Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 October 20, 2008 RE: MECHANICAL Proiect Information I Building Permit: MEC2008 -00482 Construction Type: 5B Tenant Name: Vision World Occupancy Type: B Address: 9975 SW Frewing St. Occupant Load: NA Area: NA Stories: 2 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition. The submitted plans are approved subject to the following. 1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) 2. Each appliance shall be provided with a shutoff valve separate from the appliance. The shutoff valve shall be located in the same room and within six feet of the appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC 3. Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC 4. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC 5. Manufacturer's installation instructions shall be available on the jobsite at the time of inspection. 304.1 OMSC 6. Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC 7. Smoke detectors shall be installed in return air systems with a design capacity greater than 2000 cfm. Upon activation, the smoke detector shall shut down the air distribution system. Smoke detectors shall be connected to a fire alarm system or shall activate an audible and visible alarm at a constantly attended location. 606.2, 606.4 & 606.4.1 OMSC 8. Provide drawings for attachment of all equipment on the roof showing connection of any curb to roof and equipment to the curb. Provide calculations and drawings showing seismic attachment of all equipment with a weight 400lb or greater. Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 • 9. Inspector may require additional sway bracing at the final installation inspection. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, 1)4) ILVf.lrajE9 Dan Nelson, Senior Plans Examiner (503)718 -2436 dann @ tgard- or.com • •