 SSP DEFLECTOR * • f— 2 -7/8" (73,0 mm) DIA. 3/4" NPT I PENDENT RECESSED PENDENT UPRIGHT . CROSS SECTION 1 - Frame 3 - Sealing 4-Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw FIGURE 4 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT • • ' Page 4 of 10 TFP171 7/16" (11,1 mm) —. -- .-- – 172" NOMINAL— S5U"— - - - -- --- ._ _____ - -._. ._. .. NPT MAKE -IN DEFLECTOR • *6 t 2 -3/16" • 5 2 -1/4" r I (57,2 mm) A =AI I (55,6 mm) I ' 4 1 -9/16" WRENCH 1 — 0 1 `✓ 2 (39,7mm) FLATS 4 SSP 1 DEFLECTOR CROSS . . PENDENT UPRIGHT SECTION 1 - Frame , 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. . Screw • . FIGURE 5 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS . 8.0 K- FACTOR, 1/2 INCH NPT • • Technical Operation Data The glass Bulb contains a fluid which expands when exposed to heat. When Approvals the rated temperature is reached, the - UL and C-OL Listed. fluid expands sufficiently to shatter the FM, LPCB, and NYC Approved. . glass Bulb, allowing the sprinkler to (Refer to Table A and B for complete activate and water to flow. approval information including corm- . - . sion resistant status.) • Design Maximum Working Pressure - Refer to Table C. Criteria Criteria V . Discharge Coefficient . K = 2.8 GPM /psi (40,3 LPM /barl/2) The Series TY -FRB Pendent and Up- K = 4.2 GPM /psi / (60,5 LPM /bar1/2) right Sprinklers are intended for fire K = 5.6 GPM /psi / (80,6 LPM /bar1/2) protection systems designed in ac- K = 8.0 GPM /psi / (115,2 LPM /bar1/2) cordance with the standard installation rules recognized by the applicable Temperature Ratings Listing or Approval agency (e.g., UL Refer to Table A and B Listing is based on the requirements of . • Finishes NFPA 13, and FM Approval is based Sprinkler: Refer to Table A and B. on the requirements of FM's Loss Pre - Recessed Escutcheon: White Coated, vention Data Sheets ). Only the Style Chrome Plated, or Brass Plated. 10, 20, 30, or 40 Recessed Escutch- eon, as applicable, is to be used for recessed pendent installations. Y . Physical Characteristics • Frame Bronze E Button Brass /Copper Sealing Assembly `- Beryllium Nickel w/Teflont 0 Bulb Glass • Compression Screw Bronze N D Ea eflector Copper /Bronze cc Bushing (K =2.8) Bronze 0 0 m r7 } • • • TFP171 Page 5 of 10 • • • • . . SPRINKLER FINISH (See Not 7) • K • - "TYPE —' — TEMP — — BULB — - NATURAL — — CHROME — WHITE*'* — — — -- -- - -- -- • LIQUID BRASS PLATED POLYESTER • 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red • (TY1231• ) and ) 175 °F /79 °C Yellow- 1, 2, 3, 5 •UPRIGHT 200 °F /93 °C Green 2.8 (TY1131) 286 °F /141 °C Blue 1/2" NPT 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT ( * 175 °F /79 °C Yellow • • Figure 6 200 °F /93 °C Green 1, 2, 5 • '135 °F /57 °C Orange • RECESSED 155 °F /68 °C Red PENDENT. (TY1231) ** 175 °F /79 °C Yellow • Figure T 200 °F /93 °C Green • • 135 °F /57 °C Orange '' • • PENDENT 155 °F /68 °C ,Red • ( • TY2231) and 175 °F /79 °C Yellow • UPRIGHT 200 °F /93 °C Green ' 4.2 (TY2131) 1/2" 286 "F /141 °C Blue 1, 2 NPT 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red • PENDENT (TYYY31) *• 175 °F /79 °C Yellow • Figure 8 200 °F /93 °C Green • 135 °F /57 °C Orange • RECESSED 155 °F /68 °C • Red • PENDENT • • (TY2231)** 175"F/79°C .Yellow • Figure 9 200 °F /93 °C Green • NOTES: • 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. . 2. Listed by. Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Re- sponse Sprinklers. . 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin- klers. 5. Approved by the City of New York under MEA 354 -01 -E. 7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- klers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. ** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. • *** Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE A LABORATORY LISTINGS AND APPROVALS 2.8 AND 4.2 K- FACTOR SPRINKLERS • • • • • • • . Page 6 of .10 TFP171 SPRINKLER FINISH (See Note 8) • K - - TYPE — — TEMP' — — BULB` - NATURAL — CHROME — WHITE'"' LEAD -- - —" • LIQUID BRASS PLATED POLYESTER COATED 135"F/57°C Orange PENDENT 155"F/68°C Red (TY3231) 1,2,3,4,5,6,7 1,2,3,5 and 175 °F /79 °C Yellow • • UPRIGHT 200"F/93°C Green 5.6 (TY3131) 286 °F /141 °C Blue 1/2" NPT 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 4, 5 N/A (TY3231)" 175 °F /79 °C Yellow • • Figure 10 200 °F /93 °C Green . • 135 °F /57 °C Orange - RECESSED 155"F/68°C Red PENDENT 1, 2, 3, 4, 5 N/A • (TY3231)" 175 °F /79 °C Yellow • • • Figure 11 200 °F /93 °C Green 135 °F /57 °C Orange PENDENT • 155 °F /68 °C Red (TY4231) and 175 °F /79 °C Yellow 1, 2, 5 • 1,2,3,4,5,6,7 UPRIGHT 200 °F /93 °C Green . 8.0 (TY4131) 286"F/141°C Blue 3/4" NPT 135"F/57°C Green RECESSED 155 °F /68 °C Orange PENDENT 1, 2, 4, 5 N/A (TY4231)" 175 °F /79 °C Red Figure 12 200 °F /93 °C Yellow 135"F/57°C Orange RECESSED 155 °F /68 °C Red • PENDE 1, 2, 3, 4, 5 N/A (TY4231)" 175 °F /79 °C Yellow • Figure 13 200 °F /93 °C Green 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red 8.0 (TY4931) 1, 2, 5 1/2" and 175 °F /79 °C Yellow 1, 2, 4, 5, 6 • NPT UPRIGHT 200 °F /93 °C Green (TY4831) 286 °F /141 °C Blue NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the . LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31- 53- 428- 4444/Fax 31 -53- 428 - 3377). 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved,,the sprinklers are FM Approved as a Corrosion Resistant Sprinklers. • Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. '• Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. '•• Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS 5.6 AND 8.0 K- FACTOR SPRINKLERS TFP171 Page 7 of 10 SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD BRASS PLATED POLYESTER COATED PENDENT (TY3231) and • 2 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A 1/2 RECESSED PENDENT NPT (TY323) PENDENT (TY4231) and 4 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A 3/4" RECESSED PENDENT NPT (TY4231) PENDENT (TY3231) and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR) 5.6 UPRIGHT (TY3131) OR 1/2" RECESSED PENDENT 175 PSI (12,1 BAR) NPT ) (TY3231 (SEE NOTE 1) N/A PENDENT (TY4231) and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR) 8 UPRIGHT (TY4131) 3/4" RECESSED PENDENT NPT (TY4231) N/A 8.0 PENDENT (TY4931) 1/2" and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR) NPT UPRIGHT (TY4831) NOTES: 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C -UL); and , the Approval by the City of New York. TABLE C, MAXIMUM WORKING PRESSURE tained with a torque of 10 to 20 ft.lbs. the sprinkler into the sprinkler fitting. Installation (13,4 to 26,8 Nm). A maximum of 30 Step 3. Tighten the sprinkler into the ft.lbs. (40,7 Nm) of torque is to be used sprinkler fitting using only W -T e The Series TY -FRB Sprinklers must to install sprinklers with 3/4 NPT con- p g g y yp be installed in accordance with the fol- nections. Higher levels of torque may 6 Sprinkler Wrench (Ref. Figure 14). With reference to Figures 1, 2, 3, 4, lowing instructions: distort the sprinkler inlet and cause leakage or impairment of the sprinkler. and 5, the W-Type 6 Sprinkler Wrench NOTES is to be applied to the sprinkler wrench Do not install any bulb type sprinkler if Do not attempt to make -up for insuffi- flats. the bulb is cracked or there is a loss of cient adjustment in the escutcheon The Series TY -FRB Recessed Pen - liquid from the bulb. With the sprinkler plate by under- or over - tightening the dent Sprinklers must be installed in held horizontally, a small air bubble sprinkler. Readjust the position of the accordance with the following instruc- should be present. The diameter of the sprinkler fitting to suit. tions. air bubble is approximately 1/16 inch The Series TY -FRB Pendent and Up- Step A. After installing the Style 10. (1,6 mm) for the 135 °F /57 °C to 3/32 right Sprinklers must be installed in 20, 30, or40 Mounting Plate, as appli- inch (2,4 mm) for the 286 °F /141 °C accordance with the following instruc- cable, over the sprinkler threads and temperature ratings. tions. with pipe thread sealant applied to the A leak tight 1/2 inch NPT sprinkler joint Step 1. Pendent sprinklers are to be pipe threads, hand tighten the sprin- should be obtained with a torque of 7 installed in the pendent position, and kler into the sprinkler fitting. to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- upright sprinklers are to be installed in Step B. Tighten the sprinkler into the mum of 21 ft. lbs. (28,5 Nm) of torque the upright position. sprinkler fitting using only the W -Type • may be used to install sprinklers with Step 2. W ith pipe thread sealant a 7 Recessed Sprinkler Wrench (Ref. 1/2 NPT connections. A leak tight 3/4 p p p p Figure 15). With reference to Figure 1, inch NPT sprinkler joint should be ob- plied to the pipe threads, hand tighten 2, 3, and 4, the W -Type 7 Recessed Page 8 of 10 TFP171 2 -7/8" DIA. _ 2 -7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) (73,0 mm) _ 1/2±1/8" 1/2" (12,7 mm) . (15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. J 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" (3,2 mm) •� (3,2 mm) X1111 • MM.!! �i�° rol -- �� f \ f MOUNTIN IN �r MOUNTING . f SURFACE � . SURFACE , , A--,27-12-11s.... r CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1 -5/16" (33,3 mm) TY -FRB 13/16" (20,6 mm) TY -FRB 1- 1/16" (27,0 mm) FIGURE 6 FIGURE 7 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT 2 -7/8° DIA. 2 -7/8° DIA. 5/8±1/4" • (73,0 mm) 3/4" (19,1 mm) 1/2±1/8" (73,0 mm) 1/2" (12,7 mm) (15,9±6,4 mm) 2 -1/4° DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE ' FITTING FITTING 1/8" 1/8" M�1,811, �Malta iii I mm) I A I f I,,, MOUNTING SURFACE IP MOUNTING . f • SURFACE - - -- .- .. CLOSURE SERIES 1 -1/4" (31 mm) CLOSURE SERIES 1 -1/4" (31,8 mm) TY -FRB 3/4" (19,1 mm) TY -FRB 1" (25,4 mm) FIGURE 8 FIGURE 9 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT Sprinkler Wrench is to be applied to work on the fire protection system that altered after leaving the factory. Modi- the sprinkler wrench flats. it controls, permission to shut down the fied sprinklers must be replaced. Step C. After the affected fire protection system must be Sprinklers that have been exposed to S the ceiling has been in S alted the finish coat has been n- obtained from the proper authorities corrosive products of combustion, but plied, slide on the Style 10, 20, 30, or and all personnel who may be affected have not operated, should be replaced 40 Closure over the Series TY-FRB by this action must be notified. if they cannot be completely cleaned Sprinkler and push the Closure over The owner must assure that the sprin- by wiping the sprinkler with a cloth or the Mounting Plate until its flange klers are not used for hanging of any by brushing it with a soft bristle brush. comes in contact with the ceiling. objects; otherwise, non - operation in Care must be exercised to avoid dam - the event of a fire or inadvertent opera- age to the sprinklers - before, during, C are and tion may result. and after installation. Sprinklers dam - Absence of an escutcheon, which is aged by dropping, striking, wrench Maintenance used to cover a clearance hole, may twist/slippage, or the like, must be re delay the time to sprinkler operation in placed. Also, replace any sprinkler a fire situation. that has a cracked bulb or that has lost The Series TY-FRB Sprinklers must liquid from its bulb. (Ref. Installation be maintained and serviced in accord- Sprinklers that are found to be leaking Section). ance with the following instructions: or exhibiting visible signs of corrosion must be replaced. Frequent visual inspections are rec • NOTES ommended to be initially performed for Before closing a fire protection system Automatic sprinklers must never be corrosion resistant coated sprinklers, main control valve for maintenance painted, plated, coated or otherwise after the installation has been corn- • TFP171 Page 9 of 10 2 -7/8" DIA. 2 -7/8" DIA. - 5/8±1/4" (73,0 mm) 3/4" (19.1 mm) 1/2 ±1/8" (73,0 mm) 1/2" (12,7 mm) • (15,9±6,4 mm) 1/4" (6,4 mm) (12,7 ±3,2 mm) 2-1/4° DIA. J 2-1/4" DIA. J 1/4 "(6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) I MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" I 1/8" •� (3 mm) (3,2 mm) x �,�l�ll, ��. ■ A MIIMI'Ml J il t I f \ -- I MOUNTING I MOUNTING `�� SURFACE SURFACE ,•- --- , CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm) TY -FRB 3/4" (19,1 mm) TY -FRB 1" (25,4 mm) FIGURE 10 FIGURE 11 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT 2 -7/8° DIA. 2 -7/8" DIA. 5/8±1/4" ( mm) 3/4" (19,1 mm) 1/2±1/8" (73.0 mm) 1/2" (12,7 mm) (15,9±6,4 mm) 2 -1/4' DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2 -1/4" DIA. 1/4' (6,4 mm) (57,2 mm) FACE OF MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" " III (3,2 mm) (3,2 mm) ERW ■ ,J. 1 MOUNTING �Ij MOUNTING ■ SURFACE SURFACE i NI CLOSURE SERIES 1 -5/16' (33,3 mm) CLOSURE SERIES 1 -5/16" (33,3 mm) TY -FRB 13/16" (20,6 mm) TY -FRB 1.1/16" (27,0 mm) - FIGURE 12 FIGURE 13 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT pleted, to verify the integrity of the cor- WRENCH rosion resistant coating. Thereafter, RECESS annual inspections per NFPA 25 should suffice; however, instead of in / "' WRENCH RECESS �� specting from the floor level, a random (END "A" USED FOR sampling of close -up visual inspec- 1/2" NPT MODELS) ±ions should be made, so as to better ....0 determine the exact sprinkler condi- tion and the long term integrity of the .........• corrosion resistant coating, as it may WRENCH RECESS PUSH WRENCH be affected by the corrosive conditions (END "B" USED FOR IN PUS ENSURE present. 3/4" NPT MODELS ENGAGEMENT The owner is responsible for the in- FI GURE 14 WITH SPRINKLER WRENCHING AREA spection, testing, and maintenance of W -TYPE 6 SPRINKLER their fire protection system and de- WRENCH FIGURE 15 • vices in compliance with this docu- W -TYPE 7 RECESSED ment, as well as with the applicable SPRINKLER WRENCH facturer should be contacted relative standards of the National Fire Protec- to any questions. tion Association (e.g., NFPA 25), in Inspection Service in accordance with addition to the standards of any other It is recommended that automatic local requirements and /or national authorities having jurisdiction. The in- sprinkler systems be inspected, codes. stalling contractor or sprinkler manu- tested, and maintained by a qualified ' • Page 10 of 10 TFP171 - - I TEMPERATURE MODEL/SIN RATING SPRINKLER 330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135F/57°C 331 2.8K PENDENT(1 /2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C 340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C 341 4.2K PENDENT (1/2 "NPT) TY2231 3 WHITE (RAL9010)' 200 200 °F /93 °C 370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C 371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED 390 8.0K UPRIGHT (3/4 "NPT)• TY4131 391 • 8.0K PENDENT (3/4 "NPT) TY4231 * Eastern Hemisphere sales only. 360 8.0K UPRIGHT (1/2 "NPT) . TY4831' • 361 8.0K PENDENT (1/2 "NPT) TY4931" TABLE D • PART NUMBER SELECTION SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS In no event shall TFBP be liable, in Limited contract, tort, strict liability or under Ordering Warranty any other legal theory, for incidental, indirect, special or consequential dam- P rocedure • ages, including but not limited to labor Products manufactured by Tyco Fire & charges, regardless of whether TFBP When placing an order, indicate the . • Building Products (TFBP) are war- was informed about the possibility of full product name. Refer to the Price ranted solely to the original Buyer for such damages, and in no event shall • List for complete listing of Part Num- . ten (10) years against defects in mate- TFBP's liability exceed an amount bers. rial and workmanship when paid for equal to the sales price. Contact your local distributor for"avail- and properly installed and maintained The foregoing warranty is made in lieu ability. under normal use and service. This warranty will expire ten (10)' years of any and all other warranties. ex- from date of shipment by TFBP. No press or implied. including warranties Sprinkler Assemblies with NPT warranty is given for products or corn- of merchantability and fitness for a par- Thread Connections: ponents manufactured. by companies ticular purpose. Specify: (Specify Model /SIN), Quick not affiliated by ownership with TFBP This limited warranty sets forth the ex- Response, (specify K- factor), (specify or for products and components which clusive remedy for claims based on (sm e rating), Series or Upright) Sprinkler FRB (speccify ify Pendent have been subject to misuse, improper failure of or defect in products, materi- with (specify type of finish or coating), installation, corrosion, or which have als or components, whether the claim P/N (specify from Table D). not been installed, maintained, modi- is made in contract, tort, strict liability fled or repaired in accordance with ap- or any other legal theory. Recessed Escutcheon: plicable Standards of the National Fire This warranty will apply to the full ex- Specify: Style Re- Protection Association, and /or the P fY tY ( 10, 20 standards of any other Authorities tent permitted by law. The invalidity, in cessed Escutcheon with 30, or 40 ) th (specify *) fin - Having Jurisdiction. Materials found whole or part, of any portion of this ish, P/N (specify *). by TFBP to be defective shall be either warranty will not affect the remainder. repaired or replaced, at TFBP's sole Refer to Technical Data Sheet TFP770. option. TFBP neither assumes, nor Sprinkler Wrench: authorizes any person to assume for it, Specify: W -Type 6 Sprinkler Wrench, any other obligation in connection with P/N 56-000-6-387. the sale of products or parts of prod- ucts. TFBP shall not be responsible for Specify: W -Type 7 Sprinkler Wrench, sprinkler system design errors or inac- P/N 56- 850 -4 -001. curate or incomplete information sup- plied by Buyer or Buyer's repre- sentatives. TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446