Plans[Page Too Large for OCR Processing] [Page Too Large for OCR Processing] • SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 DATE: 11/9/2010 C: \HASS74 \PITNBRKSADDN.SDF • JOB TITLE: Pittman and Brooks Addition WATER SUPPLY DATA ,^ S NODE E PRESS. PRESD. @ FLOW PRESS. @ DEMAND PRESS. EDI D 1 TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) ( . Np\1 3 0 2010 22 104.0 102.0 1680.0 103.9 297.5 94.5 C O F .�GARD ILDING DIVISION AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 297.5 GPM - t°52.() - t°52.() 1O BU - Q®( l Co OT HOSE STREAM ALLOWANCES TOTAL HER AT SOURCE 100.0 GPM GPM 15265 TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 197.5 GPM NODE ANALYSIS DATA - NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 19.5 K= 5.60 7.0 14.8 2 19.5 K= 5.60 7.8 15.6 3 19.0 - - - - 8.6 - - - 4 19.5 K= 5.60 7.4 15.2 5 19.5 K= 5.60 8.2 16.1 6 19.0 - - - - 9.1 - - - 7 19.5 K= 5.60 9.0 16.8 8 19.5 K= 5.60 9.9 17.6 'r 9 19.0 - - - - 10.9 - - - ( 10 19.5 K= 5.60 8.8 16.6 11 19.5 K= 5.60 8.7 16.5 11A 19.0 - - - - 10.1 - - - 12 19.5 K= 5.60 10.1 17.8 12A 19.0 - - - - 10.9 - - 13 19.5 K= 5.60 9.5 17.3 13A 19.0 - - - - 10.9 - - - 14 19.5 K= 5.60 9.0 16.8 15 19.5 K= 5.60 8.5 16.4 15A 19.0 - - - - 9.9 - - - 16 19.0 - - - - 12.6 - - - 17 19.0 - - - - 18.0 - - - 18 9.8 - - - - 54.8 - - - 19 4.0 - - - - 86.5 - - - 20 1.0 - - - - 88.3 - - - ' 21 1.0 - - - - 93.3 - - - 22 0.0 SOURCE 94.5 197.5 ,�� Rti0 PROFF _ �GINE S', - 2 • - 13, 8 - -- • -, T. w , • ,- - • - - �i •R ON O �L6 G P r- E 4 . 16, 1 4Q �� J. GE �� EXPIRES: 0 • VIM r. ' SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 11/9/2010 C: \HASS74 \PITNBRKSADDN.SDF ..JOB TITLE: Pittman and Brooks Addition PIPE. DATA ,,., RIPE .TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. , I NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) 1` Pipe: 1 -14.8 1.104 PL 13.25 PF 0.8 1 19.5 5.6 7.0 14.8 5.0 120 FTG - - -- PE 0.0 2 19.5 5.6 7.8 15.6 0.058 TL 13.25 PV Pipe: 2 -30.4 1.452 PL 3.00 PF 0.6 2 19.5 5.6 7.8 15.6 5.9 120 FTG- T PE 0.2 3 19.0 0.0 8.6 0.0 0.058 TL 11.00 PV Pipe: 3 -15.2 1.104 PL 13.25 PF 0.8 4 19.5 5.6 7.4 15.2 5.1 120 FTG, - - -- PE 0.0 5 19.5 5.6 8.2 16.1 0.061 TL 13.25 PV Pipe: 4 -31.3 1.452 PL 3.00 PF 0.7 • 5 19.5 ' 5.6. 8.2 16.1 6.1 120 FTG T PE 0.2 6 19.0 '0.0 9.1 0.0 ' 0.061 TL 11:00 PV Pipe: 5 -16.8 1.104 PL 13.25 PF 1.0 7 19.5 5.6 9.0 16:8 5.6 120 FTG - - -- PE 0.0 8 19.5 5.6 9.9 17.6 ' 0.073 TL 13.25 PV Pipe: 6 -34.4 1.452 PL 3.00 PF 0.8 8 19.5 5.6 9.9 17.6 6.7 120 FTG T PE 0.2 9 19.0 0.0 10.9 0.0 0.073 TL 11.00 PV Pipe: 7 • -16.6 1.104 PL 8.33 PF 1.1 10 19.5 5.6 8.8 16.6 5.6 120 FTG T PE 0.2 11A 19.0 0.0 10.1 0.0 0.072.TL 15.33 PV Pipe: 8 -16.5- 1.104 PL 8.75 PF 1.1 11 19.5 5.6 8.7 16.5 5.5 • 120 FTG T , PE 0.2 11A 19.0 0.0 10.1 0.0 • 0.07`1 TL 15.75 PV Pipe: 9 -17.8 1.104'PL 0.75 PF '0.6 12 19.5 5.6 10.1 17.8 6.0 120 FTG T PE 0.2 12A 19.0 0.0 10.9 0.0 0.082 TL 7.75 PV Pipe: 10 -33.1 1.452 PL 4.50 PF 0.8 11A 19.0 0.0 10.1 0.0 6.4 120 FTG T PE 0.0 12A 19.0 0.0 10.9 0.0 0.068 TL 12.50 PV Pipe: 11 -50.9 1.452 PL 3.42 PF 1.7 1'2A 19:0 0.0 10.9 0.0 9.9 120 FTG T PE 0.0 16 19.0 0.0 12.6 0.0 0.150 TL 11.42 PV ' Pipe: 12 -17.3 1.104 PL 8.75 PF 1.2 13 19.5 5.6 9.5 17.3 5.8 120 FTG T PE 0.2 13A 19.0 0.0 10.9 0.0 0.077 TL 15.75 PV Pipe: 13 -16.8 1.104 PL 1.50 PF 0.6 14 . _19.5 5.6 9.0 16.8 5.6 120 FTG • T PE 0.2 ' 15A 19.0 ' 0.0 9.9 . 0.0 0.074 TL 8.50 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 11/9/2010 C: \HASS74 \PITNBRKSADDN.SDF JOB TITLE: Pittman and Brooks Addition .PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. . END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. ,_. NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) Pipe: 14 -16.4 1.104 PL 9.00 PF 1.1 15 19.5 5.6 8.5 16.4 5.5 120 FTG T PE 0.2 15A 19.0 0.0 9.9 0.0 0.070 TL 16.00 PV • Pipe: 15 -33.2 1.452 PL 7.75 PF 1.1 15A 19.0 0.0 9.9 0.0 6.4 120 FTG T PE 0.0 13A 19.0 0.0 10.9 0.0 0.068 TL 15.75 PV Pipe: 16 -50.5 1.452 PL 3.42 PF 1.7 13A 19.0 0.0 10.9 0.0 9.8 120 FTG T PE 0.0 16 19.0 0.0 12.6 0.0 0.148 TL 11.42 PV Pipe: 17 -101.4 1.452 PL 2.00 PF 5.4 16 19.0 0.0 12.6 0.0 19.6 120 FTG T PE 0.0 17 19.0 0.0 18.0 0.0 0.538 TL 10.00 PV Pipe: 18 -30.4 1.452 PL 8.50 PF 0.5 3 19.0 0.0 8.6 0.0 5.9 120 FTG - - -- PE 0.0 6 19.0 0.0 9.1 0.0 0.058 TL 8.50 PV Pipe: 19 -61.7 1.452 PL 8.50 PF 1.8 6 19.0 0.0 9.1 0.0 12.0 120 FTG - - -- PE 0.0 9 19.0 0.0 10.9 0.0 0.215 TL 8.50 PV Pipe: 20 -96.1 1.452 PL 6.50 PF 7.1 9 19.0 0.0 10.9 0.0 18.6 120 FTG T PE 0.0 17 19.0 0.0 18.0 0.0 0.488 TL 14.50 PV Pipe: 21 -197.5 1.452 PL 9.75 PF 32.8 17 19.0 0.0 18.0 0.0 38.3 120 FTG T PE 4.0 18 9.8 0.0 54.8 0.0 1.848 TL 17.75 PV Pipe: 22 197:5 2.154'PL 75.75 PF 29.2 18 9.8 0.0 54.8 0.0 17.4 120 FTG 2ETB PE 2.5 19 4.0 0.0 86.5 0.0 0.271 TL. 107:75 PV Pipe: 23 -197.5 4.000 PL 38.00 PF 0.5 19 4.0 0.0 86.5 0.0 5.0 140 FTG E PE 1.3 20 1.0 0.0 88.3 0.0 0.010 TL 50.89 PV Pipe: 24 FIXED PRESSURE LOSS DEVICE 21 1.0 0.0 93.3 0.0 5.0 psi, 197.5 gpm 20 1.0 0.0 88.3 0.0 Pipe: 25 -197.5 4.000 PL 53.00 PF 0.8 21 1.0 0.0 93.3 0.0 5.0 140 FTG TG PE 0.4 22 0.0 SRCE 94.5 (N /A) 0.010 TL 81.35 PV • • SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 11/9/2010 C: \HASS74 \PITNBRKSADDN.SDF JOB TITLE: Pittman and Brooks Addition NOTES: (1) Calculations were performed by the HASS 7.4 computer program .under license no. 5010113212 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average • imbalance at each node of 0.003 gpm and a maximum imbalance at any node of 0.077 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 38.3 ft /sec at pipe 21. (4) PIPE FITTINGS TABLE Pipe Table Name: STANDARD.PIP PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v NPTee 4.026 10.00 20.00 6.00 22.00 12.00 2.00 20.00 20.00 20.00 PAGE: C MATERIAL: XL HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v NPTee 1.104 3.00 7.00 3.00 7.00 8.00 1.00 13.00 13.00 7.00 1.452 4.00 8.00 3.00 9.00 8.00 1.00 13.00 13.00 8.00 2.154 6.00 12.00 4.00 14.00 8.00 1.00 12.00 12.00 12.00 • • • • • o> . b7 H WATER SUPPLY ANALYSIS y 120.0 Static: 104.00 psi Resid: 102.00 psi Flow: 1680.0 gpm y r 1- • LEGEND hi N. N•0 • rt N 1j' 1 Available pressure ° • • 100.0 _ 103.92 psi @ 297.5 gpm • 2 Required pressure a G 2 94.54, psi @ 297.5 gpm o. ro A - 7d • U h z G o r E 80.0 __ ( z > m P a u) - R N y E r 3 S o x S 60.0 d __ U . . • R • r E • n n '�z ( 40.0 _ �> p E • s V] H • i J 4.. ) / ro 20.0 __ y z w x . U . d CJ hi Z Cu —, • `° 0.0 �o 0 cn -14.7 I I I I I I I I 400 600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM) Water Availability Curve • 110 100 - -- - 90 --- 80- 70— a F2 60 r N N a ` 50— 40 — 30 20 , 10- 1500 3000 4500 6000 7500 9000 10500 12000 13500 1500( Flow (GPM) ® Static = 104 psi. ® System demand = 20.00 psi with 12515.0 gpm flowing • • Residual = 102 psi at a flow of 1660 gpm. Pressure available = 20.04 psi when 12515.0 gpm is flow Demand is below curve by 0.40 psi (0.20 %). • tqco Fire Suppression & Buildin g Products Technical Services 800 - 381 -9312 I +1- 401 - 781 -8220 www.tyco- fire.com Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K- Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage G eneral Corrosion - resistant coatings, where _ _ applicable, are utilized to extend the - _ ' �-' °��'t - -- Description life of copper alloy sprinklers beyond _ that which would otherwise be obtained f , \\)1 The TYCO Series TY -FRB, 2.8, 4.2, 5.6, when exposed to corrosive atmo- , � :l �" ( ill 1 spheres. Although and 8.0 K- factor, Upright and Pendent g h 1 ', I; j' ;I ' Sprinklers described in this data sheet coated sprinklers have passed the ;, i[. • 1 I �JI�: are quick response, standard coverage, standard corrosion tests of the appli- Ii ` ! (� decorative 3 mm glass bulb -type spray cable approval agencies, the testing is �,1' y - .a, sprinklers designed for use in light or not representative of all possible cor - "d:, a, uent atmospheres. Consequently, ' r ordinary hazard, commercial occupan- rosive it is recommeded that the end user ' cies such as banks, hotels, and shop- ping malls. be consulted with respect to the suit- ability of these coatings for any given The recessed version of the Series TY- corrosive environment. The effects of FRB Pendent Sprinkler, where applica- ambient temperature, concentration of a ble, is intended for use in areas with a chemicals, and gas /chemical velocity, finished ceiling. This recessed pendent should be considered, as a minimum, view sprinkler uses one of the following, along with the corrosive nature of the • • A two-piece Style � iece St le 10 (1/2 inch NP chemical to which the sprinklers will be a �-� or Style 40 (3/4 inch NPT) Recessed exposed. _ , , Escutcheon with 1/2 inch (12,7 mm) of An intermediate level of the Series TY- i recessed adjustment or up to 3/4 inch FRB Pendent Sprinklers is detailed - --= '�� - (19,1 mm) of total adjustment from the in Technical Data Sheet TFP356, and '� ... • flush pendent position, or a Sprinkler Guards are detailed in Tech- ' _ '�' • • A two -piece Style 20 (1/2 inch NPT) nical Data Sheet TFP780. or Style 30 (3/4 inch NPT) Recessed Escutcheon with up (6,4 mm) of NOTICE re Model /Sprinkler recessed ssed adjustment or up to o 1/2 inch The Series TY-FRB Concealed Pendent (12,7 mm) of total adjustment from the Sprinklers described herein must be flush pendent position. installed and maintained in compliance Identification The adjustment provided by the with this document and with the appli- Number (SIN) Recessed Escutcheon reduces the cable standards of the National Fire accuracy to which the fixed pipe drops Protection Association, in addition to to the sprinklers must be cut. the standards of any authorities having TY1131: Upright 2.8K, 1/2" NPT jurisdiction. Failure to do so may impair TY1231: Pendent 2.8K, 1/2" NPT the performance of these devices. TY2131: Upright 4.2K, 1/2" NPT Owners are responsible for maintaining TY2231: Pendent 4.2K, 1/2 " NPT their fire protection system and devices TY3131: Upright 5.6K, 1/2" NPT in proper operating condition. The TY3231: Pendent 5.6K, 1/2" NPT IMPORTANT installing contractor or sprinkler manu- TY4131: Upright 8.0K, 3/4 NPT Always refer to Technical Data facturer should be contacted with any TY4231: Pendent 8.0K, 3/4" NPT Sheet TFP700 for the "INSTALLER questions. TY4831: Upright* 8.0K, 1/2" NPT WARNING" that provides cautions TY4931: Pendent* 8.0K, 1/2" NPT with respect to handling and installation of sprinkler systems and - components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to - operate in a fire situation or cause it to operate prematurely. 'Eastern Hemisphere Sales Only Page 1 of 10 JULY 2010 TFP171 TFP171 Page 2 of 10 7/16° (11,1 mm) ESCUTCHEON STYLE 10 or 20 • * NOMINAL PLATE SEATING RECESSED SSU DEFLECTOR MAKE -IN NPT SURFACE ESCUTCHEON • 6* \ _ -- _ m ..,.. .,_---, / • s.- - r ITCrl r 'rtefir - - • • 5 �1Er �--- I 1� 7/16" or,- • 2 Ili (11,1 mm) I + 2 1/4" ��� 1;', NOMINAL ' � � (57,2 mm) �� - - 11 M AKE N 1 ie (55,6 mm) 1 ily 4-AL-0, 2- 3/16" FLATS" (39 9/ m ="" 1 X1'•4 ->,?. 1 7 f ,� -1.1 1/2" NPT SSP DEFLECTOR — 2 -7/8" (73,0 mm) DIA. -- CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector • Assembl ' Temperature rating is indicated on deflector or adjacent to 2 - Button y 5 - Compression 7 - Bushing orifice seat on frame. • Screw • • • - FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS • 2.8 K- FACTOR, 1/2 INCH NPT • 7/16" (11,1 mm) ESCUTCHEON STYLE 10 or 20 * NOMINAL PLATE SEATING RECESSED SSU 1/2 MAKE -IN SURFACE ESCUTCHEON DEFLECTOR NPT 6* 5 r te' 7/1 6" I I� U (11,1 mm) � 2 3/16" �iur 4 li NOMINAL I �to � (55,6 mm) � �M - *M girls MAKE -IN 1 2 2-3/16", I rL�� 1 1/2" 3 (55,6 mm) + - WRENCH (38,1 mm) • FLATS .._ —. — --.. 1/2" NPT SSP DEFLECTOR — 2 -7/8" (73,0 mm) DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT • 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector " Temperature rating is indicated on deflector or adjacent to Assembly 5 - Compression 2 - Button orifice seat on frame. Screw FIGURE 2 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT • • • • . 1 . • TFP171 Page 3 of 10 ' 7/16" (11,1 mm) ESCUTCHEON STYLE 10 or 20 * NOMINAL PLATE SEATING RECESSED DEFLECTOR MAKE -IN NPT SURFACE ESCUTCHEON 6 /.+171nu � _ 5 ter 7/16" wr-=-111 • 2- 3/16" 4 i ( I ',�� (55,6 mm) l� MAKE -IN NOMINAL i 2 .3111. ' 2- 3/16" ` 1-1/2" 41001 3 (55,6 mm) j WRENCH I (38,1 mm) t i ---- FLATS 1/2" NPT SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. - CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 Asse bl 4 - Bulb 6 - Deflector • Temperature rating is indicated on deflector or adjacent to 2 - Button y 5 - Compression - orifice seat on frame. Screw . •FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND.PENDENT (TY3231) SPRINKLERS . 5.6 K- FACTOR, 1/2 INCH NPT • 1/2" (12,7 mm) ESCUTCHEON STYLE 30 or 40 SSU * NOMINAL 3/4 PLATE SEATING RECESSED • DEFLECTOR MAKE-IN NPT SURFACE ESCUTCHEON 6* _ I 5 1 �' 1/2" I • • (12,7 mm) . 2 -5/16" �� �( . 4 li NOMINAL I IRS (58,7 mm) �� MAKE -IN 2 X ii t 1/4" 1- 9/16" i (57,2 mm) j I (39,7 mm) I1 3/4" NPT SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly ' Temperature rating is indicated on deflector or adjacent to 2 - Button 5 - Compression orifice seat on frame. Screw FIGURE 4 . QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT • • • • TFP171 Page 4 of 10 c 7/16" (11,1 mm) SSU * NOMINAL 1/2" DEFLECTOR MAKE -IN NPT 6* _ 6 ' tri */TT> 5 Ii= 7/16" 2 1/4° li ( 11,1 mmNOMINAL ) I ' } (57,2 mm) 4 IFr MAKE -IN 3 /O, + V 2 -3/ I r_r I' (55,6 mm) WRENCH (39,7 mm) FLATS 1 } SSP * CROSS 1/2 NPT DEFLECTOR SECTION UPRIGHT PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly • Temperature rating is indicated on deflector or adjacent to 2 - Button 5 - Compression orifice seat on frame. Screw • FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT (7Y4831) AND PENDENT (TY4931) SPRINKLERS 8.0 K- FACTOR, 1/2 INCH NPT Technical Operation inch (1,6 mm) for the 135 °F /57 °C and 3/32 inch (2,4 mm) for the 286 °F /141 °C D ata The glass Bulb contains a fluid that temperature ratings. expands when exposed to heat. When Obtain a leak -tight 1/2 inch NPT sprin- Approvals the rated temperature is reached, the kler joint by applying a minimum to UL and C -UL Listed fluid expands sufficiently to shatter the maximum torque of 7 to 14 ft.lbs. (9,5 • FM, LPCB, and NYC Approved glass Bulb, allowing the sprinkler to to 19,0 Nm). Higher levels of torque Refer to Table A and B for complete activate and water to flow. can distort the sprinkler Inlet with con - approval information including sequent leakage or impairment of the corrosion - resistant status. r. ®eSigl1 sprinkler. Maximum Working Pressure Do not attempt to compensate for Refer to Table C. Criteria insufficient adjustment in the Escutch- eon Plate by under- or over - tightening • Discharge Coefficient _ - The TYCO Series TY - FRB Pendent . the sprinkler. Re- adjust the position of • and Upright Sprinklers are intended the sprinkler fitting to suit. K =2.8 GPM /psiti (40,3 LPM /bart� K =4.2 GPM /psi (60,5 LPM /barv2 for fire protection systems designed in accordance. with the•standard installs- The Series TY -FRB Pendent and K =5.6 GPM /psi (80,6 LPM /bar1/2) tion rules recognized by the applicable Upright Sprinklers must be installed • K =8.0 GPM /psiv (115,2 LPM /bar1/2) Listing or Approval agency (such as, UL in accordance with the following Temperature Rating Listing is based on the requirements of instructions. Refer to Table A and B. NFPA 13, and FM Approval is based on 1. Install Pendent sprinklers in the the requirements of FM's Loss Preven- pendent position. Install upright Finishes tion Data Sheets). Only the Style 10, sprinklers in the upright position. . Sprinkler: Refer to Table A and B. 20, 30, or 40 Recessed Escutcheon, as 2. With pipe thread sealant applied to Recessed Escutcheon: White Coated, applicable, is to be used for recessed the pipe threads, hand - tighten the Chrome Plated, or Brass Plated. pendent installations. sprinkler into the sprinkler fitting. Physical Characteristics Installation 3. Tighten the sprinkler into the sprin- Frame Bronze kler fitting using only the W-Type 6 Button Brass /Copper The TYCO Series TY -FRB Sprinklers Sprinkler Wrench (Figure 14). With Sealing Assembly Beryllium must be installed in accordance with reference to Figures 1 through Nickel w/Teflont the following instructions. ' 5, apply the W-Type 6 Sprinkler Bulb Glass Wrench to the sprinkler wrench Compression Screw Bronze 'NOME- flats. ° Deflector Copper /Bronze Bushing (K =2.8) Bronze Do not install any bulb -type sprinkler if the bulb is cracked or there is a loss • of liquid from the bulb. With the sprin- kler held horizontally, a small air bub- ble should be present. The diameter t Registered Trademark of Dupont of the air bubble is approximately 1/16 • • TFP171 Page 5 of 10 • • SPRINKLER FINISH (See Note 5) • K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME WHITE*** FACTOR COLOR BRASS PLATED POLYESTER 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red • (TY1231) and 175 °F /79 °C Yellow 1, 2, 3, 4 UPRIGHT (TY1131) 200 °F /93 °C Green 286F/141°C Blue 135 °F /57 °C Orange 2.8 RECESSED 155'F/68 °C Red 1/2" NPT PENDENT (TY1231)" 175 °F /79 °C Yellow Figure 6 200 °F /93 °C Green 1,2,4 .135 °F /57 °C Orange RECESSED 1 55 °F /68 °C Red PENDENT . (TY1231) " , 175 °F /79 °C Yellow • • Figure 7 • • 200F/93°C Green ' • ' 135 °F /57 °C • • Orange • • • PENDENT 155 °F /68 °C Red • (TY2231) and 175 °F /79 °C Yellow _ UPRIGHT (TY2131) 200 °F /93 °C Green 286 °F /141 °C Blue 135 °F /57 °C Orange 4.2 RECESSED 1 55 F /68 °C Red 1, 2 1/2" NPT PENDENT ° (TY2231)* 175 °F /79 °C Yellow Figure 8 200 °F /93 °C Green 135F/57°C Orange • RECESSED 1 55 °F /68 °C Red PENDENT . (TY2231) " . 175 °F /79 °C Yellow Figure 9 200 °F /93 °C Green . NOTES: . • • 1. • Listed by Underwriters Laboratories, Inc.; (UL) as Quick. Response Sprinklers. �� -�� _ 2. Listed by Underwriters Laboratories, Inc., for.use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354 -01 -E. 5. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion- Resistant Sprinklers. Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. " Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. "' Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K- FACTOR SPRINKLERS • • • • TFP171 • Page 6 of 10 • SPRINKLER FINISH (See Note 8) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME WHITE*** LEAD FACTOR COLOR BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange PENDENT (TY3231) 155 °F /68 °C R • and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 UPRIGHT 200 °F /93 °C Green (TY3131) 286 °F /141 °C Blue 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red 5.6 PENDENT 175 °F /79 °C Yellow 1, 2, 4, 5 N/A 1/2" NPT (TY3231)` Figure 10 200 °F /93 °C Green 286 °F /141 °C Blue 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 175F/79°C Yellow 1, 2, 3, 4, 5 N/A (TY3231)" Figure 11 200°F/93°C Green 286F/141°C Blue 135 °F /57 °C Orange PENDENT (TY4231) 155 °F /68 °C Red and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7 1, 2, 5 UPRIGHT 200 °F /93 °C Green (TY4131) 286 °F /141 °C Blue 135 °F /57 °C Orange RECESSED 155F/68°C Red 8.0 PENDENT 175F/79°C Yellow 1, 2, 5 N/A 3/4" NPT (TY4231)' Figure 12 200 °F /93 °C Green 286 °F /141 °C Blue 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red • PENDENT 175 °F /79 °C Yellow 1, 2, 3, 5 N/A (TY4231) "' Figure 13 200 °F /93 °C Green 286 °F /141 °C Blue 135 °F /57 °C Orange PENDENT (TY4931) 155 °F /68 °C Red 1/2" NPT and 175 °F /79 °C Yellow 1, 2, 4, 5, 6 1, 2, 5 UPRIGHT 200 °F /93 °C Green (TY4831) 286 °F /141 °C Blue NOTES: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6 VdS Approved (For details, contact Tyco Fire Suppression & Building Products, Enschede, Netherlands, Tel 31 -53- 428- 4444/Fax 31 -53- 428- 3377.) 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead - Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion - Resistant Sprinklers. Where Lead - Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion - Resistant Sprinklers. • Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. " Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. • Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K- FACTOR SPRINKLERS • TFP171 Page 7 of 10 • SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD FACTOR BRASS PLATED POLYESTER COATED PENDENT (TY1231) and 2.8 UPRIGHT (TY1131) 1/2" NPT 75 PSI (12,1 BAR) N/A RECESSED PENDENT (TY1231) PENDENT (TY2231) and UPRIGHT (TY2131) 1 /24'NPT 175 PSI (12,1 BAR) N/A RECESSED PENDENT (TY2231) PENDENT (TY3231) 175 PSI and 5.6 UPRIGHT (TY3131) 250 PSI (17,2 BAR) (12,1 BAR) 1/2" NPT OR 175 PSI (12,1 BAR) RECESSED (SEE NOTE 1) N/A PENDENT (TY3231) - PENDENT (TY4231) 175 PSI and (12,1 BAR) 8 0 UPRIGHT (TY4131) 3/4" NPT 175 PSI (12,1 BAR) RECESSED N/A PENDENT (TY4231) 8 U PENDENT (TY4931) 175 PSI 1/2" NPT and 175 PSI (12,1 BAR 12,1 BAR UPRIGHT (TY4831) ( BAR) NOTES: 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the • Listing by Underwriters Laboratories, Inc for use in Canada (C -UL); and, the Approval by the City of New York. TABLE C MAXIMUM WORKING PRESSURE The Series TY -FRB Recessed Pendent. Care and Exercise care to avoid damage to Sprinklers must be installed in accor- sprinklers before, during, and after dance with the following instructions. Maintenance installation. Never paint, plate, coat, 1. After installing the Style 10, 20, 30, or otherwise alter automatic sprinklers or 40 Mounting Plate, as applica- The TYCO Series TY -FRB must be after they leave the factory. ble, over the sprinkler threads and maintained and serviced in accordance Replace sprinklers that: with pipe- thread sealant applied to with the following instructions. • were modified or over - heated. the pipe threads, hand - tighten the sprinkler into the sprinkler fitting. • were damaged by dropping, striking, NOTICE wrench twisting; wrench slippage, or 2. Tighten the sprinkler into the sprin- Before closing a fire protection system the like. kler fitting using only the W-Type 7 main control valve for maintenance Recessed Sprinkler Wrench (Fig - work on the fire protection system • are leaking or exhibiting visible signs • ure 15). With reference to Figures 1 that it controls, obtain permission to of corrosion. to 4, apply the W -Type 7 Recessed shut down the affected fire protection • were exposed to corrosive products Sprinkler Wrench to the sprinkler systems from the proper authorities of combustion but have not oper- wrench flats. and notify all personnel who may be ated, if you cannot easily remove 3. After ceiling installation and finish- affected by this action. combustion by- products with a cloth. • ing, slide on the Style 10, 20, 30, or Absence of the outer piece of an • have a cracked bulb or have lost liq- 40 Closure over the Series TY -FRB escutcheon, which is used to cover uid from the bulb. Refer to the Instal - Sprinkler and push the Closure over a clearance hole, can delay sprinkler lation section in this data sheet. the Mounting Plate until its flange operation in a fire situation. . comes in contact with the ceiling. • • • • TFP171 Page 8 of 10 • 2 -7/8" DIA. 2 -7/8" DIA. 5/8 ±1/4" (73,0 mm) 3/4 "(19,1 mm) 1/2±1/8° (73,0 mm) 1/2 "(12,7 mm) (15,9±6,4 mm) 2 -1/4" DIA. 1/4 "(6,4 mm) (12,7±3,2 mm) 2 -1/4" DIA. 1/4 "(6,4 mm) . FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" / �.i (3,2 mm) •m (3,2 mm) I �__ j� —} 111Mm 6 • MOUNTING j / 11/ f MOUNTING �: SURFACE SURFACE/ / CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1-5/16" (33,3 mm) TY-FRB 13/16" (20,6 mm) TY-FRB 1- 1/16" (27,0 mm) FIGURE 6 FIGURE 7 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT • WITH. TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10'RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON . 2.8 K- FACTOR, 1/2 INCH NPT 2:8 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA. ,, • 2 -7/8" DIA. _ 5/8 ±1/4° (73,0 mm) 3/4" (19,1 mm) 1/2 ±1/8" (73,0 mm) 1/2" (12,7 mm) (15,9±6,4 mm) 2 1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) ' _._ FACE OF (57,2 mm) (57,2 mm) SPRINKLER MOUNTING FACE OF MOUNTING PLATE SPRINKLER — PLATE FITTING FITTING 1/8" 1 1/8" (3,2 mm) .. (3,2 mm) lflili / �U �� � 1 / / �, f \ _ If ` MOUNTING / 1I/ • . MOUNTING .1111911 I } SURFACE / — SURFACE __. + / / CLOSURE SERIES . 1 -1/4° (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm) . - , - . - - - - - , . . , . • - -, - . , - - _ , _ TY -FRB- ..... - 3/4 "•(19,1 mm)- • — - ... . _. _. . TY FRB- ... • 1 "•(25,4•mm) - -- - -- - - • —_ • FIGURE 8 FIGURE 9 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT Initial and frequent visual inspections of Responsibility lies with the owner for Care must be exercised to avoid dam - random samples are recommended for the inspection, testing, and mainte- age to the sprinklers - before, during, corrosion - resistant sprinklers to verify nance of their fire protection system and after installation. Sprinklers dam - the integrity of the corrosion- resistant and devices in compliance with this aged by dropping, striking, wrench material of construction. Thereafter, document, as well as with the appli- twist /slippage, or the like, must be annual inspections per NFPA 25 should cable standards of the National Fire replaced. Also, replace any sprinkler suffice. Protection Association (for example, that has a cracked bulb or that has lost Inspections of corrosion - resistant NFPA 25), in addition to the standards liquid from its bulb. (Ref. Installation • sprinklers are recommended at close of any other authorities having jurisdic- Section). tion range, instead of from the floor level : Contact the installing contractor or Initial and frequent visual inspections'of per NFPA. Inspection at close range sprinkler manufacturer regarding any random samples are recommended for - can better determine the exact sprin- questions. corrosion - resistant sprinklers to verify kler condition and the long -term integ- Automatic sprinkler systems are rec- the integrity, of the corrosion - resistant rity of the corrosion - resistant material, ommended to be inspected, tested, material of construction. Thereafter, which can be affected by the corrosive and maintained by a qualified Inspec- annual inspections per NFPA 25 should conditions present. tion Service in accordance with local suffice. requirements and /or national codes. • TFP171 Page 9 of 10 2 -7/8° DIA. 2 -7/8" DIA. _ (73,0 mm) " (73,0 mm 5/8 ±1/4" mm) 1/2±1/8" ) 3/419,1 mm (19,1 1/2 °(12,7 mm) (15,9±6,4 mm) 2.1/4" DIA. 1/4 "(6,4 mm) (12,7±3,2 mm) 2.1/4" DIA. 1/4 "(6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" / 1/8" (3,2 mm) u (3,2 mm) - � I ' / MOUNTING MOUNTING �� SU RFACE _ � SURFACE/ - NA PI -. , cam- , / CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm) TY -FRB 3/4° (19,1 mm) TY-FRB 1" (25,4 mm) FIGURE 10 FIGURE 11 SERIES TY-FRB RECESSED PENDENT SERIES TY- FRB'RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT _ WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON • 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR; 1/2 INCH NPT • 2 -7/8" DIA. 2 -7/8° DIA. 5/8 ±1/4" (73,0 mm) 3/4 "(19,1 mm) 1/2±1/8" (73,0 mm) 1/2 "(12,7 mm) • (15,9 ±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) - (12,7±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) (57,2 mm ) MOUNTING FACE OF MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" 'gril (3,2 mm) n (3,2 mm) ^DUI ,---.1 OF 1 � � � \ ,,. MOUNTING �I� MOUNTING __ SURFACE SURFACE CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1- 5/16" (33,3 mm) - . .. _ _ . TY- -FRB - _ � . ��..-w�,..���. __. ._. _ .. _... 13716 °'(20;6 mm)° - — ' , 1Y-FRB - 11%1'6 "•(27;0 mm) FIGURE 12 FIGURE 13 . SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT Inspections of corrosion- resistant WRENCH sprinklers are recommended at close RECESS range, instead of from the floor level per NFPA. Inspection at close range WRENCH RECESS can better determine the exact sprin- (END "A" USED FOR �� kler condition and the long -term integ- 1 /2" NPT MODELS rity of the corrosion- resistant material, which can be affected by the corrosive conditions present. WRENCH RECESS (END "B" USED FOR %�' " 3/4° NPT MODELS) PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH FIGURE 14 SPRINKLER WRENCHING AREA • W -TYPE 6 SPRINKLER • FIGURE 15 WRENCH W -TYPE 7 RECESSED SPRINKLER WRENCH • • TFP171 Page 10 of 10 P/N 57 - XXX - X - XXX I I • MODEL/SIN SPRINKLER TEMPERATURE FINISH RATINGS 330 2.8K UPRIGHT (1/2 "NPT) TY1131 1 NATURAL BRASS 135 135 °F (57 °C) 331 2.8K PENDENT (1/2 "NPT) TY1231 4 WHITE POLYESTER 155 155 °F (68 °C) 340 4.2K UPRIGHT (1/2 "NPT) TY2131 3 WHITE (RAL9010)' 175 175 °F (79 °C) 341 4.2K PENDENT (1/2 "NPT) TY2231 9 CHROME PLATED 200 200 °F (93 °C) 370 5.6K UPRIGHT (1/2 "NPT) TY3131 7 LEAD COATED 286 286 °F (141 °C) 371 5.6K PENDENT (1/2 "NPT) TY3231 390 8.0K UPRIGHT (3/4 "NPT) TY4131 • 391 8.0K PENDENT (3/4 "NPT) TY4231 • 360 8 OK UPRIGHT (1/2 "NPT) TY4831' * Eastern Hemisphere sales only. 361 8.0K PENDENT (1/2 "NPT) TY4931' TABLE D PART NUMBER SELECTION SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS Limited responsible for sprinkler system design errors or inaccurate or incomplete infor- Ordering Warranty mation supplied by Buyer or Buyer's representatives. ' Procedure Products manufactured by Tyco Fire In no .event shall TFSBP be liable, in Contact your local distributor for Suppression & Building Products contract, tort, strict liability or under availability. When placing an order, (TFSBP) are warranted solely to the any other legal theory, for incidental, indicate the full product name and Part original. Buyer - for- ten•(.10)- years•against mdirecYspecial `orconsequential'dam - - Numtie�'(P /N). - - — • •• - defects in material and workmanship ages, including but not limited to labor when paid for and properly installed charges, regardless of whether TFSBP Sprinkler Assemblies with NPT and maintained under normal use and was informed about the possibility of service. This warranty will expire ten such damages, and' in no event shall Thread Connections yModel/SIN), (10) years from date of shipment by TFSBP's liability exceed an amount Response, (pationses specs fa ter, q p TFSBP. No warranty is given for prod- equal to the sales price. rating), Series TY -FRB ucts or components manufactured by temperature ratinn g), Seri companies not affiliated by ownership The foregoing warranty is made in lieu (specify Pendent or Upright) Sprinkler with TFSBP or for products and corn- of any and all other warranties. express with (specify type of finish or coating), ponents which have been subject to or implied. including warranties of mer- P/N (specify from Table D). misuse, improper installation, corro- chantability and fitness for a particular Recessed Escutcheon: sion, or which have not been installed, purpose, Specify: Style (10, 20, 30, or 40) maintained, modified or repaired in This limited warranty sets forth the Recessed Escutcheon with (specify') accordance with applicable Standards exclusive remedy for claims based on finish, P/N (specify°). of the National Fire Protection Associa- failure of or defect in products, materi- tion, and /or the standards of any other als or components, whether the claim is Sprinkler Wrench Authorities Having Jurisdiction. Mate- made in contract, tort, strict liability or Specify: W -Type 6 Sprinkler Wrench, rials found by TFSBP to be defective any other legal theory. P/N 56- 000 -6 -387. shall be either repaired or replaced, at TFSBP's sole option. TFSBP neither This warranty will apply to the full Specify: W -Type 7 Sprinkler Wrench, assumes, nor authorizes any person extent permitted by law. The invalidity, P/N 56- 850 -4 -001. to assume for it, any other obligation in in whole or part, of any portion of this - Refer to Technical Data Sheet TFP770. connection with the sale of products or warranty will not affect the remainder. • parts of products. TFSBP shall not be • Copyright © 2007 -2010 Tyco Fire Suppression & Building Products. All rights reserved. 1 tqCD I Fire & Building Products Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series TY -FRB — 5.6 K- factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General ment provided by the Recessed Es- cutcheon reduces the accuracy to ��. which the fixed pipe nipples to the Description sprinklers must be cut. . . . 1 V • The Series TY -FRB, 5.6 K- Factor, Corrosion resistant coatings, where � iti Horizontal and Vertical Sidewall Sprin- applicable, - ;( a licable, are utilized to extend the Jj. ' � l klers described in this data sheet are life of copper alloy sprinklers beyond that which would otherwise be ob- , �'� quick response - standard coverage, tained when exposed to corrosive at ''.- •"— '� decorative 3 mm glass bulb type spray p sprinklers designed for use in light and mospheres. Although corrosion resis- , _, . ordinary hazard, commercial occupan- tant coated sprinklers have passed the cies such as banks, hotels, shopping standard corrosion tests of the appli- malls, etc. They are designed for in- cable approval agencies, the testing is stallation along a wall or the side of a not representative of all possible cor- beam and just beneath a smooth ceil- rosive atmospheres. Consequently, it ing. Sidewall sprinklers are commonly is recommended that the end user be \tali ;; -�\ used instead of pendent or upright consulted with respect to the suitability sprinklers due to aesthetics or building of these coatings for any given corro- •- -4 ',: i‘ ,: i‘r : • construction considerations, where sive environment. The effects of ambi piping across the ceiling is not desir- ent temperature, concentration of I '' able. chemicals, and gas /chemical velocity, i . should be considered, as a minimum, . 1. . The recessed version of the Series along with the corrosive nature of the - , TY -FRB Horizontal Sidewall Sprinkler chemical to which the sprinklers will be is intended for use in areas with a exposed. } ` � finished wall. It uses a two -piece Style 10 Recessed Escutcheon with 1/2 inch WARNINGS ' (12,7 mm) of recessed adjustment or The Series TY - FRB Sprinklers de- up to 3/4 inch (19,1 mm) of total adjust- scribed herein must be installed and ment from the flush sidewall position, maintained in compliance with this or a two -piece Style 20 Recessed Es- document, as well as with the applica- Technical cutcheon with 1/4 inch (6,4 mm) of ble standards of the National Fire Pro - recessed adjustment or up to 1/2 inch tection Association, in addition to the Data (12,7 mm) of total adjustment from the standards of any other authorities hav- flush sidewall position. The adjust- ing jurisdiction. Failure to do so may Approvals impair the performance of these de UL and C - Listed. vices. FM, LPCB, and NYC Approved. The owner is responsible for maintain (Refer to Table A for complete ap- ing their fire protection system and de proval information including corrosion IMPORTANT vices in proper operating condition. resistant status.) Always refer to Technical Data The installing contractor or sprinkler Maximum Working Pressure Y manufacturer should be contacted Sheet TFP700 for the "INSTALLER with any questions. Refer to Table B. WARNING" that provides cautions Discharge Coefficient with respect to handling and instal- Model/Sprinkler K = 5.6 GPM /psi (80,6 LPM /bar / lation of s rinklers stems and corn- Temperature s Ratin • so patio n can Improper handling and damage - sta Identification Refer to Table A. g llatio permanently a sprinkler system or its compo- Finishes nents and cause the sprinkler to fail Numbers Sprinkler: Refer to Table A. • to operate in a fire situation or cause Recessed Escutcheon: White Coated, it to operate prematurely. TY3331 - Horizontal Chrome Plated, or Brass Plated. TY3431 - Vertical Page 1 of 6 APRIL, 2006 TFP176 • Page 2 of 6 TFP176 • SPRINKLER FINISH (See Note 11) K TYPE TEMP. BULB NATURAL CHROME WHITE"' LEAD LIQUID BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange HORIZ. 155 °F /68 °C Red SIDEWALL 1, 2, 3, 4, 9, 10 1, 2, 3, 9 1, 2, 3, 9 (TY3331) 175 °F /79 °C Yellow 200 °F /93 °C Green 5.6 286 °F /141 °C Blue 1/2" NPT RECESSED 135 °F /57 °C Orange HORIZ. 155 °F /68 °C Red SIDEWALL 1,2,4,9,10 1,2;9 N/A (TY3331)• 175 °F /79 °C Yellow Figure 3 200 °F /93 °C Green RECESSED 135 °F /57 °C Orange HORIZ. 155 °F /68 °C • Red SIDEWALL 1, 2, 3, 4, 9 N/A (TY3331)•* 175 °F /79 °C Yellow • Figure 4 • 200 °F /93 °C Green VERTICAL' 135 °F /57 °C Orange SIDEWALL 155 °F /68 °C Red 5.6 (TY3431) 5, 6, 7, 8, 9 5, 6, 7, 9 1/2" Installed 175 °F /79 °C Yellow • NPT Pendent 200 °F /93 °C Green or Upright 286, °F /141 °C Blue NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector to ceiling distance. 2. Listed by Underwriters Laboratories Inc. for use in Canada (C -UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector to ceiling distance. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers for use in Light Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector to ceiling distance. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007a/04) at a 4 to 6 inch (100 to 150 mm) top of deflector to ceiling distance. The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 5 Listed by Underwriters Laboratories, Inc: as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 6. Listed by Underwriters Laboratories for use in Canada (C -UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. s. :_ ;_ _i4: ----•. 7., Approved•by•Factory- Mutual- Research •corporation- (FM)•as•Quick- Response - Sprinklers• for - use• in - Light - Hazard• Occupancies : _ :. 8 Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a /06 & 007a/04) as Quick•Response Sprinklers. 9. Approved by the City of New York under MEA 354 -01 -E. 10. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) at a 4 to 6 inch (100 to 150 mm) top of deflector to ceiling distance The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 11. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers. • Installed with Style 10 (1/2" NPT) 3/4" Total Adjustment Recessed Escutcheon. •• Installed with Style 20 (1/2" NPT) 1/2" Total Adjustment Recessed Escutcheon. ••• Frame and deflector only. Listings and approvals apply to color (Special Order). TABLE A LABORATORY LISTINGS AND APPROVALS Physical Characteristics Frame Bronze Operation Button Brass /Copper Sealing Assembly The glass Bulb contains a fluid which Beryllium Nickel w /Teflont expands when exposed to heat. When Bulb Glass the rated temperature is reached, the N Compression Screw Bronze fluid expands sufficiently to shatter the C . HSW Deflector Bronze glass Bulb, allowing the sprinkler to re VSW Deflector Copper activate and water to flow. o Patents U.S.A. 5,810,263 • 4- • • . TFP176 • Page 3 of 6 • • SPRINKLER FINISH K TYPE NATURAL CHROME WHITE LEAD BRASS PLATED POLYESTER COATED • HORIZONTAL SIDEWALL 250 PSI (17,2 BAR) (TY3331) OR 175 PSI (12,1 BAR) 175 PSI (12,1 BAR) 5.6 RECESSED HORIZ. 1/2" SIDEWALL (TY3331) (SEE NOTE 1) N/A NPT VERTICAL SIDEWALL (TY3431) 175 PSI (12,1 BAR) NOTES: 1 The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C -UL); and, the Approval by the City of New York. TABLE B, MAXIMUM WORKING PRESSURE • Design * Temperature rating is DEFLECTOR indicated on deflector or • HAT 5 C riteria . adjacent to orifice seat • :O.A� on frame. * The Series TY -FRB Horizontal and **Pipe thread — Vertical Sidewall Sprinklers are in- connections per ISO 7/1 i t ��t. \ tended for fire protection systems de- can be provided on • signed in accordance with the stand- special request. . and installation rules recognized by the 6 4 2 3 1 applicable Listing or Approval agency (e.g., UL Listing is based on the re- 9/16" WRENCH 1/2" ** quirements of NFPA 13, and FM Ap- (14,3 mm) FLATS NPT proval is based on the requirements of FM's Loss Prevention Data Sheets). �� • Only the Style 10 or 20 Recessed Es- ` 1 12r ;Illlllll111111Il cutcheon, as applicable, is to be used 0 �'nlllllllllllllllll for recessed horizontal installations. �I 1- 13/16" 7/16" (46,0 mm) (11,1 mm) NOMINAL CENTERLINE _ _ _ .. - MAKE:IN__ - - ._.. _,...OF•SPRINKL•ER° ; • - ... _........ WATERWAY 11/2" (38,1 mm) y 2- 3/16" _ (55,6 mm) 1 - Frame STYLE ESCUTCHEON • 2 - Button I 10 or 20 — PLATE SEATING 3 - Sealing Assembly RECESSED I SURFACE 4 - Bulb ESCUTCHEON 5 - Compression Screw 6 - Deflector /� 1 . (73 0 m) irTM11llllllllllll FIGURE 1 5.6 K- FACTOR QUICK RESPONSE ' • SERIES TY -FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS . Page 4 of 6 TFP176 Installation ARROW MUST POINT AWAY . The Series TY -FRB Sprinklers must 7/16" FROM AND BE Awl • be installed in accordance with the fol- ESCUTCHEON (11,1 mm) PERPENDICULAR / lowing instructions: PLATE SEATING „ ** NOMINAL TO THE BACK SURFACE 1/2 MAKE -IN WALL SURFACE NOTES • Do not install any bulb type sprinkler if _ _ * g the bulb is cracked or there is a loss of - "'� -�* • liquid from the bulb. With the sprinkler � si \ 5 held horizontally, a small air bubble 2 - 3/16° 2 - 3/16" should be present. The diameter of the (55,6 mm) 1 dIL�Ih mi (55,6 mm) li ' 4 I air bubble is approximately 1/16 inch ' 1 (1,6 mm) for the 135 °F /57 °C to 3/32 (31 / rt m) FL NCH '■ it ! 2 inch (2,4 mm) for the 286 °F /141 °C temperature ratings. 7 3 . A leak tight 1/2 inch NPT sprinkler joint i �J J - should be obtained with a torque of 7 1 to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- SHOWN SHOWN CROSS mum of21 ft. lbs. (28,5 Nm) of torque PENDENT UPRIGHT SECTION may be used to install sprinklers with . 1/2 NPT connections. Higher levels of • torque may distort the sprinkler and _ 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector cause leakage or impairment of the • 2 - Button Assembly 5 - Compression 7- Ejection Spring . sprinkler. Screw • Do not attempt to make -up for insuffi- cient adjustment in the escutcheon * Temperature rating is indicated on deflector or adjacent to orifice seat on frame. plate by under or over - tightening the * *Pipe thread connections per ISO 7/1 can be provided on special request. sprinkler. Readjust the position of the • sprinkler fitting to suit. FIGURE 2 The Series TY -FRB Horizontal and 5.6 K- FACTOR QUICK RESPONSE Vertical Sidewall Sprinklers must be SERIES TY -FRB VERTICAL SIDEWALL (TY3431) SPRINKLERS installed in accordance with the follow- - ing instructions. Step 1. Horizontal sidewall sprinklers .. are to be installed in the horizontal position with their centerline of water- Step B. After installing the Style 10 or " way perpendicular to the back wall and 20 Mounting Plate over the sprinkler C are and parallel to the ceiling. The word "TOP" threads, hand tighten the sprinkler into 'on the Deflector is to face towards the the sprinkler fitting. Maintenance ceiling. Step C. Tighten the sprinkler into' the_ The Series-T-Y-BFR-Sprinklers-must - -- - - erfica sl ewall sprinklers are to • be sprinkler fitting only the W -Type be maintained and serviced in accord - installed in the pendent or upright po- 7 Recessed Sprinkler Wrench (Ref. ante with the following instructions: ' sition with the•arrow on the Deflector •Figure 6). With reference to Figure 1, - pointing away from the wall. the W -Type 7 Recessed Sprinkler NOTES Step 2. With pipe thread sealant ap- Wrench is to be applied to the sprinkler Before closing a fire protection system plied to the pipe threads, hand tighten wrench flats. main control valve for maintenance the sprinkler into the sprinkler fitting. Step D. After the ceiling has been in- work on the fire protection system that stalled or the finish coat has been ap- it controls, permission to shut down Step 3. Tighten the sprinkler into the plied, slide on the Style 10 or 20 Clo- the affected fire protection system sprinkler fitting using only the W -Type sure over the Series TY -FRB Sprinkler must be obtained from the proper 6 Sprinkler Wrench (Ref. Figure 5), and push the Closure over the Mount- authorities and all personnel who may With reference to Figure 1 or 2, the ing Plate until its flange comes in con- be affected by this action must be no W-Type 6 Sprinkler Wrench is to be applied to the wrench flats. tact with the ceiling tifie Series TY - FRB Recessed Hori The owner must assure that the sprin The S Th etl r es TY-FRB Sprinklers must be klers are not used for hanging of any . installed in accordance with the follow objects; otherwise, non - operation in the event of a fire or inadvertent opera- ing instructions. Lion may result. Step A. Recessed horizontal sidewall Absence of an escutcheon, which is sprinklers are to be installed in the used to cover a clearance hole, may horizontal position with their centerline delay the time to sprinkler operation in . of waterway perpendicular to the back a fire situation. • . wall and parallel to the ceiling. The • word "TOP" on the Deflector is to face Sprinklers that are found to be leaking ' • towards the ceiling. or exhibiting.visible signs of corrosion • TFP176 Page 5 of 6 5/8±1/4" (15,9±6,4 mm) FACE OF WRENCH RECESS • MOUNTING SPRINKLER (END "A" USED FOR SURFACE 1/2" NPT MODELS) FITTING A FIGURE 5 CLOSURE ormi W -TYPE 6 SPRINKLER WRENCH _�= 2 -7/8" DIA. SERIES ��, (73,0 mm) WRENCH TY FRB I I��I� 2 - DIA. RECESS � (57,2 mm) MOUNTING it — jW PLATE iI 1/8" _. PUSH WRENCH (3,2 mm) • IN TO ENSURE ENGAGEMENT • 1 -1/4" (31,8 mm) 3/4" (19,1 mm) WITH SPRINKLER WRENCHING AREA 3/4" (19,1 mm) 1/4" (6,4 mm) FIGURE 3 FIGURE 6 SERIES TY -FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER W -TYPE 7 RECESSED WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT SPRINKLER WRENCH STYLE 10 RECESSED ESCUTCHEON y 1/2±1/8" must be replaced. (12,7±3,2 mm) Automatic sprinklers must never be FACE OF painted, plated, coated or otherwise • MOUNTING SPRINKLER altered after leaving the factory. Modi- - SURFACE fled sprinklers must be replaced. FITTING Sprinklers that have been exposed to corrosive products of combustion, but ... -• — -• -- - have not operated, should be replaced / - -' " -- -- ' if they cannot completely cleaned CLOSURE by wiping the with a cloth or by brushing it with a soft bristle brush. �_ II 2 -7/8" DIA. SERIES IrAirM (73,0 mm) ` • Care must be exercised to avoid dam - n age to the sprinklers - before, during, TY FRB ■ 11111 2 -1/4" DIA. and after installation. Sprinklers dam - �` (57,2 mm) aged by dropping, striking, wrench twist/slippage, or the like, must be re- �� i placed. Also, replace any sprinkler MOUNTING iI that has a cracked bulb or that has lost PLATE M liquid from its bulb. (Ref. Installation f l; Section). y Frequent visual inspections are rec- 1/8" ommended to be initially performed for (3,2 mm) corrosion resistant coated sprinklers, L after the installation has been corn - 1-1/4" (31,8 mm) _ 1/2" (12,7 mm) pleted, to verify the integrity of the cor- ' rosion resistant coating. Thereafter, . 1" (25,4 mm) 1/4" (6,4 mm) annual inspections per NFPA 25 should suffice; however, instead of in- FIGURE 4 specting from the floor level, a random SERIES TY -FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER sampling of close -up visual inspec- • WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT tions should be made, so as to better • S TYLE 20 RECESSED ESCUTCHEON determine the exact sprinkler condi tion and the long term integrity of the • • Page 6 of 6 TFP176 P/N 57 - XXX - X - XXX • SPRINKLER TEMPERATURE MODEUSIN RATING 378 HORIZONTAL SIDEWALL TY3331 1 NATURAL BRASS 135 135 °F /57 °C 375 VERTICAL SIDEWALL TY3431 4 WHITE POLYESTER 155 155 °F /68 °C 3 WHITE RAL9010)' 175 175 °F /79 °C 9 CHROME PLATED 200 200 °F /93 °C 7 LEAD COATED 286 286 °F /141 °C TABLE C ' Eastern Hemisphere sales only. PART NUMBER SELECTION SERIES TY -FRB HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS corrosion resistant coating, as it may standards of any other Authorities be affected by the corrosive conditions Having Jurisdiction. Materials found Ordering present. by TFBP to be defective shall be either repaired or replaced, at TFBP's sole P rocedure The owner is responsible for the in- option. TFBP neither assumes, nor spection, testing, and maintenance of authorizes any person to assume for it, When placing an order, indicate the their fire protection system and de- any other obligation in connection with full product name. Refer to the Price vices in compliance with this docu- the sale of products or parts of prod- List for complete listing of Part Num- ment, as well as with the applicable ucts. TFBP shall not be responsible for bers. standards of the National Fire Protec- sprinkler system design errors or inac- Contact your local distributor for avail - tion Association (e.g., NFPA 25), in curate or incomplete information sup- ability. addition to the standards of any other plied by Buyer or Buyer's repre- - authorities having jurisdiction. The in- sentatives. Sprinkler Assemblies with NPT • stalling contractor or sprinkler menu- In no event shall TFBP be liable, in Thread Connections: facturer should be contacted relative contract, tort, strict liability or under Specify: (Specify Model /SIN), Quick to any questions. any other legal theory, for incidental, Response, (specify K-factor), (specify Y 9 rY� s P (P Y s ) (P fY It is recommended that automatic indirect, special or consequential dam- temperature rating), Series TY -FRB sprinkler systems be . inspected, ages, including but not limited to labor (specify Horizontal Sidewall or Vertical tested, and maintained by a qualified charges, regardless of whether.TFBP Sidewall) Sprinkler with (specify type Inspection Service in accordance with was-informed about the possibility of of finish or coating), P/N (specify from local requirements and /or national .. _.,such damages,, and in no event shall Table C). codes. `' - TFBP's liability exceed an amount • -" -• equal to the sales price. Recessed Escutcheon: , Specify: Style (10 or 20) Recessed Limited The foregoing warranty is made in lieu Escutcheon with (specify *) finish, P/N of. any and all other warranties. ex- (specify *). Warranty . - . -. , of merchantability and fitness for a par- • Refer to Technical Data Sheet TFP770. Products manufactured by Tyco Fire & fir•.ular purpose Building Products (TFBP) are war- This limited warranty sets forth the ex- Sprinkler Wrench: ranted solely to the original Buyer for clusive remedy for claims based on Specify: W -Type 6 Sprinkler Wrench, ten (10) years against defects in mate- failure of or defect in products, materi- P/N 56- 000 -6 -387. rial and workmanship when paid for als or components, whether the claim Specify: W -Type 7 Sprinkler Wrench, and properly installed and maintained is made in contract, tort, strict liability P/N 56- 850 -4 -001. under normal use and service. This or any other legal theory. warranty will expire ten (10) years from date of shipment by TFBP. No This warranty will apply to the full ex- warranty is given for products or corn- tent permitted by law. The invalidity, in ponents manufactured by companies whole or part, of any portion of this not affiliated by ownership with TFBP warranty will not affect the remainder. or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, maintained, modi- fied or repaired in accordance with ap- plicable Standards of the National Fire Protection Association, and /or the TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 I i ' . . • • I .j D yna4hre ad Full Line Sch -40 Replacement Dyne- thread offers the life expectancy of Sch40 with superior hydraulics and greater value. Dyne- Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety and longevity of traditional Sch-40 pipe with uali and superior hydraulic advantages. 4 tY P � g Comparison to Schedule 40 Comparisotr.to l.W.T ' Pipes: . Dyna-Tbread's inside diameter is Up • • With its increased strength and lighter • More wall thickness at the thread to 3.6% larger than Soh -40 giving it wet, Dy-ead reduces (CRR =1.00) gives Dyna - Thread superior hydraulics. And, when used installation fatigue and is ideal for better Life expectancy than liglttwall in combination with Dyne -Flow pipe, ream -fit applications. threadablc pipe joints. down sizing often occurs, Corrosion Resistance Ratio (CRR) is a • Unlike lightwari threadable pipe, • Dyne- Thread is fully listed and UL (Underwriters Laboratory) term for Dyna - Thread has no thread gauge approved by UL, ULC, and FM fie the estimated life expectancy of a pipe warning, fire sprinkler applications. joint. This is based on the calculated • The life expectancy of Dyna- Thread wall thickness at the base of the first • Dyne-Mead trca n is approved (15 exposed thread. assumed to bo the standard hanger spacing (15 ft. and Sch-40 arc equal based on the 0.C•), can be used as earthquake • • calculated wall thicknesses per UL. weakest Paint of the pipe length, Dyne- away q Thread and 9ch-40 have the same ay biasing, and is safe to use as • The consistent quality of steel used to calculated wall thicknesses at this point mss' make Dyna - Thread fhoi itates smooth and bath assigned the same CRR of . Dyna- Thread is safer to weld on, threading and lower maintenance 1,00. oasts, • Dyne- Thread is more widely • The exterior of The internal nurture of all black Allied accepted than lightwall threadable Dyne - Thread is where Solt -40 is specified. protected by a clean, durable mill Tuba &Conduit Fire Sprinkler pipe coring for extended shelf life and products up to 4.5000" in diameter is • easy paint application. coated with our now Anubaoterial Formula, "ABF". In scientific laboratory test; ABS proved to have superior Specifications '& Approvals_ resistance to microbial colonization of CO ® pipe walls, thereby delaying , .. or possibly Super 40/Dyna- Thread pipe is preventing the onset el inadufaotured to meet. ASTM A -135, Listed Approved Listed • Microbiologioally Influenced corrosion Grade A and is in with (NBC) when the First Sprinkler System IVFPA -13. All sizes of Super 40 /Dyne. • is first Installed. Thread are feted at 300 psi working • pressure. Super 40/Dyna- Throad is UL Specifications and ULC Listed for wet, dry deluge and pre- action sprinkler systems and FM NP8 Naminal I,D, Wt. WL (1120 filled) Pay WIA.111(21') WULIU (24') WVLIO (25' - Approved for use in wet systems. Super In; mm In; mm Cho nKO/nm Lbs?Fk Kg/m Lift Lba; Kg Lbs; Kg U's; Kg 40/Dyne- Thread can bo "hot -dip" t• 1.080 1.930 1,75 70 1955 2234 2327 galvanized to meat FM requirement for 25 27.4 20 2.80 70 887 1013 • 103; dry systorna. Super 40/Dyna -Thread is 1W 1,408 1,870 2.54 51 2002 2288 2984 approved fbr all tbroadod couplings and 32 35,8 2.8 3,78 51 908 1438 108 welded outlets and is suitable for all 1W 1.039 2290 3.42 44 2115 2418 261 • roll grooved, and plain -end fitting. 40 41.6 3,4 4.79 44 959 1097 114' (See listing mfbrmanon). 2° 2.104 9.050 4.57 30 1921 2195 • 2287 50 53.4 4.6 9.80 30 871 996 103 tile° Raw conrml 16100 S. Lathrop • Harvey, IL 60428 Customer Service: allied 16100 Noreom Rd. •Philadelphia, PA 19154 (800) 882,5543 TUBE 6 CONDUIT 2525 N. 27th Ave. • Phoenix, AZ 85009 Fax 708 -339 -1808 S3 -3 • • , • Submittal Data Sheet Dyna - Thread Svmp Here Full Line Sch-40 Replacement • Dyna- Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety and longevity of traditional Soh-40 pipe with • quality and superior hydraulic advantages. Comparison to Schedule 40 Dyne- Threads inside dimmer is up to 3.6% larger than Sch-40 giving it superior hydraulics. Also, when used in combination with Dyna -Flow pipe, dawn siting often occurs. Dyne- Thread is fully listed and approved UL, ULC, and FM for fire sprinkler applications. The life expeotenry of Dyne- Thread and Sch-40 : _ are equal based on the calculated wall thicknesses per UL. The consistent quality of steel used to make Dyne - Thread facilitates smooth threading and lower maintenance costs. The exterior of Dyne - Thread is protected by a clean, durable mill coating for extended shelf life and easy paint application. With in increased strength and lighter } weight, Dyne - Thread reduces installation Ihtigue and is ideal for retro-fit applications. I - Con-osion Resiamnce Ratio (CRR) is a UL (Underwriters Laboratory) term for the • 1 ' Thin calculated wall thickness t: • estimated life e 3tpeotanoy of i pipe joint. is hared on the - ... at the base of the fast exposed thread, assumed to be the weakest point of the pipe a length. Dyne - Thread and Soh-40 have the same calculated wall thicknesses at this point and are both assigned the same CRR of 1.00. ' G .' I . , a • Comparison ? arison to L.W.T. Pipe More wall thickness at the thread CRR =1.00 • 1 � '�N• •" Dyne- Thread better 11th expectancy P P pipe joints. Unlike [ wall eadable &r Dyne -T h ead has no thread pipe d gauge warning. Dyne - Thread is ,� light : � approved for standard hanger spacing (15 ft. O.C), can be used as earthquake sway I,.fp t ` ' Dyne- Thread Is safer many ,� t , r. r:... afar to weld on than sin om .�� bracing, and is safe to use as drops. Dy „ :,.,, :.,:= coated s;•• ' : ;: lightwall threadable pipe products. Dyne• Thread ie more widely accepted than ; � ; , ;7� '�'.1:5'•``::: lightwall threedable where Soh-40 is specified. . • • w 'Yl' Bpedfcattons & Approvals Super 40/ Dyes. Thread pipe is manufactured to Specifications meet: ASTM A 135, Grade A and is in NP8 Nernleal I.D; WI. Wt. (H20 Filled( Pod .19111.13 121') WVLiIt (24') WWII (25') compliance with NFPA -I 3. All-sizca of In: mm Ix mm LhwF1 KKA Lb&FT; Kgttn Ll1t ins; Kg 'Lbs; Kg Lbar Kg Super 40/Dyne- Thread are rated at 300 1' 1.080 1.330 1.75 70 1955 2234 2327 psi working lam. Super 40/ Dyne- 25 27.4 2.0 260 70 887 1013 105E Thread is UL and ULC Listed for wet, 1 Y.' 1.408 1.870 2.64 31 2002 2288 2384 dry and pro-action. sprinkler systems and 9 ?.8 5.78 51 808 1098 1081 • FM Approved for use in wet systems. Super 40/Dyna- Thread can 'lrot -dip" 1W 1.639 2.280 3.22 44 2115 2418 2519 galvanized to meet FM requirement for 4D 41.6 3.4 4.79 44 959 1097 1143 dry systems. Super 40/Dyne- Thread is 2' 2.104 3.050 4.67 30 1921 2196 2287 approved for all threaded couplings and 60 53.4 45 8.80 30 871 698 1032 welded outlets and is suitable for all roll- grooved, and plain -end fittings. (See American Tube and Pipe was acquired by Allied Tube and Conduit on February I, listing information), 1997. The engineered lightwall and standard wall family of products although they The internal surface of all black Fire have different names arc the same in all respects with regard to strragth, weight, Sprinkle pipe up to 4.5000" in diameter bundle count, listings and approvals. For example, shall be coated with Allied Tube & Dyne -Flow and Super Flo arc the same product as Conduit Antibacterial Formula "ABP.", are a Thread and Super 40. XL is i smrfaotured .� LC with Exterior galvanized coating. BLT is manufactured with Black lacquer coating Crated Approved bred Project. Sprinkler Contractor: Data: Engineer: SpecdiCation Reference: System Type: Locutions: Comments: S3 -4 ,f" t. V ff � 1 ..____J A \.- Li \„,...-,,,- t.__) I 1 . d Fittings and Flange ,i `� ,F 12600 CARDINAL MEADOW • SUGAR LAND, TX 77498 Toll: 888.999.3588 • Fax: 281.275.3995 SPECIFICATIONS; . - . .... . -.: • ..:.. : . • • ��_ 1 CAST IRON THREADED FITTINGS fl ALL CAST IRONS MANUFACTURED FOR AND BY UNIQUE FITTINGS & FLANGES® CONFORM TO, COMPLY WITH, AND ARE MANUFACTURED TO THE FOLLOWING STANDARDS: APPROVED ASTM Al26- Class B Standard Spec for Cupola Cast Iron . „- . , r. ; . y� ' ANSI B 16.4- Cast Iron Threaded Fittings Classes 125 , ANSI /ASME B1.20.1- Pipe Threads, General Purpose (inch) NPT C l'', `'O v L , t 1 s ,;■i,1. ❑ C.I. THREADED FITTINGS ARE UL. CUL LISTED AND FACTORY MUTUAL APPROVED FOR 300 PSI SERVCE. GRAY IRON PER ASTM 126 CLASS B. DIMENSIONS CONFORM TO ANSI B 16 4 CLASS 125 EXCEPT PLUGS CONFORM TO ASME B 16,14. THREADS ARE NPT PERANSUASME B1.20.1. i if I . ,::. 1 t 1- . _ .1 W .--- - .- . - . . . FIELD INFORMATION r - 1 CONTRACTOR JOB LOCATION A. LL Fittings andFhng a TOLL FREE 1 8 8 8. 9 9 9. 3 5 8 8 UNIQUEFITTINGSANDFLANGES.COM tqcn / Fire & Building Products CENTRAL • Customer Service/Sales: Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Tel: (215) 362 -0700 / (800) 523 -6512 www.tyco - fire.com Fax: (215) 362 -5385 Grinnell Grooved Fire Protection Products Grooved Fittings General Material: Limited Cast: Figures 201, 210, 219, 250, 260, 501, 510, ■�� Description 519, 510DE, 501S, 510S and 519S - Warranty IPCB See Fire Protection Ductile iron conforming to ASTM A -536, Products manufactured by Tyco Fire Products are Vd S Submittal Sheet for Grade 65 -45 -12 warranted solely to the original Buyer for ten (10) Pressure Rating and Fabricated Steel: Figures 391, 392, 393, 312, years against defects in material and workmanship Listing /Approval Information 313, 321, 327, 341 and 350 Carbon Steel, when paid for and properly installed and maintained (Sizes 1'/<° - 6° are Schedule 40); (Sizes 8" -12° are Schedule 30), under normal use and service. This warranty will conforming to ASTM A 53 Grade B expire ten (10) years from date of shipment by Tyco Fire Products. No warranty is given for products or The grooved fittings provide an economical Protective Coatings: components manufactured by companies not and efficient method of changing direction, • Non -lead orange paint affiliated by ownership with Tyco Fire Products or for adding an outlet, reducing, or capping • Fire brigade red (optional) non -lead paint products and components which have been subject grooved piping systems. Grooved fittings • Hot dipped galvanized conforming to ASTM to misuse, improper installation, corrosion, orwhich are available in durable ductile iron or A -153 have not been installed, maintained, modified or fabricated steel as indicated. repaired in accordance with applicable Standards of Note: Figure 510S and 519S fittings are Ordering the National Fire Protection Association (NFPA), special short radius fittings with smaller and /orthestandards of any other Authorities Having center to end dimensions than standard Procedure Jurisdiction. Materials found by Tyco Fire Products grooved fittings. Depending on the size and When placing an order, indicate the full product to be defective shall be either repaired orreplaced,at coupling used, there may be interferences at name. Please specify the quantity, figure number, Tyco Fire Products' sole option Tyco Fire Products the bolt pads that require repositioning of the wall thickness, and size. neither assumes, nor authorizes any person to coupling orientation. The use of flange Grinnell Grooved Piping Products, valves, assumeforit, anyotherobligationinconnecbonwith adapters is not recommended with Figures accessories and other products are available the sale of products or parts of products. Tyco Fire 510S and 519S fittings. Contact Tyco Fire throughout the U.S., Canada, and internationally, Productsshallnotberesponsibleforsprinklersystem Products for details. through a network of distribution centers You designerrorsorinaccurateorincomplete information WARNING may write directly or call 215 - 362 -0700 for the supplied by Buyer or Buyer's representatives. The Fittings described herein must be installed distributor nearest you. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE and maintained in compliance with this document, LIABLE, IN CONTRACT, TORT, STRICT LIABILITY as well as with the applicable standards of the C are and OR UNDER ANY OTHER LEGAL THEORY, FOR National Fire Protection Association, in addition M a i ntenance INCIDENTAL, INDIRECT, SPECIAL OR to the standards of any other authorities having CONSEQUENTIALDAMAGES, INCLUDING BUTNOT jurisdiction. Failure to do so may impair the The owner is responsible for the inspection, LIMITED TO LABOR CHARGES, REGARDLESS OF performance of this device. testing, and maintenance of their fire protection WHETHERTYCOFIREPRODUCTSWASINFORMED The owner is responsible for maintaining their system and devices in accordance with the ABOUT THE POSSIBILITY OF SUCH DAMAGES, fire protection system and devices in proper applicable standards of the National Fire Protection AND IN NO EVENT SHALL TYCO FIRE PRODUCTS' operating condition. The installing contractor or Association (e.g., NFPA 25), in addition to the LIABILITY EXCEED AN AMOUNT EQUAL TO THE spnnkler manufacturer should be contacted with standards of any authority having jurisdiction. SALES PRICE any questions. The installing contractor or product manufacturer JHE FOREGOING WARRANTY IS MADE IN UEU OF should be contacted relative to any questions. ANY AND ALL OTHER WARRANTIES EXPRESS OR Technical Any impairment must be immediately corrected IMPLIED. INCLUDING WARRANTIES OF It is recommended that automatic sprinkler MERCHANTABILITY AND FITNESS FOR A • Data systems be inspected, tested, and maintained by PARTICULAR PURPOSE. Approvals: a qualified Inspection Service. UL, FM, ULC, VdS, and LPCB; • Note: See Fire Protection Submittal Sheet for exact Listing / Approval information. Page 1 of 6 September 2004 TFP1810 • Page 2 of 6 TFP1810 Figures 201, 210, 219, and 260 C to ; Figure 201 Figure 210 Figure 219 Figure 260$ 45° Elbow 90° Elbow Tee End Cap If Nominal C to E Appx. Wt. C to E Appx. Wt. C to E Appx. Wt E to E Appx. Wt. I Size Inches Lbs. Inches Lbs. Inches Lbs. Inches Lbs c to E • c to E mm Kg. mm Kg. mm Kg. mm Kg. L �_ = i 11/4 1.75 0.9 2.75 1.0 2.75 1.4 0.88 0.4 C to E 44.5 0.4 69.9 0.5 69.9 0.6 22.4 0 2 1.75 1.1 2.75 1.2 2.75 1.8 0.88 0.6 Figure 201 1' /2" Figure 210 44.5 0.5 69.9 0.5 69.9 0.8 22.4 0.3 2° 2.00 1.8 3.25 2.0 3.25 2.7 0.88 0.9 50.8 0.8 82.6 0.9 82.6 1.2 22.4 0.4 2 '/2° 2.25 2.2 3.75 3.0 3.75 5.8 0.88 0.9 t- -ctoE1 EtoE 57.2 1.0 95.3 1.4 95.3 2.6 22.4 0.4 76.1 mm 2.25 2.2 3.75 3.0 3.75 5.8 0.94 1.1 ll ------!--- -- - - / I \ 57.2 1.0 95.3 1.4 95.3 2.6 23.9 0.5 " " 2.50 3.5 4.25 4.5 4.25 7.0 0.88 1.1 � 3 ° 63.5 1.6 108.0 2.0 108.0 3.2 22.4 0.5 • C to E 108.0mm 2.88 5.5 4.75 8.5 4.75 11.5 73.0 2.5 120.7 3.9 120.7 5.2 Figure 260 3.00 5.2 5.00 8.5 5.00 11.8 1.00 2.6 4° 76.2 2.4 • 127.0 3.9 127.0 5.4 25.4 1.2 Figure 219 133.0mm 3.25 7.7 5.25 11.3 5.25 10.6 82.6 3.5 133.4 5.1 133.4 4.8 139.7mm 3.25 7.7 5. 11.3 5.55.3 0.92 4. 82.6 .3.5 139 50 5.1 139 1 . 7 6.9 23.4 • 2 .1 3.25 8.5 5.50 13.5 5.50 17.0 1.00 5.0 Friction Resistance' S° 82.6 3.9 139.7 6.1 139.7 7.7 25.4 2.3 (Expressed as Equivalent Straight Pipe) 3.50 12.0 6.00 14.6 6.00 13.9 Elbow Tee 159.0mm 88.9 5.4 152.4. 6.6 152.4 6.3 - - Size 90° 45° Branch Run 165.1mm 3.50 12.0 6.50 18.5 6.50 26.0 1.00 7.5 Inches Feet Feet Feet Feet 88.9 5.4 165.1 8.4 ' 165.1 11.8 25.4 3.4 mm Meters Meters Meters Meters 3.50 12.0 6.50 18.5 6.50 26.0 1.00 7.5 11/4 1.9 1.0 4.8 1.9 " 6° 88.9 5.4 165.1 8.4 1651 11.8 25.4 3.4 42.4 0.6 0.3 1.5 0.6 4.25 23.0 7.75 36.5 7.75 45.0 11/2 2.3 1.2 5.8 2.3 216.3mm 108.0 10.4 196.9 16.6 196.9 20.4 - 48.3 0.7 0.4 1.8 0.7 4.25 23.0 7.75 36.5 7.75 45.0 1.19 12.8 2 3.2 1.6 8.0 3.2 8° 108.0 10.4 196.9 16.6 196.9 20.4 30.2 5.8 60.3 1.0 0.5 2.5 1.0 4.75 31.0 9.00 60.0 - 9.00 72.1 1.25 20.0 21/2 3.9 2.0 9.8 3.9 10 120.7 14.1 228.6 27.2 228.6 32.7 31.8 9.1 73.0 1.2 0.6 3.0 1.2 5.25 40.0 10.00 67.0 10.00 92.5 1.25 36.0 76.1 mm 4.1 2.1 10.3 4.1 12° 133.4 18.1 254.0 30.4 254.0 42.0 31.8 16.3 1.2 0 6 3.1 1.2 3 4.9 2.4 12.2 4.9 # - Available with tapped plugs, contact Tyco Fire 8 Building Products 88.9 1.5 0.7 3:7 1.5 . • • 108.Omm 6.5 3.3 16.3 6.5. . 2.0 1.0 5.0 2.0 4 6.5 3.3 16.3 6.5 114.3 2.0 1.0 5.0 • 2.0 133.0. 8.0 4.0 20.0 8.0 2.4 1.2 6.1 2.4 139.7mm 8.0 4.1 20.0 8.0 2.4 1.3 6.1 2.4 5 8.2 4.1 20.5 8.2 141.3 2.5 1.3 6.3 2.5 159.Omm 9.5 4.8 23.8 9.5 2.9 1.4 7.2 2.9 165.imm 9.5 4.8 23.8 9.5 2.9 1.4 7.2 2.9 6 9.9 5.0 24.8 9.9 168.3 3.0 1.5 7.6 3.0 216.3mm 13.1 6.6 32.8 13.1 4.0 2.0 10.0 4.0 8 13.1 6.6 32.8 13.1 219.1 4.0 2.0 10.0 4.0 10 16.5 8.3 41.3 16.5 273.0 5.0 2.5 12.6 5.0 12 19.9 9.9 49.7 19.9 323.4 6.1 3.0 15.1 61 • For reducing tees and branches, use the value that iscorrosponding to the branch size. Example. for 8' x 8' x 2' tee, the branch value 2' is 8.0 feet. • Friction resistance for all elbows and tees except Figures 5105 • • and 519S. • • • • • • • • Page 3 of 6 TFP1810 • Figures 501, 510, 519 and 510DE Cto i --1 Ct E ! I I C o CtoE t L I 1 _ CtoE II , as •I -- i- CtoE la A- -+ - CtoE Figure 501 Figure 510 Figure 519 Figure 510DE Figure 501 Figure 510 Figure 519 Figure 510DE 45° Elbow 90° Elbow Tee 90° Drain Elbow Nominal C to E Appx. Wt. C to E Appx. Wt. C to E Appx. Wt. C to E A B Appx. Wt. Size Inches Lbs. Inches Lbs. Inches Lbs. Inches Inches Inches Lbs. mm Kg. mm Kg. mm Kg. mm mm mm Kg. 11/2° 1.75 0.9 2.75 10 2.75 1.4 - - - - 44.5 0.4 69.9 0.5 69.9 0.6 1' /z° 1.75 1.1 2.75 1.2 2.75 1.8 44.5 0.5 69.9 0.5 69.9 0.8 -- 2 „ 2.00 1.8 3.25 2.0 3.25 2.7 50.8 0.8 82.6 0.9 82.6 1.2 2' /z" 2.25 2.2 3.75 • 3.0 3.75 5.8 3.75 2.00 2.75 2.7 57 2 1.0 95:3 1.4 95.3 2.6 95.3 50.8 69.9 1.2 3° 2.50 3.5 4.25 4.5 . - 4.25 7.0 4.25 2.34 2.75 3.7 63.5 1.6 108.0 2.0 108.0 3.2 • 108.0 59.4 69.9 1.7 4 „ 3.00 5.2 5:00 8.5 5.00 11.8 5.00 2.85 2.75 7.0 76.2 2.4 127.0 •3.9 127.0 5.4 127.0 72.4 69.9 3.2 5 „ 3.25 8.5 5.50 13.5 5.50 17.0 5.50 3.38 2.75 13.0 82.6 3.9 139.7 6.1 139.7. 7.7 139.7 . 85.9 69.9 5.9 6 „ 3.50 12.0 6.50 18.5. 6.50 26.0 6.50 3.92 2.75 13.4 88.9 5.4 165.1 8.4 165.1 11.8 165.1 99.6 69.9 6.1 8" 4.25 23.0 7.75 36.5 7.75 45.0 7.75 4.95 2.75 26.3 108.0 10.4 196.9 16.6 196.9 20.4 196.9 125.7 69.9 11.9 • Figures 501S, 510S and 519S '--C to E Cto i _ 1 c roE CtoE • � ! C to E •Lmom= 4- C to E o Figure 501S Figure 510S" • Figure 519S° ' ' Figure 501S Figure 510S Figure 519S Friction Resistance 501S, 510S & 519S 45° Elbow 90° Elbow Tee (Expressed as Equivalent Straight Pipe) Nominal C to E Appx Wt. C to E Appx. Wt. C to E Appx. Wt. Inches Lbs. Inches Lbs. Inches Lbs. Elbow Tee Size Size 90° 45° Branch Run mm Kg. mm Kg. mm Kg. Inches Feet Feet Feet Feet 2 ,. ' 2.00 1.8 2.75 1.5 2.75 2.1 mm Meters Meters Meters Meters 50.8 0.8 69.9 0.7 69.9 1.0 2 3.2 1.6 8.0 3.2 2,/2 2 2.2 3.00 2.2 3.00 3.0 60.3 1.0 0.5 2.5 1.0 572 • 1.0 76.2 1.0 76.2 1.4 2'/2 3.9 2.0 9.8 3.9 76 1.. 2 25 2.2 3.00 2.3 3.00 3.1 73.0 1.2 0.6 3.0 1.2 57.2 1.0 76.2 1.0 76.2 1.4 4.1 2.1 10.3 4.1 3 „ 2.50 3.5 3.38 3.0 3.38 4.1 76.1.. 1.2 0.6 3.1 1.2 63.5 1.6 85.9 1.3 85.9 1.9 3 4.9 2.4 12.2 4.9 4 „ 3.00 5.2 4.00 5.6 4.00 7.7 88.9 1.5 0.7 3.7 1.5 76.2 2.4 101.6 2.6 101.6 3.5 4 6.5 3.3 16.3 6.5 139.7 3.25 7.7 4.88 8.6 4.88 12.0 114.3 2.0. 1.0 5.0 2.0 82.6 3.5 124.0 3 9 124.0 5.4 8.0 4.1 20.0 8.0 5° 3.25 8.5 4.88 8.8 4.88 12.0 139.7.. 2.4 1.3 6.1 2.4 82.6 3.9 124.0 3.9 124.0 5.4 5 8.2 4.1 20.5 8 2 165.1 ° ° 3.50 12.0 5.50 11.00 5.50 15.0 • 141.3 2.5 1.3 6.3 2.5 88.9 5.4 139.7 5.0 139.7 6.8 9.5 4.8 23.8 9.5 6° 3.50 12.0 5.50 11.2 5.50 15.2 165.1.. 2.9 1.4 7.2 2.9 88.9 5.4 139.7 5.1 139.7 6.9 • 6 9.9 5.0 24.8 9.9 8 „ 4.25 23.0 6.88 23.4 6.88 31.2 168.3 3.0 1.5 7.6 3.0 108.0 10.4 174.8 10.6 174.8 14.2 . • 8 13.1 6.6 32.8 13.1 ' Note: Figure 510S and 519S fittings are special short radlus littings with smaller center to end dimensions 219.1 4.0 2.0 10.0 4.0 than standard grooved Ilttings. Depending on the size and coupling used, there may he interferences at the bolt pads which requires repositioning of the coupling orientation. The use of Ilenge adapters Is not recommended with'Figures 510S and 519S fittings. Contact Tyco Fire Products for detalis. Page 4 of 6 TFP1810 Figures 250 and 350 • Figures 250 and 350 Concentric Reducer - Groove x Groove Nominal E to E Appx. Wt. ^ Nominal E to E Appx. Wt. Nominal E to E Appx. Wt. f-- EtoE-1 Size Inches Lbs. Size Inches Lbs. Size Inches Lbs. Ir Inches mm Kg. Inches mm Kg. Inches mm Kg. 2.50 1.0 3.50 4.2 4.00 5.8 '2X1' /< 63 5 0.5 •139.7mmx3 889 1.9 •6X5 101.6 2.6 '2X1' /z 2.50 1.3 •1 3.50 4.4 8 5.00 12.2 63.5 0.6 88.9 2.0 127.0 5.5 Figure 250 •2'/z x 2 2.50 1.2 5 x 11/2 3.50 4.6 8 x 2' /z 5.00 12.1 63.5 0.5 88.9 2.1 127.0 5.5 Cast 2.50 1.5 3.50 4.6 5.00 12.0 "76.1mmx11/2 63.5 0.7 5 x 2 88.9 2.1 8x3 127.0 5.5 2.50 1.6 3.50 4.5 5.00 11.9 •76.1mmx2 5X2' /z 8X4 f to E--{ 63.5 0.8 88.9 2.0 127.0 5.4 3X11/4 2.50 1.3 5 3.50 4.4 8 •5.00 11.3 63.5 0.6 88.9 2.0 127.0 5.1 - - -- 11 - 3 x 1' /z 2.50 1.3 •5 x 4 3.50 4.5 ' 8 x 6 5.00 10.8 63.5 0.6 88.9 2.0 127.0 4.9 •3 x 2 2.50 1.3 •165.1. x 3 4.00 5.5 10 X 4 6.00 21.9 Figure 350 63.5 0.6 101.6 2.5 152.4 10.0 Fabricated x 2, /z 3.00 1.5 •1 x 4 4.00 6.0 10 x 5 6.00 21.6 Sizes 3" to 6" - 76.2 0 .7 101.6 27 152.4 9.8 • •3 X 76.1 mm 3.00 2.0 ' •165.1� x 139.7m" 4.00 5.6 • 10 x 6 6.00 21.1 76.2 0.9 101.6 ' 2.5 15.2.4 9.6 �EtoE - .1 6.0 6.00 19.5 4x1%, 3.00 2.2 ` 4.00 76.2 1.0 '6' 101.6 2.7. 10 152.4' 8.9 3.00 2.3 ' 4.00 6.0 7.00 28.0 4 x 11/2 76.2 1.0 6 x 21/2 101.6 2.7 • 12 x 4 177.8 127 '4 x 2' 3.00 2.3 •6 x 76.1mm 4.00 6.0 12 x 6 7.00 30.0 Figure 350 • 76.2 1.0 1 01.6 2.7 177.8 13.6 Fabricated '4 x 2Y2 3.00 2.3 6' 3 4.00. 6.0 12 x 8 7.00 28.0 76.2 1.0 101.6 2.7 177.8 12.7 ' Sizes 8" to 12" 3.00 3.2' 4.00 5.9 7.00 33.0 '4x76.1mm 76.2 1.5 •6x4 101.6 2.7 12x10 177.8 15.0 4 x 3 3.00 2.6 • x 139.7 4.00 6.3 mm 76.2 12 101.6 2.9 Note Sizes marked with an astensk (') are only available in Figure 250 Cast. Sizes without an astensk are only available in Figure 350 Fabncated. . • ADA CAP® Patented . • Pipe • Nominal Dimensions . • Size • Outlet • A. Tak CentertoEnd Net D Inches Inches Inches Inches Inches' Inches K mm mm mm mm Kg. Vs 1.25 1.75 1.89 0.77 31.8 44.5 48.0 0.3 1.. 1' / z 3/� 1.900 1.25 1.75 1.89 0.77 imie 1 --- 1 c 48.3 31.8 44.5 48.0 0.3 B 1 1.37 2.00 2.02 0.88 34.8 50.8 51.3 0.4 , 1.25 : 1.75 1.89 0.92 L. i 31.8 44.5 48.0 0.4 2 3/< 2.375 1.25 1.75 1.89 0.92 60.3 31.8 44.5 48.0 0.4 ' 1 1.37 • 2.00 2.02 1.06 34.8 50.8 51.3 0.5 1/2 1.47 1.97 1.89 1.28 37.3 50.0 48.0 0.6 2V2 3/4 2.875 1.47 1.97 1.89 • 1.28 73.0 37.3 50.0 .48.0 0.6 1 1.37 2.00 2.02 1.50 • 34 8 50.8 51.3 0.7 ISO.7 threaded outlets are available upon request. Page 5 of 6 TFP1810 Figures 391, 392, 393, 312 and 313 hi-- E to E--.1 Figures 391, Figure 312 Figure 313 -- - , 392 and 393 22 Elbow 11 Elbow 1 Adapter Nipples Figure E to E Appx. Wt. C to E Appx. Wt. C to E Appx. Wt. -• - -- Nominal '- - ""�' 391 Inches Lbs. Inches Lbs. Inches Lbs. Size mm Kg. mm Kg. mm Kg. I -0 - E to E 11/4" 4.00 0.8 1.75 0.4 1 38 0.4 _ -- 101.6 0.4 44.5 0.2 35.1 0.2 1 /z" 4.00 0.9 1.75 0.5 1.38 0.5 Figure 101.6 0.4 44.5 0.2 35.1 0.2 • 2 " 4.00 1.2 1.88 0.6 1.38 0.6 101.6 0.5 47.8 0.3 35.1 0.3 4.00 1.9 2.00 0.7 1.50 1.1 E to E ---►I - '•-- 21/2" 101.6 0.9 50.8 0.3 38.1 0.5 3° 4.00 2.5 2.25 1.4 1.50 1.2 101.6 1 1 57.2 0.6 38.1 0.5 Figure 6.00 5.5 2.63 2.4 1.75 2.2 393 4° 152.4 2.5 66.8 1.1 44.5 1.0 5 „ 6.00 7.4 2.88 4.1 2.00 3.3 152.4. 3.4 73.2 1.9 50 8 1.5 C to E 6 " 6.00 9.5 3.13 5.6 2.00 4.6 4.3 79.5 2.5 50.8 2.1 Figure **"., 6.00 6.00 14.2 .3.8.88 11.1 2.00 8.7 312 8 :152.4 6.4 98.6 5.0 50.8 3.9 CtoE� 8.00 27.0, 4:38 14.0 2.13 9.1 • 10" 203.2 12.2 11.3 6.4 54.1 4.1 C to E 12° 8.00 33.0 4.88 22.0 2.25 16.7 Figure 203.2 15.0 124.0 10.0 • 572 7.6 C t0 -- 313 Figures 327 and 341 • " -CtoE Figure 327 Figure 341 Cross . • i E;F!aPLTSel;VL ' Nominal C to E Appx. Wt. S nches Lbs. . mm kg. mm kg. - -- - -- - - - - 1 , /4 " 2.75 2.0 4.00 2.8 69.6 0.9 101.6 .1.3 CtoE 11/e 2.75 .2.2 4.00 3.2 69.9 2.0 101.6 1.5 l 2 „ 3.25 2.7 4.0 5.2 . • • • Figure 327 82.6 1.2 101.6 2.4 2' /z" 3.75 5.0 4.00 8.0 95.3 2.3 101.6 3.6 3° 4.25 7.1 4.00 10.2 108.0 3.2 101.6 4.6 iji i j i 4 „ 5.00 11.9 6.00 17.2 1270 5.4 152.4 7.8 I I I 5.50 17.1 6.00 21.4 E lo E 5" 139.7 7.8 152.4 9.7 6.50 27.5 - I t t tI 1 6° 165.1 12.5 152.4 6.00 26.0 11.8 j 8 „ 7.75 47.0 6.00 38.4 Figure 341 196.9 21 3 152.4 17.4 10" 9.00 68.0 8.00 65.0 228.6 30.8 • 203.2 29.5 - 12" 10.00 107.0 8.00 91.0 • 254.0 48.5 203.2 41.3 • • • Page 6.of 6 TFP1810 Figure 321 _ ! __ c toE -1 Figure 321 Reducing Tee Nominal C to E Appx. Wt. Nominal C to E Appx. Wt. Size Inches Lbs. Size Inches Lbs. Inches mm Kg. Inches mm Kg. - - -- , , 3.25 2.0 6.50 26.6 I ik xl /2 x1/. 82.6 0.9 6x6x4 165.1 12.1 + t CtoE 2x2x1'/2 3.25 2.7 6 x 6 x 5 6.50 27.0 I } 82.6 1.2 165.1 12.2 Figure 321 21/2 x21/2 x1% 3.75 4.2 8x8x2 7.75 36.2 95.3 1.9 196.9 16.4 2' x 2'h x 1' 3.75 4.2 8 x 8 x 3 7.75 36.5 • 95.3 1.9 196.9 16.6 2'/2x2' x2 3.75 4.3 8x8x4 7.75 36.6 95.3 2.0 196.9 16.6 3x3x1' /z 4.25 5.3 8x8x5 7.75 36.8 108.0 2.4 196.9 16.7 • - - 3x3x2 4.25 5.5 8x8x6 7.75 37.0 108.0 2.5 196.9 16.8 3x3x2'/2 4.25 5.8 10x10x2 9.00 57.1 108.0 2.6 228.6 25.9 4x4x1% 5.00 9.8 10x10x3 9 .00 57.4 127.0 4.4 228.6 26.0 4x4x1' 5.00 9.9 10x10x4 9.00 57.6 • • 127.0 4.5 228.6 26.1 4x4x2 5.00 - 10.1 10x10x5 9.00 • 57.8 . • 127.0 • 4.6 228.6 • 26.2 4x4x21/2 5.00 10.3 10x - 1 0x6 9.00. 58.0 . 127.0 4.7 228.6 . 26.3 4x4x3 5.00 10.5 • 10x10x8 9.00 58.4 • 127.0 4.8 228.6 26.5 • 5x5x2 • 5.50 14.5 12x12x3 10.00 80.2 139.7 6.6 254.0 36.4 5x5x21/2 5.50 14.8 12 x 12 x 4 10.00 80.5 139.7 6.7 254.0 36.5 5 x 5 x 3 5.50 15.2 12 x 12 x 5 10.00 80.7 139.7 6.9 254.0 36.6 5x5x4 5.50 15.8 12x 12x6 10.00 80.9 139.7 7.2 254.0 36.7 6x6x2 6.50 26.5 12x12x8 10.00 91.4 165.1 11.9 254.0 41.5 • 6x 6x2'/2 6.50 26.5 12 x 12 x 10 10.00 91.8 • • 165.1 12.0 254.0 41.6 . _ .... _ - _6 • z 6 z. 3' • - ,6.50 - 26:5 - 165.1 12.0 . • , General Notes: It is the Designer's responsibility to select products suitable for the intended service and to ensure ISO '• that pressure ratings and performance data is not exceeded. Always read and understand the installation instructions .e.- I 9001 , (IH- 1000). Never remove any piping component or correct or modify any piping deficiencies without first depressurizing and draining the system. Material and gasket selection should be verified to be compatible for the specific application. . Certified.Company TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19946 Printed U.S A. • ` JT * � S . .` c .- ' 1 wiy H I r : , . > y {, ", :r.! f '-','4:-., . t? - Ls} • .I . -1 ''ni I i t 4 IF L ,, Ih • fl: r a , l..0 .1 . ' S r 1D�i = tibER �VII�D�, > � ► C3 t _ �1 E 'tj et�nllSo , �1 ` , � � . . 3 `5 � k>t . , •.,r :! _ .: ,. _ 'r , 4 , 1 ,, .'-..,: , .: r 3 ,. :J_ ..a . 0 }. _J _ n'dh 4 .6' 1 .'_ ,,, .,_,. . e ., ,, r.'! u. .. , d ~ , ) ' QUALIFIED FOR USE IN FIRE SPRINKLER SYSTEMS, PER NFPA #13, 2 -6.1, FROM NFPA #13, 1994 EDITION. 4 1 SWDR.75 SHANK SHANK WT. /10' ;'' nR's'f. ' ITEM N MODEL • ROD SIZE DIA. LENGTH PIECE �' {., I "..,,..:4 M i ' ;+-+ � SELF DRILLING AND _. _ ... _.�.. _. .. .... - ''�; � TAPPING IN LIGHT GAUGE n 1/4" u L' r_'i:J 43 SWDR .75 3/8 /16 1/4 1 6.7811 STEEL INCLUDES RETAINER " NUT 44 SWDR 516 !L 3/8 "/16 5/16" I 1/4'' 8.06 • 39 SWD 10 3/8 "/16 1/4" I" 5.8611 Imo^ UL 41 SWDR 516 46 SWDR 3/8 "/16 1/4" 1 1/2" 6.9211 P' y fRl s. ;� Nk:;•1; 7 , SELF DRILLING AND 40 SWD 15 3/8 "/16 1/4" 1 1/2" 6.4011 1 n ' : r' ' . "' TAPPING IN STEEL UP TO 42 SWD 516 3/8"/16 5/16" 1 1/4" 6.7211 I.. '4!. ,.,1 :- >.. 3/16" DEPTH 41 SWD 20 3/8 "/16 1/4" 2" 6.8311 LISTED 45 SWT 15 3/8 "/16 1/4" 1 1/2" 6.1211 • ‘` ' ?% SWD 18 SWG 10 3/8 "/16 1/4" I" 5.7811 — — — — 19 SWG 20 3/8 "/16 1/4" 2" 7.1311 a arc. F • i, • , f N,h ,00.. SELF DRILLING AND 65 SWC 20 3/8 "/16 5/16" 2" 7.5711 S -� f TAPPING IN STEEL UP TO `,r {1•�'- ' „'' 3/16” DEPTH INSTALLATION TOOLS , :,4 'It'„,J 4 1 S T/SI �A� DR ITEM# A. HEX SHANK a 104 3/16" RECEIVER i °,� 'I'1M f — 12 X 24 - WITH RETAINER 105 .236 RECEIVER NUT. SELF DRILLING AND .i T •. 5 ' r 1 x + , :APPING IN STEEL UP TO - ® ITEM# B. CARBIDE TIP BIT 1/2" DEPTH 106 3/16" DIAMETER LISTED 107 .236 DIAMETER . - ' SWD 516 a .n, S 4 ITEM C. SDS BIT r • W iiia. A SS • SELF DRILLING AND 108 3/16" DIAMETER • • " 1,4,', ,_ ,u4.! :. „!„, . ' t. " TAPPING IN STEEL UP TO 109 .236 DIAMETER • { P' 3/16" �: ; D EPTH ITEM# D. SLEEVE TOOL 110 3/16" & .236 i ' er r tiR!,q ,.. - ITEM# E. NUT DRIVER #14 , SWT r ~' ` ', 1.5; 100 (16MM BLACK) • • !,Irk '' + _ •' ,i it >= 1. 't r SELF DRILLING AND ' r t ''' • I -' =i ITEM# F. NUT DRIVER #14 SW VC 1 _ : •3: ° i �l��C V+mC' TAPPING IN STEEL UP TO ,t � � Ii -' 1/2" D EPTH 1 01 (16MM RED) WITH ' "vim,.. 3/16" MARKER II HOLE . ' L i . I , - 44 SWG k � •i ' ` , r 1i P SELF DRILLING AND j! ' THREADING INTO WOOD - a' _ 1 #.,,, - � . ' • NO PREDRILLING REQUIRED it l i I : . ! : ! ® L :!if, ? ,. �a► . yy S W C 'r � i , 0;0010,6, SELF THREADING ` DING INTO . w r, 'iai ` CONCRETE. PREDRILLING t. ^1i. , �1 k " " ' -- ' REQUIRED `. SEE LOCAL AUTHORITY FOR USE OF THIS FASTENER. P ,, .�; . : 1 I# 70 l i , .. •N 4 TEM' h. SST b . . Tl, ,:f 1 , {,,. T OGGLE FOR r? 4 ,-. ' • 'r , SHEETROCK _ •'I K ° rc 3 ,4 ,n 1 . • OR PLYWOOD < ( %!• t � J i "11 1 ,5 r ' 1/4 "/20 x 3" t A. r �,° j 1 Y , ;� WITH 3/8" HEAD 'r. =6;0 G �V•_ I II �� } .:.11` . H.1 ±i(�1i t1 T 4.� lf6 1 , /Cr1 ) , ,A..7-i Imti M.!, . I t h ~ '� r 4 • t ` E % F ITEM# USE FOR SAMMY ITEM# USE FOR SIDEWINDER 100 INSTALLATION 101 INSTALLATION `FACTORY MUTUAL SEISMIC ZONE 70 & 150 REQUIRE APPROVAL BY AUTHORITIES HAVING JURISDICTION. CONTACT YOUR FACTORY REPRESENTATIVE FOR DETAILS. ,- 7 Ib INCORPORATED • • ADJUSTABLE RING HANGER FIG.2 Size Range: 1/2" thru 6" Approvals: Underwriters' Laboratories listed and Factory Mutual approved. Conforms to Federal Specification WW -H -171 E (Type 10) and Manufac- turers Standardization Society SP -69 (Type 10). �"' Service Application: For general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. Spring tension on swivel nut B holds it securely in hanger before installation. Swivel nut easily removed. Special Note: Also available to accomodate the new rod schedule per the National Fire Protection Association Pamphlet 13, 1973. i.e., 1/2" - 4" A ... 3/8" rod; 5 ", 6" and 8" ... 1/2" rod. Specify Fig. 2 NFPA and pipe l,, size. Ordering: Specify pipe size and figure number. PIPE ROD HOLE - MATERIAL MAX. SIZE SIZE SIZE A B C • D E SIZE LOAD FIG. 2 1/2 3/8 35/64 3 -1/4 2-7/8 2 15/16 1-1/2 1 x 16ga 400 • ADJUSTABLE RING HANGER 3/4 3/8 35/64 3 2-1/2 • 1-5/8 15/16 1-1/8 1 x 16ga 400 1 3/8 35/64 3-1/4 2.5/8 1.7/8 15/16 1-1/4 1 x 16ga 400 Carbon Steel - Plated or Galvanized 1.1/4 3/8 35/64 3-1/2 . 2 -11/16 1-13/16 15/16 1 1 x 16 ga 400 1-1/2 3/8 35/64 3.7/8 2-7/8 2 15/16 1 1 x 16 ga 400 2 3/8 35/64 4-1/2 3 -5/16 2-3/8 15/16 1-3/16 1 x 16 ga 400 2-1/2 1/2• 43/64 5-3/8 3-7/8 2-13/16 1 1-5/16 1-3/16 x 14 ga 600 3 1/2• 43/64 6 4-1/4 3 -1/4 1 - 1-1/2 1 -3/16 x 14 go 600 3 -1/2 12• 43/64 7 5 4 1 2 1-3/16 x 14 ga 600 4 5/8• 51/64 7-1/4 5 4-1/4 1 -1/8 1 -3/4 1-1/4 x 14 ga 1000 5 5 /8•• 51/64 9 6-1/4 5-3/8 1-1/8 2-1/4 1 -1/4 x 12 ga 1250 6 3/4•• 63/64 9-7/8 6-5/8 5 1-1/4 2-1/8 1-5/8 x 12 ga 1250 • 3/8" not is used when 1973 NFPA rod sizing in requested. •• 1 /2" not is used when 1973 NFPA rod sizing Is requested. • • PIPE FIG. 2 FIG. 2 SIZE FIG.2 WON NFPA 1/2 17 14 17 3/4 17 14 17 1 18 16 18 • 1-1/4 19 17 19 WEIGHTS ON RING HANGERS 2 -1 /2 4 2 2 0 27 40 3 2-1/2 41 1 37 40 3 NET PER HUNDRED 2 D 3 45 40 43 E 3-1/2 52 48 50 4 59 53 56 B C 5 97 91 95 6 139 130 134 A RING HANGER LESS NUT FIG. 2WON J.. Made the same as Fig. 2 except without swivel nut. Generally hung using nuts Q and washers, or spring type tension nuts. Conforms to Federal Spc' ification WW-H-171E (Type 7) and Manufacturers Standardization Society SP -69 (Type 7), 3/4" - 6 ". • • PIPE HOLE MATERIAL - FIG. 2 WON SIZE SIZE A B C 0 E SIZE RING HANGER LESS NUT 1/2 35/64 3-1/4 2-7/8 2 15/16 1-1/2 1 x 16ga 3/4 35/64 3 2-1/2 1.5/8 15/16 1 -1/8 1 x 16 ga Carbon Steel - Plated or Galvanized 1 35/64 3-1/4 2-5/8 1 -7/8 15/16 1-1/4 1 x 16 go 1 -1/4 35/64 3 -1/2 2-11/16 1 -13/16 15/16 1 1 x 16 ga 1-1/2 35/64 3-7/8 2 -7/8 2 15/16 1 1 x 16 ga ♦ 2 35/64 4-1/2 3-5/16 2.3/8 15/16 1-3/16 1 x 16 ga 2 -1/2 _ 43/64 5-3/8 3 -7/8 2-13/16 1 1 -5/16 1.3/16 x 14 go 3 43/64 6 4-1/4 3-1/4 1 1 -1/2 1.3/16 x 14 ga 3 -1/2 43/64 7 5 4 1 2 1.3/16 x 14 ga 4 51/64 7 -1/4 5 4 - 1/4 1 -1/8 1-3/4 1 -1/4 x 14 ga • i 5 51/64 9 6 -1/4 5-3/8 1-1/8 2 -1/4 1-1/4 x 12 ga 6 63/64 9-7/8 6 -5/8 5 1-1/4 2 -1/8 1-5/8 x 12 ga - TOLCO INCORPORATED / 601 W. LAMBERT ROAD / BREA, CALIFORNIA 92621 • . 6 -- -- ---- -- y . i F- Yf'� : -.: . - ..; r L - E- •. Ti: _ r . x i s . iT , . , .>, y �ti ��. _ -- _ - ' 7 fir Y- : J. ±�., ?�% r . -t5 t - _ .,. n .:A—: ` '< , 5- . „ :4- i .: Fi p ; , ::,, .- �h „1, ,,,.: • ',•.,, �.'.'r�'C -�i:, �::r.r iti�',,�F" 5. a ; yti' '�': _ .l`i ,-G- t y � i:.sr =•� % J�A�r : .t U a a•, 5•. t dTr� .c-;tr' r - , i+ r , , y : :F . � 4: y � � �; r.--.'2' �� : ' :_.�'. -, t v / FA ® Ay�C�CE .T \�Y N Y•12 -_ __ _ = �:.= :ivi,aLlr',•X v.i !z1F5,,'l ::; ,; ,� .±.� ;,. .,'�:; - ��;:_; : = , r..;ri:, :: ,, F UNCTION _- n : , r.w:.. - _ = . Designed for u se in pipe han assembly. [, ,�= � ' �j . •��� s; , a_-::•; r -.• ' . 2 ; , MATERIAL � ' Low carbon steel g= g f:LT I;L C TI' :_ i ; r.' s -; =:!ei.. FINISH: s i ; 1 ; .. _ : � . Plain ..'''' :> . .. ....,•:: <. ..:fC :7” ..=,;'•. .:, '�.‘” ORDERING: Specify rod size, length (B) and figure number. Max. Rec. Rod Load/lbs. Wt. Per � 1111�11111� Size Inch /lbs. B 650 °F 750 °F 1111��1� 3 /a x B 610 540 .02 l ���ll '/z x B 1130 1010 .04 \ �� lllll1�11 % x B 1810 1610 .07 3 /4 x B 2710 2420 .11 ' /axB 3770 3360 .14 r, '' :...,. . - ': : ' ai ..,7 _ '+`_..131- •1 4 • -i- V .)`i•1. Y ;. k„C .aA. ,� r 1,.frr ,:!?a.. : „ . • ., , r 5+ fi r. �..� .. :Vv:;^ } •t -I , AM :j :s iA . Ly�'si; rrts °.: ��. P'. } 4 � ” "', Designed ?' °� FUNCTION: = � geed for use in pipe hanger assembly. ;ice � V" 'h., a ;�s�i,�jt= ••�.�:Gi�`s: ''.. �'`'; b�'; ry HL �• � . �1;try Y4El il ur r , •tip MATERIAL. Low carbon steel 1. �lti ":1 + +:• S 1 C�c• %c _w:�' t'4 °:�.�r::le tr"{ ": Xti ,- l S hit ' +:_ '.".t l FINISH: Plain `. - 3Z;i�,:r `ANGER =nROD '' : ;:. �:.� . i_k7:� S._:n - � �'.` �':.: J+ 3 ..aF.i: {::MrC:'.. Fig. 15 RIGHT -HAND THREADS ORDERING: Specify rod size, length (B) and figure number. Fig. 15L RIGHT - AND LEFT -HAND - THREADS ..:. Rod •� - ' .lT a W r _ d� _M ax. R ec: ,, - ' oad %Ibs ..:.... " _ t, Pe s 'Size Length `` "� ' � -' � � • � � .Inch %Ib. C-.2.: .: 650 °.F; : 750 °F B 1 11 1111 3 /ax 2 610 540 • %xB 2% 1130 1010 .06 C 5 /axB 2% 1810 1610 .09 3 /4 x B 3 2710 2420 .13 , � llll �yllll l � l � ' /axB 3Yz 3770 3360 .17 1 x B 4 4960 4420 .22 his'- ^...;(P:r -, - ::-/ wr., °„'•,.,cg =. ,1kitK.Y.iS ra- srssr,. . - _ -K :'? :`tir:.:2N:-.'a:"t:'.� r -._ _.�. F ? .: s• r...9:e.;.•r. rwrS a; -. .a� 7r ,nl?- rF!.yt >.•.ccw +.r� °, :11i, , r = 1' i ;:.- iRATIt1tiVI FUNCTION �; '• �'' b � Fj i �`+aot— d ' :,. g zk F Useful in ,_ rs�: •x., g•, & ` � i �; y uy �s applications where stud lengths cannot be ;__- � ,,. r ;�, ,.. ,M .. r<.:. �,...: aPPlic .�'�,. •, �� >" �;• G�T�T•1 ,.s : . predetermined. {gy 4 m v. ,. ,{ty+ 1bti,Y - • . r - -- t'9l', „,, ,,,,, - ma ,,-r i nor i` ..• 7 � +, , MATERIAL: l r 9FHRI �_ 1Z O D`� 'x Low carbon steel Fig. 20 PLAIN ORDERING: Specify rod size, length and figure number. Fig. 21 ELECTRO- GALVANIZED Packaging Max. Rec. Rod Feet Per Bundle Load /lbs. Wt. Per Size - 6 ft. 10 ft. 12 ft. 650 °F 750 °F Foot/Ibs. �� .4.,- � �� '/4 -20 300 500 600 240 210 .12 ��� �� % -16 150 200 240 610 540 .29 r ■ \ 40 1 �1� .' �,e� '0 ' O .t i l l • � '/z -13 72 120. 144 1130 1010 .54 ,t,ll� /e -11 48 80 96 1810 1610 .83 • �,�,1�14�,1 3 4 -10 30 50 60 2710 2420 1.25 �” '/a-9 24 40 48 3770 - 3360 1.65 1 -8 12 20 24 4960 4420 2.25 l � .:......... -- - 3 ".' '_,:.=, o--••: rT. 1:.: r ::...i:S`•Ra.,y:i_.Lt . ?�.� —,..- .ate -:. ;tor^. : - 'F":� ' -.:•� • PHD Manufacturing, Inc. ,Z P.O. Box 3365 SOUTH EL MONTE, CA 91733 626.444.0541 FAX 626.444.3887 www.afcon.org • 001/020 SWAY BRACE MODEL E Part N 077 I ■1 O 1�1 U lm r�1 • SIZE - Pipe to be braced: 1" tluu 8" Steel SCH 7 thru 40 IPS. Pipe used for bracing: 1" and 1 1/4" SCH 40 IPS. • MATERIAL - Carbon Steel. FINISH - Plain, Electro - Galvanized, H.D.G. and Stainless Steel. • LISTING - UL in US and CANADA. Only for use with other AFCON bracing products. APPROVAL - OSHPD pending PATENT - No. 3,570,794 — FUNCTION - For bracing pipe against sway and seismic disturbances. The sprinkler pipe attachment component of a lateral sway brace assembly, consisting additionally of AFCON 70 series attachment end joined with brace pipe sized per N.F.P.A. INSTALLATION - Place Wile] E over pipe to be braced. Insert brace pipe through MODEL "E" under channel bracket, leaving 1" minimum extension beyond. Tighten bot_, hex nuts until gage spring lays flat. Minimum torque (.1f65 in. -lb. Install as a lateral sway brace per N.F.P.A. FEATURES * UL Horizontal Load Ratings: 2015# Sch. 10 Iluu 40, All Sizes 65511 Sch. 7 - 1" dull 4" 1500# Sch. 7 - 6" * Can be used as a 4 -way sway brace. 4 • Visual inspection, proper installation when gage spring lays flat. ORDERING - Part #, Pipe size to be braced, Brace pipe size and Finish. 01 02 • n • P.O. Box 3365 SOUTH EL MONTE, CA 91733 626.444.0541 FAx 626.444.3887 www.afcon.org 070 • ATTACHMENT END THREADED • • • • • • SIZE - 1 tluu 2 inch bracing pipe. • Use in combination with 1 tlu'u 10 inch AFCON sway braces. MATERIAL - Carbon Steel. F INISIi - Plain and Electro- Galvanized. LISTING - UL in US and CANADA. Only for use with other AFCON bracing products. APPROVAL - OSHPD pending. FUNCTION - For bracing pipe against sway and seismic disturbances. The building attachment component of a sway brace assembly, consisting additionally of AFCON_001 thru 40 series sway brace joined with bracing pipe sized per N.F.P.A. INSTALLATION - Make -On to brace pipe then secure to the • • building structure with appropriate fastener. FEATURES • • * 1 UL Horizontal Load Rating: 2765 #, All Sizes * Swivel design allows attachment at any angle. * To be used with threaded pipe. * May be ordered with larger hole. - Consult Factory. ORDERING - Part #, pipe size and finish. • 02/01 • •