Correspondence .a March 31, 2005 CITY OF VLMK Consulting Engineers 3933 SW Kelly Ave OREGON Portland, Oregon 97239 .t RE: FIRE LINE REVIEW — REPLACEMENT OF EXISTING PIPE LINE Project Information Permit: BUP2005 -00121 Address: 8100 SW Hunziker Rd The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and the Tualatin Valley Fire & Rescue Fire & Life Safety Requirements for Fire Department Access and Water Supplies (Based on the 2003 International Fire Code as amended by TVF &R). The submitted plans are approved subject to the following conditions. HYDROSTATIC TESTING Hydrostatic testing of the system shall occur at sprinkler final. The contractor's material and test certificate required by NFPA 13, 16.1 shall be completed and signed by both the installer and building owner. Failure TESTING: - Section 16.2.1 1. All piping and attached appurtenances subjected to system working pressure shall be hydrostatically tested at 200 psi (13.8 bar) and shall maintain that pressure • without loss for 2 hours. Loss shall be determined by a drop in gauge pressure or visual leakage. The test pressure shall be read from a gauge located at the low elevation point of the system or portion being tested. EROSION 2. Erosion control measures shall be in place prior to excavation. LM FIRE 3. The private fire service main shall be at least 30 inches below grade. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 4. The private fire service main shall be flushed thoroughly before connection to the system riser in order to remove foreign materials that might have entered the main during the course the installation. The flow rate shall not be less than the water demand rate of the system. 5. All piping shall be inspected prior to backfill. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Val a 1, Senior Plans Examiner •