Plans FP52 - ao1a 13 27-1 S kA/ (05 Pkwy 2c' - Global Project Values: It s SILENT Project Name: Health Net Standby Hours: 24 KNIGI IT Project ID:1 Alarm Mins: 5 Prepared By:IADAM SWEET Derating Factor:1 1.2 I 5495 Power Expander Calculations Date:I9 /13 /2010 I Voltage Drop Warning Threshold % : 10 I Panel ID: 15495(1) Model: Silent Knight 5495 Power Expander Max Circuit Current: 3 Amps Location: I1 ST FLOOR ELECT RM Volts: 24 VDC Max Panel Current: 6 Amps Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ %Drop Circuit Name /oDrop Standby Alarm & Type 1000 Ft. One -Way Ohms EOL 1 1.1 0.000 0.440 #14 Solid 3,19 220 1.40 19.78 3.03% 2 1.2 0.000 0.280 #14 Solid 3.19 205 1.31 20.03 1.80% 3 1.3 0.000 0.280 #14 Solid 3.19 160 1.02 20.11 1.40% 4 1.4 0.000 0.400 #14 Solid 3.109 145 0.90 20.04 1.77% Aux 5495(1) Aux Power Out 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% 5495 5495 Power Expander 0.075 0.205 1.400 (Amps) Total Output Power Required Total Standby Current (Amps) 0.075 1.605 Total Alarm Current (Amps) Standby Time In Hours 24 0.083 Alarm Time In Minutes / 60 (5 Mins) Total Standby AH Required 1.800 _ 0.134 Total Alarm AH Required Total Combined AH Required 1.93 wire resistances are based upon an ambient temperature of 72 degrees F. Because of Multiply By The Derating Factor 1.20 the minimal difference between solid and stranded wire no differential was made. Minimum Battery AmpHours Required 2.32 Panel ID: 15495(2) Model: Silent Knight 5495 Power Expander Max Circuit Current: 3 Amps Location: Volts: 24 VDC Max Panel Current: 6 Amps Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ o Ckt.# Circuit Name /oDrop Standby Alarm & Type 1000 Ft. One -Way Ohms EOL 1 5495(2) Circuit 1 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% 2 5495(2) Circuit 2 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% 3 5495(2) Circuit 3 0.000 0.000 #14 Solid 1.59 0.00 20.40 0.00% 4 5495(2) Circuit 4 0.000 0.000 #14 Solid 1.59 0.00 20.40 0.00% Aux 5495(2) Aux Power Out 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% 5495 5495 Power Expander 0.075 0.205 0.000 (Amps) Total Output Power Required Total Standby Current (Amps) 0.075 0.205 Total Alarm Current (Amps) Standby Time In Hours 24 0.083 Alarm Time In Minutes / 60 (5 Mins) Total Standby AH Required 1.800 _ 0.017 Total Alarm AH Required Total Combined AH Required 1.82 Wire resistances are based upon an ambient temperature of 72 degrees F. Because of Multiply By The Derating Factor 1.20 the minimal difference between solid and stranded wire no differential was made. Minimum Battery AmpHours Required 2.18 RECEIVED SEP 17 2010 CITY OF TIGARD BUILDING DIVISION El ' - Circuit Configuration Project Information Project Name: Health Net Project ID: 0 Prepared By: ADAM SWEET Date: 9/13/2010 Ckt. Number: 1 Panel ID: 5495(1) Ckt. Name: 4.1.1 Max Circuit Current: 3 Amps Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 8 GES3 -24WW 15 0.000 0.055 0.000 0.440 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.440 Ckt. Number: 2 Panel ID: 5495(1) Ckt. Name: 4.1.2 Max Circuit Current: 3 Amps Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 7 MT- 12/24 -R 0.000 0.040 0.000 0.280 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0 280 Ckt. Number: 3 Panel ID: 5495(1) Ckt. Name: 1.3 Max Circuit Current: 3 Amps Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 7 MT- 12/24 -R 0.000 0.040 0.000 0.280 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0,000 0.000 Totals 0.000 0.280 Ckt. Number: 4 Panel ID: 5495(1) Ckt. Name: 1.4 Max Circuit Current: 3 Amps Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 10 MT- 12/24 -R 0.000 0.040 0.000 0.400 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0 000 0.400 FIRE SYSTEM ACCESSORY Model 5495 Distributed Power Module In an emergency, (- • you need maximum power. E3 ,. g The 5495 Distributed Power Module by Silent Knight is the most powerful and cost - effective power supply available today. It delivers 6 amps of notification appliance circuit power and built -in synchronization for appliances from System Sensor®,Gentex®, AMSECO ®, Wheelock and Faraday — what you need to drive power- hungry components like ADA notification appliances. The 5495's advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies. And, ADA retrofits are easier and less expensive with the 5495 because it integrates into current systems without the costly investment in new components. For the most sophisticated and cost - effective notification power supply available, you need the 5495. Call Silent Knight today for more information at 1- 800 -446 -6444. Model 5495 • Independent trouble relay • Distributed Power Module • AC loss delay option shuts off power The 5495 is a 6 amp notification power to non - essential high- current expander that provides its own AC accessories like magnetic door power connection, battery charging holders circuit, and backup battery for use with • Built -in synchronization for fire and security controls such as the appliances from System Silent Knight Model 5208 Fire Control Sensor®,Gentex®, AMSECO ®, /Communicator. The 5495 is the cost- Wheelock and Faraday effective solution for powering • notification appliances required by the Stand alone operation Americans with Disabilities Act (ADA). • Lightweight design adds to ease of The 5495 has built -in ANSI cadence installation and reduces shipping pattern, which can upgrade older costs control panels that lack cadence • Operates with most polarized, UL capability. Listed notification devices Features • UL 864 & 1481 listed fc; • UL Listed for 6 amps of notification • CSFM approved power Model 5495 • Power supply's advanced switch • ANSI Cadence pattern output mode design reduces damaging capability built -in Distributed Power Module heat and manages power up to 50% Connection to Local Fire Control more efficiently than other systems The 5495 may be connected to a local 4.7kL2 end -of -line resistors provided. • Dip switches allow for easy fire control which utilizes Class A or Since the 5495 draws very little power reconfiguration Class B type notification circuits from the control, it is possible to • 24 VDC filtered output voltage operating between 9 and 32 VDC. The connect one 5495 to each notification control panel's notification circuit is circuit on the control panel and still • Four power - limited notification provide full supervision of the • outputs; 2 Class A or 4 Class B, or 1 connected to one of the inputs on the 5 495. The control panel's notification notification circuits all the way back to Class A and 2 Class B the control panel. • Additional continuous auxiliary circuit end-of-line resistor is also output connected across two terminals on the 5495, which provides supervision SILENT • 3 amps per output circuit between the 5495 and the fire control • 2 inputs; 2 Class B or 2 Class A panel. Polarized audible and /or visual ` KNIGHT • Ground fault detector /indicator notification devices are then connected to the 5495 signal circuits using the by Honeywell FIRE SYSTEM ACCESSORY Model 5495 Distributed Power Module 2 Supervision Current: Input The 5495 supervises a variety of Standby 75 mA voltage range: 9 - 32 VDC functions including: Alarm 175 mA Battery charging • Low AC power Auxiliary capacity: 33.0 AH • Low battery condition power circuit: 1 Ambient temp.: 32° to 120° F • Earth ground fault Notification 0° to 49° C • Auxiliary output power limit circuits: 4 Mechanical condition Output Dimensions: 12.25" W x 16" H x • EOL supervision trouble or configuration: 2 Class A (Style Z) 3" D (30.88 cm W power limited condition at an 4 Class B (Style Y) x 40.64 cm H x output (1 Class A & 7.62 D cm) When a trouble condition occurs, 2 Class B) Indicator Lights the 5495 creates a trouble Amps per AC power on : Green condition on the host control signal circuits to which it is connected. the output circuit: 3.0 (6.0 amps total) Battery trouble: Yellow 5495 still maintains the ability to be Notification Ground fault: Yellow activated by the host control. In circuit output: 20.4 to 27.3 VDC addition, the 5495 provides a Form @ 3.0 amps each, Aux trouble: Yellow C trouble relay output as an 4.7 k52 EOL Output alternative to using the notification resistor required troubles (1 -4): Yellow circuit trouble. on each Class B Approvals: Electrical Specification circuit UL: 864 & 1481 No. of inputs 2 NFPA: 72 AC input: 120 VAC at 2 amps Output: 24 VDC at 6 amps Input CSFM configuration: 2 Class B or 2 Class A Model 5495 Block Diagram Signal Circuit Output Signal 1 Signal 1 Input Distributed Signal 2 Signal Circuit Output Signal 2 Power Input Module 5495 Signal 3 (Optional) Signal 4 120 VAC Aux. Power i Trouble Output Local Fire Control (Alternative to notification circuit trouble.) SILENT This document is not intended to be used for installation purposes. We try to MADE IN AMERICA Ti KNIGHT keep our product information up -to -date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are FORM# 350395 Rev B, 12/05 subject to change without notice. For more information, contact Silent Knight by Honeywell 7550 Meridian Circle Suite 100, Maple Grove, Mn 55369 -4927. Copyright © 2005 Silent Knight Phone: (800) 328 -0103, Fax: (763) 493 -6475. wheelo ■ I lilillU INC. FIRE ALARM SYSTEMS m � • CSFM: 7125-0785:122 SERIES MT and MT STROBE MULTITONE ELECTRONIC APPLIANCES Description Wheelock's Series MT and MT Strobe Multitone electronic appliances offer _ - a choice of eight (8) nationally and internationally recognized alerting sounds: Horn, Bell, March Time Horn, Code -3 Tone, Code -3 Horn, Slow t l I I Whoop, Siren or Hi /Lo Tone. The Code -3 horn and tone patterns are engineered to comply with NFPA/ANSI Temporal Pattern specifications without requiring additional equipment. With MT and MT Strobe appliances, one alarm appliance meets most of your signaling needs. Synchronized strobe versions are available. The MT Strobes are designed for ADA applications with maximum performance, reliability and cost - effectiveness while meeting or exceeding the latest requirements of NFPA 72 (the National Fire Alarm Code), ANSI - 117.1 (the American National Standard For Accessible and Usable Buildings and Facilities) and UL Standard 1971 (Standard for Signaling Devices for the Hearing Impaired). MT Strobes, when properly specified and installed in accordance with NFPA/ANSI Standards, can provide the Equivalent Facilitation allowed underADAAccessibility Guidelines (ADAAG General Section 2.2) by meeting or exceeding the illumination which results from the ADA specified strobe intensity of 75 candela at 50 feet. This is an illumination of 0.030 lumens per square foot. SERIES MT WITH STROBE Each MT and MT Strobe appliance has two user selective sound output levels: STANDARD dBA and HIGH dBA. Non - strobe versions provide selectable voltage capability in one unit, 12VDC or 24VDC, filtered or FWR. Strobe versions are specific for either 12VDC or 24VDC and may be used with filtered or unfiltered (full- wave - rectified) input voltages. Separate input terminals are available, shunt wires are provided to enable both tone and strobe to operate simultaneously from a single input. • The Multitone Strobe appliances are UL Listed for indoor use, ceiling and wall mount, under Standard 1971 (Signaling Devices for the Hearing Features Impaired) and Standard 464 (Audible Signal Appliances), and use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan® lens to • Approvals include: Underwriters Laboratories UL 1971 and UL 464 provide maximum reliability for effective visible signaling. Options include Listings, FCC Part 15, Factory Mutual (FM), California State Fire LS, LSM, MS and IS Series which are Listed at 15, 15/75. 30 and 75 Marshal (CSFM), New York City (MEA) and Chicago (BFP), European candela intensity. Also available with the WM (117cd) strobe model which Community (CE), approvals on all models. is UL 1638 Listed for indoor or outdoor applications. The LSM 15/75 • Designed to meet or exceed NFPA /ANSI Standards and ADA candela wall mounted strobes are Listed at 15 candela under UL 1971 and Accessibility Guidelines. Meet OSHA 29 Part 1910.165. meet 75 candela intensity on axis for ADA guidelines with low current draw. • MT & MT -WM Strobe model available for outdoor installation requiring weatherproof devices. In private mode location where UL 1971 strobes are not required the MT -WM strobe model is UL 1638 Listed at 117 cd and is designed for mounting indoors or outdoors. • Series MT appliances have IN and OUT wiring terminations that accept two #12 to #18 American Wire Gauge (AWG) wires at each terminal. Inputs are polarized for compatibility with standard reverse polarity type supervision. • One alarm appliance with (8) eight selective signals to provide superior sound penetration for various ambient and wall conditions with two field selectable sound output levels. • Code -3 Horn and Tone meet ANSI /NFPA temporal pattern for standard •. emergency evacuation signaling. • • Audible and strobe can operate from a single NAC circuit with any of the (8) eight audible sounds. I • MT Strobe models available with 15, 15/75, 30 and 75 candela ratings for , independent or single input activations and synchronized strobe design. • Wheelock's patented Series LS, LSM, MS, IS and synchronized SL, SLM offer fire alarm system designers, specifiers and installers the industry's widest selection of UL 1971 Listed strobe products. • Series MT Strobe multitone electronic appliances equipped with SL /SLM synchronized strobes, when used in conjunction with Wheelock SM /DSM sync modules, produce a synchronized strobe flash for compliance with ADA guidelines concerning photosensitive epilepsy. SERIES MT WITHOUT STROBE SERIES MT STROBE WITH 106 • Selectable input voltage on non - strobe versions. Strobe versions are • factory set for either 12 or 24VDC, with wide- Listed voltage range, filtered (DC) and FWR. • Mounts to either 4" square or double gang boxes (important for retrofit installations). Attractive flush or surface mounting. Copyright 1998 Wheelock, Inc. All rights reserved. • No additional trimplate required for flush mounting. • NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. 41 WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. . Alarm Tones ALARM TONES TONE PATTERN DESCRIPTION HORN BROADBAND HORN (Continuous) BELL 1560 Hz MODULATED (0.07 sec. ON /Repeat) MARCH TIME HORN HORN (0.25 sec. ON/0.25 sec. OFF /Repeat) CODE -3 HORN HORN (ANSI S3.41 Temporal Pattern) CODE -3 TONE 500 Hz (ANSI S3.41 Temporal Pattern) SLOW WHOOP 500 -1200 Hz SWEEP (4.0 sec. ON /0.5 sec. OFF /Repeat SIREN 600 -1200 Hz SWEEP (1.0 sec.ON /Repeat) HI /LO 1000/800 Hz (0.25 sec. ON /Alternate) General Notes: • Strobes are designed to flash at 1 flash per second minimum from 20 -31VDC (for 24VDC models) or 12- 15.6VDC (for 12VDC models). Note that ADA guidelines presently specify a flash rate of 1 to 3 flashes per second and NFPA -72 (1996) specify a flash rate of 1 to 2 flashes per second. • All candela ratings represent minimum effective Multitone Strobe intensity based on UL 1971. • MT Strobe models are UL 1971 Listed for indoor use with a temperature range of 32 °F to 120 °F (0 °C to 49 °C) and maximum humidity of 85 %. All MT and MT4 with WM or WH strobe models for outdoor use are Listed For -31°F to 150 °F ( -35 °C to 66 °C) and maximum humidity of 95 %. Specifications Table 1: dBA and Current Ratings for Multitone Signals Without Strobes Typical Anechoic' Rated Reverberant dBA' Input Current Input Current dBA at 10 Feet at 10 Feet Per UL 464 Tone AMPS @ 24VDC AMPS @ 12VDC At Nominal At Minimum At Nominal - Input Voltage Input Voltage Input Voltage HI STD HI STD HI STD HI STD HI STD • Horn 0.040 0.023 0.100 0.020 101 95 88 82 91 85 Bell 0.014 0.012 0.031 0.010 94 89 82 75 85 79 March Time Horn 0.040 0.023 0.100 0.020 101 95 85 79 88 82 Code -3 Horn 0.040 0.023 0.100 0.020 101 95 85 75 85 79 Code -3 Tone 0.028 0.017 0.060 0.015 97 92 79 75 82 75 Slow Whoop 0.048 0.026 0.100 0.025 101 96 88 82 88 82 Siren 0.036 0.023 0.082 0.020 100 95 85 82 88 82 HI /LO 0.020 0.014 0.044 0.012 95 90 82 79 85 79 Table 2: dBA and Current Ratings for Audible Portion of Multitone Si nals With Strobes Typical Anechoic' Rated Reverberant dBA' Input Current Input Current dBA at 10 Feet at 10 Feet Per UL 464 Tone AMPS @ 24VDC AMPS @ 12VDC At Nominal At Minimum At Nominal Input Voltage Input Voltage Input Voltage HI STD HI STD HI STD HI STD HI STD Horn 0.040 0.023 0.100 0.020 99 93 85 79 88 82 Bell 0.014 0.012 0.031 0.010 92 87 79 75 82 75 March Time Horn 0.040 0.023 0.100 0.020 99 93 82 75 85 79 Code -3 Horn 0.040 0.023 0.100 0.020 99 93 79 75 82 75 Code -3 Tone 0.028 0.017 0.060 0.015 95 90 75 70 ' 79 73 • Slow Whoop 0.048 0.026 0.100 0.025 99 94 82 75 85 79 Siren 0.036 0.023 0.082 0.020 98 93 82 75 85 79 • HI /LO 0.020 0.014 0.044 0.012 93 88 79 75 82 75 - 1. Anechoic dBA is measured on axis in a non - reflective (free field) test room using fast meter response. For peak dBA (measured with peak meter response), add 5 dBA to typical anechoic values shown in Table 1 and 2. 2. Reverberant dBA is a minimum UL rating based on sound power measurements in a reverberant test room. "A CAUTION: This setting is acceptable only for general signaling (non -fire alarm) use. Use the "high" dBA setting with this lone or use a different tone for public mode fire alarm service. Wiring Diagrams (for all models) • MT Signal Audible signal and strobe operate independently Audible signal and strobe operate in unison. Red and black shunt -wires are supplied. FROM + + TO FROM PRECEDING + + TO NEXT FROM + + PRECEDING _ NEXT SIGNAL AUDIBLE OR AUDIBLE OR PRECEDING TO NEXT • SIGNAL OR - I, OR EOLR FACP - II - ii — EOLR SIGNAL OR RED SIGNAL OR rACP FACP I■ — EOLR • _ ii S FROM PRECEDING + + TO NEXT 9 Al STROBE OR j STROBE OF FACP I' III - EDER STROBE AUDIBLE S GNAT _ `i ■ `l STROBE AUDIBLE Ordering Information MODEL ORDER INPUT RATED AVERAGE' MOUNTING" NUMBER CODE VOLTAGE CANDELA STROBE CURRENT (AMPS)_ OPTIONS — MT- 12/24 -R 5023 12/24 - -- - - -- D,E,F,G,L,M,O,R_ _ MT4 -115 -R 6223 115 VAC - -- - - -- D,E,J,K,O,R,Z MT -24 -LS -VFR 5183 24 15 .074 D,E,F,G,L,M,O,R MT -24 -SL -VFR 6306 24 15 .096 D,E,F,G,L,M,O,R MT -24 -LSM -VFR 5182 24 15/75 .100 D,E,F,G,L,M,O,R MT -24 -SLM -VFR 6307 24 15/75 .138 D,E,F,G,L,M,O,R MT -24 -MS -VFR 5321 24 30 .124 D,E,F,G,L,M,O,R MT -24 -IS -VFR 5355 24 75 .200 D,E,F,G,L,M,O,R MT4- 115 -WH -VFR "•" 6224 115 VAC 15 .060 D,E,J,K,O,R,Z MT -24 -WM- VFR'" 5025 24 117 .088 D,E,F,G,L,M,O,R MT -12 -LS -VFR 5383 12 15 .155 D,E,F,G,L,M,O,R MT -12 -MS -VFR 5384 12 30 .227 D,E,F.G.L.M,O,R MT- 12- LSM -VFR 5683 12 15/75 .210 D,E,F,G,L,M,O,R SYNC MODULES " " "" SM- 12/24 -R 6369 12 or 24 .014/.025 E,N DSM- 12/24 -R 6374 12 or 24 .020/.038 W NOTE: If the strobe and audible operate on the same circuit, add the strobe current from above The letters SL and SLM denote synchronized models. to the proper current from Table 2. • Average current per actual Wheelock Production testing at 12 & 24VDC nominal voltage. For rated average, peak and inrush currents across the listed voltage ranges for both filtered DC and full waved rectified (FWR), see the Installation Instruction for this product series or Wheelock's current catalog. •• For additional information, please refer to Data Sheet #S7000 for mounting options. •"• Listed for UL 1638 only. • SM Sync Modules are rated for 3.0 amperes at 12/24 VDC; DSM Dual Circuit Modules are rated for 3.0 amperes per circuit. The maximum number of interconnected DSM modules is twenty (20). Refer to Data Sheet #53000. MT -12/24 models can be used wth Wheelock's model RSSP -24110 W -FR 110 candela strobe plate appliance. Suffix: V = vertical lens: H = horizontal lens: F = fire lettering; R = red plate. A WARNING: CONTACT WHEELOCK FOR THE CURRENT "INSTALLATION INSTRUCTIONS" (P82475) AND "GENERAL INFORMATION" SHEET (P82380) ON THESE PRODUCTS. THESE DOCUMENTATIONS DO UNDERGO PERIODIC CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING: • TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM PRIMARY AND SECONDARY POWER SOURCES. • FUSE RATINGS ON NAC CIRCUITS TO HANDLE MAXIMUM INRUSH OR PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS. THE TIME DURATION OF THE MAXIMUM STROBE INRUSH OR PEAK CURRENT IS 2 MILLISECONDS FOR LS /LSM /MS MODELS AND 4 MILLISECONDS FOR IS MODELS. • COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW. • THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR RATED INPUT VOLTAGE RANGE. • INSTALLATION OF 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS. • INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES. • USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBE ON CODED OR INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBE MAY NOT FLASH. • FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER INSTALLATION, APPLICATION, AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. • CONDUCTOR SIZE (AWG) LENGTH AND CAPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS. Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters' Laboratories (UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). Architects and Engineers Specifications The notification appliance shall be a Wheelock Series MT audible /visual appliance or equivalent. Notification appliance shall be electronic and use solid state components. Electromechanical alternatives are not approved. Each electronic appliance shall provide eight (8) field selectable alarm tones. The tones shall consist of: TONE, HORN, MARCH TIME HORN, CODE -3 HORN, CODE -3 • TONE, SLOW WHOOP, SIREN and HI /LO. Tone selection shall be by durable dip switch assembly and not clips or jumpers. The audible and the strobe shall be able to operate from a single NAC circuit while producing any of these tones. The appliance shall provide two output sound levels: STANDARD and HIGH dBA. The HIGH dBA setting shall provide a minimum 5 dBA increase in sound output at nominal voltage. The HIGH anechoic dBA measurement at 10 feet at the alarm HORN SETTING shall be 101 dBA minimum for MT and 99 dBA minimum for MT Strobes, at nominal voltage. Operating voltages shall be either 12VDC or 24VDC using filtered power or unfiltered power supply (full- wave - rectified). All models shall have provisions for standard reverse polarity type supervision and IN /OUT field wiring using terminals that accept #12 to #18 AWG wiring. Combination audible /visual appliances shall incorporate a Xenon flashtube enclosed in a rugged Lexan' lens or equivalent with solid state circuitry. Strobe shall meet UL 1971 and produce a flash rate of one (1) flash per second minimum over the Listed input voltage (20VDC- 31VDC) range. The strobe intensity shall be rated per UL 1971 for 15, 15/75, 30, 75 or 110 Candela (by using the RS5P 110cd strobe /plate). The LSM 15/75 candela strobe shall be specified when 15 candela UL 1971 Listing with 75 candela intensity on- axis is required (e.g., ADA compliance). Series SL /SLM Models shall incorporate circuitry for synchronized strobe flash and shall be designed for compatibility with Wheelock: SM and/or DSM Sync Modules. The strobes shall not drift out of synchronization at any time during operation. If the module fails to operate (i.e., contacts remain closed), the strobes shall revert to a non - synchronized default flash rate. The Sync Module shall be designed and available in two versions; the SM 12/24 for control of a Class B circuit; and a dual output version, the DSM -12/24 for control of either Class A or multiple Class B circuits. Rated average current requirement for the SM 12/24 shall be .014/.025 amperes; the DSM 12/24 shall be .020/.038 amperes. A single circuit SM Sync Module shall be capable of handling a 3 ampere load @ 12 or 24 VDC; dual circuit DSM Sync Modules shall be capable of handling a load of 3 amperes per circuit @ 12 or 24 VDC. All UL 1971 Listed strobe appliances shall be verified to meet FCC Part 15, Class B and incorporate low temperature compensation to insure the lowest possible current consumption. Strobe activation shall be via independent input or from the same input circuit as the audible. The combination audible /visual appliances may be installed indoors and surface or flush mounted. They shall mount to standard electrical hardware requiring no additional trimplate or adapter. The aesthetic appearance shall not have any mounting holes or screw heads visible when the installation is completed. The appliance shall be finished in a textured red color. The audible appliance may be installed indoor or outdoor with the proper backbox. The WM and WH Strobes are UL 1638 Listed and are for outdoor use. Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock, Inc. Standard Terms and Conditions. 3 YEAR WARRANTY Distributed By: NATIONAL SALES OFFICE 1 -800- 631 -2148 Canada 800 - 397 -5777 E -mail: Info @wheelockinc.com � �i /� http: //www.wheelockinc.com Member WHEELOCK, INC. • 273 BRANCHPORT AVENUE • LONG BRANCH, N.J. 07740 • 732 - 222 -6880 • FAX: 732 - 222 -8707 S2000 Rev. 6/98 [Page Too Large for OCR Processing] [Page Too Large for OCR Processing]