Specifications FP520tl © (9°3` I 100 S r , ✓ llliy° - L Advanced Security & Fire 2218 NE Sunrise Lane, Hillsboro OR 97124 (503) 519 -4550 Fax (503) 357 -8157 RECEIVED March 13` 2011 MAR 18 ?011 Fire Alarm Operational Matrix CITY OF BUILDING DIVISION General Overview The fire alarm system will have battery back up to sustain it in the case of an AC power failure. Alarm system will have dual phone lines, a primary and secondary, if the primary fails the secondary will transmit signals to central station. All functions of the fire alarm system are supervised, (AC power, low battery, phone line integrity, and all alarm circuits. ) Fire alarm troubles and alarms are both transmitted to the central station and annunciated locally at the keypad. Specific Operation • Troubles are annunciated at keypad in English text, at the same time they are transmitted to the central station. Operator at central station will call a predetermined response list to notify of trouble. Advanced Security & Fire will be notified of system troubles at the same time. • Alarms will be transmitted to the central station as well as annunciated locally. Central station will notify 911 of fire alarm, and then call premises to try and verify alarm. Response list will be called to notify users of alarm. • Alarms can be silenced at the keypad by pressing fire silence button. • Fire system will be in trouble until fire alarm system is reset by pressing the fire reset button. • Equipment room smoke detector monitors for smoke in equipment room, and sprinkler water flow monitors for water flow in fire sprinkler system, both will trigger a fire alarm. • Upon trigger of fire alarm by smoke detector, sprinkler water flow, or manual fire pull station alarm will be annunciated locally via outside bell and central station will be signaled Company Information Advanced Security & Fire is located in Hillsboro, Oregon and is owned and operated by David Moravik. I have been in the alarm industry since 1981 and licensed as a journeyman low voltage electrician since 1984, ( license # 611LEA ). My state of Oregon electrical license is ( CLE -8 ). Advanced Security & Fire is registered with the state of Oregon contractor's board (contractor's board # 166176). We are a member of the NFPA, and the local fire and burglary alarm association. Central Station Information Advanced Security & Fire monitors its alarm systems through Central Station Monitoring in Estacada, Oregon. They are certified to monitor all alarm system types. Phone # is ( 503- 630 -2896 ). Sincerely, Advanced Security & Fire rp5zotC - 3 - Global Project Values: Ml=MMI -4111 s o SILENT Project Name: Dow ArgoSciences Bid. C I Standby Hours: 60 1 KNIGHT Project ID:1 I Alarm Mins: 5 1 Prepared By:lAdvanced Security & Fire l Derating Factor: 1.2 1 5700 Calculations Date: 13/14/2011 1 Voltage Drop Warning Threshold % :1 10 Panel ID: 15700 Model: 5700 Add. Fire Alarm Control Panel Max NAC Current: 2.5 Amps Location: 'Electrical Room 1 Volts: 24 VDC Max Panel Current: 2.5 Amps Ckt.# Circuit Name Qty Current Draw Wire AWG Ohms Per Length(ft) Actual Volts %Drop Alarm & Type 1000 Ft. One -Way Ohms EOL p 5700 5700 CTRL Panel 1 0.200 0.325 SLC -DEV Addrsbl SLC Devices 3 0.002 0.002 5860 LCD Remote Annunc 1 0.020 0.025 5824 Serial /Parallel Module 0.000 0.000 5496 Power Expander 1 0.010 0.010 5865 -4 LED Annunciator (4G) 0.000 0.000 5865 -3 LED Annunciator (3G) 0.000 0.000 5880 LED Driver Module 0.000 0.000 Other 0.000 0.000 Other 0.000 0.000 SD -Duct Duct Hsg w /Relay 0.000 0.000 5883 Relay Module 0.000 0.000 PGM -I/0 #1 Notification Appl Circuit 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% PGM -I /O #2 Notification Appl Circuit 0.000 0.000 #12 Solid 1.59 0.00 _ 20.40 0.00% Total Standby Current (Amps) 0.232 0.362 Total Alarm Current (Amps) Standby Time In Hours 60 0.083 Alarm Time In Minutes i 60 (5 Mins) Total Standby AH Required 13.899 0.030 Total Alarm AH Required Total Combined AH Required 13.93 Command Shortcuts Multiply By The Derating Factor 1.20 Minimum Battery AmpHours Required 16.71 Configure Circuits Print Page — Global Project Values: SILENT Project Name:IDow AgroSciences Bld. C Standby Hours: 24 I KNIGHT Project ID:1 I Alarm Mins: I 5 Prepared By: Advanced Security & Fire Derating Factor: 1.2 5496 Power Expander Calculations Date: 13/14/2011 I Voltage Drop Warning Version 02.24.09 Threshold °6 :I 10 Panel ID: 5496 Model: 5496 Power Expander Max NAC Current: 3.0 Amps Location: By Sprinkler Riser I Volts: 24 VDC Max Panel Current: 6.0 Amps Current Draw Wire AWG Ohms Per Length(ft) Actual Volts Part.# Description Qty %Drop Standby Alarm & Type 1000 Ft. One -Way Ohms EOL 5496 5496 Pwr Module 1 1 0.040 0.160 NAC #1 Notification Appl Circuit 0.000 1.315 #14 Solid 2.52 300 1.51 18.41 9.75% NAC #2 Notification Appl Circuit 0.000 1.152 #14 Solid 2.52 285 1.44 18.75 8.11% NAC #3 Notification Appl Circuit 0.000 0.655 #14 Solid 2.52 411 2.07 19.04 6.65% NAC #4 Notification Appl Circuit 0.000 1.361 _ #12 Solid 1.59 427 1.36 18.55 9.06% Total Standby Current (Amps) 0.040 4.643 Total Alarm Current (Amps) Standby Time In Hours 24 0.083 Alarm Time In Minutes / 60 (5 Mins) Total Standby AH Required 0.960 _ 0.387 Total Alarm AH Required Total Combined AH Required 1.35 Command Shortcuts Multiply By The Derating Factor 1.20 Minimum Battery AmpHours Required 1.62 Configure Circuits 1 Print Page J SILENT ce KNIGHT Circuit Configuration - Project Information Project Name: Dow AgroSciences Bld. C Project ID: 0 . Prepared By: Advanced Security & Fire Date: 3/14120/1 Ckt. Number: NAC #1 Panel ID: 5496 Ckt. Name: Notification Appl Circuit USe:rNotification Appl Circuit ■ Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 3 Wheelock RSS /RSSP Strobe (15cd) 0.000 0.090 0.000 0.270 3 Wheelock HS Horn /Strobe (1575cd) 0.000 0.075 0.000 0.225 1 Wheelock HS Horn /Strobe (30cd) 0.000 0.084 0.000 0.084 y Wheelock HS Horn /Strobe (110cd) 0.000 0.184 0.000 0.736 0.000 0.000 Totals 0.000 1.315 Ckt. Number: NAC #2 Panel ID: 5496 Ckt. Name: Notification Appl Circuit Use: Notification Appl Circuit Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 5 Wheelock RSS /RSSP Strobe (15cd) 0.000 0.090 0.000 0.450 Wheelock HS Horn /Strobe (30cd) 0.000 0.084 0.000 0.000 2 Wheelock HS Horn /Strobe (15/75cd) 0.000 0.075 0.000 0.150 3 Wheelock HS Horn /Strobe (110cd) 0.000 0.184 0.000 0.552 0.000 0.000 Totals 0.000 1.152 Ckt. Number: NAC #3 Panel ID: 5496 Ckt. Name: Notification Appl Circuit , U se: N otification Appl Circuit V I Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 4 Wheelock RSS /RSSP Strobe (15cd) 0.000 0.090 0.000 0.360 1 Wheelock HS Horn /Strobe (75cd) 0.000 0.136 0.000 0.136 1 Wheelock HS Horn /Strobe (15/75cd) 0.000 0.075 0.000 0.075 1 Wheelock HS Horn /Strobe (30cd) 0.000 0.084 0.000 0.084 Wheelock HS Horn /Strobe (110cd) 0.000 0.184 0.000 0.000 - Totals 0.000 0.655 Il r SILENT e KNIGHT Circuit Configuration - Project Information Project Name: Dow AgroSciences Bld. C Project ID: 0 . Prepared By: Advanced Security & Fire Date: 3/14/2011 Ckt. Number: NAC #4 Panel ID: 5496 Ckt. Name: Notification Appl Circuit Use: Notification Appl Circuit v Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 4 Wheelock RSS /RSSP Strobe (15cd) 0.000 0.090 0.000 0.360 3 Wheelock HS Horn /Strobe (75cd) 0.000 0.136 0.000 0.408 3 Wheelock HS Horn /Strobe (15/75cd) 0.000 0.075 0.000 0.225 2 Wheelock HS Horn /Strobe (110cd) 0.000 0.184 0.000 0.368 0.000 0.000 Totals 0.000 1.361 . FJ5 - Lc t1- d-U-r' 341 COOPER Notification 273 Branch port Ave. • Long Branch, N.J. 07740 Thank you for using our products. (800) 631 -2148 INSTALLATION INSTRUCTIONS www.coopernotification.com EXCEDER 2 -WIRE FIELD SELECTABLE HORN, STROBE, AND HORN /STROBE APPLIANCES ■ (WALL MOUNT) Use this product according to this instruction manual. Please keep this instruction manual for future reference. GENERAL: The Cooper Notification Series Exceder HN horn, ST strobe, and HS horn /strobe appliances are designed for easy installation. All models are for 12V or 24V operation. The appliance comes in two main parts. The universal mounting back plate allows the wall appliance to be mounted to a single -gang, double -gang, or four square backbox. Appliance wiring is then connected to the mounting back plate. This allows a continuity check of the entire NAC circuit before any appliances are attached. It also allows the appliances to be installed after all finish work has been completed. The installer can snap or install the appliances when all other work is complete. • WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, CANDELA SETTING, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. SPECIFICATIONS: Table 1: Models and Settings Model Regulated Voltage Range Limit Strobe Horn Current Draw Mounting Voltage per UL/ULC (cd) See Table 12 (VDC) 8.0 -17.5 15/15 -75 ST 24 (VDCNRMS) 16.0 -33.0 15/15 - 75/30/75/95/110 /135/185 3 Wall 12 (VDC) 8.0 -17.5 15/15 -75 HS 24 (VDCNRMS) 16.0 -33.0 15/15 - 75/30/75/95/110 /135/185 X 4 Wall 12 (VDCNRMS) 8.0 -17.5 HN 24 (VDCNRMS) 16.0- 33.0 "' X 5 Wall STROBE AND HORN STROBE APPLIANCES: Cooper Notification's Exceder Multi - Candela Strobes can provide a non - synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP), or provide a synchronized strobe appliance when used in conjunction with an FACP that incorporates the Cooper Notification sync protocol, a Cooper Notification Sync Module, or the Cooper Notification Power Supply. The Strobe Appliances are UL Listed under Standard 1971 (Signaling Devices for the Hearing Impaired) for indoor Fire Protection Service. They are listed for indoor use only. Cooper Notification's Exceder Horn Appliances provide a selectable Continuous or Code 3 Horn tone when connected directly to the Fire Alarm Control Panel (FACP). They can also provide a synchronized Code 3 Horn tone when used in conjunction with an FACP that incorporates the Cooper Notification sync protocol, a Cooper Notification Sync Module, or the Cooper Notification Power Supply. The Horn Appliances can be field set for High (HI), Medium (MED), or Low (LO) dBA sound output. The Horn Appliances are UL Listed under Standard 464 for Audible Signal Appliances. They are listed for indoor use only All models are designed for use with either filtered DC (VDC) or unfiltered Full- Wave - Rectified (VRMS) input voltage. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a FACP. The ST Strobe, HS Horn /Strobe, and the HN Horn are for 12V or 24V operation. Strobe devices for 12V are only approved by UL to be set at 15cd, and 15 -75cd, and only to be powered by DC not FWR. NOTE: The Code 3 temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1 -1/2 off and repeat) is specified by ANSI and NFPA 72 for standard emergency evacuation signaling. The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose. Table 2A: HN and HS dBA Sound Output Reverberant Dba Per UL 464 Anechoic Per CAN /U LC- S525 -07 Description Volume HN and HS at 12V HN and HS at 24V HN and HS at 12V HN and HS at 24V 8.OV 12.0V 17.5V 16.0V 24.OV 33.0V 8.OV 12.OV 17.5V 16.0V 24.0V 33.0V High 83 88 91 91 93 96 89 93 96 95 99 101 Continuous Medium 79 82 86 86 89 92 85 89 92 91 95 97 Horn Low 72 76 79 78 82 85 79 84 87 86 90 92 High 80 84 86 86 89 91 87 93 96 95 99 101 Code 3 Medium 74 78 82 81 85 84 85 89 92 91 95 97 Horn Low - 68 72 76 74 78 80 79 84 87 86 90 92 Table 2B: ULC Directional Characteristics Axis dBA Angle i t Horizontal -3dBA 80 degrees left and right -6dBA 85 degrees left and right Vertical -3dBA 80 degrees up and down - 6dBA 90 degrees up and down Copyright 2009 Cooper Wheelock Inc., dba Cooper Notification. All rights reserved. P85060 C Sheet 1 of 6 CURRENT DRAW: Table 3: ST Strobe Current Draw (Amps) Strobe Candela Settings (cd) 16.0 -33.0 Volts 8.0 -17.5 Volts Current 15 15/75 30 75 95 110 135 . 185 Current 15 15/75 DC 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 DC 0.110 0140 FWR 0.083 0.105 0 105 0.185 0.223 0.256 0.328 0.372 FWR Table 4: HS Horn /Strobe Current Draw (Amps) Strobe Candela Settings (cd) Current Horn 16.0 -33.0 Volts 8.0 -17.5 Volts Settings 15 15/75 30 75 95 110 135 185 15 15/75 High' 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159 DC Medium' 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153 Low* 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148 High* 0.131 0.138 0.138 0.216 0.258 0.289 0.357 0.384 FWR Medium' 0.112 0.126 0.126 0.201 0.247 0.272 0.340 0.378 - - Low' 0.106 0.120 0.120 0.196 0.235 0.265 0 331 0.375 - • Current Draw is the same for the Continuous Horn and Code 3 Horn Settings. Table 5: HN Horn Current Draw (Amps) Current Horn 8.0-17.5 Volts 16.0 -33.0 Volts Settings High* 0.047 0.064 • DC Medium` 0.026 0.044 Low` 0.017 0.022 High* 0.073 0.086 FWR Medium' 0.048 0.074 Low` 0.036 0.054 • Current Draw is the same for the Continuous Horn and Code 3 Horn Settings. NOTE: Candela and Horn Setting will determine the current draw of the product. When calculating the total currents use Tables 3 -5 to determine the highest value of RMS current for an individual appliance, then multiply these values by the total number of appliances. Be sure to add the currents for any other appliances, including audible signaling appliances powered by the same source, and to include any required safety factors. NOTE: The maximum number of strobes on a single notification appliance circuit shall not exceed 50. NOTE: These notification appliances are UL Listed as "Regulated ". They are intended to be used with Fire Alarm Control Panels (FACPS) whose notification circuits are UL Listed as "Regulated." These appliances shall not be used on UL Listed "Special Application" notification circuits unless the appliances are identified to be compatible in the installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual. NOTE: THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0 -33.0 VOLTS FOR 24 VOLT MODELS AND 8.0 -17.5 VOLTS FOR 12 VOLT MODELS USING FILTERED DC FOR THE 12 VOLT RANGE AND EITHER FILTERED DC OR UNFILTERED DC FOR THE 24 VOLT RANGE VOLTAGE. DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE. NOTE: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO THE STROBES. THE MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS. NOTE: Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off. NOTE: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM'S PRIMARY AND SECONDARY POWER SOURCES, NOTIFICATION APPLIANCE CIRCUITS, SM, DSM SYNC MODULES, OR COOPER NOTIFICATION POWER SUPPLIES DOES NOT EXCEED THE POWER SOURCES' RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. P85060 C Sheet 2 of 6 • LIGHT OUTPUT: Table 6A: Horizontal HS and ST Light Output Horizontal UL Min Required Typical Percentage of Rated Candela of Rated Candela -90 25% 31% -85 25% 41% -80 30% 53% -75 30% 62% -70 35% 78% -65 35% 93% Table 6B: Vertical HS and ST Light Output 60 40% 107% Vertical UL Min Required Typical Percentage 55 45% 104% of Rated Candela of Rated Candela -50 55% 101% -90 12% 25% -45 75% 101% 1 -85 12% 52% ' -80 12% 76% -40 75% 104% -75 13% 95% -35 75% 101% -70 15% 116% -30 75% 103% -65 16% 132% -25 90% 107% -60 18% 134% -20 90% 110% -55 22% 135% -15 90% 111% -50 27% 132% -10 90% 124% ' -45 34% 129% -5 90% 215% -40 46% 121% 0 100% 27146* -35 65% 142% 5 90% 222% -30 90% 125% 10 90% 141% -25 90% 135% 15 90% 113% -20 90% 118% 20 90% 118% -15 90% 103% 25 90% 104% -10 90% 111% ' 30 75% 100% -5 90% 132% 35 75% 100% 0 100% 271%* 40 75% 98% 45 75% 105% 50 55% 106% 55 45% 112% 60 40% 113% 65 35% 98% 70 35% 82% 75 30% 68% 80 30% 56% 85 25% 43% 90 25% 31% * - Use 108% for 15/75 candela setting. P85060 C Sheet 3 of 6 WIRING AND MOUNTING BASE: 1. All strobe appliances have in -out wiring terminals that FROM PRECEDING TO NEXT APPLIANCE accept two #12 to #18 American Wire Gauge (AWG) APPLIANCE, FACP OR OR END OF LINE wires at each screw terminal. Strip leads 3/8 inches SYNC MODULE { -, RESISTOR (EOLR) and connect to screw terminals. • O ® O s 2. Break all in -out wire runs on supervised circuits to ensure integrity of circuit supervision as shown in Figure 1. The polarity shown in the wiring diagrams is Figure 1. Figure 2. for the operation of the appliances. The polarity is reversed by the FACP during supervision. NOTE: Wiring method shall be in accordance with CSA C22.1, Canadian Electrical Code, Part 1, Safety Standard for Electrical Installations, Section 32. WIRING AND MOUNTING SETTINGS: NOTE: The HS and HN are factory set for the most common application of Medium dB and Code 3. The HS and ST are set to 15 candela. TONE SELECTION r n_ I 9! 99 II: ice° CANDELA W INDOW CANDELA SELECTION I u DP 11 )11 Figure 3: Candela Selector NOTE: Candela factory settings are shown in above illustrations. O CAUTION: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed multiconductor cable or 3/4" conduit fittings are used. Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Cooper Notification recommends use of the largest backbox option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from wiring. 1CAUTION: DO NOT OVER TIGHTEN MOUNTING SCREWS. EXCESSIVE TORQUE CAN DISTORT THE BASE AND MAY AFFECT OPERATION. /! \ CAUTION: WHEN USING POWER TOOLS TO SCREW DOWN THE MOUNTING PLATE TO THE ELECTRICAL BACKBOX, ENSURE THE TORQUE IS SET TO THE LOWEST SETTING AVAILABLE. MOUNTING OPTIONS: P85060 C Sheet 4 of 6 c' .r oano SECURIN G ��t�; � °•r SCREWS 11/411i--A ) INSERT AND PULL Figure 4: Installation Figure 5: Removal (See step 8 below) 1. Install mounting plate as shown in Figure 1 to a single -gang, double- 6. Important: Device only has one mounting orientation. Match the top of gang, 4" square backbox with the provided pan head screws. the base to the top of the device. Engage both top hooks, then snap 2. Connect field wiring per Figures 1 and 2. the bottom in place. 3. Dress wires back into backbox. 7. If it is desired to further secure the device to the base, then one 4. While performing wiring continuity check, leave terminal cover in place. optional screw is provided. To install this screw punch out the screw 5. Remove terminal cover before snapping or installing the appliance onto hole located at the top of this device. the mounting plate per Figure 3. 8. To remove the appliance, insert a small flat - bladed screwdriver into the bottom opening %" as shown in Figure 5. Then pry off housing with the screwdriver. A\ WARNING: THESE APPLIANCES ARE A "FIRE ALARM DEVICE - DO NOT PAINT." WARNING: WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT CAN BE SEEN BY ALL INTENDED VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION, REGARDLESS OF THE VIEWER'S ORIENTATION. WARNING: A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW, UNDER CERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO - SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY. STROBE REFLECTIONS IN A GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE. TO MINIMIZE THIS POSSIBLE HAZARD, COOPER NOTIFICATION STRONGLY RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH EXCEEDS FIVE (5) Hz AT THE OPERATING VOLTAGE OF THE STROBES. COOPER NOTIFICATION ALSO STRONGLY RECOMMENDS THAT THE INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, STANDARDS, REGULATIONS, CODES AND GUIDELINES. NOTE: NFPA 72 /ANSI 117.1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer, higher intensity strobes within the same protected area. NOTE: Final acceptance is subject to Authorities Having Jurisdiction. - CAUTION: Check the installation instructions of the manufacturers of other equipment used in the system for any guidelines or restrictions on wiring and /or locating Notification Appliance Circuits (NAC) and notification appliances. Some system communication circuits and /or audio circuits, for example, may require special precautions to assure immunity from electrical noise (e.g. audio crosstalk). NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: 1) Reorient or relocate the receiving antenna. 2) Increase the separation between the equipment and receiver, 3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected, and 4) Consult the dealer or an experienced radio/TV technician for help. Compatible "Cooper Notification" Devices: SM -12/24 and DSM -12/24 P85060 C Sheet 5 of 6 ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM COOPER NOTIFICATION MANUALS OR OTHER DOCUMENTS DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE. INCLUDING DESCRIPTION • OF THE PRODUCTS APPLICATION, OPERATION, INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER AND COOPER NOTIFICATION WILL NOT HAVE ANY LIABILITY FOR SUCH USE. LIMITED WARRANTY Cooper Wheelock, Inc. dba Cooper Notification and Cooper Notification, Inc. (each, a "Seller ") products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with these instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriter's Laboratories (UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations laws and codes including, but not limited to, all appendices and amendments and the requirements of thc local authority having jurisdiction (Am). Seller products when properly specified, applied, installed, operated, maintained and operationally tested as provided above are warranted against mechanical and electrical defects for a period of (a) three (3) years from date of manufacture with respect to MEDC and Seller Industrial Signals and Seller Fire and Security Notification Appliances and Devices, or (b) one (1) year from date of manufacture with respect to Waves and SafePath Voice Evacuation and Mass Notification Systems (date of manufacture is determined by date code.) Correction of defects by repair or replacement shall be at Seller's sole discretion and shall constitute fulfillment of all obligations under this warranty. THE FOREGOING LIMITED WARRANTY SHALL IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY SELLER IS INSTALLED IN THE PRODUCT. THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT. SELLER MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND, EXPRESS, IMPLIED OR STATUTORY WHETHER AS TO MECHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER. USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR THE USER'S PURPOSES, OR WHETHER IT WILL ACHIEVE THE USER'S INTENDED RESULTS. THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLIACATION, IMPROPER SPECIFICATION, ABUSE, ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND SELLER'S CONTROL. SELLER DOES NOT WARRANT THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR -FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE, OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER'S REQUIREMENTS. SELLER SHALL NOT BE LIABLE FOR ANY DELAYS, BREAKDOWNS, INTERRUPTIONS, LOSS, DESTRUCTION, ALTERATION, OR OTHER PROBLEMS IN THE USE OF A PRODUCT ARISING OUT OF OR CAUSED BY THE SOFTWARE. THE LIABILITY OF SELLER ARISING OUT OF THE SUPPLYING OF A PRODUCT, OR ITS USE, WHETHER ON WARRANTIES, NEGLIGENCE, OR OTHERWISE, SHALL NOT IN ANY CASE EXCEED THE COST OF CORRECTING DEFECTS AS STATED IN THE LIMITED WARRANTY AND UPON EXPIRATION OF THE WARRANTY PERIOD ALL SUCH LIABILITY SHALL TERMINATE. SELLER IS NOT LIABLE FOR LABOR COSTS INCURRED IN REMOVAL, REINSTALLATION OR REPAIR OF A PRODUCT BY ANYONE OTHER THAN SELLER OR FOR DAMAGE OF ANY TYPE WHATSOEVER, INCLUDING BUT NOT LIMITED TO, LOSS OF PROFIT OR INCIDENTAL, INDIRECT, CONSEQUENTIAL, SPECIAL, PUNTIVE OR EXEMPLARY DAMAGES. THE FOREGOING SHALL CONSTITUTE THE SOLE REMEDY OF THE PURCHASER AND THE EXCLUSIVE LIABILITY OF SELLER IN NO CASE WILL SELLER'S LIABILITY EXCEED THE PURCHASE PRICE PAID FOR A PRODUCT. LIMITATION OF LIABILITY SELLER'S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING NEGLIGENCE AND BREACH OF WARRNTY, FOR ANY LOSS OR DAMAGE RESULTING FROM, ARISING OUT OF, OR CONNECTED WITH THIS CONTRACT, OR FROM THE MANUFACTURE, SALE, DELIVERY, RESALE, REPAIR OR USE OF ANY PRODUCT COVERED BY THIS ORDER SHALL BE LIMITED TO THE PRICE APPLICABLE TO THE PRODUCT OR PART THEREOF WHICH GIVES RISE TO THE CLAIM. SETTER'S LIABILITY ON ANY CLAIM OF ANY KIND SHALL CEASE IMMEDIATELY UPON THE INSTALLATION IN THE PRODUCT OF ANY PART NOT FURNISHED BY SELLER IN NO EVENT SHALL SELLER BE LIABLE FOR ANY CLAIM OF ANY KIND UNLESS IT IS PROVEN THAT ITS PRODUCT WAS THE DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN NO EVENT, INCLUDING IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL SELLER BE LIABLE FOR INCIDENTAL, INDIRECT, CONSEQUENTIAL, SPECIAL, PUNITIVE OR EXEMPLARY DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE PRECEDING LIMITATION MAY NOT APPLY TO ALL PURCHASERS. 7/09 P85060 C Sheet 6 of 6 f 2_01. ( 0-0034( • Wheelock INC. 273 Branchport Ave. Long Branch, N.J. 07740 Thank you for using our products. (800) 631 -2148 (USA) (800) 397 -5777 (CANADA) INSTALLATION INSTRUCTIONS www.wheelockinc.com SERIES RSS AND RSSP STROBE APPLIANCES (WALL MOUNT VERSIONS) Use this product according to this instruction manual Please keep this instruction manual for future reference. GENERAL: Wheelock's Series RSS and RSSP Strobes can provide a non - synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP), or provide a synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or Wheelock's Power Supplies. The Series RSS and RSSP Strobe Appliances are UL Listed under Standard 1971 (Signaling Devices for the Hearing Impaired) for indoor fire protection service. The 24V Series RSS Strobe Appliances are also ULC Listed under Standard CAN/ULC- S526-02 for Visual Signaling Appliances. The 1575W candela wall mounted strobes are listed at 15 candela under UL Standard 1971 and meet 75 candela intensity on axis with low current draw. These Strobes are listed for wall mount and indoor use only, with the backboxes specified in these instructions (See Mounting Options). RSS models have an integrated Strobe Mounting Plate (SMP) that can be mounted to a single -gang, double -gang, 4" backbox, 100mm European backbox or SHBB surface backbox. The strobes use a xenon flashtube with solid state circuitry enclosed in a polycarbonate lens to provide maximum visibility and reliability for effective visible signaling. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by the FACP. NOTE: All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems - CAN/ULC-S524-01 and Canadian Electrical Code, Part I. Final acceptance is subject to Authorities Having Jurisdiction (AHJ) WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. SPECIFICATIONS: Table 1: Ratings Per UL and ULC Model Regulated Voltage Range Limit Voltage Range Per Strobe Mounting Voltage Per UL 1971 CAN/ULC-S526-02 Candela Options (VDC/VRMS) (VDC/VRMS) (VDC/VRMS) (ed) RSS- 241575W 24 16.0- 33.0 20.0 -31.0 15 A,B,C,D RSSP- 241575W 24 16.0 -33.0 20.0 -31.0 15 E,F RSS- 121575W 12 8.0- 17.5 -- — 15 A,B,C,D RSSP- 121575W 12 8.0 -17.5 - - -- 15 E,F All 1575 models are UL Listed at 15cd and meet 75cd on a xis. RSS- 121575W and RSSP- 121575\V are n l "L (' approved Tab le IA: Audible/Speakers for R SSP Stro -Plate Product Series Multitone Appliances AMT, MT, MT4 Motor Bells MB- G6 /G10 Speakers ET -1010 /1080, ET70, E70 Chimes CH70 NOTES: 1. Strobes will produce 1 flash per second over the "Regulated Voltage" range. 2. These strobes meet the required light distribution patterns defined in UL 1971 and ULC- S526-02. 3. All models are listed by UL/ULC for indoor use with a temperature range of +32 °F to +120'F (0 °C to +49'C) and maximum humidity of 93% ± 2 %RH. The effect of shipping and storage temperatures shall not adversely affect the performance of the appliance when it is stored in the original cartons and is not subjected to misuse or abuse. Table 2: Current Ratings (AMPS)far 24VDCModels Tabfe2B: Current Ratings (AMPS) for 12VDCModels Maximum RMS Current Maximum RMS Current Voltage 241575W Voltage 121575W DC L 16 -33VDC 0.090 DC l 8- 17.5VDC 0.255 r 1 \t 1Z r 16- 33VRMS 0.145 FWR l 8- 17.5VRMS _ 0.335 When calculating the total currents use Table 2 to determine the highest value of RMS current for an individual strobe, then multiply these values by the total number of strobes. Be sure to add the currents for any other appliances, including audible signaling appliances powered by the same source, and to include any required safety factors. NOTE: The maximum number of strobes on a single notification appliance circuit shall not exceed 50. /� / : \CAUTION: These notification appliances are UL Listed as "Regulated ". They are intended to be used with FACPs whose notification circuits are UL Listed as "Regulated." These appliances shall not be used on UL Listed "Special Application" notification circuits unless the appliances are identified to be compatible in the installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual. Copyright 2005 Wheelock, Inc. All rights reserved. P84233 L Sheet 1 of 4 4 A.\ WARNING: THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING FILTERED DC OR UNFILTERED FULL- WAVE - RECTIFIED VOLTAGE. DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE. WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPPLIED VOLTAGE TO THE STROBES. THE M AXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS. /t\ CAUTION: Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off. / WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM'S PRIMARY AND SECONDARY POWER SOURCES, NOTIFICATION APPLICIANCE CIRCUITS, SM, DSM SYNC MODULES, OR WHEELOCK POWER SUPPLIES DOES NOT EXCEED THE POWER SOURCES' RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. W IRING AND MOUNTING INFORMATION: 4 .\ CAUTION: The following figures (A -F) show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product. / : \ CAUTION: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed multiconductor cable or 3/4" conduit fittings are used. Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Wheelock recommends use of the largest backbox option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from wiring. A FLUSH MOUNTING B FLUSH OR SURFACE MOUNT C FLUSH OR SURFACE MOUNT STD. SINGLE-GANG 4' SQ X 1 - 12' DEEP BACKBOX DOUBLE -GANG X 2 - 1/4" Q BACKBOX 2' DEEP CR 100m X 37.5mm \DEEP BACKBOX STROBE MDINfNJG #632 SCREWS \ I r R ® PLAT (SNP CI, I #6 32 SCREWS i �(� ei.„...-, ....„. STROBE MNTING \ %411° 111, PLATE (SMP) \ STROBE MOUNTING PLATE (SMP) BEAUTY PLATE MAXIMUM NUMBER OF CONDUCTORS BEAUTY PLATE f BEAUTY PLATE AWG #18 AWG#16 AWG #14 AWG #12 MAXIMUM NUMBER OF ODPDJCTCf2S MAXIMUM NUMBER OF CONDUCTORS 4 4 4 4 4 #18 AWG #16 AWG #14 AWG #12 AW 4 #18 AW 4 #16 AWG #14 AW 4 #12y D SURFACE MOUNTING E Eunitaamtha F SURFACE MOUNTING SHALLOW S DACE STANDARD 4' X 2 -1/8' BACKBOX (SBL -2) 'Nilo, - BACKBOX 1 32 SCt n APPLIA • F DEEP BACKBOX l II 4000. !I o,,, \ A UA `CE ,, ;, /'r \ i : • I / �J ,..k. ,......._ STROBE MOUNTING 'N. �Jl. % •I PLATE (SMP) A i BEAUTY PLATE - MAXIMUM NUMBERCFCONDUCTORS MAXIMUMNLJE ER OF CONDUCTORS MAXIMU NUMBER OF C ONDUCTORS AWG, #18 AWG #16 AWG #14 AWG #12 NAG #14 Atom &G#14 &Qui A #18 AWG #16 AWG #14 NAG #12 4 4 4 4 8 8 8 8 8 8 8 8 Figures E and F are shown with optional 6" bell. See Table lA for other possible appliance combinations. P84233 L Sheet 2 of 4 4 Figure 1: Wiring Diagrams Figure 2: s ■ • MF£, FACP S OR eTOFa( f SYNC STROBES OR SYNC MODU. E RESISTOR (EOM) It 1 PLAT ALO/B "a' • All strobe appliances have in -out wiring terminals that accepts two #12 ASSEMBLY Auw i�_ I I II to #18 American Wire Gauge (AWG) wires at each screw terminal. OPERATE F , a ,, ,r �, I I r � T Strip leads 3/8 inches and connect to screw terminals. OR SYNC uoDULE �� �~ OR ECLR • Break all in -out wire runs on supervised circuits to assure integrity of AUDIBLE VISIBLE circuit supervision as shown in Figure 2. Strobe/Plate assembly has two f - =1 red leads and two black leads for in -out wiring. The polarity shown in the wiring dia ams is for the operation of the appliances. The polarity STROBE/PLATE FROM PIECECINO 0 1� TO NEXT 8 8r P PP P ty' APPLIANCES APPLIANCE FACP APFLIANCL is reversed by the FACP during supervision. CPET A 'NODULE L. TE OR SYNC OR EOR Y 8 uP INDEPENDENTLY FROM PRECEEING . _• BLX TO NEXT OR S A" r FACP OR EOLFt Refer to instruction sheets for SM (P83123), DSM (P83177) or Wheelock NC power supplies for additional information. 1. This RSS model can be flush mounted to a standard single -gang backbox (Figure A), 4" or 100mm backbox (Figure B) or double -gang backbox (Figure C). It can also be surface mounted to a 4" or 100mm backbox (Figure B), double -gang backbox (Figure C) or the SIIBB (Figure D). The RSSP model can be flush mounted to a 4" backbox (Figure E) or surface mounted to a SBL -2 backbox (Figure F). Mounting hardware for each mounting option is supplied. 2. Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product. Do not pass additional wires (used for other than the signaling appliance) through the backbox. Such additional wires could result in insufficient wiring space for the signaling appliance. 3. When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring space for the appliance. 4. Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product. This is especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 5. This RSS model has an integrated Strobe Mounting Plate (SMP) which must be oriented correctly when it is mounted to the backbox. Turn the SMP so that the arrow above the words "Horizontal Strobe" points to the top side. 6. Mount the SMP first to the backbox. Next slide the beauty plate over the SMP until the 2 snaps of the beauty plate engage with the SMP. 7. The beauty plate can be removed from the strobe assembly once engaged. First, gently insert a screwdriver into one of the slots located on the top and bottom edges of the beauty plate. Second, gently pull away from the wall with the inserted screwdriver to disengage the snap. Third, repeat the first and second steps for the second slot. Finally, gently lift the beauty plate away from the SMP. WARNING: REMOVAL OF THE BLACK COVER AT THE BACK OF THE MOUNTING PLATE COULD RESULT IN SEVERE ELECTRIC SHOCK. / ! \ WARNING: THE RSS STROBE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT." A WARNING: WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT CAN BE SEEN BY ALL INTENDED VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION, REGARDLESS OF THE VIEWER'S ORIENTATION. FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. WARNING: A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW, UNDER CERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO - SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY. STROBE REFLECTIONS IN A GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE. TO MINIMIZE THIS POSSIBLE HAZARD, WHEELOCK STRONGLY RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH EXCEEDS FIVE (5) Hz AT THE OPERATING VOLTAGE OF THE STROBES. WHEELOCK ALSO STRONGLY RECOMMENDS THAT THE INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, STANDARDS, REGULATIONS, CODES AND GUIDELINES. N OTE: NFPA 72/ANSI 117.1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer, higher intensity strobes within the same protected area. !' \CAUTION: Check the installation instructions of the manufacturers of other equipment used in the system for any guidelines or restrictions on wiring and/or locating Notification Appliance Circuits (NAC) and notification appliances. Some system communication circuits and/or audio circuits, for example, may require special precautions to assure immunity electrical noise (e.g. audio crosstalk). ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER DOCUMENTS DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE PRODUCT'S APPLICATION, OPERATION, INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER AND WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE. IMPORTANT: READ SEPARATE "GENERAL INFORMATION" SHEET FOR INFORMATION ON THE PLACEMENT, LIMITATIONS, INSTALLATION, FINAL CHECKOUT, AND PERIODIC TESTING OF NOTIFICATION APPLIANCES. P84233 L Sheet 3 of 4 NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: 1) Reorient or relocate the receiving antenna, 2) Increase the separation between the equipment and receiver, 3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected, and 4) Consult the dealer or an experienced radio/TV technician for help. Limited Warranty Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with these instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters' Laboratories (UL), Underwriters' Laboratories of Canada (ULC), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). Wheelock products when properly specified, applied, installed, operated, maintained and operationally tested as provided above are warranted against mechanical and electrical defects for a period of three years from date of manufacture (as determined by date code). Correction of defects by repair or replacement shall be at Wheelock's sole discretion and shall constitute fulfillment of all obligations under this warranty. THE FOREGOING LIMITED WARRANTY SHALL IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY WHEELOCK IS INSTALLED IN THE PRODUCT. THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT. WHEELOCK MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND, EXPRESS, IMPLIED OR STATUTORY WHETHER AS TO MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR THE USER'S PURPOSES, OR WHETHER IT WILL ACHIEVE THE USER'S INTENDED RESULTS. THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLICATION, IMPROPER SPECIFICATION, ABUSE, ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK'S CONTROL. SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE. WITH RESPECT TO THOSE PRODUCTS, WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR -FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE, OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER'S REQUIREMENTS. WHEELOCK SHALL NOT BE LIABLE FOR ANY DELAYS, BREAKDOWNS, INTERRUPTIONS, LOSS, DESTRUCTION, ALTERATION, OR OTHER PROBLEMS IN THE USE OF A PRODUCT ARISING OUT OF OR CAUSED BY THE SOFTWARE. THE LIABILITY OF WHEELOCK ARISING OUT OF THE SUPPLYING OF A PRODUCT, OR ITS USE, WHETHER ON WARRANTIES, NEGLIGENCE, OR OTHERWISE, SHALL NOT IN ANY CASE EXCEED THE COST OF CORRECTING DEFECTS AS STATED IN THE LIMITED WARRANTY AND UPON EXPIRATION OF THE WARRANTY PERIOD ALL SUCH LIABILITY SHALL TERMINATE. WHEELOCK IS NOT LIABLE FOR LABOR COSTS INCURRED IN REMOVAL, REINSTALLATION OR REPAIR OF THE PRODUCT BY ANYONE OTHER THAN WHEELOCK OR FOR DAMAGE OF ANY TYPE WHATSOEVER, INCLUDING BUT NOT LIMITED TO, LOSS OF PROFIT OR INCIDENTAL OR CONSEQUENTIAL DAMAGES. THE FOREGOING SHALL CONSTITUTE THE SOLE REMEDY OF THE PURCHASER AND THE EXCLUSIVE LIABILITY OF WHEELOCK. • IN NO CASE WILL WHEELOCK'S LIABILITY EXCEED THE PURCHASE PRICE PAID FOR A PRODUCT. Limitation of Liability WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING NEGLIGENCE AND BREACH OF WARRANTY, FOR ANY LOSS OR DAMAGE RESULTING FROM, ARISING OUT OF, OR CONNECTED WITH 11-US CONTRACT, OR FROM THE MANUFACTURE, SALE, DELIVERY, RESALE, REPAIR OR USE OF ANY PRODUCT COVERED BY THIS ORDER SHALL BE LIMITED TO THE PRICE APPLICABLE TO THE PRODUCT OR PART THEREOF WHICH GIVES RISE TO THE CLAIM. WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND SHALL CEASE IMMEDIATELY UPON THE INSTALLATION IN THE PRODUCT OF ANY PART NOT FURNISHED BY WHEELOCK. IN NO EVENT SHALL WHEELOCK BE LIABLE FOR ANY CLAIM OF ANY KIND UNLESS IT IS PROVEN THAT OUR PRODUCT WAS A DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN NO EVENT, INCLUDING IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL WHEELOCK BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE PRECEDING LIMITATION 9/05 P84233 L Sheet 4 of 4 • INTELLIKNIGHT ACCESSORY j PS�i� SK -ION ( 3' ' An Intelligent Ionization Smoke Sensor Hospitals, industrial environments and other locations where rapid fire I development is expected should consider ionization smoke detectors as # , part of their IntelliKnight detection package. Ionization smoke detectors provide early warning in fast - flaming fires that show little visible smoke. The IntelliKnight panel recognizes each detector by its specific address, so precious seconds are not wasted in determining location of an alarm. For more information about the IntelliKnight system, or to locate your nearest source, please call 800 - 328 -0103, or in Connecticut, call (203) 484 -7161. Model SK -ION a local, visible sensor indication. Intelligent Ionization The status LED lights continuously during an alarm. . 3ie - , � 1 Smoke Sensor 1� , , The SK -Ion has responsive, yet Features , high operational stability for an • Low profile design _ , extremely wide range of uses. The • 6" Mounting base included a r SK -Ion can be used in areas where . Rotary address switches �, - early warning of trouble from super- 4 heated or flaming combustibles is • Built -in fire test feature � expected. • Dual LED indicators for 360° visibility The SK -Ion detector incorporates a • single source dual chamber Detector transmits signal to SK -ion (Base Included) designed to respond quickly in to a indicate maintenance is required broad range of fires. • Plug -in mounting provides ease Height 2.0" (51 mm) of installation Diameter 6.1" (155 mm) Operation • Vandal- resistant locking feature (installed in base B210LP) The SK -Ion ionization smoke • Field cleanable detector has two chambers: a Weight 5.4oz (153 g) • Optional remote LED sampling chamber, and a reference annunciator (PN System Compatibility chamber. Smoke or invisible combustion gases can freely Sensor RA100Z) The SK -Ion is compatible with the penetrate the sampling chamber, • UL listed, meets NFPA 72 following IntelliKnight FACP's: but the reference chamber is • CSFM listed 5700 virtually closed to prevent easy • MEA 5808 entry. With both chambers ionized • FM approved 5820XL by a single radioactive source, a very small current flows. Specifications The SK -Ion is compatible with the Operating Voltage: 15 to 32 VDC following detector bases: Presence of visible smoke or invisible gases greatly influences Current Consumption: B210LP (included) 6" base the current flow in the sampling Standby: 300pA @ 24VDC B501 2 wire base chamber, changing the voltage Alarm: 6.5mA @ 24VDC B224B1 Isolator base ratio between the two chambers. Operating Temperature: 32 °F to B224RB Relay base This difference is amplified inside 120 °F(0 °C to 49 °C) B501BH Tou base the detector. After reaching the 6501BHT- 2 Tempp oraora l base critical level, the detector triggers Relative Humidity. 10% to 93% into alarm. noncondensing SILENT The SK -Ion includes two LEDs on Velocity Range: 0 - 1200 FPM KNIGHT each sensor which light to provide by Honeywell INTE'LLIKNIGHT ACCESSORY Model SK -Ion Engineering Specifications The contractor shall furnish and install where indicated on the plans, dual - chamber, addressable ionization smoke detector Silent Knight SK -Ion. The combination detector head, and twist -lock base, shall be UL® listed compatible with Silent Knight's IntelliKnight fire alarm control panels. The base shall permit direct interchange with Silent Knight SK -Ion Ionization Smoke Detector. Base shall be the appropriate twist -lock base B210LP. The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal- resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SK -Ion shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. SLC IN OUT RA 1002 1O9tionaly r ■ Kt- 411\ Tsai EV - "t", of %lie NIT, • r MAIMS $01-11W he Onnwor 'bawling Grow SILENT This document is not intended to be used for installation purposes. We try to MADE IN AMERICA keep our product information up- to-date and accurate. We cannot cover all mom-Fr specific applications or anticipate all requirements. All specifications are FORM# 350119 Rev. A subject to change without notice. For more information, contact Silent Knight ©2009 Honeywell International Inc. 12 Clintonville Road Northford, CT 06472 -1610 Phone: (800) 328 -0103, by Haneywol Fax: (203) 484 -7118. www.silentknight.com INTELLIKNIGHT ACCESSORY SILENT SK- Pull -SA and SK- Pull -DA KNIGHT F1� �o i 1 _ G --v - e9 3 c/ Intelligent Pull Stations by Honeywell The SK- Pull -SA and SK- Pull -DA are a single action or dual action addressable fire alarm pull station for use with Silent Knight's IntelliKnight fire control panel. Extremely easy to operate, the SK- Pull -DA and SK- Pull -SA provide a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. For more information about the IntelliKnight system, or to locate you nearest source, please call 1- 800 - 328 -0103. Description The SK- Pull -SA is a single action pull station requiring only I R E • one motion to activate the station. The SK- Pull -DA is a dual action pull station requiring two motions to active the station. Both pull stations are designed to work with Silent Knight I I PULL ir DOWN Intellikni series fire alarm control panels (FACPs). Features • Installer can open station without causing an alarm condition 5,,,N, • Dual -color LED is visible through handle of station blinks green to indicate normal operation and remains steady red in an alarm condition SK- Pull -SA • Key operated test and reset lock using lock plate actuator • Key matches compatible FACP locks F I R i • Meets the Americans with Disabilities Act Accessibility Guidelines (ADAAG) controls and operating mechanisms , PUSH guidelines (Section 4.1.3[13]) PULLDO • Meets ADA requirement for 5 lbs maximum pull force to active • Shell, door, and handle molded from durable LEXAN ; gi • Reliable analog communications for trouble -free operation • Braille text on station handle SK- Pull -DA • Handle latches in down position and the word Activated Compatibility appears, clearly indicating the station has been pulled The SK- Pull -SA and SK- Pull -DA are compatible • Rotary address switches for fast installation with the following IntelliKnight FACP's: 5600 • UL Listed, including UL 38, Standard of Manually Actuated 5700 Signaling System 5808 5820XL INTEy.LIKNIGHT ACCESSORY r Model SK- Pull -DA and SK- Pull-SA Engineering Specifications The contractor shall furnish and install where indicated on the plans, Addressable Pull Stations, Silent Knight model SK- Pull -SA single action pull station or SK- Pull -DA, dual action pull station. SK- Pull -DA or SK- Pull -SA meet the ADAAG controls and operating mechanisms guidelines, and the ADA requirements for a 5 lb. maximum pull force to activate the pull station. y t _ _._._._._._. _....._._._..._......_.._.__._. Class 1 !.__...._._._.__._. IN re SLC OUT [ a , Class B Compatible FACP J I ! l ] 33 v b C L o i 4 airs :Jai WOOD I oO�� ■ e — Class A Wiring: Class B Wiring: mw Er] Wiring SK- Pull -SA & SK- Pull -DA Pull Stations Specifications Electrical Physical Operating Voltage: 15-32 VDC Height: 5.5" (14 cm) Average Operating Current (LED flashing): 300 pA Width: 4" (10.2 cm) Wire Gauge: Up to 12 AWG (3.1 mm Depth: 5.4 oz. (3.7 cm) Environmental Housing Material: LEXAN polycarbonate resin Operating Temperature 32° - 120 °F (0 °C - 49 °C) Bi- Colored LED: Humidity: 10% - 93% non - condensing Blinking Green: Normal Steady Red: Alarm Accessories Switch: Single pole, single throw (SPST) normally open (N /O) BG -TR Optional trim ring. switch which closes upon activation of the pull station SB -I /O Surface backbox This document is not intended to be used for installation purposes. We try to MADE IN AMERICA • SILENT keep our product information up- to-date and accurate. We cannot cover all N KNIGHT specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Silent Knight FORM# 350135 Rev A 12 Clintonville Road, Northford, CT 06472 -1610 Phone: (800) 328 -0103, © 2009 Honeywell International Inc. by Honeywell Fax: (203) 484 -7118. www.silentknight.com ,a, INTELLIKNIGHT ACCESSORY 44 SILENT _ .2 01/ Gv -o 3 SK- Monitor KNIGHT by Honeywell Intelligent Monitor Module The SK- Monitor module provides an interface to contact devices, such as security contacts, waterflow switches, or pull stations. For more information about the IntelliKnight system, or to locate you nearest source, please call 1 -800- 328 -0103. Description The SK- Monitor is an addressable monitor module for use with Silent Knight IntelliKnight series fire alarm control panels ( FACPs). The SK- Monitor is intended for use in intelligent, two -wire systems, where individual address of each module is selected using the built -in rotary - - - - - -- switches. The SK- Monitor supports Class A supervised or • Class B supervised wiring to the load device. Conventional 4 -wire smoke detectors can be monitored for alarm and trouble conditions. Features • Single contact monitor • Support for Class A and Class B wiring • Fully supervised • Panel controlled status LED that flashes green SK- Monitor in normal state and is solid red in alarm • Attractive ivory cover plate • Rotary address switches for fast installation The 5K - - Mo Moity The SK-Monitor is compatible with the • SEMS screws for easy wiring following IntelliKnight FACP's: • UL Listed 5700 5808 Installation 5820XL The SK- Monitor mounts directly into a 4" square electrical box. The box must have a minimum depth of 2 -1/8 ". A surface mount electrical box (System Sensor® PN SMB500) is available from Silent Knight. INT'I_ i.IKNIGHT ACCESSORY Model SK- Monitor Intelligent Monitor Module To Next Device IN O O ClassB ■• , ` ; . el•l IAa l t` # e a NE - From Compatible Silent Knight file , FACP or Previous Device Communication Loss (Optional Conenction Initiating Device Circuit NFPA Style S ^ for Panels Which Support this Feature) Power Limited 230A Max tg 12 VDC Max V 0 ■ ■ Class A Wiring - T — Class S Wiring- o Next Device + 1 Any Number of UL Listed Contact Closure f Devices May Se Used. Do Not Mix Flre Alarm O O ° O (� Initiating Devices, Supervisory, or Security Devices \ on the Same Module. ......... Class A ................ ®s t e NI ....� ern a - From Compatible Silent Knight L FACP or Previous Device :. Communication 1 cos (Optional Conenction r` -� \ for Panels Which Support this Feature) EOL Resistor Is Internal V 0 O fl st Terminus 8 & 9 (� u u Wiring IDP- Monitor Modules Specifications 5.5 mA (with LED latched on) Physical LED Current: 5.5 mA (with LED latched on)End -of -Line Height: 4.5" (11.4 cm) Resistance: 47K Width: 4" (10.2 cm) Initiating Device Circuit Wiring Resistance: 1,500 max Depth: 1.25' (3 cm) SLC Loop Resistance: 40 max. Shipping Weight: 6.3 oz (196 g) Environmental Electrical Operating Temperature: 32 °F - 120 °F (0 °C - 49 °C) Operating Voltage: 15 - 32 VDC Humidity: 10% - 93% non - condensing Current Draw (LED on): 5.0 mA max Operating Current (LED flashing): 375 pA Ordering Information SK- Monitor Monitoring Module Standby Current: 400 pA max @ 24 VDC (one communication every 5 sec with Accessories 47K EOL) SMB500 4" Square Surface Mount Electrical 550 pA max @ 24 VDC (one communication every 5 sec with Box EOL <1K) This document is not intended to be used for installation purposes. We try MADE IN AMERICA SILENT to keep our product information up-to -date and accurate. We cannot cover N KNIGHT all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Silent FORM# 350131 Rev B Knight 12 Clintonville Road, Northford, CT 06472 -1610 © 2010 Honeywell International Inc. by Honeywell Phone: (800) 328 -0103, Fax: ( 203 )484 -7118. www.silentknight.com [Page Too Large for OCR Processing] [Page Too Large for OCR Processing] [Page Too Large for OCR Processing]