Loading...
Specifications BUP 00 3/'t 5 V/.5 w O ►-►-_a- METRO Safety & Fire, Inc. 14324 SE Stark St. RECEIV Portland, Oregon 97233 ocT 14 503- 231 -2999 ?IGO WOW Description of Scope of work for: The City of Tigard Senior Center — Fire Alarm Panel Upgrade. We are proposing to install a Silent Knight Addressable fire alarm Panel to replace the existing Edwards Conventional fire alarm system. We will be connecting the fire sprinkler system water flow switch and valve supervisory switches to the new panel along with replacing all smoke detectors with Addressable smoke detectors. In addition to the sprinkler and the smoke detections, we will be connecting the kitchen ansul suppression fire system to the fire alarm system. The manual pull stations will remain and we will install conversion modules behind each on to give them an individual address. The existing horns, horns strobes and strobes will remain. The garden room additions is not part of this scope of work, but was added to ensure proper capacity. When the smoke detector, manual, pull station, kitchen fire suppression system, or fire sprinkler water flow switch are activated, the horn strobes will activate and remain activated until silenced by someone at the fire alarm control panel. The fire alarm control panel has battery backup capability provided by (2) 12 volt, 12.0 amp hour batteries. (See Battery Calc.) This system is monitored by a central monitoring station. • METRO Safety & Fire, Inc. 14324 SE Stark St. Portland, Oregon 97233 503 -231 -2999 City of Tigard, Senior Center - LEGEND SYM DESCRIPTION BOX REQUIRED MOUNTING HEIGHT I FACP1 Fire Alarm Control Panel N/A Bottom at 54" A.F.F. O S Smoke Detector Switch Box On Ceiling P Manual Pull Station Single Gang Bottom at 48" A.F.F. O Alarm Horn / Strobe 4" Square Bottom at 88" A.F.F. or On Ceiling. I ANSUL] Kitchen Fire Suppression N/A At Suppression System Control. METRO Safety & Fire, Inc. 14324 SE Stark St. Portland, Oregon 97233 • 503 - 231 -2999 City of Tigard, Senior Center, Panel Upgrade - Zone Description & Layout Zone Description Standby Alarm Total 1 Library Room Smoke .055uf .055uf .055uf 2 Library Room Pull Station .055uf .055uf .055uf 3 Entry Lobby Smoke Detector .055uf .055uf .055uf 4 Entry Lobby Pull Station .055uf .055uf .055uf 5 Entry Lobby Pull Station .055uf .055uf .055uf. 6 Up Stairs Office Area Smoke .055uf .055uf .055uf 7 Outside Upper Bath Smoke .055uf .055uf. .055uf 8 Hall Smoke Detector .055uf .055uf .055uf 9 Hall Smoke Detector .055uf .055uf .055uf 10 Hall Smoke Detector .055uf .055uf .055uf 11 Hall Smoke Detector .055uf .055uf .055uf. 12 Upper Lvl Rear Exit Pull .055uf. .055uf .055uf 13 Ansul Suppression System .055uf .055uf .055uf 14 Lower Lvl FACP Smoke .055uf .055uf .055uf 15 Lower Lvl Water Flow .055uf .055uf .055uf 16 Lower Lvl Sprinkler Tampers .055uf .055uf .055uf 17 LL Conference Room Smoke .055uf. .055uf. .055uf. 18 LL East Exit Pull Station .055uf .055uf .055uf 19 LL Hall Smoke Detector .055uf .055uf .055uf 20 LL Hall Smoke Detector .055uf .055uf .055uf 21 LL Hall Smoke Detector .055uf .055uf .055uf 22 LL West Exit Pull Station .055uf .055uf. .055uf 23 Arts / Crafts Smoke Detector .055uf .055uf .055uf 24 Garden Room Entry Smoke .055uf .055uf .055uf 25 Garden Room Conf. Rm Smk .055uf .055uf .055uf 26 Garden Rm Entry Lobby Pull .055uf .055uf .055uf 27 Garden Room Conf. Rm Pull .055uf .055uf .055uf Silent Knight 5700 Fire Alarm Control Unit 200ma. .325ma. NAC Circuit #1 (3) 15 Candela Strobes .0 .060ma. .180ma. (5) 15 Candela H/S .0 .074ma. .370ma. (2) 75 Candela H/S .0 .184ma. .368ma. NAC Circuit #2 (5) 15 Candela H/S .0 .074ma. .370ma. (1) 110 Candela H/S .0 .244ma. .244ma. CURRENT DRAW ON DEVICES ' .349ma. 1.85 lamp. STAND BY ALARM TOTAL TOTAL TOTAL STANDBY .349ma. X 24 HOURS X 24 8.376amp. TOTAL ALARM 1.857amp X 5 MINUITES ALARM (.083333) X.084 .1560ma. Standby Total 8.376amp. + .Alarm Total .1560ma. = 8.532amp. Total Battery Amp Hours Required = 8.532 AH. De rating of batteries by 1.2 = 1023 AH. We will be using (2) 12 volt 12.0 AH batteries. r METRO Safety & Fire, Inc. 14324 SE Stark St. Portland, Oregon 97233 503- 231 -2999 City of Tigard, Senior Center - Tigard, Oregon - Equipment List Silent Knight Addressable Fire Alarm Control Panel SK -5700 Silent Knight Addressable Photoelectric Smoke Det. SD505 -APS Silent Knight Manual Pull Station SD500 -PS Wheelock Horn / Strobe, Multi Candela ZNS -24MC Battery Patrol Battery PS 1270 System Sensor Supervisory Switch PTS- C(Provided by others) System Sensor Water Flow Switch WF(Provided by others) INTELLIKNIGHT FIRE ALARM CONTROL PANEL • 15 u p goz} s'- 0 IntelliKnight® Model 5700 Single Loop Addressable i 4 6and 4"! Fire Alarm Control System 1 ..:1 ; JH The affordable addressable fire alarm ¢ control panel solution. , v.t",:.,,:, /e . : , -.7_,„..,. - ., ( IntelliKnight Model 5700 is a 50 point class leading single loop addressable fire alarm control /communicator system. 5700 provides you :n .W. - with the revolutionary value and performance of addressable sensing technology combined with exclusive, built -in digital communication, distributed intelligent power, that includes an easy to use interface. Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from Silent Knight. For more information about the IntelliKnight system, or to locate your nearest source, please call 1- 800 -446 -6444, or in Minnesota, call 763 - 493 -6435. Description • RS-485 bus provides communication 5700 performs drift compensation and to system accessories . '.. ' - �, : - -, calibration checks on each of the • Upload or download programming, - _J sensors in the system. event history, or detector status - . The basic IntelliKnight 5700 system onsite or from a remote location can be enhanced by adding modules using a PC and 5660 Silent Knight such as 5860 remote annunciator, Software Suite (SKSS) • - ? - - 5824 serial /parallel printer interface • Improvements in SKSS deliver five module (for printing system reports), times faster upload /downloads ` and 5496 intelligent power module. • Built -in RS -232 interface for 5700 also features a powerful built -in programming via PC • dual line fire communicator that allows • Built -in Form C trouble relay rated at .. • : . for reporting of all system activity to a 2.5A at 27.4 VDC ! i, remote monitoring location. • Two built -in Form C programmable , Features relays rated at 2.5A at 27 VDC • Programmable date setting for . • Up to 50 addressable points Daylight Saving Time • Up to 125 zones and 125 output Model 5700 groups Electrical Specifications • Uses standard wire —no shielded or Primary AC: 120 VAC, 60 Hz, 1.5A Telephone Requirements: twisted pair required Total Accessory Load: 2.5A @ 27.4 FCC Part 15 and Part 68 approved • Built -in digital communicator. VDC Type of Jack: RJ31X (two required) • Central station reporting by point or Notification Power. 2.5A @ 27.4 VDC, by zone power limited Approvals • Supports Class B (Style 4) and Class Standby Current: 200 mA NFPA 13, NFPA 15, NFPA 16, NFPA A (Style 6 or 7) configuration for SLC Alarm Current: 325 mA 70, & NFPA 72: Central Station; • Distributed, intelligent power Notification /Aux Power Circuits: Remote Signalling; Local Protective • Drift compensation 2.5A @ 27.4 VDC per circuit, Signalling Systems; Auxiliary Protected power - limited Premises Unit; & Water Deluge • 13 pre - programmed output cadences Battery Charging Capacity: 7.0 -35.0 AH Releasing Service. Suitable for (including ANSI -3.41) and 4 g programmable outputs Battery Size: 7 AH max. allowed in automatic, manual, waterflow, sprinkler FACP cabinet. Larger capacity supervisory (DACT non - coded) • Notification circuits configurable as 1 batteries can be housed in an RBB Class A (Style Z) or 2 Class B (Style accessory cabinet. signalling services. Y), or auxiliary power for resettable, Other Approvals: UL Listed; constant, or door holder power Mechanical S CSFM 7170 -0559: 144; • Built -in synchronization for AMSECO, Dimensions: MEA 429 -92 -E Vol. XVI. Gentex®, Faraday, System Sensor 12.75" W x 15.2" H x 3.4" D and Wheelo rail appliances (32.39 W x 38.42 H x 8.57 D cm) k SILENT • Built -in annunciator with 80- character Weight: 11.5 lbs. (5.2 kg) KNIGHT r LCD display Color: Red by Honeywell IN`FELLIKNIGHT FIRE ALAREv1 CONTROL PANEL SLC Detectors_ S Modules 5880 LED /lO Module SD505 -APS Model SD500 -AIM Features 40 LED Addressable photoelectric smoke detector. Dry contact input module for use with outputs, 8 normally open dry c SD505 - AIS normally open dry contacts. It features an and one piezo out f c ont a ct inputs Addressable ionization smoke detector. indicator LED to show alarm status. SD500 -MIM 5865 and 5865 -4 SD505 -AHS Remote LED Absolute temperature heat detector that Mini dry contact input module is a small Annunciator goes into alarm immediately if the version of the SD500 -AIM. For use with pull Features 30 temperature exceeds the programmable trip stations and other normally open dry contact Programmable LED (15 point. Trip point range from 135 °F -150 °F inputs. red and 15 yellow) outputs and a piezo (0 °C- 37 °C). SD500 - ANM sounder. The 5865 -4 adds a silence and Addressable notification module providing a reset switch to the package. SD505 single Class A or Class B notification circuit Six inch base for use with detector heads 9 5883 Relay Board SD505 -APS, SD505 -AIS and SD505 -AHS. on the SLC. Features 10 general purpose Form C relays. SD505 - 4AB SD500 - ARM Used with 5880 module. Four inch base for use with detector heads Addressable relay module that features two 5824 Serial /Parallel Printer SD505 -APS, SD505 -AIS, and SD505 -AHS. Form C output relays. Provides indicator Interface Module LED to show output status. Provides one parallel and one RS-232 senal SD505 - 6SB port for connecting a printer to 5808. Use to Six -inch sounder base for use with existing T SD500 -SDM wo -Hire detector i nput module. Allows for Print a real -time log of system events, sensor and base. Operates in single and the connection of conventional 2 -Hire detector status reports, and event history. multi- station modes and /or as a system detectors on the SLC loop. Requires two Interfaces with building control system. sounder. Requires 2 additional wires for power. additional wires for power. Miscellaneous Accessories SD505 - 61B SD500 - LIM A short circuit isolator module for SLC 5660 Silent Knight Software Suite Short circuit isolator base for SD505 AHS, devices. When a short occurs on the SLC User - fnendly Windows software for remote SD505 -APS, and SD505 -AIS detectors loop, it is detected as a trouble, but all SLC programming of 5700s using a PC. Upload SD505 - 6RB devices protected by the isolator module and view panel account information, event Six -inch relay base for use with existing continue to operate. history, and detector status. sensor and base. Provides one Form C SD500 - LED 5670 Silent Knight Software Suite contact. An LED driver capable of driving 80 LEDs End -user facility management software SD505 - ADH through the SLC loop. Up to 40 allows viewing of detector status and event Duct housing that detects smoke in HVAC SD500 -LEDs can be used per system. history via modem or direct connection. ducts. RBB • S Accessories R emote Battery Box Accessory Cabinet. Use SD505 - ADHR rY rY Duct detector base with relay. Provides 5860/R Remote Fire Annunciator if backup batteries are too large to fit into . Form C alarm contact. For use with Features the same 80 character backlit LCD FACP cabinet. Dimensions: - SD505 -APS and SD505 -AIS sensors. display keypad and firefighter's key switch 16" W x 10" H x 6" D Compatible with SD505 -DTS remote test as the 5700. The system can be fully (406 mm W x 254 mm H x 152 mm D) switch. programmed and operated from any 5860. SD505 - DTS SD500 PS /SD500 - PSDA 5860 is gray and 5860R is red. Remote test switch that provides remote key SD500 -PS is a single action pull station and 5496 Intelligent Power Module operated test function and annunciation of SD500 -PSDA is a dual action pull station. A 6 amp notification power expander that detector alarm with SD505 -ADHR. provides four additional power - limited notification appliance circuit outputs. Y .1.5gi �ti ! n , -r., , -r., , i sax: __ 4, it,,, t P< k t g "Mioat: .dr 1 ,Wt. 01 'Il. , . f t 4 +" , ti b 1, i .'_. .:.." s - s f s ova �r C J.J f a ' 4 r H i. , r. p,. .,as,,,, gab ,° .., rye �] ;~1 i� . %; y n4 �" y i i.. ;.a2. y t' 4 .,2=1, ,..,&_;','&47.,..h.-=4!._-.... ..,& t o rim.: t . ia- ....i.. 'Li;� 5700 5496 SILENT This document is not intended to be used for installation purposes. We try to MADE IN AMERICA ` KNIGHT keep our product information up -to -date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are FORM# 350392 Rev. D, 04/06 subject to change without notice. For more information, contact Silent Knight Copyright ©2006 Silent Knight by Honeywell 7550 Mendian Circle Suite 100, Maple Grove, Mn 55369 -4927. g Phone: (800) 328 -0103, Fax. (763) 493 -6475. • IntelliKnight & JumpStart are Registered Trademarks of Silent Knight Flexput is a Trademark of Silent Knight INTELLIKNIGHT ACCESSORY - '' Addressable y 2 Lu C1 � ° , Photoelectric Type : ,_ <���' Smoke Detector . , :, Detect smoldering fires quickly and get } ,,� -.' , . help fast with IntelliKnight® photoelectric y am ` . s moke detectors. IntelliKnight addressable photoelectric smoke detectors are the clear choice for commercial settings where smoldering fires are a threat. In addition to accurately detecting a smoldering fire, each SD505 -APS photoelectric detector has a unique address, which is recognized by the IntelliKnight panel. No precious seconds are wasted in determining location of an alarm. The SD505 -APS compensates automatically for contamination in the environment. And detector testing is simple —even from a remote site. Like other IntelliKnight detector models, the SD505 -APS offers a low profile for pleasing aesthetics. The IntelliKnight family of detectors has been designed to use a common base, Model SD505 -6AB, allowing complete application and placement flexibility. Combine all this with the features you've come to expect from Silent Knight smoke detectors —easy installation, stable operation, RF /transient protection, and vandal- resistant locking —and it adds up to a flexible solution for all your fire protection needs. Model SD505 -APS The light received is converted into Analog / Addressable an electronic signal. Under normal ,ta "' ' ,' Photoelectric Type conditions, the status LED blinks ' t _4,, ` - _ ,� Smoke Detector approximately every 15 seconds, _ - `•k / ' The SD505 -APS is particularly indicating that the head is • ' " i r+' , suited to detecting dense smoke communicating with the loop. The t • " typical of fires involving materials LED lights continuously during the such as soft furnishings, plastic, alarm period. °° foam or other similar materials Features which tend to smolder and produce • Low profile, 2 inches, including SD505 -APS Smoke Detector large visible particles. base Specifications The detector features automatic • Simple and reliable addressing Operating Voltage: 17 VDC compensation for contamination without mechanical switches Current Consumption: and a simple detector calibration • Automatic compensation for test procedure that can be run from sensor contamination Standby: .55 mA the panel or remotely (using the • Built -in fire test feature Alarm: .55 mA WindowsTM based downloading Simple detector calibration Ambient Temperature:32 °F to 120 °F • software ). ) testing through the control panel (0 C to 49 C Operation or remotely through a Mounting: 4" Square, 4" The SD505 - APS units made up of WindowsTM based computer OCT, single an LED light source and a silicon software. gang mud ring photo diode receiving element. In a • Vandal- resistance locking Relative Humidity: 85% normal standby condition, the features noncondensing receiving element receives no light • Field cleanable from the pulsing light source. In the Air Velocity: 0 300 FPM • UL listed, meets NFPA 72 Ch 7 event or fire, smoke enters the requirements Compatible Bases. SD505 - 6AB detector and light is reflected from (Sold Separately) (6" Base) • CSFM approved SD505 -4AB the smoke particles to the receiving MEA approved (4" Base) • element. • FM Approved SILENT KNIGHT by Honeywell IN`YELLIKNIGHT ACCESSORY Model SD505 -APS Addressable Photoelectric Type 2 - Smoke Detector Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable photoelectric smoke detector Silent Knight SD505 -APS. The combination detector head, and twist -lock base, shall be UL® listed compatible with Silent Knight's IntelliKnight fire control panels. The base shall permit direct interchange with Silent Knight SD505 -AIS Ionization Smoke Detector, or SD505- AHS Heat Detector. Base shall be the appropriate twist -lock base SD505 -6AB. The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal- resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SD505 -APS shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. III = 5 III Diameter = 3- 15116" N W o i ) t ,*---N (7 ' - Height = 2 inches -- - - - - - T Ic% -• including base • EVIGHT Model SD505 -6AB Detector Base Model SD505 -APS Detector Head (front view) (front view) SILENT This document is not intended to be used for installation purposes. We try to MADE IN AMERICA KNIGHT keep our product information up -to -date and accurate. We cannot cover all • specific applications or anticipate all requirements. All specifications are FORM# 350225 Rev C,. 05/05 subject to change without notice. For more information, contact Silent Knight by Honeywell 7550 Mendian Circle Suite 100, Maple Grove, Mn 55369 -4927 Copyright © 2005 Silent Knight _ Phone (800) 328 -0103, Fax. (763) 493 -6475. INTELLIKNIGHT ACCESSORY SD500 -AIM & SD500 -MIM ' -' Addressable Input Modules ' 'i • t 4r117 1, s , IntelliKnight's addressable contact monitor modules combine fast response with pinpoint � v ' , •, _:: location ID. A combination that saves lives and ' : M4 property. t ,, ;.4.:‘, j ; _: The SD500 -AIM and SD500 -MIM are addressable input modules for use with Silent Knight IntelliKnight fire alarm control panels (FACP). The SD500 -AIM and SD500 -MIM are designed to be used with pull stations, water flow switches, and other applications requiring dry contact alarm initiation devices. The SD500 -AIM addressable input module mounts to a 4 "- square box. The SD500 -MIM mini input module fits inside a single gang box. The modules are supervised, single input contact monitors. Using an EOL resister, they monitor for alarm contact closures and for open circuit wiring fault conditions. The SD500 -AIM and SD500 -MIM offer a compact design for adaptability and pleasing aesthetics as well as easy installation and stable operation —a flexible solution for all your fire protection needs. For more information about the IntelliKnight system, or to locate your nearest source, please call 1- 800 -446 -6444, or in Minnesota, call 763 -493 -6435. Description • DIP switch programmable for fast The SD500 -AIM and SD500 -MIM are installation addressable input modules for use with • Up to 2500 ft wiring distance from the Intelliknight fire alarm control either input module to contact panels (FACPs). The SD500 -AIM • Use up to 14 gauge wire 42 . addressable input module mounts to a • UL listed 4 "- square box. The SD500 -MIM mini - input module fits inside a single gang Electrical Specifications D - ' 1 - box. Both input modules are designed Standby Current: 0.55 mA to be used with pull stations, water flow Alarm Current: 23 mA max for one switches, and other applications SD500.MM requiring dry contact alarm initiation device; 46 mA max for two devices; 0.55 mA for each additional device devices. These modules are supervised, single Line Resistance: 500 max , input contact monitors. Using an EOL Mechanical Specifications resistor, they monitor for alarm contact SD500 -AIM Physical Description closures and for open circuit wiring Dimensions: fault conditions. If a fault occurs in the 4.9" W x 4.9" H x 1" D winng, the module alerts the FACP. (12.4 W x 12.4 H x 2.5 D cm) Each addressable input module is Weight: 3.6 oz (120.1 g) SD5o0•ntlM programmed with a unique signal line Color: Ivory cover plate circuit (SLC) loop address. SD500 -MIM Physical Description Approvals Features Dimensions: NFPA 71 & NFPA 72 • Single contact monitor 1.5" W x 2.5" H x 0.7" D UL 864 • SD500 -AIM supports Class A (Style (3.8 W x 6.4 H x 1.8 D cm) CSFM 7300 -0559: 132 D) or Class B (Style B) contact Weight: 1.6 oz (45 4 g) MEA 429-92-E Vol. IX monitor wiring FM Approved for use with the 5820XL Environmental • SD500 -MIM support for Class B Operating Temperature: (Style B) contact monitor wiring 32 °F — 120 °F (0 °C — 49 °C) • Attractive ivory cover plate with the • SD500 -AIM Humidity: SILENT • Small and lightweight size allows for 10% — 93% non - condensing KNIGHT flexible mounting options with the ,. . SD500 -MIM bt Honeyo l IN''FELLIKNIGHT ACCESSORY SD500 -AIM & SD500 -MIM Addressable Input Modules Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable input modules Silent Knight SD500 -AIM or SD500 -MIM. The modules shall be UL listed and compatible with Silent Knights IntelliKnight FACPs. The SD500 -MIM shall fit inside a single gang electrical box. The SD500 -AIM shall be supplied with a plastic cover and shall be suitable for mounting to a 4 "- square or double gang electrical box. The SD500 -AIM addressable input module must provide a monitor LED that is visible from outside the cover plate qp LC CVT „ •y 14 -. , ..::. l'S. T Compatible FACPs Ordering Information 5820XL SD500 -AIM Input Module 5808 Addressable input module with ivory cover plate. 5700 SD500 - MIM Input Module Addressable mini input module. S) I E y This document is not intended to be used for installation purposes. We try to MADE IN AMERICA - ����l keep our product information up -to -date and accurate. We cannot cover all FORM# 350231 Rev D, specific applications or anticipate all requirements. All specifications are • subject to change without notice. For more information, contact Silent Knight © 2008 Honeywell International Inc v Ho : , 7550 Meridian Circle Suite 100, Maple Grove, Mn 55369 -4927. Phone (800) 328 -0103 or 763 -493 -6400 Fax: (763) 493 -6475. www.silentknight.com INTELLIKNIGHT ACCESSORY • Model SD500 -ARM , ._ • __., Addressable Relay Module i . S J-. Place relay applications anywhere y PP yw on the .. `:- IntelliKnight loop with the SD500 -ARM , ' : ' ► Addressable Relay Module. The SD500 -ARM is an addressable device that adds great flexibility to the IntelliKnight system. Providing two Form C contacts rated at 2.0 amps @ 30 VDC or .6 amp @ 120 VAC. The SD500 -ARM allows you to control a wide variety of normally open and normally closed applications, including elevator recall, door closing, fan operation, and auxiliary notification. And, because the relay module is addressable, these applications can be located at any point in the signaling line circuit. Like other IntelliKnight SLC devices, the SD500 -ARM is compact for adaptability and pleasing aesthetics. Combine this with the features you've come to expect from Silent Knight fire protection devices—easy installation and stable operation —and it adds up to a flexible solution for all your fire protection needs. Model SD500 -ARM Features . Addressable Relay Module ; • Two sets of Form C contacts. — \ � • Contacts are rated at 2A @ 30 The 50500 - ARM provides two VDC or .6A @ 120 VAC. © ' ' • { Form C contacts rated at 2A @ NM , 30 VDC or .6A @ 120 VAC. • Up to 127 relays can be used on These contacts can be used for each SLC loop. virtually any normally open or • Relay programming is - normally closed application. completely flexible —can be Model SD500 -ARM mapped to zone conditions. cations • Polling LED visible through Spedfl Operation cover plate. • UL listed, complies with NFPA Contact Rating Form C Each relay module is 72. 2A @ 30 VDC programmed with a unique SLC • CSFM approved .6A @ 120 VAC loop address. When an event • MEAApproved, 429 - 92 - E, Vol. 9 that controls the relay module • FM approved Standby Current: .55 mA occurs, the relay is triggered by Alarm Current. .55 mA the IntelliKnight panel. Ambient 32 °F to 120 °F Temperature (0 °C to 49°C) • SILENT Mounting 4- square electncal box KNIGHT . e INTELLIKNIGHT ACCESSORY Model SD500-ARM Addressable Relay Module Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable relay modules, Silent Knight SD500 -ARM. The modules shall be UL listed compatible with Silent Knight's Intelliknight FACPs. The relay module must provide two Form C dry contacts rated at 2.0 amps at 30 VDC or .6 amp at 120 VAC. The relay module must be suitable for mounting in a standard 4- square electrical box and must include a plastic cover plate. The relay module board must provide an LED that is visible from the outside of the cover plate. The relay must be fully programmable for such applications as are required by the installation. FRONT VIEW 0 .I C .lei. p IC.. Q ICS:; ea�cxr 0 4 -7/8" 1 4 " 1" Model SD500 -ARM Addressable Relay Module Dimensions its SILENT KNIGHT • 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800- 446 -6444 or in Minnesota 763 - 493 -6435 FORM# 350218, Rev. 11/01 FAX: 763-493-6475 World Wide Web: http: //www.silentknight.com Copyright © 2001 Silent Knight • Series Z Strobes, Horns and Horn Strobes - SNAP' COOPER Wheelock Features an easy snap on base designed Strobes to simplify the installation and testing of strobes, horns and horn strobes. Fir k Available features and options: Color: Red or white Mounting: Wall or ceiling Wall Mount Strobe UL Max. Current 15cd 30cd 75cd 110cd ZRS- MCVV-FR Red 4085 EZ mount SNAP design ZRS- MCW-FW White 0302 24 VDC 0.060 0.092 0.165 0.220 ZRS - MCWH -FR Red 5242 Universal mounting plate - single ZRS- MCWH -FW White 0303 UL Max. Current 135cd 185cd plate for wall and ceiling mount in- Ceiling Mount Strobes 24 VDC 0.300 0 420 stallations ZRS- MCC -FW White 0309 Disposable cover to protect base ZRS- MCC -FR Red 0308 UL Max. Current 15cd 30cd 75cd 95cd ZRS - MCCH -FW White 0314 plate ZRS- MCCH -FR Red 5240 24 VDC 0 065 0.105 0.189 0.249 Strobes produce 1 flash per sec- UL Max. Current 115cd 177cd and over the Regulated Voltage 24 VDC 0.300 0.420 Range - Horns and Horn Strobes • Wall or Ceiling Mount Horn ZNH -R Red 0300 ZNH -W White 0301 Wall Mount Horn Strobe ZNS- MCW-FR Red 0304 ZNS- MCVV -FW White 0305 ZNS- MCWH -FR Red 0306 ZNS- MCWH -FW White 0307 Ceiling Mount Horn Strobe ZNS- MCC -FW White 0311 ZNS- MCC -FR Red 0310 ZNS - MCCH -FW White 0313 ZNS - MCCH -FR Red 0312 UL Max. Current 15cd 30cd 75cd 110cd High (95) dBA 24 VDC 0.074 0.107 0.184 0.244 Low (90) dBA 24 VDC 0.066 0.101 0 177 0.232 UL Max Current 15cd 30cd 75cd 95cd High (95) dBA 24 VDC 0.082 0.124 0.209 0.275 Low (90) dBA 24 VDC 0.071 0.114 0.201 0 261 UL Max Current UL Max. Current Audible 115cd 177cd 24 VDC 12 VDC High (95) dBA 0.350 0.477 High (95) dBA 0 044 0 021 Low (90) dBA 0 306 0 429 Low (90) dBA 0.018 0 012 1 -2 09/06 (800) 631 -2148 • www.cooperwheelock.com