Loading...
Correspondence July 2, 2007 City of Tigard, Oregon Tigard Building Department 13125 SW Hall Blvd. ABBOT + ABBOT Tigard, OR 97223 ARCHITECTS, P.L.L. Dan Nelson, Senior Plans Examiner (503) 718 -2436 Re: Permit #'s BUP2007 -00288 & MEC2007 -00288 Ruehl @ Washington Square Mall 9524 SW Washington Sq. Space H08 Tigard, OR 97223 Dear Sir, This letter is in response to your plan review correction letter dated June 19, 2007. Permit #BUP2007 -00288 1. Calculations and diagrams showing support for walls, storefronts, etc., for lateral and vertical load per ASCE7 9.6.1.3. a. Calculations have been included, corrections for additional bracing have been added to sheets A00.9, A08.3, A08.4 and A08.6 2. Taking in consideration the exceptions in OSSC 603.1, provide noncombustible construction throughout. a. All of the exposed combustible construction is not structural, thus not governed by OSSC 603.1, but by OSSC 803 Wall and Ceiling Finishes. Table 803.5, Use Group M, Rooms and Enclosed Spaces allows a Class C flame spread rating. Furthermore all of the wall and ceiling finishes are separated from the structure by a layer of 5/8" gypsum board. ‘C Permit #MEC2007 -00288 `U 1. Calculations and diagrams showing support for VAV boxes for lateral and vertical load per ASCE7 9.6.1.3. a. Calculations have been included. In addition to these comments /revisions there have been some revisions to the plans per Landlord & the Owner comments /requirements. Please review the attached Revision Bulletins If you have any additional questions please call. Sincerely, William E. Abbot, Abbot + Abbot Architects 130 East Chestnut Street, Suite 302, Columbus, Ohio 43215 -2543 phone: 614.461.0101 fax: 614.461.1107 www.abbot- abbot.com WWI _15 ,.A . mac doYY ___Lewilo_i_----, s------J--774 --,0 r71 DI )-0(P1/4 REVISION BULLETIN ABBOT + ABBOT ARCHITECTS, P.L.L. AA#: 12070010135 Revision #:1 Revision Date: 6/27/07 Division: Ruehl Project: Washington Square Location: Tigard, Or This bulletin, if issued after the execution of the contract, described proposed revisions of the contract documents and requests from contractor, the amount of change, if any, in contract sum to accomplish the work described. It is assumed no change in contract time will be necessary unless contractor submits written request for time extension, including justification, with his proposal for work described in this bulletin. Except as otherwise described herein, or as shown on drawings issued with this bulletin, current contract documents apply to proposed work. This bulletin is not an order to do work. After receipt and review of the proposal requested, a change order will be issued to authorize execution of the work, or portion thereof, if the owner so directs. Proposals: Submit proposals for change described herein on contractor's letterhead. List each item individually as listed below: SHEET DESCRIPTION A00.0 Corrected index of drawings A00.5 Revised Responsibility Schedule A00.9 Bracing details modified per Building Department comments A01.2 Added Landlord notes; Barricade by Landlord at Tenants expense A02.1 Added additional framing for cabinet support Leather shop and Mens2; corrected fitting room numbering; revised storefront at neutral piers; eliminated access to unused space. A02.2 Corrected fitting room numbering A03.1 Revised storefront at neutral piers — Unused space is now Void Space. Corrected pass -thru height from Leather Shop to Leather Shop; Revised Mudroom 'false' beam dimensions. A04.1 Revised storefront at neutral piers — Unused space is now Void Space; removed associated lighting; revised Mudroom light dimensions A04.3 Revised storefront at neutral piers — Unused space is now Void Space. A05.1 Revised storefront at neutral piers — Unused space is now Void Space. Voided detail 'C' A05.2 Added waterproof membrane note for Restrooms A06.1 Revised storefront at neutral piers — Unused space is now Void Space. A07.1 Revised elevations 'A & B' A07.2 Revised elevation 'A' Page 1 of 2 130 East Chestnut Street, Suite 302, Columbus, Ohio 43125 -2543 phone: 614.461.0101 fax: 614.461.1107 www.abbot - abbot.com \\ e1 1 ' S ABBOT + ABBOT ARCHITECTS, P.L.L. A07.4 Revised details 5, 6 & 22 A08.1 Revised Storefront Elevation & Plan per Landlord comments; A08.2 Revised Details F, G & H A08.3 Revised Storefront Sections A, B & C per Landlord comments A08.4 Revised Storefront Sections A, B & C per Landlord comments A08.5 Revised detail C A08.6 Revised Storefront Sections /Elevation A, B & E per Landlord comments A08.7 Revised Storefront Elevation & Plan per Landlord comments; A11.1 Revised detail H & K A11.3 Revised detail C, dimensions A11.4 Revised detail C, hanger notes A11.8 Revised detail D Al2.2 Revised detail A MEP Refer to document — MEP - 135- RV1- 06- 27 -07.doc for MEP revisions I End of Bulletin I Signed by: Don Schumacher 614.461.0101 x243 Dschumacher @abbot - abbot.com Date: 7 -2 -07 Copies To: File Page 2 of 2 130 East Chestnut Street, Suite 302, Columbus, Ohio 43125 -2543 phone: 614.461.0101 fax: 614.461.1107 www.abbot- abbot.com 1 °Z'' Emphasis on Excellence M•Retail Engineering, Inc. Landlord Comments, B.D. Comments - Revision #1 Date To Re June 27, 2007 GC for Ruehl Ruehl Store #135 Washington Square 9585 Washington Square Rd. Tigard, OR 97223 Revision No. 1 Please incorporate the following clarification / revision into your bid price. NOTE: WE ARE ISSUING ALL ADDENDA TO THE G.C. BIDDERS FOR CLARIFICATION AND COORDINATION. Sheet M01.1 No Change. Sheet M01.2 No Change. Sheet MD1.1 Added VAV detail per B.D. comments. Sheet MD1.2 Added Landlord notes per Landlord Comments. Sheet MS1.1 No Change. Sheet P01.1 Added Landlord notes per landlord comments. Added note to dream steamer detail per tenant directive. Sheet P01.2 Revised coded notes per Landlord Comments. Sheet P01.3 Removed roof routing of gas pipe per Landlord comments. Sheet FP1.1 Added Landlord note per Landlord Comments. Sheet FP1.2 Added Landlord note per Landlord Comments. Sheet E01.1 Removed receptacle in women's 1 and revised cash/wrap conduits per tenant directives. Sheet E01.2 Revised coded note #21 per tenant directives. Sheet E02.1 Removed skylight fixtures in mudroom and garage per tenant directives. Removed lighting in unoccupied space per tenant directives. 750 BROOKSEDGE BLVD. • WESTERVILLE, OHIO 43081 Page 1 of 2 614 -818 -2323 • FAX 614 -818 -2337 • E-MAIL mretallem-corporations.com An M *Corporation • 11 " Emphasis on Excellence M•Retail Engineering, Inc. Sheet E02.2 Revised master lighting switch bank and coded note #20 per tenant directives. Sheet E03.1 No Change. Sheet E04.1 No Change. Sheet E04.2 No Change. Sheet ED1.1 No Change. Sheet ED1.2 Revised sales area emergency light specification in lighting fixture schedule per tenant directives. Sheet ES1.1 No Change. 750 BROOKSEDGE BLVD. • WESTERVILLE, OHIO 43081 Page 2 of 2 614 -818 -2323 • FAX 614 -818 -2337 • E-MAIL mretailQmcornorations.com An M *Corporation City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 June 19, 2007 11 „, RE: CHAMPS TENANT INPROVEMENT ` .r Project Information Building Permit BUP2007 -00288 Construction Type: IIN Address: 9524 Washington Sq. Occupancy Type: M Area: 9375 sq. ft. Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code • Please provide calculations and diagram showing support for storefronts, soffit and all ceiling grid, taking into consideration a 17 Ft. distance between the grid and the roof, for lateral and vertical load as per ASCE7 9.6.1.3 • Mall structure is constructed as a noncombustible, nonrated building. Please indicate on your response whether one hour rated walls will be required. • Please provide accurate code summery. American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC, which may not include all of the requirements of the ADA. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. (106.3.1 OSSC) Res . ectfully FrAfk)' • an Nelson Senior Plans Examiner Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 95.a/ %/ad/, r/w IL/K7 MAYES TESTING ENGINEERS; INC. Lynnwood Office 200225 Cedar Valley Road : Suite 110 „ `''� ....,. t ... , Lynnwood, WA 98036 ph 425.742.9360 fax 425.745.1737 Tacoma Office 10029 S. Tacoma Way MTE No: P7210 Suite E -2 Project: Ruehl No. 135, Store #0135 Tacoma, WA 98499 Address: 9585 SW Washington S Rd, Sp H08, Tigard, OR 253.584.3720 g q g f fa ax 253.584.3707 Permit No.: BUP 2007 - 600288 City of Tigard Portland Office 7911 NE 33rd Drive Owner: Suite 190 Portland, OR 97211 Engineer: ph 503.281.7515 Architect: fax 503.281.7579 Contractor: Dimension One Page: 2 Date: October 19, 2007 Weather: Indoors Inspection: Structural Steel Erection Samples: None MTE inspector arrived onsite and provided periodic special inspection of single pass fillet welds at truss and roof reinforcement. Trusses were reinforced per detail 00 /000 drawing S0.1 and roof reinforcing was per details 11 and 12/S0.1. Welding was done by Red Frost Welding. Certification of welder Christopher P. Kellogg, # W06344, expires on 10- 01-08. Welding procedure was previously verified as meeting the pre - qualification requirements of AWS D1.1. Welds meet the visual acceptance criteria of AWS D1.1 -04. To the best of our knowledge, items inspected this date are in accordance with approved plans and specifications: INSPECTOR: W.J. Belleveau COP #760 REVIEWED BY: .//..5A, L_.. ark A. G. lusha, P.E. c: Scott Warren — Dimensi. One Buildin• • cial — City of Tigard Building Dept. 1 'iOlsl (1 '110t4 1001 toga : rip CI3A13 Page 1 of 1 MAYES TESTING ENGINEERS, INC • • Field Copy / Subject to Review • 20225 Cedar Valley Road, Suite 110 Ph 425.742.9360 Project No.: P7210 Date: 10 -15 -07 Lynnwood, WA 98036 Fax 425.745.1737 ?9 S. Tacoma Way, Suite E -2 Ph 253.584.3720 Project: Ruehl No. 925 Store # 0135 ..oma, WA 98499 Fax 253.584.3707 Tigard 7911 NE 33'" Drive, Suite 190 Ph 503.281.7515 Permit No.: BUP2007 -00288 Weather: Indoors Portland, OR 97211 Fax 503.281.7579 Project Address: 9585 SW Washington Sq. Rd., Sp H08 Inspector: Bill Belleveau Hours: Owner. Washington Square LLC Time: to Engineer: Inspector: Hours: Architect William Edward Abbot Time: to Contractor: Dimension One Inc. Inspector: Hours: Type of Inspection: SS -Er Time: to Samples: None SUMMARY: At jobsite, Mayes Tseting Engineers provided periodic special inspection of single pass fillet welds at framing for window sashes and attachment of sashes to the framing. Sashes were all owner supplied. No drawings were available showing weld details. All welds at the sashes were ground flush. Welding was done by Red Frost Welding. Certification of welder Christopher P. Kellogg, # W06344, expired on 10- 01-07. His card was sent to WABO for renewal. MTE was given a copy of the certification that expired to show that it is recent. Welding procedure was previously verified as meeting the pre - qualification requirements of AWS D1.1. Melds meet the visual acceptance criteria of AWS D1.1 -04. W.J. Belleveau COP # 760 RECEIVED FILE OCT 1 6 LUUI COPy CITY OF fIGABD BUILD1NGDIVISION To the best of our knowledge, all items inspected today are in conformance with approved plans and specifications. ® Yes ❑ No ❑ Preliminary Inspection NONCONFORMING CONDITIONS /CORRECTIVE ACTIONS TAKEN: City of Tigard, Oregon ® 13125 SW Hall Blvd. . Tigard, OR 97223 `��';,�, { ,1i } "���b $41:4;%;!:14-T r i l #� i� July 31, 2007 ; 7 ;1 RE: CHAMPS 'TENANT INPROVEMENT " '�j 'A R G f ' 'D .s f �, m Project Information Building Permit: BUP2007 -00288 Construction Type: IIN Address: 9524 Washington Sq. Occupancy Type: M Area: 9375 sq. ft. Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code 1) All improvements made to the building shall be inspected prior to covering. 2) Make approved set of plans available for all inspections. FIRE LIFE AND SAFETY / GENERAL The main exterior door or doors are permitted to be equipped with key - operated locking devices from the egress side provided: 1. The locking device is readily distinguishable as locked, 2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. (Sec. 1008.1.8.3) All exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. (Sec. 1008.1.8) Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. (Sec. 1011.1) Exit signs shall be illuminated at all times and shall be provided with a second source of power that will provide 1 1 /2 hours of illumination in case of primary power loss. (Sec. 1006.3) FYI Additional exit signs may be required by the city field inspector to clearly indicate the path of egress. The means of egress shall be provided with illumination of not less than 1 foot candle at the floor level anytime the building is occupied. The means of egress Phone. 503.639.4171 o Fax: 503.684.7297 ® www.tigard- or.gov 0 TTY Relay: 503.684.2772 illumination shall be provided with a second source of power in case of primary power loss. (Sec. 1006.2) Portable fire extinguishers shall be installed in new and existing Group A, B, E, F, H, I, M, R -1, R -2, R -4, and S occupancies. (OFC Sec. 906) American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC, which may not include all of the requirements of the ADA. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. (106.3.1 OSSC) r Respectfull , Dan Nelson Senior Plans Examiner City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 July 10, 2007 RE: RUEHL TENANT INPROVEMENTTIAR Project Information Building Permit BUP2007 -00288 Construction Type: IIN Address: 9524 Washington Sq. Occupancy Type: M Area 9375 sq. ft. Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code FIRE LIFE AND SAFETY / GENERAL The main exterior door or doors are permitted to be equipped with key - operated locking devices from the egress side provided: 1. The locking device is readily distinguishable as locked, 2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating. THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. (Sec. 1008.1.8.3) All exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. (Sec. 1008.1.8) Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. (Sec. 1011.1) Exit signs shall be illuminated at all times and shall be provided with a second source of power that will provide 1 1 /2 hours of illumination in case of primary power loss. (Sec. 1006.3) FYI Additional exit signs may be required by the city field inspector to clearly indicate the path of egress. The means of egress shall be provided with illumination of not less than 1 foot . candle at the floor level anytime the building is occupied. The means of egress illumination shall be provided with a second source of power in case of primary power loss. (Sec. 1006.2) Phone: 503.639.4171 o Fax: 503.684.7297 o www.tigard- or.gov • TTY Relay: 503.684.2772 Live Loads Posted: The live loads for which each floor has been designed to exceed 50 psf shall be conspicuously posted by the owner in that part of each story in which they apply, using durable metal signs, and it shall be unlawful to remove or deface such notices. The occupant of the building shall be responsible for keeping the actual load below the allowable limits. (1603.3 OSSC) American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC, which may not include all of the requirements of the ADA. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. (106.3.1 OSSC) Certificate of Occupancy: No building or structure shall be used or occupied until the Building Official has issued a certificate of occupancy (109.1 OSSC) Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Respectfully, dr , an Nelson Senior Plans Examiner 1 City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 June 19, 2007 • RE: RUEHL 'TENANT INPROVEMENT T I G RD' Project Information Building Permit BUP2007 -00288 Construction Type: IIN Address: 9524 Washington Sq. Occupancy Type: M Area: 9375 sq. ft. Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code • Please provide calculations and diagram showing support for walls, storefronts, soffit and all ceiling grid, taking into consideration a 17 Ft. distance between the grid and the roof, for lateral and vertical load as per ASCE7 9.6.1.3 • Taking in consideration the exceptions in OSSC 603.1, provide noncombustible construction throughout. American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC, which may not include all of the requirements of the ADA. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. (106.3.1 OSSC) Respectfully, oi • an Nelson Senior Plans Examiner Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772