Loading...
Specifications r.(- q. lk S ARCHITECTS, P.C. 1307 Seventh Street Oregon City, OR 97045 p: 503 -656 -1942 f: 503 -656 -0658 EIVE MEMO -? 0 5 2012 C111"1 1G IS ON T Steve Sprawkins, Bartel Contracting Senior Project Mana uILDING vcr CC: Viktor Sorokin, Bartel Contracting Superintendent From: Todd Iselin Date: September 4, 2012 Re: HVAC Support at Therapeutic Associates 16083 SW Upper Boones Ferry Road, Suite 300, Tigard, OR 97224 Steve, Per your request I met with your superintendent; Viktor, at the site this morning and observed the (1) new and existing duct heater and mixing boxes suspended from the existing roof structure, examined the original construction documents and approved shop drawings for the • building shell. All in -line duct heating units appear to be adequately supported structurally. The new unit (Trane Y2C 243_A) weighs 125# and is supported from a 20 ga ASC type 'DGB -36' composite deck with 4" concrete slab supported by 28 LH joists at 8' o.c.. Per building shell drawings (sheet S5.1 b) and approved shop drawings the roof structure is capable of supporting a 600# pt load at any point in addition to fire sprinklers and specified roof top units. The supporting structure is adequate without modifications. The new unit is suspended with (8) 1" wide x 20 ga straps with (2) #8 screws to unit and (1) #8 screw to side of lapped deck flanges 8 x 272# = 2,176# allowed > 125/8 = 16# / fastener required. Refer to attached table 1 from ER 5280 for limiting shear values of screws: Please let me know if you have any questions or need additional information. City of Tigard , Ap • rov - d Plans v 03272 By a44 i Date L T 151(2 TODD i it GOES c Sa) _ RJeS 306 � R E GO ( N CITY, OREGON 1. REVISION OF O r ■201: projmAl250 -Oorte1 thaaputie a3 ociatc, doq'memo to Stcvc cprawtin, doe OFFICE COPY • Page 3 of 6 ER -5280 • TABLE 1— METAL -TO -METAL CONNECTIONS, ALLOWABLE SCREW LOADS FOR TENSION AND SINGLE SHEAR (pounds) GAGE OF MATERIAL NOT IN CONTACT WITH SCREW HEAD GAGE OF MATERIAL IN CONTACT WITH SCREW HEAD lir GAGE 25 25 20 20 18 18 16 16 14 14 12 12 Thickness (inch) 0.0188 0.0188 0346 0.0346 0.0451 0.0451 0.0565 0.0565 0.0713 0.0713 0.1017 0.1017 Thickness (mm) 18 18 33 33 43 43 54 54 68 68 97 97 F, = ksI 33 33 33 33 33 33 50 50 50 50 50 50 Allowable Nominal Shear Tension Shear Tension Shear Tension Shear Tension Shear Tension Shear Tension Loads Screw (pullout) (pullout) (pullout) (pullout) (pullout) (pullout) Dia. (Inch) 47 Streaker 0.151 98 40 327 ' 89 — — — — — — — — 08 Streaker 0.164 130 58 314 137 — — — — — — — — 46 Self -drill 0.138 — — 223 95 319 115 317 — — — — — 48 Self -drill 0.164 — — ( 272 J 106 418 136 382 177 405 180 — — #10 Self-drill 0.19 — — —cry 147 429 166 533 217 558 263 664 433 412 Self -drill 0.216 — — 268 140 435 160 551 233 731 231 814 390 014 Sclf.drill 0.250 _ — — 299 96 451 184 594 224 798 241 970 386 V = shear T = tension Notes: 3 Sam pounds 1. V = Single shear capacity in pounds. for two pieces of Diameters l 1 Th �_ same -gage steel in r 1 r ` 1 Diameters Diameters 3 Screw emeters close contact. • V F , ' 1/ , -'1 V ,, / 2. T = Tension (pullout) of 3 full threads nun1� / screw through one piece 3 full threads minimum of steel. 3. Steel sheets conform to ASTM A 653 -96, Grade 33 or SS Grade 50. Detail at shear Detail at tension ' For SI: 1 inch = 25.4 mm, 1 Ibf = 4.45 N. 1 ksi = 6.89 MPa. - Unless otherwise noted, for purposes of this report, NDS refers to the revised 1991 edition of, and the supplement to. the ANSI /NFoPA NDS -91 National Design Specification for Wood Construction (NDS) as adopted by reference in Division III, Part I, Chapter 23. of the UBC. TABLE 2— ATTACHMENT OF. WOOD STRUCTURAL PANELS AND PARTICLEBOARD'" PANEL THICKNESS SCREW DESCRIPTION SUBFLOOR '/, inch and less No. 8 by 1 Grabber coarse thread or plywood screw AND WALL ' inch - 3 / No. 8 by 2 -inch Grabber coarse thread or plywood screw SHEATHING TO .FRAMING . r / A inch - 1 inch No. 8 by 2 Grabber coarse thread screw 1'/ inches - 1'/ inches No. 8 by 2 /inch Grabber coarse thread screw COMBINATION 3 / 4 inch and less No. 8 by 2 -inch Grabber coarse thread or plywood screw SUBFLOOR— '4 inch - 1 inch No. 8 by 2'/, -inch Grabber coarse thread screw UNDERLAYMENT TO FRAMING _ 1'/, inches - 1'/ inches No. 8 by 2 -inch Grabber coarse thread screw For SI: 1 inch = 25.4 mm. 'Installation is in accordance with Figure 1 of this report and Part XI of the NDS'. = Screws are spaced 6 inches on center at edges, and 12 inches on center at intermediate supports; where spans are 48 inches on center or more. spacing is 6 inches on center at all supports. 'Refer to Tables 3 and 4 for diaphragms and shear walls. [Page Too Large for OCR Processing] [Page Too Large for OCR Processing]