DESIGN OF - HVAC UNIT CONNECTION TO ROOF CURB
AND CONNECTION OF ROOF CURB TO ROOF
DESIGN CRITERIA:
GROUP: • SEISMIC USE II
• SEISMIC DESIGN CATEGORY: D, E, OR F � -��}
• HEAVIEST UNIT TOTAL WEIGHT: WP = 1600# 30 06 2012
CITY OF i OIL
TOTAL LATERAL FORCE (USING ASCE 7 -02 9.6.1.3) BUILDING
F _ 0.4 apSDSWPIP 1 +2 z
Fp RP(1.4) h
ap =1.0
SDS =1.0 (max)
WP =1600#
IP =1.0
RP = 2.5
z = UNIT ATTACHMENT POINT IN STRUCTURE ABOVE BASE
h = ROOF HEIGHT ABOVE BASE
— = 1.0 FOR ROOF TOP HVAC UNITS
Fp -
(0.4)(1 .0) (1.0) (1600) (1.0) k1+ 2(1.0))
2.5 (1.4)
Fp = 549#
CHECK,
FpMm = 0.3 SDS WP IP 1
Fpm = (0.3) (1.0) (1600) (1.0) 1 = 343# < 549# OK
1.4
USE 549#
. • ARROW MECHANICAL CONTRACTORS, INC.
10330 S.W. TUALATIN RD.
TUALATIN, OREGON 97062
PHONE: (503) 692 -1565
FAX: (503) 691 -1879
OVERTURNING ON UNITS:
3.5'
MIN.
1.5'
MIN.
40 Wp = 1600#
- Fp = 549#
C.G.
3.5'
MAX.
UNIT TO CURB
CURB TO ROOF
END VIEW HVAC UNIT
DIMENSION REQUIREMENTS
MOT = (Fp) (Vert. Dist. to Center of Gravity) = (549) (3.5) = 1922 FT - LBS
MR = (Wp) (Reduction for Load Combination) (Least Horiz. Dist. to Center of Gravity) = (1600) (0.9X1.5) = 2160 FT - LBS
Mn > MOT .. TENSION AND UPLIFT CONNECTIONNOT REQUIRED DESIGN FOR SHEAR ONLY.
.f i (4) #10 SCREWS BASE UNIT (20 GA)
AT LOCATIONS SHOWN
AI A
Al (4) #10 SCREWS
� `:`_` INACCESSIBLE 16 GA CURB
`�� AREA, CONDENSER
COIL END
PLAN VIEW DETAIL A -A
UNIT TO CURB DESIGN:
549
V (ACTUAL) = =137# / SCREW
4 SCREWS
' V (ALLOWABLE) =177# / SCREW IN 20 GA MATERIAL (REF : ER - 4943P)
177# >137# OK
USE (4) #10 SCREWS
,/ d ,2o / —ar
7379 5 72c
COM check Software Version 3.8.2
Mecha Comp Certificate
Oregon Energy Efficiency Specialty Code
Section 1: Project Information
Project Type: Addition
Project Title : Spectra Contract Flooring
Construction Site: Owner /Agent: Designer /Contractor:
7379 SW Tech Center Dr. Arrow Mechanical
Tigard, OR 97223 10330 SW Tualatin Rd
Tualatin, OR 97062
503 -692 -1565
Section 2: General Information
Building Location (for weather data): Tigard, Oregon
Climate Zone: 4c
Section 3: Mechanical Systems List
Quantity System Type & Description
1 HVAC System 1 (Single Zone) :
Heating: 1 each - Central Furnace, Gas, Capacity = 60 kBtu/h, Efficiency = 95.50% Et
Cooling: 1 each - Split System, Capacity = 24 kBtu/h, Efficiency = 13.00 SEER, Air - Cooled Condenser
Section 4: Requirements Checklist
In the following requirements, the relevant code section reference is shown in [ ]. ' +' denotes that more details exist in the specified code
section.
Requirements Specific To: HVAC System 1 :
1 1. [503.2.3 +] Equipment meets minimum efficiency: Central Furnace (Gas): 80.0 % Et (or 78% AFUE)
0/2. [503.2.3 +] Equipment meets minimum efficiency: Split System: 13.0 SEER
Generic Requirements: Must be met by all systems to which the requirement is applicable:
L+4 ' . [503.2.1 +] Calculation of heating and cooling loads. Design loads are determined in accordance with the procedures described in the
ASHRAE/ACCA Standard 183. Alternatively, design loads have been determined by an approved equivalent computation procedure.
2. [503.2.1.1 +] Packaged Electric Equipment. Specified packaged electrical equipment has a heat pump as the primary heating source.
O Exception: Unstaffed equipment shelters or cabinets used solely for personal wireless service facilities.
Location In plans/specs where compliance can be identified (enter NA if not applicable)• 4-11A
G °• [503.3.1 +] Cooling equipment economizers: The total capacity of all cooling equipment without economizers must be less than 240
kBtu /h. This project lists 24 kBtu/h capacity without economizers. That portion of the equipment serving dwelling units and guest rooms
is not included in determining the total capacity of units without economizers.
Location In plans/specs where compliance can be Identified (enter NA If not applicable) •
lld". [503.2.2 +] Equipment and system sizing. Heating and cooling equipment and systems capacity do not exceed the loads calculated in
accordance with Section 503.2.1.
o Exception: Required standby equipment and systems provided with controls and devices that allow such systems or equipment to
operate automatically only when the primary equipment is not operating.
o Exception: Multiple units of the same equipment type with combined capacities exceeding the design load and provided with
controls that have the capability to sequence the operation of each unit based on load.
Project Tdle: Spectra Contract Flooring Report date: 06 /04/12
Data filename: Untitled.cck Page 1 of 5
•
• • • •
Location in plans/specs where compliance can be identified (enter NA if not applicable):
' 34". [503.2.3 +] HVAC Equipment Performance Requirements. Reported efficiencies have been tested and rated in accordance with the
applicable test procedure. The efficiency has been verified through certification under an approved certification program or, if no
• certification program exists, the equipment efficiency ratings are supported by data furnished by the manufacturer.
ov4. [503.2.4.1 +] Thermostatic Controls. The supply of heating and cooling energy to each zone is controlled by individual thermostatic
controls that respond to temperature within the zone.
•
Location in plans/specs where compliance can be Identified (enter NA if not applicable)"
7. [503.2.4.1.1] Heat pump supplementary heat_ Heat pumps having supplementary electric resistance heat have controls that, except
• "air-4 defrost, prevent supplementary heat operation when the heat pump x1/41. can heating load. -
• Location in plans/specs where compliance can be Identified (enter NA if not applicable)"
• 3 [503.2.4.2] Set point overlap restriction. Where used to control both heating and cooling, zone thermostatic controls provide a
temperature range or dead band of at least 5 °F (2.8 °C) within which the supply of heating and cooling energy to the zone is capable of
being shut off or reduced to a minimum.
❑ Exception: Thermostats requiring manual change over between heating and cooling modes.
Location in plans/specs where compliance can be identified (enter NA if not appliirabte)
. l9. [503.2.4.3] Optimum Start Controls. Each HVAC system has controls that vary the start-up time of the system to just meet the
temperature set point at time of occupancy.
Location in plans/specs where compliance can be identified (enter NA If not applicable)"
L9 [503 :2.4.4 +] Off -hour controls. Each zone is provided with thermostatic setback controls that are controlled by either an automatic time
clock or programmable control system.
❑ Exception: Zones that will be operated continuously. •
❑ Exception: Zones with a full HVAC load•demand not exceeding 6,800 Btu/h (2 kW) and having a readily accessible manual shutoff
• 'switch. _ ..
•
L ocation in plans/specs w comp can be Identified (enter NA if not applicable) '
❑ 11. [503.2.4.5 +] Shutoff damper controls. Both 'o'utdoor air supply and exhaust are equipped with not less than Class I motorized dampers.
. ❑ Exception: Gravity dampers shall be permitted for outside air intake or exhaust airflows of 300 cfm or less.
Location in plans /specs where compliance can be Identified (enter NA if not applicable)" IVA
•
❑ 12. [5032.4.6 +] Freeze Protection and Snow melt system controls. Freeze protection systems, such as heat tracing of outdoor piping and
heat exchangers, including self - regulating heat tracing, include automatic controls capable•of shutting off the systems when outdoor air
temperatures meet code criteria.
•
Location In plans /specs where compliance can be Identified (enter NA if not applicable)
❑ 13. [503.24:8] Separate air distribution systems. with special process temperature requirements and /or humidity requirements are
served by separate air distribution systems from those serving zones requiring only comfort conditions; or shall include supplementary
control provisions so that the primary systems may be specifically controlled for comfort purposes only.
❑ Exception: [503.2.4.8 +) Zones requiring only comfort heating or comfort cooling that are served by a system primarily .used for
process temperature and humidity control.
•
Location in plans/specs where compliance can be identified (enter NA if not applicable) Ml�
❑ 14. [503.2.4.9] Humidity control. If a system is equipped with a means to add or remove moisture to maintain specific humidity levels in a
zone or zones, a humidity control device is provided.
• • Location In plans/specs where compliance can be identified (enter NA if not applicable)" Al' /Ay, • • 0 .15. [503.2.4.9.1] Humidity control. Where a humidity control device exists it is.set to prevent the use of fossil fuel or electricity to produce
relative humidity.in excess of 30 percent. Where a humidity control device is used for dehumidification, it is setto prevent the use of
fossil fuel or electricity to reduce relative humidity below 60 percent.
❑ Exception: Hospitals, process needs, archives, museums, critical equipment, and other non-comfort situations with specific humidity
requirements outside this range. •
Location In plans/specs where compliance can be identified (enter NA if not applicable)" A)
❑ 16. [503.2.4.9.2] Humidity control. Where a humidity control device,exists it is set to maintain a deadband of at least 10% relative humidity
• where no active humidification or dehumidification takes place. •
❑ .Exception: Heating for dehumidification is provided with heat recovery or heat pumping and the mechanical cooling system
efficiency is 10 percent higher than required in section 503.2.3, HVAC equipment performance requirements.
•
•
• Project Title: Spectra Contract Flooring : Report date: 06/04/12
•
Data filename: Untitled.cck Page 2 of 5
Location in plans/specs where compliance can be identified (enter NA if not applicable). � /
d ' 17. [503.2.5] Ventilation. Ventilation, either natural or mechanical, is provided in accordance with Chapter 4 of the International Mechanical
Code. Where mechanical ventilation is provided, the system has the capability to reduce the outdoor air supply to the minimum
required by Chapter 4 of the International Mechanical Code.
Location in plans/specs where compliance can be identified (enter NA if not applicable)"
❑ 18. [503.2.5.1 +] Demand controlled ventilation (DCV). DCV is required for spaces larger than 500 ft2 for simple systems and spaces larger
than 150 ft2 for multiple zone systems.
❑ Exception: Systems with energy recovery complying with Section 503.2.6
❑ Exception: Spaces less than -750 ft2 (69.7 m2) where an occupancy sensor turns the fan off, doses the ventilation damper, or doses
the zone damper when the space is unoccupied. ee//II�p
Location in plans/specs where compliance can be identified (enter NA if not applicable) MIS
❑ 19. [503.2.5.2 +] Kitchen hoods. Kitchen makeup is provided as required by the Oregon Mechanical Specialty Code.
❑ Exception: Where hoods are used to exhaust ventilation air that would otherwise be exhausted by other fan systems.
❑ Exception: Kitchen exhaust systems that include exhaust air energy recovery complying with section 503.2.6.
Location in plans/specs where compliance can be identified (enter NA if not applicable)* 1 4
❑ 20. [503.2.5.3 +j Enclosed parking garage ventilation controls. In Group S -2, enclosed parking garages used for storing or handling
automobiles employs automatic carbon monoxide sensing devices. p
Location In plans/specs where compliance can be identified (enter NA if not applicable)* /w 1
❑ 21. [503.2.6 +] Energy recovery ventilation systems. Individual fan systems that have both a design supply air capacity of 5,000 cfm or
greater and a minimum outside air supply of 70 percent or greater of the design supply air quantity have ah energy recovery system.
❑ Exception: Where energy recovery systems are prohibited by the International Mechanical Code.
❑ Exception: Systems serving spaces that are not cooled and are heated to less than 60 °F.
❑ Exception: Where more than 60 percent of the outdoor heating energy is provided from site- recovered or site solar energy.
❑ Exception: Type 1 kitchen exhaust hoods.
❑ Exception: Cooling systems in climates with a 1- percent cooling design wet -bulb temperature less than 64 °F (18 °C).
❑ Exception: Systems requiring dehumidification that employ series -style energy recovery coils wrapped around the cooling coil when
the evaporative coil is located upstream of the exhaust air stream.
❑ Exception: Systems exhausting toxic, flammable, paint exhaust, corrosive fumes, or dust.
❑ Exception: Laboratory fume hood systems that include qualifying features.
Location in plans/specs where compliance can be Identified (enter NA if not applicable)* i4)
0722. [503.2.7 +] Duct and plenum insulation and sealing. All supply and return air ducts and plenums are insulated with the specified
insulation. When located within a building envelope assembly, the duct or plenum is separated from the building exterior or
unconditioned or exempt spaces by a minimum of R -8 insulation. All ducts, air handlers and filter boxes are sealed. Joints and seams
comply with Section 603.9 of the International Mechanical Code.
❑ Exception: When located within equipment.
❑ Exception: When the design temperature difference between the interior and exterior of the duct or plenum does not exceed 15 °F
(8 °C).
.43. [503.2.7.1.1 +] Low - pressure duct systems. All longitudinal and transverse joints, seams and connections of low- pressure supply and
return ducts are securely fastened and sealed with welds, gaskets, mastics (adhesives), mastic -plus- embedded -fabric systems or
tapes installed in accordance with the manufacturer's installation instructions.
❑ Exception: Continuously welded and locking -type longitudinal joints and seams on ducts operating at static pressures less than 2
inches w.g. pressure classification.
Location in plans/specs where compliance can be identified (enter NA if not applicable)'
❑ 24. [503.2.7.1.2 +] Medium - pressure duct systems. All ducts and plenums designed to operate medium - pressure are insulated and sealed
in accordance with Section 503.2.7. Pressure classifications specific to the duct system are clearly indicated on the construction
documents. 1 �
Location in plans/specs where compliance can be identified (enter NA if not applicable)
❑ 25. [503.2.7.1.3 +] High - pressure duct systems. Ducts designed to operate at high - pressure are insulated and sealed in accordance with
Section 503.2.7. In addition, ducts and plenums are leak- tested in accorrrdal y� with the SMACNA HVAC Air Duct Leakage Test Manual.
Location in plans/specs where compliance can be identified (enter NA if not applicable)* , yi A
Project Title: Spectra Contract Flooring Report date: 06/04/12
Data filename: Untitled.cck Page 3 of 5
0726. [503.2.9.1 +] Air system balancing. Each supply air outlet and zone terminal device is equipped with means for air balancing in
- • accordance with the requirements of IMC 603.17. Discharge dampers intended to modulate airflow are prohibited on constant volume
fans and variable volume fans with motors 10 horsepower.
Location In plans/specs where compliance can be identified (enter NA if not applicable)'
• /27. [503.2.9.3 +] Manuals. The construction documents require that an operating and maintenance manual be provided to the building
owner by the mechanical contractor. See long description for specifications.
Location in plans/specs where compliance can be identified (enter NA if not applicable):
❑ 28. [503.2.10 +] Air System Design and Control. Each HVAC system having a total fan system motor nameplate hp exceeding 5 hp meets
- the - provisions of Sections 503.2.10.1 through 503.2.10.2. - - -
Location In plans/specs where compliance can be Identified (enter NA if not applicable) A/
• ❑ 29. [503.2.10.1 +) Allowable fan floor horsepower. Each HVAC system at fan system design conditions does not exceed the allowable fan
system motor nameplate hp (Option 1) or fan system bhp (Option 2) as shown and calulated in requirement details.
❑ Exception: Hospital and laboratory systems that utilize flow control devices on exhaust and /or return to maintain space pressure
relationships necessary for occupant health and safety or environmental control shall be permitted to use variable volume fan power
limitation.
❑ Exception: Individual exhaust fans with motor nameplate horsepower of 1 hp or less. •
Location in plans/specs where compliance can be identified (enter NA If not applicable)' 1,1,/
❑ 30. [503.2.10.2 +] Motor nameplate horsepower. For each fan, the selected fan motor is no larger than the first available motor size greater
than the brake horsepower (bhp).
❑ Exception: For fans less than 6 bhp, where the first available motor larger than the brake horsepower has a nameplate rating within
50 percent of the bhp, selection of the next larger nameplate motor size is allowed.
❑ Exception: For fans 6 bhp and larger, where the first available motor larger than the bhp has a nameplate rating within 30 percent of
the bhp, selection of the next larger nameplate motor size is allowed.
Location In plans/specs where compliance can be identified (enter NA if not applicable)* / /
❑ 31. [503.2.10.3.1] Large Volume Fan Systems. Fan systems over 8,000 (7 m31s) cfm without direct expansion cooling coils that serve
single zones reduce airflow based on space thermostat heating and cooling demand. A two -speed motor or variable frequency drive
reduces airflow to a maximum 60 percent of peak airflow or minimum ventilation air requirement as required by Chapter 4 of the
International Mechanical Code, whichever is greater.
❑ Exception: Systems where the function of the supply air is for purposes other than temperature control, such as maintaining specific
humidity levels or supplying an exhaust system.
Location in plans/specs where compliance can be identified (enter NA if not applicable)*
❑ 32. [503.2.10.3.2 +] All air - conditioning equipment and air - handling units with direct expansion cooling and a cooling capacity at ARI
conditions greater than or equal to 110,000 Btu/h that serve single zones have their supply fan operation controlled according to code
specific requirements.
❑ Exception: Systems where the function of the supply air is for purposes other than temperature control, such as maintaining specific
humidity levels or supplying an exhaust system.
Location in plans/specs where compliance can be identified (enter NA if not applicable)* 14/4,
❑ 33. [503.2.10.4] Series fan - powered terminal unit fan motors. Fan motors for series fan - powered terminal units are
electronically- commutated motors and have a minimum motor efficiency of 70 percent when rated in accordance with NEMA Standard
MG 1 -2006 at full load rating conditions.
Location in plans /specs where compliance can be identified (enter NA if not applicable)'
❑ 34. [503.2.12] Hot Gas Bypass Limitation. For cooling systems <= 240 kBtu /h, maximum hot gas bypass capacity is no more than 50%
total cooling capacity.
Location in plans/specs where compliance can be identified (enter NA if not applicable) M 4
Section 5: Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the Oregon
Energy Efficiency Specialty Code requirements in COMcheck Version 3.8.2 and to comply with the mandatory requirements in the
• Requirements Checklist. /,
•
t7t✓s72r k' c ' PL
Project Title: Spectra Contract Flooring Report date: 06/04/12
Data filename: Untitled.cck Page 4 of 5
REQUIRED OUTDOOR VENTILATION AIR
IN ACCORDANCE WITH TABLE 403.3 2010 OMSC
UNIT AREA SQUARE PEOPLE NUMBER OF O.S.A. CFM PER MIN.
SERVED FOOTAGE PER 1000 SQ -FT PEOPLE CFM / SQFT PERSON O.S.A. CFM
F -1 Office 353 5 2 -- 5 9
TOTAL -- 353 -- 2 -- -- 9
GAS PIPE CALCULATIONS
Based on 2010 OMSC Table C402.4(3)
Schedule 40 Metallic Pipe, 2.0 PSI Inlet Pressure
GAS INPUT DELIVERY
• EQUIPMENT BTU PRESSURE
EXISTING GAS PACK - GP -1 60,000 2 PSI
EXISTING GAS PACK - GP -2 115,000 2 PSI
EXISTING UNIT HEATER - UH -1 350,000 2 PSI
NEW FURNACE - F -1 60,000 2 PSI
TOTAL LOAD 585,000 2 PSI
LONGEST RUN 297'
GAS PIPE SIZING BASED ON 2 PSI DELIVERY AT 300'
SIZE MAX. CAPACITY
1 1/2" 1,442,000
1" 947,000
3/4" 232,000
1
N 9 , MSE
- -- - ..IE , PS 9 0;
i s
Heating and J1)ducts Product Specifications i.
95.5% AFUE Single Stage PSC Gas Furnace
EASIER TO SELL
• 95.5% AFUE, all models all positions, California NOx approved -,--_,.,-,•!14,-.. ,r -`
• Certified to leak 2% or less of nominal air conditioning CFM
delivered when pressurized to 1 -inch water column with all �#
present air inlets, air outlets, and condensate drain port(s) sealed vs}
• Approved for Twinning applications (0601714 through 1202420)' j
with accessory (order separately) ,� k>�
• Approved for Manufactured Housing/Mobile Home applications ,4,1:;,,L , i k ' ' 4
(0401410 through 1202420) with accessory (order separately) 4 0K i ,r j
TOUGHER s It. . _
• Flame roll -out sensors standard - . , r"; ` ' ` { 1
• Adjustable heating blower OFF delay . .,,,,'„7.ea a '
• Factory set blower ON delay ' y;, a'
• RPJ aluminized steel primary heat exchanger .' w Gxf -
• Stainless steel secondary heat exchanger , -,_e-,"4 - 1^4,i1 '
• High temperature limit control prevents overheating trs 3. : _i
• Direct ignition with Silicon Nitride ignitor ' f�
• High quality, corrosion- resistant, prepainted steel cabinet
EASIER TO INSTALL AND SERVICE Das and are Drdy representative.
Some product models may vary.
• Direct vent (2- pipe), single -pipe venting or ventilated combustion 0 WARNING
air • 24 VAC humidifier terminal & electronic air cleaner terminal CARBON MONOXIDE POISONING AND FIRE HAZARD
• 35" (889mm) high, for ease of installation Failure to follow this warning could result in personal injury,
Simplified, factory installed internal condensate drain system death, and/or property damage.
• Si
►nP �Y � This furnace is not designed for use in recreation vehicles or
• Innovative knobs for easy door removal and secure outdoors. This furnace is designed for use in manufactured
attachment (Mobile) homes when an optional Mobile Home accessory kit is
installed.
• Factory shipped for natural gas, with propane Failure to follow this warning could result in personal injury,
gas conversion kits available death, and/or property damage.
• Four position - upflow /downflow/horizontal (left/right) installation
• At least twelve different venting configurations ENER�ji n %
• Through the casing flue pipe for counterflow or horizontal
applications with accessory (order separately) aaer Fur um:maaYaewcy (AFUE)
, -I
• Concentric vent available
• Setf diagnostics with super bright LED I FRiIF‘t"
• Slide out heat exchanger and blower assembly Ell ); dwx: I
WARRANTY * a 9
• 20 heat exchanger limited warranty
• 5 year parts limited warranty a .. Lipp
CERTIFIED
- With timely registration, an additional 5 year parts limited r ■TS CERTIFIED
warranty
• Applies to original purchaser/homeowner, some limitations may uea of aw AHRI GNfied TM MaM indeatea a
manufacturer's partutipaton to " urn p`°°`°"'' For
apply. See warranty certificate for complete details.
rwifioatnn of carfififatlon fn vrdnidual product,
go to were .ahridireclory .ap .
Cooling Capacity
Input Efficiency CFM range Dimensions H x W x D Shipping Wt.
Model Number (MBTUH) AFUE @ .5 in. w.c. (125 Pa) Inches (Millimeters) Lbs (Kg)
N9 S 04 01410 A 40,000 95.5% 625 -905 35 x 14 -3/16 x 29 -1/2 (889 x 361 x 750) 123 (55)
, f�\ t-9 N9MSE0601410A 60,000 95.5% 675 -1130 35 x 14 -3/16 x 29 -1/2 (889 x 361 x 750) 127 (57)
N9MSE0601714A 60,000 95.5% 650 -1420 35 x 17 -1/2 x 29 -1/2 (889 x 445 x 750) 144 (65)
N9MSE0801716A 80,000 95.5% 810 -1600 35 x 17 -1/2 x 29 -1/2 (889 x 445 x 750) 154 (69)
N9MSE0802120A 80,000 95.5% 1225 -2025 35 x 21 x 29 -1/2 (889 x 533 x 750) 162 (73)
N9MSE1002114A 100,000 95.5% 695 -1565 35 x 21 x 29 -1/2 (889 x 533 x 750) 169 (76)
• N9MSE1002120A 100,000 95.5% 1225 -2145 35 x 21 x 29 -1/2 (889 x 533 x 750) 169 (76)
N9MSE1202420A - 120,000 95.5% 1245 -2065 35 x 24 -1/2 x 29 -1/2 (889 x 622 x 750) 186 (84)
N9MSE1402420A 140,000 95.5% 1230 -2100 35 x 24 -1/2 x 29 -1/2 (889 x 622 x 750) 190 (86)
Specifications are suelect to change without notice. 440 21 4401 01 Feb. 2012
El _ .
. PRODUCT SPECIFICATIONS Gas Furnace: N9MSE
:. PHYSICALjt
. UNIT SIZE (NATURAL GAS Ratings) 0401410A ( O60 0601714A 0801716A 0802120A
Input Heat (BTUH) 40,000 60,000 60,000 80,000 80,000
Output Heat (BTUH) 39,000 58,000 58,000 78,000 78,000
Efficiency AFUE % (ICS) 95.5 .
Certified Temperature Rise Range 4 F (¢C) 40- 70(22 -39)
UNIT SIZE (NATURAL GAS Ratings) 1002114A 1002120A 1202420A 1402420A
Input Heat (BTUH) 100,000 100,000 120,000 140,000
Output Heat (BTUH) 97,000 97,000 117,000 135,000
Efficiency AFUE % (ICS) 95.5
Certified Temperature Rise Range °F (QC) 40- 70(22 -39)
ICS - Isolated Combustion System
- AIRFLOW CAPACITY AND BL).UER,DATA: _ - " ;
UNIT SIZE 0401410A 0601410 0601714A 1 0801716A 0802120A
Heating 0.10(.025) 0.12(.05) 0.12(.05) 0.15(.38) I 0.15(.38)
Certified External Static Pressure in.w.c.(kPa)
Cooling .5 (.125)
• Heating 820 840 980 1040 1500
Airflow Delivery @ Rated ESP (CFM) Cooling 005 1130 1420 1600 2025
Cooling Capacity (tons) @ 400 CFM/ton 2 2.5 3.5 4 5
400, 350 CFM/ton • 350 CFM/ton 2.5 3 4 4.5 5.5
Direct -Drive Motor Type PSC - Permanent Split Capacitor
Direct -Drive Motor HP 0.5 0.5 0.5 0.75 0.75
Motor Full Load Amps 6.2 6.2 6.8 + 7.9 I 13.8
RPM Range 500 -1150
Speed Selections 4 4 5 5 5
Blower Wheel Dia x Width I inches 11 x 7 11 x 7 11 x 8 11 x 8 11 x 10
Air Filtration System Field Supplied
Filter Used for Certified Watt Data • NAHAO0806FB I NAHA00506FB I NAHA00606FB
UNIT SIZE 1002114A 1002120A I 1202420A I 1402420A
Heating 0.24050) 0.20(050) 0.20(.050) 0.20(.050)
Certified External Static Pressure In.w.c.(kPa)
Cooling .5 (.125)
. Heating 1565 1520 2210 2190
Airflow Delivery @ Rated ESP (CFM)
Cooling 1565 2145 2085 2100
Cooling Capacity (tons) @ 400 CFM/ton 4 5 5 5
400, 350 CFM/ton 350 CFM/ton 4.5 6 6 6
Direct -Drive Motor Type PSC - Permanent Split Capacitor
Direct -Drive Motor HP 0.75 0.75 0.75 0.75
Motor Full Load Amps 6.5 13.8 I 14.1 14.1,
RPM Range 500 -1150
Speed Selections 5 5 I 5 I 5
Blower Wheel Dia x Width I inches 11 x 10 11 x 10 11 x 11 11 x 11
Air Filtration System Field Supplied
Finer Used for Certified Watt Data NAHA00606FB I NAHA00706FB
•
440 21 4401 01 Specifications subject to d1°"ge without notice. 3
, .
, .
. .. . . . .
. . . .
PRODUCT SPECIFICATIONS • . „ . . ' .. - - . '. - p. - 1 : - . . Gas Furnace: N9M$E
CONTROLS
. UNIT SIZE 0401410A 601410A I 0601714A I 0801716A I 0802120A
Gas Connection Size 1/2" - NPT
Burners (Monoport) 2 I 3 I 3 I 4 I 4
Gas Valve (Redundant) I Manufacturer White Rogers'
Minimum Inlet Gas pressure in. w.c. (kPa) 4.5 (1.1)
. Maximum Inlet Gas pressure in. w.c. (kPa) 13.6 (3.4)
Gas Conversion Kit - Natural to Propane NAHA00901 LP
Gas Conversion Kt - Propane to Natural NAHA00901NG
Manufactured (Mobile) Home Kit NAHA00101MH
Ignition Device Silicon Nitride
Limit Control 165 I 165 I 180 I 170 I 200
Heating Blower Control (Heating Off-Delay) Adjustable: 90, 120, 150, 180 seconds
Cooling Blower Control (Time Delay Relay) 90 seconds
Thermostat Connections R, W, Y, G, C
Accessory Connections EAC (115vac); HUM (24vac) •
UNIT SIZE 1002114A I 1002120A I 1202420A I 1402420A
Gas Connection Size 1/2" - NPT
Burners (Monoport) 5 I 5 I 6 1 7
Gas Valve (Redundant) I Manufacturer White Rogers'
Minimum Inlet Gas pressure in. w.c. (kPa) 4.5 (1.1)
Maximum Inlet Gas pressure in. w.c. (kPa) 13.6 (3.4)
Gas Conversion Kt - Natural to Propane NAHA00901 LP
Gas Conversion Kit - Propane to Natural NAHA00901 NG
Manufactured (Mobile) Home Kit NAHA00101MH I N/A
Ignition Device Silicon Nitride
Limit Control 180 I 180 I 160 I 155
Heating Blower Control (Heating Off-Delay) Adjustable: 90, 120, 150, 180 seconds
Cooling Blower Control (lime Delay Relay) 90 seconds
Thermostat Connections R, W, Y, G, C
Accessory Connections EAC (115vac); HUM (24vac)
v ,''''' •-•'-': :;;'.. : ; '-. '''
:...,• ',-*,:: ',- '-''''' - ,.■'...:: - _c '..-
UNIT SIZE 0401410A I 0601410A) I 0601714A I 0801716A I 0802120A
Input Voltage (Volts-Hertz-Phase) 115 - 60 - 1
Operating Voltage Range Min-Max 104 - 127
Maximum Input Amps Amps 6.8 7.0 8.4 9.8 14.5
Unit Ampacity Amps 9.5 9.7 11.5 13.0 19.1
Minimum Wire Size AWG 14 14 14 14 12
Maximum Wire Length @ Min Wire Size Feet (M) 39(11.9) 38(11.6) 32(9.8) 28(8.5) 30(9.1)
Maximum Fuse/Circuit Breaker
(lime-Delay Type Recommended) Amps 15 15 15 15 20
Transformer Capacity (24 vac Output) 40 VA
Heating 27.9 VA
External Control Power Available
_ Cooling 34.8 VA
UNIT SIZE 1002114A I 1002120A I 1202420A I 1402420A
Input Voltage (Volts-Hertz-Phase) 115 - 60 - 1
Operating Voltage Range Min-Max 104 - 127
Maximum Input Amps Amps 7.6 14.6 14.9 14.9
Unit Ampacity Amps 10.4 19.2 19.6 19.8
Minimum Wire Size AWG 14 12 12 12
Maximum Wire Length @ Min Wire Size Feet (M) 35(10.7) 29(8.8) 29(8.8) 29(8.8)
Maximum Fuse/Circuit Breaker
(Time-Delay Type Recommended) Amps 15 20 20 20
Transformer Capacity 24 vac Output / 40 VA
1 Heating 27.9 VA
External Control Power Available
Cooling 34.6 VA
4 Specifications subject to change without notice. 440 21 4401 01
. PRODUCT SPECIFICATIONS • Gas Furnace: N9MSE s
' UNIT`DIMENSIONS ' .
1
, ,-
. a li
!I e $ I
e SI eg
i I .S I
°s o�
O a1 rr„ 0 ...
I .:2__
A A .5._
P RE
li • e � �
LI
si
<
1.(1
RE e_
M -
5
FIR
&
c as ^ 1 —
—
eG j + 1 1 boy 4
gEl 41 &
a r ... a c� � ^/ i , *Ta giv,. Ep og - —T
p, I
flt i `�1 Ri e 7_, cl 1 m. 1. 1 1 1 4 4ffi
si f
440 21 4401 01 Specifications sugect to change without notice. 5
•
- PR ODUCT SPECIFICATIONS : Gas Furnace: N9MSE
A B C D
CABINET BOTTOM SHIP WT.
FURNACE SIZE WIDTH OUTLET WIDTH INLET WIDTH AIR INTAKE LB (KG)
0401410 14 -3/16 (361) 12 -1/2 (319) 12 -9/16 (322) 7 -1/8 (181) 123 (55)
f e- , (0601410 14 -3/16 (361) 12-1/2 (319) 12 -9/16 (322) 7-1/8 (181) 127 (57)
0601714 17 -1/2 (445) 15 -7/8 (403) 16 (406) 8 -3/4 (222) 144 (65)
0801716 17 -1/2 (445) 15 -7/8 (403) 16 (406) 8 -3/4 (222) 154 (69)
0802120 21 (533) 19 -3/8 (492) 19 -1/2 (495) 10 -1/2 (267) 162 (73)
1002114 21 (533) 19 -3/8 (492) 19 -1/2 (495) 10 -1/2 (267) 169 (76)
1002120 21 (533) 19 -3/8 (492) 19 -1/2 (495) 10 -1/2 (267) 169 (76)
1202420 24-1/2 (622) 22 -7/8 (581) 23 (584) 12-1/4 (311) 186 (84)
1402420 24-1/2 (622) 22 -7/8 (581) 23 (584) 12-1/4 (311) 190 (86)
NOTE:
1. Doors may vary by model.
2. Recommended air duct dimensions and configurations:
a. For 800 CFM 16 -in. (406 mm) round or 14 1/2 x 12 -in. (368 x 305 mm) rectangle.
b. For 1200 CFM 20 -in. (508mm) round or 14 14 x 19 / -in. (368 x 495 mm) rectangle.
c. For 1600 CFM 22 -in. (559 mm) round or 14'1 x 22 1/16 -in. (368 x 560 mm) rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Installation Instructions for specific use of single side
inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only return air openings may be
required for airflow requirements above 1800 CFM at 0.5 in. w.c. ESP
.i4L�.'.'.r..a'.'i'M1a�'�4L"` %.R i: �: � � - ��'�.Fi.. .., ..iii �! `..c�, �,. .
-r. `:K; ,1,11 _ ,90. EARA g °
- IPCOU$ BT; HIA S' OFt, Li ,1 t S' : : �° ��� w _ ;';;
J rs >.J` .. +. y F� H . , ..m • _ .Y'sp F .MQ
. -'m � a... , LE :MA W. , xle dry .� -r b, ,..
v�3 k.
POSITION CLEARANCE
REAR 0
FRONT (Combustion air openings in furnace and in structure) 1 (25)
Required for service 24 (610)
All Sides of Supply Plenum 1 (25)
Sides 0
Vent 0
Top of Furnace 1 (25)
6 Specifications subject to change without notice. 440 21 4401 01
N4
c Performance Series
.-.,--,••,,,,•:,•••-: :and:;OOhng °Proucts •: b-w.. :Product . S ecifica# .
EFFICIENT 13 SEER AIR CONDITIONER
ENVIRONMENTALLY SOUND R -410A REFRIGERANT
1 -1/2 THRU 5 TONS SPLIT SYSTEM 1 ;}J
208 / 230 Volt, 1- phase, 60 Hz
REFRIGERATION CIRCUIT
• Scroll compressors on all models ,,iI = = 7 -- y - i i ,
• Filter -Drier supplied with every unit for field installation
,,II 1 1_,...J_.:----1, ;,III.
• Copper tue / aluminum fin coil ��1 -i; t EASY TO INSTALL AND SERVICE 1 Iji t t 6I M : IP
• Easy Access service valves on all models (1 _ i : ; :i ,
• External high and low refrigerant service ports l ~ -
• Only two screws to access control panel I� 1 : i - l---` • • Factory charged with R -410A refrigerant 1 '. . :: - - -. - -- -- -� ; , 1
,i
BUILT TO LAST '% -= — " i - i _, it
• Baked -on powder coat finish over galvanized steel i ; ;- _- - __ - - -- . ��j
• Post-painted (black) coil fins i ` - 1 --? - ._ - i •i.
• Coated, weather - resistant cabinet screws
• Coated inlet grille with 2" (51mm) spacing standard, '`
alternate models available with 3/8" (10mm) gnlle spacing
for extra protection (hail guard) A RIOP -
WARRANTY* 1 ■ ■%l CERTIFIED,. C ® US c - w v: r:. abridireblo'Y. cry,
• 5 year compressor limited warranty LISTED
Use of the `u'Rp in the Indicates °
• 5 year parts limited warranty (including compressor
manufacturer's program. For
and coil) verification of certification for individual products,
go to wnrw.ehrldirectory.org .
- With timely registration, an additional 5 year parts
limited warranty (including compressor and coil)
* Applies to original purchaser/homeowner, some limitations may apply. See Warranty certificate for complete details.
Model Size Nominal Min. Circuit Max. Fuse Operating Dimensions Ship I Operating
. Number (tons) BTU /hr Ampacity or Breaker height x width x depth in. (mm) Weight lbs. (kg)
N4A318AKB 1 -1/2 18,000 11.8 20 25 -5/16 x 23 -1 /8 x 23 -1/8 130 / 107
18G KB same model with 3/8" (10mm) spacing inlet grille (hail guard (643 x 587 x 587) (59 / 49)
. /t- ( 6N4A324A14 2 1 24,000 I 17.6 I 25 25 - 5/16 x 23 - 1/8 x 23 - 1/8 134 / 110
24GKB same model with 3/8" (10mm) spacing inlet grille (hail guard) (643 x 587 x 587) (61 / 50)
N4A330AKC 2 - 1/2 I 30,000 1 16.8 25 28 - 11/16 x 23 - 1/8 x 23 - 1/8 136 / 111
30GKC same model with 3/8" (10mm) spacing inlet grille (hail guard) (729 x 587 x 587) (62 / 50)
N4A336AKB 3 I 36,000 I 21.5 I 30 31 - 13/16 x 25 - 3/4 x 25 - 3/4 170 / 141
36G KB same model with 3/8" (10mm) spacing inlet grille (hail guard) (808 x 654 x 654) (77 / 64)
N4A342AKA 3 - 1/2 I 42,000 I 23.5 I 40 32 - 5/16 x 31 - 3/16 x 31 - 3/16 208 / 180
42GKA same model with 3/8" (10mm) spacing inlet grille (hail guard (821 x 792 x 792) (94 / 82)
. N4A348AKB 4 I 48,000 I 26.2 1 40 35 - 3/4 x 31 - 3/16 x 31 - 3/16 215 / 178
48GKB same model with 3/8" (10mm) spacing inlet grille (hail guard) (908 x 792 x 792) (98 / 81)
N4A360AKC 5 I 60,000 I 34.2 I 50 25 - 1/2 x 31 - 3/16 x 31 - 3/16 218 / 184
60G KC same model with 3/8" (10mm) spacing inlet grille (hail guard) (648 x 792 x 792) (99 / 84)
Specifications subject to change without notice.
421 21 5103 01 Sep 2010
•
•
A • 'f0
IN) . O
po A m. M AIR IN AIR
Cf
8 AIR DISCHARGE D DISCHARGE I '
I / ;'13,
( CENTER OP GRAIRY }
I FIELD CONTROL AIR IN //
1 1 111
SUPPLY COON. frit(")!'"--,:—..',.-.. Y 1111 B �i /8• HOLE _ 1 �, ,
FIELD POWER SUPPLY COIN, o 1 \t /1� 1 i CI 1
ql ve HOLE NM hil
I ` ` F
Qil lir NNOCAOUr 1 �1 {\ /•
ale �`., A � . ' :3 LIQUID well. 17, P .' �� \ \ ` ��
C 3 112' �_ , a_ _ R c �''_\\` � --� /
_ 1 116• I a • i _ __ /
Er OD VAPOR LINE CONK. I L
I
5/1r-- I •3/8' 1IEDONN ANOCAOUIS
g Ii) PLACES Y •:.'
5 — K
IR IN I
Dimensions Inches (English) , v r
Model Minimum crated . ,y
(` = A or G) A B C D E F G K L M N P Mounting Dimensions ,•
Pad Size hxwxd I, m
�' rt
N4A318*KB 23-1/8 25 -5/16 3-3/4 3/4 4-7/16 18-1/16 7 -13/16 2 -13/18 1/2 16-12 15 12 23-12 x23-12 33-12 x 27-3/8 x 24-1/4 "3
N4A324 *KB 23-1/8 25 -5/1e 3-3/4 3/4 4-7/16 18-1/16 7 -19/19 2 -13/16 1/2 16-1/2 15 12 23- 12x23 -12 33-12 x 27-3/8 x 24-1 /4 � '+
N4A330*KC 23-1/8 28 -11/18 3-3/4 3/4 4-7 /16 18-1/16 7 -13/16 2 -13/16 1/2 16-12 15 14 23-12 x 23-12 33-12 x 27-3/8 x 24-1/4 ;: 0 •
N4A336°KB 25-3/4 31 -13/18 3-7/8 7/8 6-0/16 21 -1/4 9-1/8 2 -15/16 5/8 14-1/4 10-1/2 to 26x26 35- 15/16x90- 1/1®Q6 -7/8 1 p ,'
N4A342°KA 31-3/16 325/16 3-7/8 7/8 8-0/16 24 -11/16 9-1/8 2 -15/16 5/8 15-3/4 16-1/4 13-3/4 31 -12 0 31 -12 33-12 x 35-12 x 32-3/8 , o
3 ■
N4A348 *KB 31-3/16 35-9/4 3-7/8 7/8 6-0/16 24-11/16 ` 9-1/8 2 -15/16 5/8 14-3/4 15-9/8 15 31 -12 x 31 -1/2 39-3/8 x 35 323/8 • • m •
N4A360 *KC 315/16 25-12 3-7/8 7/8 6-0/16 24-11/16 9-1/8 2 -15/16 518 14-1/8 15-318 11-314 31 -12 x 31 -12 32 -0/18 x 35-12 x 32-3/8 ' Z •
C.: t
•
PRODUCT SPECIFICATIONS : • S plit.S y sterim Air Conditioner -N4A3
�l
Model Size 18 NYSIC
24 30 36 42 48 60
Nominal Cooling Capacity (BTU/hr) 18,000 24,000 30,000 36,000 42,000 48,000 60,000
Nominal SEER 13.0 13.0 13.0 13.0 13.0 13.0 13.0
Sound Rating (dBA)** 72 76 74 75 78 80 78
PSC Fan Motor HP 1/12 1/10 1/10 1/4 1/5 1/4 1/4
Fan RPM (single speed) 1100 1100 1100 1100 1100 1100 800
Fan CFM 1792 2218 2218 2954 3167 3365 3365
Coil Face Area ft (m2 8.40 8.40 9.80 13.13 17.25 19.40 12.93
(.78) (.78) (.91) (1.22) (1.6) (1.8) (1.2)
Coil Rows - fins per inch 1 - 20 1 - 25 1 - 25 1 - 25 1 - 25 1 - 25 2 - 20
Liquid Line Connection Size in. (mm) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10)
Vapor Line Connection Size in. (mm) 3/4 (19) 3/4 (19) 3/4 (19) 7/8 (22) 7/8 (22) 7/8 (22) 7/8 (22)
Recommended Line Set Liquid Tube 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10)
Diameter in. (mm)
Recommended Line Set Vapor Tube 3/4 (19)* 3/4 (19)* 3/4 (19)* 7/8 (22)* 7/8 (22)* 7/8 (22)* 1 Ye (29)*
Diameter in. (mm)
* Recommended Vapor Tube Line size is for standard installations. These recommendations may not apply to
"Long Line" installations. When the total equivalent line length exceeds 80 feet (24.4m) or there is more than 20
feet (6.1m) vertical separation between indoor and outdoor units, consult the Long Line Application Guideline
document before purchasing/installing line sets.
Factory Charge R -410A lbs. (kg) 3.50 3.80 4.10 5.34 5.84 7.00 8.19
(1.59) (1.72) (1.86) (2.42) (2.65) (3.18) (3.71)
Required Subcooling °F (°C) 10 (6) 10 (6) 10 (6) 14 (8) 10 (6) 15 (8) 13 (7)
Weight, shipping lbs. (kg) 130 (59) 134 (61) 136 (62) 170 (77) 208 (94) 216 (98) 218 (99)
Weight, operating lbs. (kg) 107 (49) - 110 (50) _ 111 (50) 141 (64) 180 (82) 179 (81) 184 (84)
ELECTRICAL DATA (208/230.1 --:,60, voltage range.197V = -2531n
Model Size 18 24 30 36 42 48 60
Minimum Circuit Ampacity -
11.8 17.6 16.8 21.5 23.5 26.2 34.2
MCA (amps)
Maximum OverCurrent 20 25 25 30 40 40 50
Protective device - MOCP (amps)
Compressor RLA (Rated Load Amps) 9.0 13.5 12.8 15.3 17.9 19.9 , 26.4
LRA (Locked Rotor Amps) 48.0 58.3 64.0 77.0 112.0 109.0 134.0
Fan Motor FLA (Full Load Amps) _ .5 .77 .77 1.4 1.1 1.4 - 1.2
**Sound Rating tested in accordance with ARI Standard 270 -95 (not listed with ARI).
•
421 21 5103 01 Specifications subject to change without n°6ce. 5
[Page Too Large for OCR Processing]