Specifications I=1 9 - GC 11 5
q 5 '75 tt/ct-g I. Sb. Rol B 1 2
tqcci Fire & Building
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series RFII — 5.6 K- factor
"Royal Flush II" Pendent Concealed Sprinklers
Quick & Standard Response, Standard Coverage
General Cap. The Protective Cap is temporarily
removed for installation, and then it . 'i . :;:: . -
can be replaced to help protect the
Description • sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro- 'i
The Series RFII Quick Response tective Cap can also be used to mark
(3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas- .
mm bulb), 5.6 K- Factor, "Royal Flush
Y ter board, ceiling tiles, etc. by gently
-- --�
II" Concealed Pendent Sprinklers are pushing the ceiling product against the•_" - ; _
decorative sprinklers featuring a flat Protective Cap. When the ceiling in- •3,�
cover plate designed to conceal the stallation is complete the Protective
sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate
tecturally sensitive areas such as hotel Assembly installed. �,_
lobbies, office buildings, churches, As an option, the Series RFII Standard
and restaurants. Response (5 mm bulb) "Royal Flush II"
Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be
sembly that conceals the sprinkler op- fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175
erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by yM.
The separable two -piece design of the intended for sensitive areas where' it is
Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical
blies allows installation of the sprin- through the cover plate from the area
klers and pressure testing of the fire above the ceiling. Data
l protection system prior to installation
of a suspended ceiling or application WARNINGS
of the finish coating to a fixed ceiling. The Series RFII Concealed Pendent Approvals for Series RFII
They also permit removal of sus Sprinklers described herein must be UL and C -UL Listed. FM Approved.
pended ceiling panels forr access to install and maintained in compli NYC under MEA 353 -01 -E. LPCB (Ref.
building service equipment without ance w this document, as well as No. 094a/09 for TY3551 & 094a/10 for
aving to first shut down the fire pro - w ith the applicable standards of the TY3531) Approved.
h
hav system and remove sprinklers. Nat F Protection Association, The approvals apply only to the serv-
Also, the separable two-piece design i addition to the standards of any ice conditions indicated in the Design
f o e the Sprinkler other authorities having jurisdiction. Criteria section and maximum pres-
inch (12,7 mm) of vertical p provides
adjustment, for design for 2 . Model /S Failure to do so may impair the per- sure ratings indicated in the
formance of these devices. rinkler Identification Num-
. to reduce the ) accuracy to hich the p
length of fixed pipe drops to the sprin The owner is responsible for maintain tiers section.
klers must be cut. i ng their fire protection system and de Approvals for Air & Dust Seal
vices in proper operating condition. Part #10908100
The Series RFII Sprinklers are The installing contractor or sprinkler ( )
g p RFII and C-UL Listed for use with the •
shipped with a Disposable Protective
manufacturer should be contacted RFII (TY3551 & TY3504) Standard Re-
with any questions. sponse Concealed Sprinkler.
IMPORTANT Temperature Ratings
Always refer to Technical Data Model /Sprinkler 155F/68C Sprinkler - 135F/57C Plate
Sheet TFP700 for the "INSTALLER 200F/93C Sprinkler - 165F/74C Plate
WARNING" that provides cautions Identification Discharge Coefficient
•
with respect to handling and instal- K = 5.6 GPM /psi / (80,6 LPM /bar /2 )
lation of sprinkler systems and com- Numbers 'Adjustment
ponents. Improper handling and in- - 1/2 inch (12,7 mm)
stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm Finishes
1 a sprinkler system or its compo bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass
l nents and cause the sprinkler to fail UL, C -UL, FM, LPCB and NYC. Plated, or White Painted (Custom paint • to operate in a fire situation or cause. , (5 mm bulb) & TY3505 (3 mm matches and colors other than white
it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by are available on request.)
Page 1 of 4 JULY, 2004 TFP181
•
Page 2 of 4 TFP181
c ' Physical Characteristics 1/2' NPT 5
1 Frame Bronze , f ASSEMBLY
Support Cup . Chrome Plated Steel
Guide Pins Stainless Steel i
Deflector Bronze FRAME _j/ ` ` t.
Compression Screw Brass it •1 i_nl � Att. 1' CAP
Bulb Glass < 1111111 t ` �� Cap Bronze or Copper SUPPORT Sealing Assembly CUP WITH BULB
Beryllium Nickel w/Teflon' ROLL FORMED )
Cover Plate Brass THREAD ) _ � I'�I
Retainer Brass A S COMPRESSION
Ejection Spring .... Stainless Steel ,
GUIDE 01 .�,'� SCREW
Patents PINS (2)
4,014,388 () �� /
I - I DEFLECTOR
(DROPPED
Operation DEFLECTOR s:,= POSITION)
ti
When exposed to,heat from a fire, the SPRINKLER/SUPPORT CUP
Cover Plate, which is normally sol- I ASSEMBLY I
dered to the Retainer at three points,
falls away to expose the Sprinkler As THREAD INT I RETAINER
SUPPORT CUP k) I WITH THREAD
sembly. At this point the Deflector sup- • , UNTIL MOUNTING ` O 0 ` DIMPLES
ported by the Guide Pins drops down SURFACE IS
to its operational position. FLUSH WITH EJECTION
The glass -Bulb contains a fluid that CEILING SPRING
expands when exposed to heat. When •
the rated temperature is reached, the
fluid expands sufficiently to shatter then �,
glass Bulb, activating the sprinkler and
allowing water to flow. SOLDER COVER
TABS (3) COVER PLATE/RETAINER PLATE
ASSEMBLY
D FIGURE 1
Cri SERIES RFII CONCEALED SPRINKLER
ASSEMBLY
The RFII (TY3551 & TY3504), 5 mm
Bulb Type, Concealed Pendent Sprin- Step 1. The sprinkler must only be
klers are UL and C -UL Listed as stand- Installation installed in the pendent position and
ard, response - standard spray sprin- with the centerline of the sprinkler per -
klers for use in accordance with the The Series RFII must be installed in pendicular to the mounting surface.
current NFPA standard. They are FM accordance with the following instruc- ••
Step Remove the Protective Cap.
Approved as standard response - tions: •
standard spray sprinklers for use in NOTES Step 3. With pipe thread sealant ap-
accordance with the current FM Loss plied to the pipe threads, hand tighten
Prevention Data Sheets. Do not install any bulb type sprinkler if the sprinkler into the sprinkler fitting.
the bulb is cracked or there is a loss of Ste 4. W rench tighten the sprinkler
The RFII (TY3531 & TY3505) 3 mm liquid from the bulb: With the sprinkler p g p
using F
Bulb Type, Concealed Pendent Sprin- held horizontally, a small air bubble the RFII Sprinkler Wrench
(Ref. Figure nkler
k
W
klers are UL and C -UL Listed as quick should be present. The diameter of the. s to ' be The RFII Sprin
response - standard spray sprinklers air bubble is approximately 1/16 inch Wrench h h w in n Figure 3.
applied to the Sprin
kler as
for use in accordance with the current (1,6 mm) for the 155 °F /68 °C and 3/32 shown i
NFPA standard. They are FM Ap- inch (2,4 mm) for the 200 °F /93 °C tern Step 5. Replace the Protective Cap
proved as standard response - stand- perature ratings. (Ref. Figure 4) by pushing it upwards
ard spray•sprinklers for use in accord- until it bottoms out against the Support
ante with the current FM Loss A leak tight 1/2 inch NPT sprinkler join Cup. The Protective Cap helps prevent
Prevention Data Sheets. should be obtained with a torque of ' damage to the Deflector and Arms dur-
The Series RFII Concealed Pendent to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi i ng ceiling installation and /or during
Sprinklers Seri aye only,, o Concealed mum of 21 ft.lbs. (28,5 Nm) of torque application of the finish coating of the
listed and ant is to be used to install sprinklers.
proved with the Series ncealed
ceiling.- It may also be used to locate
Cover Plates having a metallic or white Higher levels of torque may distort the the center of the clearance hole by .
painted finish. 'sprinkler inlet with consequent leak gently pushing the ceiling material up
age, or impairment of the sprinkler. against the center point of the Protec-
The Series RFII must not be used in p
Do' not attempt to compensate for in tiv e Cap.
applications where • the air pressure sufficient adjustment in the Sprinkler
�: above the ceiling is greater than that Assembly by under- or over- tightening NOTE .
below. Down drafts •through the Sup . the Sprinkler /Support Cup Assembly. As long as the Protective Cap remains
port Cup could delay sprinkler,opera Readjust the position of the sprinkler in place; the system is considered to
tion in a fire situation. ' • ' fitting to suit. be "Out of Service ".
Registered Trademark of DuPont
1
TFPI 81 Page 3 of 4
FACE OF CLEARANCE HOLE CLEARANCE
cj
\SPRINKLER - DIAMETER HOLE
FITTING DIMENSION C
J ►
l =i
SPRINKL •
r
l 11 SUPPEMBLY \
ASSEMBLY ii
1/2° (12,7 mm) , ,
tAll IR W
THREADED
_____
D ADJUSTMENT I �
FACE OF CEILING t
RETAINING RING �' FIGURE 4
MOUNTING DISPOSABLE PROTECTIVE CAP
1
SURFACE 1 • i
�/ QI ' \ / ► � Step 6. After the ceiling has been com
_ pleted with the 2 -1/2 inch (63,5 mm)
A I -- diameter clearance hole and in prepa-
Y ration for installing the Cover Plate As-
' I _ I ' _ sembly, remove and discard the Pro -
• 1.
T tective • Cap,.'and verify that the
3/16" to 11/16° MANUFACTURER DEFLECTOR COVER PLATE Deflector moves up and down freely. If
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER the Sprinkler has been damaged and
REFERENCE . 3/32" (2,4 mm) ' POSITION' ASSEMBLY the Deflector does not move up and
down freely, replace the entire Sprin-
COVER PLATE COVER PLATE kler assembly. Do not attempt to mod-
- PROFILE DEPTH : - DIAMETER ify or repair a damaged sprinkler.
DIMENSION'B DIMENSIONA Step 7. When installing an Air and
Dust Seal, refer to Figure 5, otherwise
proceed to Step 8. To attach the Air and ,
A: 3 -1/4" (82,6 mm) C: 2 -3/8" to 2 -5/8" (60,3 to 66,7 mm) Dust Seal, verify the angle of the out -
B: 3/16" (4,8 mm) D: 1 -3/4" to 2 -1/4" (44,5 to 57,2 mm) side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
FIGURE 2 the Retainer in the grooved slot of the
SERIES RFII CONCEALED SPRINKLER Air and Dust Seal and continue around
INSTALLATION DIMENSIONS Dust Seal retainer until the entire Air and
Dust Seal is engaged.
• NOTE
P The Air and Dust Seal is only to be
installed on the periphery of the Re-
• tamer.
►t� FRAME % ► �
_ % } Step 8. Screw on the Cover Plate /Re- •
ii T1 ! — tamer Assembly until the Retainer -
(
C i � % — � � Figure 2 (or Air and Dust Seal - Figure
SUPPORT 5) contacts with the ceiling. Do not
continue to screw on the Cover
' CUP ; Plate /Retainer Assembly such that it
11111* 1 ' 0 — 11E1� ' lifts a ceiling panel out of its normal
MI i � ,,,�, �� position. If the Cover Plate /Retainer
�% Assembly cannot be engaged with the
Support Cup or the Cover Plate /Re-
7/8° (23 mm) tamer Assembly cannot be engaged
SQUARE sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
ALIGN
O
ARROWS WITH Care and
FRAME ARM
Maintenance
ACCEPTS The Series RFII must be maintained
O 1/2° sOCKET and serviced in accordance with the
DRIVE following instructions:
.
� NOTES
FIGURE 3 Absence of the Cover Plate Assembly
. RFII SPRINKLER WRENCH • may delay sprinkler operation in a fire
situation. .
•
Page 4 of 4 TFP181
When properly installed, there is a SUPPORT SPRINKLER FACE OF ORIENT
' i nominal 3/32 inch (2,4 mm) air gap CUP =------ CEILING SEAL
between the lip of the Cover Plate and
;
I % BEVEL AS
the ceiling, as shown in Figure 2. This l =�` i SHOWN
air gap is necessary for proper opera- PLATE �1 G.j
tion of the sprinkler. If the ceiling is to + RETAINER repainted after the installation of ith — i►` ASSEMBLY " - -. . the Sprinkler care must be exercised - -/ to ensure that the new paint does NOT ) ' Al 5 . seal off an of the air a t � I. CLEAN
1
Factory painted Cover Plates MUST / " '���� ROOM
� r � � LIP OF COVER SEAL
NOT be repainted. They should be re RETAINER PLATE
placed, if necessary, by factory
painted units. FIGURE 5
Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504)
the Enclosure. Separation may result.
Before closing a fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT
main control valve for maintenance local requirements and /or national SHALL TYCO FIRE PRODUCTS' LI-
work on the fire protection system that codes. ABILITY .EXCEED AN AMOUNT
it controls, permission to shutdown the EQUAL TO THE SALES PRICE.
affected fire protection system must be L imited THE FOREGOING WARRANTY IS
obtained from the proper authorities MADE IN LIEU OF ANY AND ALL.
and all personnel who may be affected
by this action must be notified.. W arranty OTHER WARRANTIES EXPRESS OR
Sprinklers that are found to be leaking IMPLIED. INCLUDING WARRANTIES
S
P 9 Products manufactured by Tyco Fire OF MERCHANTABILITY AND FIT -
or exhibiting visible signs of corrosion y Y /NESS FOR A PARTICULAR PUR-
must be replaced. Products are warranted solely to the
original Buyer for ten (10) years
Automatic sprinklers must never be POSE.
against defects in material and work-
painted, plated, coated or otherwise manship when paid for and properly
altered after leaving the factory. Modi- installed and maintained under normal Ordering
fied sprinklers must be replaced.
Sprinklers that have been exposed to use and service. Ti warranty will ex- Procedure
products of combustion, but pire ten (10) years s from date of ship -
co not operated, should be replaced ment by Tyco Fire Products. No war- When placing an order, indicate the full
ranty is given for products or roduct name. Contact our local dis-
if they cannot be completely cleaned P Y
by wiping the sprinkler with a cloth or components manufactured by compa- tributor for availability.
. by brushing it with a soft bristle brush. Hies not affiliated by ownership with Sprinkler Assembly:
Tyco Fire Products or for products and Specify: (SIN), (specify temperature
Care be exercised dam- components which have been subject rating) Series RFII Concealed Pen -
age the sprinklers nklers before, during, 9. to misuse, improper installation, corro- dent Sprinkler, P/N (specify).
and after installation. Sprinklers dam- sion, or which have not been installed,
aged by dropping, striking, wrench maintained, modified or repaired in ac-
twist/slippage, or the like, must be re- cordance with applicable Standards of 1 79 0 - 1-1 2790 - 1-2
placed. Also, replace any sprinkler that PP TY355 51-790-1-155 51-790-1-200
P P Y P the National Fire Protection Associa- TY3504 51- 796 -1 -155 51 -796-1-200
has a cracked bulb or that has lost tion, and /or the standards of any other TY3531 51- 792 -1 -155 51 -792 -1 -200
liquid from its bulb. (Ref. Installation Authorities Having Jurisdiction. Mate - TY3505 51- 797 -1 -155 51- 797 -1 -200
Section). rials found by Tyco Fire Products to be
If a sprinkler must be removed, do not defective shall be either repaired or Separately Ordered Cover Plate:
reinstall it or a replacement without replaced, at Tyco Fire Products' sole Specify: (specify temperature rating)
reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate
If a Cover Plate 'Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify).
dislodged during service, replace it im- assume for it, any other obligation in
mediately. connection with the sale of products or 6- 792 1-1 3) 165Fn4c
parts of products. Tyco Fire Products Brass 56- 792 -1 -135 56- 792 --165
P P Y Bright Brass 56- 792 -2 -135 56 =792 -2 2 -165
The owner is responsible for the in- shall not be responsible for sprinkler chrome 56 -792 -9 -135 56- 792 -9 -165
spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome - --- - protection system and de- incomplete information supplied by White 56 792 792 -3 8 -135 135 56 792 792 -3-165 8 -165
their fire
P Y P PP Y White (RAL9010)' 56- 792 -3 -135 56- 792 -3 -165
vices in compliance with this docu- Buyer or Buyer's representatives. Bright White 56- 792.4 -135 56- 792 -4 -165
ment, as well as with the applicable IN NO EVENT SHALL TYCO FIRE OH White 56- 792 -5-135 56- 792 -5 -165
standards of the National Fire Protec- PRODUCTS BE LIABLE, IN CON- Clack 56-792-6-135 56- 792 -X -165
Custom 56- 792 -X -135 56- 792 -X -165
tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR
addition to the standards of any other UNDER ANY OTHER LEGAL THE- (a) For use with 155F/68C sprinklers.
authorities having jurisdiction. The in- (b) For use with 200F/93C sales s onl y . ers.
91 ORY, FOR INCIDENTAL, INDIRECT, • Eastern Hemisphere sales only.
stalling contractor or sprinkler manu- SPECIAL OR CONSEQUENTIAL
A facturer should be contacted relative to DAMAGES, INCLUDING BUT NOT . Sprinkler Wrench:
any questions. LIMITED TO LABOR CHARGES, RE- Specify: RFII Sprinkler Wrench,
'.' It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56-000-1-075.
sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal:
tested, and maintained by 'a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal,
P/N 56- 908 -1 -001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
•