Plans[Page Too Large for OCR Processing]
[Page Too Large for OCR Processing]
[Page Too Large for OCR Processing]
RECEIVED F p 201--col 33
R I S 3 50 5 v Se rn
� 15 2011 32c
CITY OFTIGARD
BUILDIN DIVISIO
• �� S1 YSTEM
SENSOR'
Selectable Output ` '
y
Horns, Strobes, and
Horn /Strobes
SpectrAlert' Advance selectable - output horns, strobes,
and horn /strobes are rich with features guaranteed to
cut installation times and maximize profits. SPECTRitilert o s E
Features The SpectrAlert Advance series of notification appliances is
• Electrically compatible with existing SpectrAlert products designed to simplify installations, with features such as plug in
Automatic selection of 12 or 24 -volt operation at 15 and 15/75 designs, instant feedback messages to ensure correct installation of
• candela individual devices, and 11 field - selectable candela settings for wall
and ceiling strobes and horn /strobes.
• Plug -in design
• Field selectable candela settings on wall and ceiling units: 15,15/75, When installing Advance products, first attach a universal mounting
30, 75, 95, 110, 115, 135, 150, 177,185 plate to a four -inch square, four -inch octagon or double -gang
• Same mounting plate for wall- and ceiling -mount units junction box.The two-wire mounting plate attaches to a single -gang
• Shorting spring on mounting plate for continuity check before junction box.
installation
Next, connect the notification appliance circuit wiring to the SEMS
• Tamper resistant construction terminals on the mounting plate,
• Outdoor wall and ceiling products rated from -40'F to 151°F
• Design allows minimal intrusion into the back box Finally, attach the horn, strobe or horn /strobe to the mounting plate
Horn rated at 88+ dbA at 16 volts by inserting the product's tabs in the mounting plate's grooves. The
• device will rotate into position, locking the product's pins into the
• Rotary switch for horn tone and three wlume selections mounting plate's terminals.The device will temporarily hold in place
• Outdoor products UL listed to UL 1638 (strobe) and UL 464 (horn) with a catch until it is secured with a captured mounting screw.
outdoor requirements
• Outdoor products NEMA 4X rated The SpectrAlert Advance series includes outdoor notification
Compatible with MDL sync module appliances. Outdoor strobes and horn /strobes (two wire and four
• wire) are available for wall or ceiling. Outdoor horns are available for
wall only. All System Sensor outdoor products are rated between
minus 40 degrees Fahrenheit and 151 degrees Fahrenheit In wet or
Agency Listings dry applications.
'1/ " 71751653 18e(nOw ivcoril
MEik
1 7)pp 166) 87(alrpav fv°MV
(04 7175165) 168 chvNy .%
(�� A��p I�1 7t1Stf6)1l9 man.c7.meU
a
• 54011 397.1572 1.15.1457-051
55S12
53593
SpectrAlert Advance Specifications
Architect /Engineer Specifications
General 1'
SpectrAiert Advance horns, strobes and horn/strobes shall mount to a standard 4 x 4 x 134-inch back box, 4 inch octagon back box or double gang back
box Two -wire products shall also mount to a single -gang 2 x 4 x 1 back box A universal mounting plate shall be used for mounting ceiling arx1 wall
products The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the
Sync•Circuit' Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate cn a nominal 12 Of 24 volts When
used with the Sync-Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between nine and 175 volts; 24 -volt rated notification
appliance circuit outputs shall operate between 17 and 33 volts Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit
from a regulated DC, or full-wave rectified, unfiltered power supply. Strobes and horn/strobes shall have field- selectable candela settings including 15,15/75, 30.
75,95, 110, 115, 135, 150,177,185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be
wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at
I Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system
Horn /Strobe Combination
The horn /strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.
The horn/strobe shall be wired as a primary- signaling notification appliance and comply With the Americans with Disabilities Act requirements for visible
signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and assooated
lens/reflector system The horn shall have three audibility options and an option to switch between a temporal three-pattern and a non - temporal (continuous)
pattern These options are set by a multiple position switch. On four -wire products, the strobe shall be powered independently of the sounder. The horn on
horn/strobe models shall operate on a coded or non -coded power supply.
Outdoor Products
SpectrAlert Advance outdoor horns, strobes and horn/strobes shall be listed for outdoor use by UL and shall operate between ntinus 40 degrees and 151
degrees Fahrenheit. The products shall be listed for use with a System Sensor outdoor/weatherproof bade box with half inch and three-four the inch conduit
entries
Synchronization Module
The module shall be a System Sensor Syncttcuit model MDL listed to UL 464 and shall be approved for fire protective service. The module shall synchronize
SpectrAlert strobes at 1Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn /strobe models over a
single pair of wires The module shall mount to a Orr /b x 41/4 x 21/4-ich back box The module shall also control two Style Y (class B) circuits or one Style Z
(class A) circuit The module shall synchronize multiple zones Daisy chairing two or more synchronization nodules together wit synchronize all the zones they
control. The module shall not operate on a coded power supply.
Physical /Electrical Specifications
Standard Operating Temperature 32•E to 1201 (0 to 49'C)
K Series Operating Temperature -40°F to 151 ( -40 to 66
Humidity Range 10 to 93% non - condensing (indoor products)
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12DC/FWRox regulated 24DC/F1ArR'
Operating Voltage Range' 8 to 175 V (12V nominal) a 16 to 33 V Q'4 nominal)
Input terminal wire gauge 12 to 18 AWG
Ceiling mount dimensions (including lens) 6.8 x 2.5 high (173 nrrn diameter x 64 mm high)
Wall mount dimensions (including lens) 561 x 47W x 75131(142 mrn L x 119 mm W x 64 mm D)
Horn dimensions 5.61. x4.7Wx 1.31)(142 mm Lx 119rnmWx33trmD)
Wall -mount back box skirt dimensions (BBS-2, BBSW -2) 5.91 x SOW x 2.21) (151 mm L x 128 mm W x 56 mm D)
Ceiling - mount back box skirt dimensions (BBSC - 2, BBSCW - 2) 7.1 diameter x 2.25' high (18O non diameter x 57 mm high)
Wall -mount weatherproof back box dimensions (SA -WBB) 5.71 x 5.1'W x 2.01)(145 mm L x 130 mm W x 51 mm D)
Ceiling -mount weatherproof back box dimensions (5A -WBBC) 7.1' diameter x 2.0" high (180 mm diameter x 51 mm high)
Wall -mount trim ring dimensions (TR -HS, TRW -HS) 5.71 x 4817W x 0350 (146 mm L x 122 W mm x 9 D mm)
Ceiling - mount trim ring dimensions (TRC -HS, TRCW -HS) 6.9 " diameter x 0.35 high (176 trim diameter x 9 mm high)
Notes:
1. Full Wave Rectified (F W11) voltage is a non - regulated, time varying power source that is used on some power supply and panel outputs
2. P,, S, PC, and SC products will operate at 12 V nominal only fa 15 and 15/75 cd
xecnr�r�
f
UL Currant Draw Data
UL Max. Strobe Current Draw (mA RMS) Ul Max. Horn Current Draw ImA RMS)
8 -17.5 Volts 16-33 Volts 8 -17.5 Volts 16 -33 Volts
Candela DC FWR DC FWR Sound Pattern dB DC FWR DC F WR
Standard 15' 123 128 66 71 Temporal High 57 55 69 75
Candela Range 15115 142 148 77 81 Temporal Medium 44 49 58 69
30' NA NA 94 96 Temporal low 38 44 44 48
75' NA NA 158 153 Non - temporal High 57 56 69 75
95' NA NA 181 176 Non - temporal Medium 42 50 60 69
110 NA NA 202 195 Non-temporal Low 41 44 50 50
115 NA NA 210 205 Coded High 57 55 69 75
High 135 NA NA 228 207 Coded Medium 44 51 56 69
Candela Range 150 NA NA 246 220 Coded Low 40 46 52 50
177 NA NA 281 251
185 NA NA 286 258
UL Max. Current Draw (mA RMS), 2 - wire Hom/Strobe, Standard Candela Range (15 - 115 col)
8 -17.5 Volts 16 -33 Volts
DClnput 15 15/75 15 15 /75 30 75 95 110 115
Temporal High 137 147 79 90 107 176 194 212 218
Temporal Medium 132 144 69 80 97 157 182 201 210
Temporal Low 132 143 66 77 93 154 179 198 207
Non - temporal High 141 157 91 100 116 176 201 221 229
Non - temporal Medium 133 145 75 85 102 163 187 707 216
Na i-terrlporal Low 131 144 68 79 96 156 182 201 210
FWR Input
Temporal High 136 155 88 97 112 168 190 210 218
Temporal Median 129 152 78 88 103 160 184 202 206
Temporal Low 129 151 76 86 101 160 184 194 201
Non-temporal High 142 161 103 112 126 181 203 221 229
Non - temporal Medium 134 155 85 95 110 166 189 208 216
Non- temporal Low 132 154 80 90 105 161 184 202 211
. UL Max. Current Draw (mA RMS), 2 -wire Hom /Strobe, High Candela Range (135 -185 cd)
16-33 Volts 16 - Volts
DClnput 135 150 177 185 FWR input 135 150 177 185
Temporal High 245 259 290 297 Temporal High 215 231 258 265
Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258
Temporal Low 232 251 282 292 Temporal Low 207 221 248 256
Non-terrporalHigh 255 270 303 309 Non - temporal High 233 248 275 281
Non - temporal Medium 242 259 293 299 Non- temporal Medium 219 232 262 267
Non - temporal Low 238 254 291 295 Non - temporal Low 214 229 256 262
Candela Doratinp Horn Tongs and Sound Output Data
For K series products used at low temperatures, listed candela Horn and Horn Strobe OutputidBAI
ratings must be reduced in accordance with this table. 24 Volt Nominal
Strobe Output (cdl 8 17.5
Switch Volts Volts Vohs Reverberant Anechok
Listed Candela Candela rating at -40*F Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR
15 1 Temporal High 78 78 84 84 88 88 99 98
15/75 Do not use below 32'F 2 Temporal Medium 74 74 80 80 86 86 96 96
30 3 Temporal Low 71 73 76 76 83 80 94 89
75 44 4 Non-temporal High 82 82 88 88 93 92 100 100
95 70 5 Non-temporal Medium 78 78 85 85 90 90 98 98
110 110 6 Non-temporal low 75 75 81 81 88 84 96 92
115 115 7' Coded High 82 82 88 88 93 92 101 101
135 135 8 Coded Medium 78 78 85 85 90 90 97 98
150 150 9' Coded Low 75 75 81 81 88 85 96 92
177 177 'Settings 7, 8, and 9 are not available on 2 -wire horn/strobe
185 185
ACISmrsaos
1
SpectrAlert Advance Dimensions ,
..r :s' Q e•
o+
11. 1 lb _
f � �
Wall -mount horn/strobes Ceiling -mo unt horn/strobes
r.s
7 1' . 751 0 a
5.06 -• 2.23 1 1 — - - -.
s.sb
II 7 op000\ . . , ' ' - -7 `10 . lo.
P 4 o et.r
e 0 e e ® i o s t � Q � � po e0 1 \ p O ' \\
` 0 -`
Wall back box skirt Ceiling back box skirt Wall weatherproof back box Ceiling weatherproof back box
SpectrAlert Advance Ordering Information
Model Description Model Description
Wall Hom/Strobes Ceiling Hom /Strobes (cont'd.)
P2R" 2 -wire Han/Strobe, Standard cd', Red PC4W 4 -wke Han/Strobe, Standard cd, White
P2RH' 2 -wire Horn/ Strobe, High cd. Red PC4WH 4-wire Hom/Strobe, High cd Wile
P2FK'° 2 -wire Han/Strobe, Standard cd Red, Outdoor Ceiling Strobes
P2R'IK° 2 -wire Horn/Strobe, High cd, Red, Outdoor SCR' Strobe, Standard cd Red
P2W 2 -wire Horn/Strobe, Standard cd White 5014' Strobe. High cd Red
P2WH' 2 -wire Horn/Strobe, High al, White SCRIP Strobe, Standard cd Red, Outdoor
P4R' 4 -wire Han/Strobe, Standard cd Red SCM' Strobe, High cd Red, Outdoor -
P4F1H' 4-wIre HorrVSirobe, High cd, Red SCW" Strobe, Standard cd, White
P4R C' 4-wire Horn/Strobe, Standard cd Red Outdoes SCWH" Strobe. High cd White
P4RHHK' 4 -wire Horn/Strobe, High cd, Red, Outdoor Horns
P4W• 4-wire Horn/Strobe, Standard cd White HR Horn, Red
P4WH' 4-wire Horn/Strobe, High cd, White HPo(° Han, Red, Outdoor
Wall Strobes HW Han, White
SR" Strobe, Standard cd, Red Accessories
SRH" Strobe, High cd Red BBS-2 Back Box Skirt, Wall, Red
SR P Strobe, Standard cd, Fed, Outdoor BBSW -2 Back Box Skirt, Wall, White
SRHK Strobe, High cd Red, Outdoor BBSC -2 Back Box Skirt, Wing, Red j
SW' Strobe, Standard cd, White BBSCW -2 Bads Box Skirt, Ceiling, White
SWH' Strobe, High cd, White TR-HS Trim Reg, Wall, Red
Ceiling Hom/Strobes TRW-HS Trim Ring, Wail White
PC2R• 2 -wire Horn/Strobe, Standard cd, Red T1* -HS Trim Rig, Ceiling, Red
PC2RH' 2 -wire Horn/Strobe, High cd, Red TRCW -HS Trim Fling, Ceiling, White +
PC2FIC 2 -wire Han/Strobe, Standard cd Red, Outdoor Notes
PC2RHil(' 2 -wire Horn/Strobe, High cd. Red, Outdoor • Add' -P' to model number for plain housing (no 'FIRE'marking on coved. eg,
PC2W" 2 -wire Horn/Strobe, Standard cd, White P2R-P.
F'C2WM" 2-wire Horn/Strobe, High <d, Write t Add"-SP" to model number for 'FuEGO'marWng on cover, e.g, P2R-SP
Red 4'Standard cd; refers to strobes that l dole 15,15/75,30, 75,95,110, and 115
PC4R 4-wire Horn/Strobe, Standard cd,
candela settingt'High cc refers to strobes that Include 135,150,177, and 185
PC4RH 4 -wire Horn/Strobe, High cd, Red candela settings
PC4RK 4-wire Horn/Strobe, Standard cd Red. Outdoor Al outdoor units ending In IC include a weatherproof back box
PC4IU(' 4 -wire Horn/Strobe, High cd, Red Outdoor o Add' -R` to model number for weatherproof replacement device (no back bat
Included).
,, ,..„ =1
3825 Ohio Avenue .St. Charles, IL 60174 noesewecewmmu /ea +a«ca
Phone 800- SENSOR2 • Fax 630. 377. 6495 anent po°""1pA "hest" °°"p°"'"""""° °o1stnaO c ■
A05 395905•MI•ROt.
i
1535 5•A/ Pkwy 32b p5 zot ► -o0 133
RECEIVED
- Global Project Values: 1
it i4 SILENT Project Name:IPACTRUST - 15350 SEQUOIAPI< Standby Hours 1 24 NOV 1 5 2011
KNIGH'I' Project ID:IPROFESSIONAL EYE Alarm Mins :1 5
Prepared By:1Gary Tauscher I Derating Factor 1 2 CITYOFTIGARD
5495 Power Expander Calculations Date:111 /9/2011 I Voltage Drop Warning BUILDING DIVISION
Version 02.18.09 Threshold %: 1 10 1
Panel ID: 15495 I Model: 5495 Power Expander Max NAC Current: 3.0 Amps
Location: 115350 SW SEQUOIA 2ND FL0 Volts: 24 VDC Max Panel Current: 6.0 Amps
Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ %Drop
Circuit Name Standby Alarm & Type 1000 Ft. One -Way Ohms EOL /oDrop
5495 5495 Pwr Module 1 1 0.075 1 0.205 _
NAC #1 5495 Circuit 1 0.000 0.000 #14 Solid 2.52 0 0.00 20.40 0.00%
NAC #2 5495 Circuit 2 0.000 0.000 #12 Solid 1.59 0 0.00 20.40 0.00%
NAC #3 5495 Circuit 3 0.000 0.000 #14 Solid 2.52 0 0.00 20.40 0.00%
NAC #4 5495 Circuit 4 0.000 0.878 #14 Solid 2.52 245 1.23 19.32 5.31%
Aux 5495 Aux Power Out 0.000 0.000 #14 Solid 2.52 _ 0 0.00 20.40 0.00%
Total Standby Current (Amps) 0.075 1.083 Total Alarm Current (Amps)
Standby Time In Hours 24 0.083 Alarm Time In Minutes / 60 (5 Mins)
Total Standby AH Required 1.800 _ 0.090 Total Alarm AH Required
Total Combined AH Required 1.89
Wire resistances are based upon an ambient temperature of 72 degrees F. Because of
Multiply By The Derating Factor 1.20 the minimal difference between solid and stranded wire no differential was made.
Minimum Battery AmpHours Required 2.27
1
C onfigure Circuits Print Page
. ' .
MI I_IN'I'
;:NI Circuit Configuration
r Project Information
Project Name: PACTRUST - 15350 SEQUOIAPKW #300 Project ID: PROFESSIONAL EY E
Prepared By: Gary Tauscher Date: 11/9/2011
Ckt. Number: NAC #1 Panel ID: 5495
Ckt. Name: 5495 Circuit 1 Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
System Sensor P2 /PC2 Horn /Strobe (115cd) 0.000 0.229 0.000 0.000
System Sensor S /SC Strobe (115cd) 0.000 0.210 0.000 0.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
0.000 0.000
Totals 0.000 0.000
Ckt. Number: NAC #2 Panel ID: 5495
Ckt. Name: 5495 Circuit 2 Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
System Sensor P2 /PC2 Horn /Strobe (115cd) 0.000 0.229 0.000 0.000
System Sensor S /SC Strobe (115cd) 0.000 0.210 0.000 0.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
0.000 0.000
Totals 0.000 0.000
Ckt. Number: NAC #3 Panel ID: 5495
Ckt. Name: 5495 Circuit 3 Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
System Sensor P2 /PC2 Horn /Strobe (115cd) 0.000 0.229 0.000 0.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
0.000 0.000
Totals 0.000 0.000
Ckt. Number: NAC #4 Panel ID: 5495
Ckt. Name: 5495 Circuit 4 Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
_ Standby _ Alarm Standby Alarm
2 System Sensor S /SC Strobe (115cd) 0.000 0.210 0.000 0.420
2 System Sensor P2 /PC2 Horn /Strobe (115cd) 0.000 0.229 0.000 0.458
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
0.000 0.000
Totals 0.000 0.878
Ckt. Number: Aux Panel ID: 5495
Ckt. Name: 5495 Aux Power Out Max Circuit Current: 3 Amps
Qty Device Current Draw Each Current Draw Total
Standby Alarm Standby Alarm
' SpectraAlert P2475 Horn /Strobe 0.000 0.148 0.000 0.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
Unused 0.000 0.000 0.000 0.000
0.000 0.000
Totals 0.000 0.000