Specifications /oIN5 ova 4 4,1. , 5 , PeC Th-1 44£C 00377 , 4 , COMMERCIAL Model 581 B I b r y a \ SINGLE PACKAGE ROOFTOP Sizes 036 -150 GAS HEAT /ELECTRIC COOLING UNITS 3 to 12 Tons T UNRA S E R I E S 1 _.......i_. `� y 0 _ _ ___�_ i . ° -��� - I _� iv Unit 581B036-072 Unit 581B090 -150 Bryant has designed the Tundraim series based on customer • high- pressure switch needs and requests to be the most efficient and reliable ever. • freeze - protection thermostat • internal compressor overload FEATURESIBENEFITS • exclusive Cycle- LOCT"" circuit board that provides anti- com- • Efficient rooftop line for cooling using scroll compressor pressor cycling •refrigerant filter drier technology • Efficient rooftop line for heating using dimpled heat The cabinet is constructed of galvanized steel. bonderized. and exchangers coated with a prepainted baked enamel finish. The paint finish is 9 a non - chalking type, and is capable of exceeding Federal Test • High reliability — non - corrosive condensate pans. prepainted Method Standard No. 141 (Method 6061) 500 -hour Salt Spray cabinets and primed interior panels. and all units are fully pro- Test In addition, all cabinet interior surfaces are primed, allow - tected by internal safeties ing the entire unit to have longer life and a more attractive • Quiet operation — isolated compressor plate. All compressors appearance. mounted on independent vibration isolators. Standard. belt- EASY MAINTENANCE AND INSTALLATION driven evaporator fan motors on all units • Ease of maintenance achieved by self diagnostics on the In- All Units are Factory Shipped in the Vertical Discharge Con - rated Gas Controller (IGC), standard size filters, no tool fil- figuration for frt -up to standard roof curbs. (One accessory curb tegrated ) fits sizes 036-072; another accessory curb fits sizes 090 -150.) ter access. simple compressor access. permanently Contractors can order and install the roof curbs early in the con - lubricated fan motors. optional disconnect switch. and op- strudion stage, before decisions on size requirements have tonal 115-v convenience outlet been made. BRYANT MEANS TOP QUALITY AND REUABIUTY — Each All Units Feature Heavy -Gage Roll- Formed Baserail design component utilized in the Tundra series is designed and with forklift slots on 3 sides of the unit and rigging holes for tested for a minimum of 15 years operation under the harshest easier maneuvering and installation. Stretch -wrap packaging conditions. protects the unit during shipment and storage. Every unit is thoroughly run tested at the factory in each oper- Units are Easily Converted from vertical to horizontal applica- ating mode and evacuated prior to final charging. Every coil is lions to make retrofit and add-on jobs easier. To convert from leak tested with helium particles. Automated run testing allows vertical to horizontal discharge. simply exchange 2 panels. The accurate, undisputed tests and measurements which are sec - same basic unit can be used for a variety of applications and and to none in the industry. can be quickly modified at the jobsite. Each unit contains a factory printout indicating tested pressures. Standard high - performance. high - static, belt- driven evaporator - amperages, dates, and inspectors, providing certification of the fan motors enable 581B036 -150 units to operate in most duct - unit's status at the time of manufacture. work configurations. Units are equipped with valuable safety controls designed to Ductwork Connections are Made Easy by the logical 2 to 1 monitor and protect for the life of the unit The standard safeties aspect ratio. On vertical discharge units, ductwork attaches di- include: redly to the roof curb. • low- pressurefoss -of- charge switch Form No. PDS 581 B.36.4 FEATURESBENEFITS (cont) FACTORY - INSTALLED REFRIGERATION OPTIONAL SYSTEM BALL BEARING. PERMANENTLY - DISCONNECT SWITCH PROTECTION LUBRICATED MOTORS a 11114,•;;Pr- .... 0 . ow , _ illo ,rip H ..--0 - _ ,., Ur A 0 m° 1- tigib4r-- A w - I_W r ..„,,,,,„, 1 ti jor d ,......igor ,n ,,,,,,„,,,, ,,, ,, -1 ` � - I. if/ rwiTtli, „..... 1.4: co. ,, • S g oes k tO FACTORY - INSTALLED PREMIUM QUALITY DIMPLED HEAT BELT DRIVEN OPTIONAL SCROLL COMPRESSORS EXCHANGERS EVAPORATOR FANS CONVENIENCE OUTLET SINGLE PIECE NO TOOL SLEEVE BEARING PERMANENTLY - TOP PANEL FILTER ACCESS LUBRICATED MOTORS o . o 0 1 4,..N,7 21 "'''--- ON-SITE CONVERTIBILITY o - ' FROM VERTICAL TO • HORIZONTAL DISCHARGE ° �"�� 0 "te /% HIGH- EFFICIENCY 0. % /� COILS AND TM ° 1 a /� % ' ��'��i ACUTRQL �� REFRIGERANT •0 %. � O. 0 METERING DEVICE ° SLOPED, t NON - CORROSIVE � . CONDENSATE DRAIN PAN HIGH- EFFICIENCY COILS FULLY MODULATING DURABLADE ECONOMIZER (OPTION OR ACCESSORY) 2 FEATURESIBENEFITS (cont) Thru - the - Bottom Service Connection Capability comes LP Conversion Kit — Standard units are designed for natural standard with the rooftop unit to allow power and control wiring gas. An LP Conversion Kit is available as an acces -sory, if re- to be routed through the unit's basepan, thereby minimizing roof quired. Installation of the accessory LP kit simply involves penetrations (to prevent water leaks). Both power and control changing the gas orifices to accommodate liquid propane gas. connections are made on the same side of the unit to simplify Refrigerant Circuit Protection assures dependability. All units installation. have standard: The Non - Corrosive, Sloped, Condensate Drain Pan is stand- 1) loss of- charge/low- pressure protection switch which allows and and in conformance with ASHRAE (American Society of operation at lower ambient conditions while protecting Heating, Refrigeration, and Air Conditioning Engineers) Stand- against low- charge operation and 62 to meet many Indoor Air Quality (IAQ) specifications. The 2) freeze - protection thermostat, which protects against evapo- condensate drain pan offers both bottom and end drain cape- rator coil frost build -up bility to minimize roof penetrations. The bottom drain can be 3) high - pressure switch, which protects against above normal used in conjunction with thru -the -bottom connections. An exter- operating pressure nal trap must be field supplied. 4) fitter driers, which trap moisture and debris in the refrigera- Standard 2-in. Throwaway Filters are easily accessed tion system. through an easily removable filter access panel located directly 5) Carrier's exdusive AcutroI ' metering device, which pre - above the air intake hood; no tools are required to change the cisely controls refrigerant flow, preventing slugging and filters. floodback, while maintaining optimum unit performance by All Units are Designed with a Single Continuous Top Piece metering the circuits individually. to eliminate leaking at the seams or gasketing, which tends to Two Independent Compressor Circuits (all 71/2 to 121 ton deteriorate over time and shift during rigging procedures. units) provide pinpoint comfort control. im proved efficiency, and Belt- Driven Evaporator -Fan Motors allow maximum on -site bade up capability. flexibility without changing motors or drives. The Standard Control System is ready adaptable to all con- Low-Voltage Wiring Connections are easily made due to the ventional thermostats. large terminal board which is conveniently located for quick, Integrated Gas Unit Controller (IGC) — All ignition compo- simple access. nents are contained in the compact Integrated Gas Controller QUIET, EFFICIENT OPERATION AND DEPENDABLE (IGC) that is easily accessible for service. The IGC provides PERFORMANCE built in diagnostic capabilities. An LED simplifies troubleshoot- ing by providing visual fault notification and system status infor- All Units are Equipped With Scroll Compressors which are mation. The IGC board provides exdusive anti-cycle protection fully hermetic with internal vibration isolators for extremely quiet for its gas heat operation. The IGC also contains burner control operation. The scroll compressors are quieter and more reliable logic for dependable heating operation. The LED is visible with - than reciprocating designs. Compressors are mounted on an in- out removing the unit control box access panel. The 581 B units dependent plate for additional sound integrity and structural maximize healing efficiency through the IGC's control of evapo- support. Efficient condenser fan and motor design permits op- rator fan ON/OFF delays. The IGC helps make 581B units reli- eration at low sound levels. able for many years. Totally Enclosed Condenser -Fan Motors and permanently lu- Patented Cycle- LOCT Protection System provides protec- bricated bearings provide additional dependability. tion against compressor cyding by monitoring compressor cur - All Coils Use State-of -the -Art Internally Enhanced Copper rent draw When lack of compressor current exists, the Cyde- Tubing — Coils are thoroughly tested with helium partides as LOC circuit board locks out the compressors. The Cyde -LOC well as pressure tested at the factory. Condenser coils have lou- board may be manually reset by simply switching thermostat to vered, aluminum lanced fins to provide maximum heat transfer OFF, and then back to the Cooling or AUTO modes. No manipu- for optimum efficiency and easy deaning. lation of the unit disconnect switch is needed. Exclusive Dimpled Heat Exchangers optimize heat transfer for improved efficiency. The tubular design permits hot gases to TABLE OF CONTENTS make multiple passes across the path of the supply air. In ad- Page dition, dimpled heat exchanger tubes act as baffles, forcing the Features/Benefits 1-4 hot gases to stay in dose contact with the cell walls to maximize Model Number Nomenclature 4 heat transfer and efficiency. ARI capacities 5 The California Air Quality Management NO, requirement of Options and Accessories 6-8 40 nanograms/joule or less is met when Low NO„ kit Physical Data 9,10 CRLOWNOX001A00 is installed on 036 -060 sizes. Base Unit Dimensions 11,12 The Induced Draft Combustion System eliminates the un- Accessory Dimensions 13,14 sightly appearance of flue stacks, and diminishes the effects of Selection Procedure 15 winds on heating operation. The inducer fan draws hot combus- Performance Data 16 -33 lion gas through the heat exchanger at the optimum rate for the Electrical Data 34,35 most effective heat transfer. The induced draft also prevents Application Data 36 contaminants from entering the supply air if a leak in the heat Typical Piping and Wring 37 exchanger occurs. Typical Wring Schematic 38,39 The Direct Spark Ignition System saves operating expense Controls 40,41 when compared to old -style pilot ignition systems. No crossover Guide Specifications 42-44 tube is required, therefore no sooting or pilot fouling problems can occur. 3 • FEATURESBENEFITS (coot) INDOOR AIR QUALITY PAC) Easily Accessible Refrigerant Access Ports on all discharge, The Quality of Building Air is Improved as the Tundras, suction, and liquid lines permit easy and accurate measure - series utilizes certain key features that assist in improving in- ments as well as simple accessibility. door air quality. A sloped condensate pan eliminates possible Resettable 24-v Circuit Breaker On 5818090 -150 Units al- . biological growth in the rooftop unit A face-split evaporator coil lows room for error without replacing transformers or fuses design proves effective in removing additional moisture from the Single-Side Utility Connections provide easy access to per - supply air. Two-in. filters are standard in all rooftop units and an form any necessary service. optional filter status sensor is available. Standard enthalpy con- Color-Coded Wires permit easy tracing and diagnostics. trot on the Parablade economizer regulates humidity in the building. Belt -Driven Motors are accessible through a single access SERVICEABILITY door to facilitate servicing and adjusting after installation. • Compressors and Safety Switches are Easily Accessible for Standardized Components for the complete Tundra line of troubleshooting and system analysis. products are found in all safety devices, condenser -fan motors, evaporator -fan motors, and control boards, while the gas sec- tions use common inducer motors, limit switches, and rollout switches. This allows for greater inventory control, familiarity of parts, and fewer stocked parts. MODEL NUMBER NOMENCLATURE 5818 E V 090 180 A A 581 B — Single Package High- Efficiency Gas/Electric Unit Voltage Designation E — - 3 - 60 Evaporator -Fan Motor — 208/2301 A — Sett Drive Motor J P — 208/230-3-60 T — 575-3-60 Fuel and Control Type Factory Installed Options* A — Standard Unit V — Natural Gas/Direct Spark Ignition Nominal Tons Gas Heat Input (Btuh) 036 — 3 090 — 71/2 072 — 72,000 180 — 180,000 048 — 4 702 — 81/2 115 — 115400 220 — 224,000 060 — 5 120 — 10 125 — 125,000 250 — 250,000 072 — 6 150 — 121/2 150 — 150,000 'Refer to the Trade Prices for ordering codes of factory-installed options. 4 . ARI' CAPACITIES UNIT NOMINAL STANDARD COOUNG TOTAL SOUND RATING 581B TONS CFM (Btuh) kW SEERt EER (BeIs) IPLV" 036 3 1200 36.000 3.21 13.00 11.20 7.6 - 048 4 1450 47,000 4.25 13.00 11.05 7.6 - 060 5 1750 60,000 5.55 13.00 11.00 8.0 - 072 6 2100 74.000 6.70 - 11.00 8.0 - 090 7.5 3000 90.000 8.18 - 11.00 8.2 11.6 102 8.5 3000 102.000 9.44 - 10.80 8.2 10.9 120 10 3200 120.000 10.91 - 11.00 8.4 9.7 150 12.5 4300 140,000 14.04 - 9.50 8.6 9.8 LEGEND BeIs - Sound Levels (1 bel = 10 decibels) EER - Energy Efficiency Ratio IPLV - Integrated Part-Load Value SEER - Seasonal Energy Efficiency Ratio `Air - Conditioning & Refrigeration Institute. tApplies only to units with capacity of 65,000 Btuh or less. The IPLV is not applicable to single-compressor units. NOTES: 1. Rated in accordance with ARI Standard 210/240 (size 036 -120 units) or 360 (size 150 unit) and 270 (size 036 -150 units). 2. Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard: 80 F db, 67 wb indoor entering-air temperature and 95 F db outdoor entering-air temperature. IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature. .,: co: , i. � ° Sizes 036-120 Size 150 only Only HEATING CAPACITIES AND EFFICIENCIES HEATING INPUT HEATING OUTPUT HEATING INPUT HEATING OUTPUT CALIFORNIA UNIT (Btuh) (Btuh) (Btuh) (Btuh) STEADY STATE TEMPERATURE AFUE SEASONAL 581B Single -Phase Single-Phase 3 -Phase Unitst 3 -Phase Unitst RISE ( ( °,�) EFFICIENCY EFFICIENCY Units Units' First Stage/ First Stage/ ( %) ( %) First Stage First Stage Second Stage Second Stage 036072 72.000 57,100 50,000/ 72,000 41,000/ 59,040 15-45 82 • 82 78.7 036115 115.000 89,000 82,000/115,000 65,600/ 92,000 55-85 80 80 77.3 048072 72.000 57,100 50,000/ 72,000 ,41,000/ 59.040 15-45 82 82 78.7 048115 115,000 92.000 82 .000/115.000 66.420/ 93.150 35-65 81 81 77.7 048150 150,000 118,000 120. 000 /150.000 96,000/120.000 50-80 80 80 76.9 060072 72,000 57.100 50,000/ 72.000 41.000/ 59,040 15-45 82 82 78.7 060115 115.000 92,000 82.000/115.000 66,420/ 93.150 35-65 81 81 77.8 060150 150.000 118,000 120 .000/150,000 96,000 /120.000 50-80 80 80 76.9 072072 - - 50,000/ 72.000 41,000/ 59,040 15-45 82 82 78.7 072115 - - 82,000/115,000 66.420/ 93.150 35-65 81 81 77.8 072150 - - 120.000/150,000 96.000 /120.000 .50-80 80 80 76.9 HEATING INPUT OUTPUT CAPACITY CALIFORNIA UNIT (Blob) (Blot) TEMPERATURE AFUE STEADY STATE SEASONAL 581B First Stage/Second Stage First Stage /Second Stage RISE ( °F) ( %) EFFICIENCY ( %) EFFICIENCY ( %) 090125 90,000/125:000 72,900/102,500 20-50 82 82 77.5 090180 120,000/180,000 98.400 /147,600 35-65 82 82 77.5 090220 180,000/224.000 147,600/183,700 45-75 82 82 79.4 102125 90.000/125.000 72,900/102.500 20-50 82 82 78.4 102180 120,000/180,000 98.400/147.600 35-65 82 82 78.4 102220 180,000/224.000 147.600/183.700 45-75 82 82 79.4 120180 120, 000 /180,000 98,400/147,600 35-65 82 82 78.4 120220, 150220 180,000/224,000 147,600/183,700 35-65 82 82 79.3 120250, 150250 200,000/250,000 160,000/200,000 40-70 80 80 76.4 LEGEND AFUE - Annual Fuel Utilization Efficiency 'Single -phase units are rated for output capacity in accordance with �� U.S. Government Standard Tests. tThree -phase units are rated for output capacity in accordance with ANSI 221.47 Standard for gas -fired, central furnaces. 5 OPTIONS AND ACCESSORIES ITEM OPTION' ACCESSORYt Integrated Economizer — Durablade X X Integrated Economizer — Parablade X Manual Outdoor -Air Damper X Convenience Outlet X Unit Mounted Disconnect X TWo -Position Damper (25% Open) X TWo-Position Damper (100% Open) X Roof Curb (14 in.) X Roof Curb (24 in.) X Thru- the$ottom Service Connections X Flue -Hood Protector Assembly X Thermostat and Subbase X Time Guard® II Control Circuit (3 -Phase Units Only) X Motonnaster® Low Ambient Control X Motormaster II Low Ambient Control X Accusensor' II Enthalpy Control X Accusensor III Differential Enthalpy Sensor X Liquid Propane Conversion Kit X Condenser Coil Hail Guard X NO Reduction Kit (sizes 036-060)" X Flue Discharge Deflector X Coil Guard Grille X Parablade Economizer and Power Exhaust X Fan/Fitter Status Switch X `Indicates a factory-installed option. tlndicates a field- installed accessory. Allows the unit to meet the California Air Quality Management NO requirement of 40 nanogramsryoule or less. LOW AMBIENT CONTROLS LIQUID PROPANE CONVERSION KIT The 5818036 -150 standard units are designed to operate in cooling at outdoor tem- peratures down to 25 F. With accessory Motormaster control (condenser -fan speed modulation), or Motormaster II control (condenser -fan cycling), units can operate at `}...� outdoor temperatures down to –20 F. The head pressure controls, which mount in • I I I II I I I I I I I L � the condenser section, control the condenser -fan motor to maintain correct con- densing temperature. ® BURN SUD I (ORIFICE S} P s I .� I _ o 0 • av� �� X11 �� qt r•,. `L / ir. _ 11 MOTORMASTER I MOTORMASTER II ! Wl - ol 1 11 *PC Liquid propane conversion kit allows the unit to utilize a liquid propane fuel supply a - areas where natural gas is not avail - `. s �' )_ «= �® able. (Kit shown is for sizes 036-072.) �®v mr3 I TIME GUARD II CONTROL Zino •A] r 3 lime Guard II Control automatically prevents compressor from restarting ' jam AT/2Xt - , for at least 5 minutes after a shutdown. Field- installed accessory prevents s � i , � , l - • short cycling of compressor if thermostat is rapidly changed. Time Guard II , • 0 device mounts in the control compartment of unit: The Time Guard II device G O - is not required when a programmable thermostat is applied. 6 . OPTIONS AND ACCESSORIES (cont) UNIT MOUNTED DISCONNECT PARABLADE ECONOMIZER r w kc,, ,v. 4 lnstlb „ s3 la :::: I i' eink....tl...:.• ...a....:.. 1 62 g 1.11:0101:0010. 11110.111.0.111.11111 0.0:010.110:1110.4 11.114.1111:1111111:01 iii -, ) 1.1 I a I" i \ I PA E I 111 II IS , AM i ir liSt:111:111: 11:42110111:11 o l f s ift ICA CA CA 0:4: , - : :1 ! 4 1 liwomormimokV A:24 a u Factory- installed, internally- mounted, NEC (National Electrical o . In Code) and UL (Underwriters' Laboratories) approved non -fused switch provides unit power shutoff with disconnect lockout protection lac. capability. The switch is accessible from outside the unit. C Factory- installed Parablade economizer utilizes parallel opposed - blade dampers, a motor with built-in spring return for close upon power loss, standard enthalpy controls, and 30% (sizes 036 -072) or 45% (sizes 090 -150) barometric capability for added flexibility in high outdoor-air applications. CONVENIENCE OUTLET NOTE: Parablade economizer is only available for vertical ductwork applications. It is factory- installed only. ..iiii iploo___ —.....--- 1 ® DURABLADE ECONOMIZER E:=1 ! , Or• •••:••11 :1111 , 1:•.•:• :•.�-�: ... • dilitiNvourill1111.1tv, ..- ' = 41 4 1 - 0 i I, Factory- installed, internally mounted •11 and externally accessible 115 -v fe- •:1 male receptacle. Includes 15-amp GFI ! I IS a (Ground Fautt Interrupter) receptacle with independent fuse protection. Volt- - - age required to operate convenience o outlet is provided by a factory-installed i 1 a° . transformer. - fie no... Exclusive Durablade economizer damper design saves energy while providing economical and reliable cooling. A sliding plate on the face of the economizer controls the amount of outdoor air entering the system. When the sliding plate is closed, it provides a leakproof seal which prevents ambient air from seeping in or conditioned air from seeping out. It can be easily adjusted for 100% outdoor air or any proportions of mixed air. Equipped with standard controls and 30% barometric relief capabilities. 7 • • OPTIONS ANb ACCESSORIES (cont) HAIL GUARD ACCUSENSOR"' II ENTHALPY CONTROL - m �� R/IIII� .- — � �� — rte — "--- ltl♦h ?1111 MIaE :...:ate / Lug _ l!I I M _ III IMIPAINIIMIR mimn, Or ammi llIMMIS 11411 MP �.r ta I /� ' 11' r.i�� / '/ ' lid; • ` • w i ill 1 . �- �3fip;t:ll td�ti /// o t f} j ��li ��XAIF�9tl,1tR33� I /0� �� /u It E ®� '/. ■91 t . is i' i �� %- i i +i l Hail guard accessory (field installed) protects condenser coils against damage from hail and other flying debris. W 1. ' ACCUSENSOR III DIFFERENTIAL ENTHALPY COIL GUARD GRILLE ‘1111 'e'; ° 9;� E . .; ::::::@a:;:;e • �;:: "��� Accusensor economizer controls help provide efficient, economical economizer operation. The Accusenuor I dry-bulb sensor measures ' outdoor temperature and is standard with the Durablade economizer (not required with Parablade economizer). ,s•,� The accessory Accusensor 11 solid -state enthalpy control senses both dry and wet bulb of the outdoor air to provide an accurate en- - thalpy reading. Accusensor II is standard with the Parablade econo- Coil guard grille protects coils against large objects and vandalism. mizer and available as a field -installed accessory for the Durablade , economizer. The accessory Accusensor Ill differential enthalpy sensor control compares outdoor temperature and humidity to return-air tempera- ture and humidity and determines the most economical mixture of air. Accusensor Ill is available for both Durablade and Parablade economizers. THERMOSTAT •, Thermostat (24 v) provides one- or 2 -stage cooling for control j; . ; r of unit. Matching subbases are available with or without - - : — "T ' I '. tamperproof switches and automatic changeover. f ' il i I ■ N •1 r,_ _ 8 • PHYSICAL DATA BASE UNIT 581B 036 048 060 072 NOMINAL CAPACITY 3 4 5 6 OPERATING WIGHT (WI Unit 530 540 560 615 With Durablade Economizer 564 574 594 649 With Parablade Economizer 572 582 602 657 Root Curb 115 115 115 115 COMPRESSOR .Scroll - - Quantity 1 1 1 1 Oil (oz) 42 53 50 60 REFRIGERANT TYPE - R - 22 Operating Charge (lb 5 8 10 9.10 CONDENSER FAN ? Quantity...Diameter (in.) 1..22 1...22 1...22 1...22 Nominal Cfm 3500 3500 4100 4100 Motor Hp...Rpm 14...825 1/4...825 1/4...1100 1/...1100 Watts Input (Total) 180 180 320 320 CONDENSER COIL Enhanced Copper Tubes. Aluminum Lanced Fins Rows...Fins/in. 1..17 2...17 2...17 2...17 Total Face Area (sq ft) 14.6 16.5 16.5 16.5 EVAPORATOR FAN Centrifugal Size (in.) 10x 10 10x 10 10x 10 10x 10 Type Drive Belt Belt Belt Belt Nominal Cfm 1200 1600 2000 2400 Maximum Continuous Bhp 1.20 1.20 2.40 2.40 Motor Frame Size 48 48 56 56 Fan Rpm Range 760- 1090 840 -1185 1020 -1460 1120 -1585 Motor Bearing Type Ball Ball Ball Ball Maximum Fan Rpm 2100 2100 2100 2100 Motor Pulley Pitch Diameter A/B (in.) 1.9/2.9 1.9/2.9 2.4/3.4 2.4/3.4 Nominal Motor Shaft Diameter (in.) Y4 / 14 Y8 Fan Pulley Pitch Diameter (in.) 4.5 4.0 4.0 3.7 Belt - Type...Length (in.) A...33 A...36 A...40 A...38 Pulley Center Line Distance (in.) 10.0 -12.4 10.0 -12.4 14.7 -15.5 14.7 -15.5 Speed Change Per Full Turn of 65 70 75 95 Movable Pulley Flange (rpm) Movable Pulley Maximum Full 5 5 6 5 Turns from Closed Position Factory Setting - Full Turns Open 3 3 3 3 Factory Speed Setting (rpm) 890 980 1240 1305 Fan Shaft Diameter at Pulley (in.) Ye Ye Ye Ys EVAPORATOR COIL Enhanced Copper Tubes, Aluminum Double Wavy Fins, Acutrol''•' Feed Device Rows...Fins /in. 2..15 2..15 4...15 4...15 Total Face Area (sq ft) 5.5 5.5 5.5 5.5 FURNACE SECTION Rollout Switch Cutout Temp (F)• 195 195 195 195 Burner Orifice Diameter (in....drill size)t Natural Gas - Std .113...33 .113...33/.113...33 /.129...30 .113...33/.113...33 /.129...30 .113...33!.113...33 /.129...30 Liquid Propane - Alt" .089...43 .089...431.089...431.102...38 .089...431.089...431.102...38 .089...43/.089...43 /.102...38 Thermostat Heat Anticipator Setting (amps) First Stage 14 .14 .14 .14 Second Stage .14 .14 .14 .14 Gas Input (Btuh) Single-Phase Units First Stage 72,000/115,000 72.000/115,000/150,000 72,000/115,000/150,000 - Efficiency (Steady State) ( %) 82/80 82/81/80 82/81/80 - Gas Input (Btuh) 3 -Phase Units First Stage 50,000/ 82.000 50,000/ 82,000/120,000 50,000/ 82,000/120,000 50,000/ 82,000/120.000 Second Stage 72,000/115,000 72,000/115,000 /150,000 72,000/115,000/150,000 72,000/115.000/150,000 Efficiency (Steady State) ( %) 82/80 82/81/80 82/81/80 82/81/80 Temperature Rise Range 15- 45/55 -85 15-45/35-65/50.80 15- 45/35- 65/50 -80 15- 45/35 - 65/50 -80 Manifold Pressure (in. wg) Natural Gas - Std 3.5 3.5 3.5 3.5 Liquid Propane - AIY' 3.5 3.5 3.5 3.5 Maximum Static Pressure (in. wg) 1.0 1.0 1.0 1.0 Field Gas Connection Size (in.) Yz Yz 14 Yz HIGH - PRESSURE SWITCH (psig) Standard Compressor Internal Relief 450 ± 50 Cutout 428 Reset (Auto.) 320 LOSS -OF- CHARGE /LOW- PRESSURE SWITCH _, _ _ _ (Liquid Line) (psig) Cutout 7 ±3 Reset (Auto.) 22 ± 5 FREEZE - PROTECTION THERMOSTAT Opens (F - 30 t 5 Closes (F) 45 t 5 OUTDOOR - AIR INLET SCREENS Cleanable Quantity...Size (in.) 1...20 x 24 x 1 RETURN - AIR FILTERS - • -- Throwaway Quantity...Size (in.) 2...16 x 25 x 2 LEGEND 'Indicates automatic reset Bhp - Brake Horsepower 1 -072 -072 units have 2 burners. 58113036115-072115 and 5818048150. 072150 units have 3 burner:. An LP conversion Kit is available as an accessory 9 PHYSICAL DATA (cost) BASE UNIT 48HJ 090 102 120 150 NOMINAL CAPACITY (tons) 71/2 8'% 10 121 OPERATING WEIGHT (II)) Unit 870 880 1035 1050 With Durablade Economizer 914 924 1079 1094 Wth PrJablado Economizer 932 942 1097 1112 Roof Curb 143 143 143 143 COMPRESSOR Scrca' Quantity 2 2 2 2 Oil (oz) (each compr) 53 53 50 60 REFRIGERANT TYPE - Operating Charge (lb -oz) Circuit 1 7 - 10 7 - 14 9 9 Circuit 2 8- 2 8- 5 10-3 9 CONDENSER FAN 'ope'ter Quantity...Diameter (In.) 2 .22 2 .22 2.. 22 2 22 Nominal Cfm 6500 6500 7000 7000 Motor Hp...Rpm 'A 1100 'A...1100 '/....1100 'A. 1100 Watts Input (Total) 650 650 650 650 CONDENSER COIL _nra =Li C2:r r'_.,zs Ai. °.' :'Y,an.:::: '.1`ii Rows..FlnsM. 2...17 2.. 17 2...17 2 ..17 Total Face Area (sq ft) 20.5 20.5 25.0 25 0 EVAPORATOR FAN . Ce-.:•it...gii' Size(in.) 15 x15 15x15 15x15 15x Type Drive Belt Belt Bett Belt Nominal Cfm 3000 3400 4000 5000 Maximum Continuous Bhp 2 90 2.90 3.70 5 25 Motor Frame 56 56 56 56 Fan Rpm Range 840- 1085 840 -1085 860 - 1080 900 - 1260 Motor Bearing Type Ball Ball Ball Ball Maximum Fan Rpm 2100 2100 2100 2100 Motor Pulley Pitch Diameter 3.4/4.4 3.4/4.4 4.0/5.0 2.8/3.8 AB (in.) 4.0/5.0 Nominal Motor Shaft Diameter (In.) Mi 7 .fi ' ' Fan Pulley Pitch Diameter (In.) 7.0 7 0 8.0 5 8 Belt — Type...Length (in.) A...51 A ..51 A. 51 BX. 46 Pulley Center Line Distance (in.) 16.75 - 19.25 16.75 - 19 25 15 85 - 17.50 15 85 - 17 50 Speed Change per Full Turn of 50 50 45 60 Movable Pulley Flange (rpm) Movable Pulley Maximum Full 5 5 5 6 Turns from Closed Position Factory Setting — Full Turns Open 5 5 5 5 Factory Speed Setting (rpm) 840 840 860 960 Fan Shaft Diameter at Pulley (in.) 1 1 1 1 EVAPORATOR COIL F ' re; Cr o 7..czs A 'u� 7c,.tic Oavv r �� Rows..FlnsIn. 3...15 3...15 4...15 4 _ 15 Total Face Area (sq ft) 8.9 8 9 11 1 11.1 FURNACE SECTION Rollout Switch Cutout (Temp (F)` 195 195 195 195 Burner Orifice Diameter (in....drill size)t Natural Gas — Std 120 31 .120.. 31 120.. 31/.120...31/ 129...30 120...31/ 129 30 Liquid Propane — Air .096..41 . 096..41 096.. 41/096...41/ 102...38 096. 41/ 102 ..38 Thermostat Heat Anticipator Setting (amps) Stage 1 .14/ 14/.14 .14/.14/.14 .14 .14 Stage 2 .14/.20/.20 14/ 20/.20 20 20 Gas Input Stage 1 90. 000/ 120. 000 /180.000 90.000/120.000 /180.000 120,000/180.000 /200.000 180.000/200.000 Stage 2 125.000/180.0001224.000 125.000/180.0001224.000 180.000/224 .000/250.000 224.000 /250.000 Efficiency (Steady StaLe) ( %) 8282/82 82/82/82 82/82/80 82/80 Temperature Rise Range 20- 50/35 - 65/45 -75 20-50/35-65/45-75 35-65/35-65/40-70 35- 65/40 -70 Manifold Pressure (in. wg) Natural Gas — Std 3.5 35 35 35 Liquid Propane — Alt" 3.5 3 5 3.5 3 5 Field Gas Connection Size (In.) .50/.75/.75 50/.75/ 75 75/.75/ 75 75/ 75 HIGH - PRESSURE SWITCH (psig) Standard Compressor Internal Relief 450 ± 50 Cutout 428 Reset (Auto.) 320 LOSS -OF- CHARGE /LOW - PRESSURE SWITCH (Liquid Line) (psig) Cutout 7 ± 3 Reset (Auto.) 22 ± 5 FREEZE - PROTECTION THERMOSTAT - Opens (F) 30 ± 5 Closes (F) 45 ± 5 OUTDOOR -AIR INLET SCREENS • cie Quantity...Size (in.) 1...20 x 25 x 1 1...16x25x1 RETURN -AIR FILTERS Quantity...Size(in.) 4 16x20x2 4. 16x20x2 4. 20x20x2 4 20x20x2 LEGEND *Indicates automatic reset Brake Horsepower 1581B090125, 102125 units have 3 burners. Bhp — 581B090180- 120180 units have 4 burners. 5818090220- 150220 units, and 581B120250, 150250 units have 5 burners "An LP Conversion Kit is available as an accessory. 10 BASE UNIT DIMENSIONS - 581B036 -072 STANDARD DURABLADE PARABLADE CORNER CORNER CORNER CORNER CONNECTION SIZES UNIT UNIT ECONOMIZER ECONOMIZER WEIGHT WEIGHT WEIGHT WEIGHT A 1W Dla [35] Field Power Supply Hole 5818 WEIGHT WEIGHT WEIGHT (A) (B) (C) (0) B Dia [51] Power Supply Knockout Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg 0311 530 240 34 153 42 19.1 127 5�.6 {22 55.3 138 62 6 143 64 9 C 1W Dia [44] Charging Port Hole 048 540 245 34 15.4 42 19.1 129 58 5 124 56.2 141 64.0 146 66.2 D W Dia [22] Field Control Wiring Hole 060 560 254 34 15 4 42 19.1 134 60.8 129 58.5 146 66.2 151 68 5 E W-14 NPT Condensate Drain 072 615 279 34 15.4 42 19 1 147 66.7 142 64 4 160 72.6 166 75 3 F W-14 NPT Gas Connection G 2+h" Dia [64] Power Supply Knockout NOTES: 1. Dimensions in ] ] are in millimeters. 2. ® Cerar of gravity. p 1' -7 3/16" 0' -3 13/16" I [487.47. [� 3. %� // Direction of airflow I 4. On vertical discharge units, ductwork to be attached to accessory roof curb only For I FACTORY SUPPLIED trotimtutal discharge units, field- supplied flanges should be attached to honzontal die- B FLUE HOOD charge openings, and all ductwork should be attached to the flanges r dktl 5. Minimum clearance (local codes or lurison may prevail). / ;: ,i i a Between unit, flue side and corndstile surfaces, 48 inches. (18 In when using so- I A cessory flue discharge deflector.) 2 5/16" CONDENSER COIL � b. Bottom of unit to combustible surfaces (when not using curb). 1 inch. [846.5] a [. 1 • -4 5/16" �m of base rail to combustible surfaces (when not using curb) 0 inches • [J [414.53 c in Doti, for proper airflow, 36 one ands, 12 In the other The side getting greater clearances optional. BOTTOM , d. Overhead. 60 in to assure proper condenser fan operation UNIT I ( , e. Between units. control box side, 42 In per NEC (National Electrical Code) . r f. Between unit and ungrounded surfaces, control box side. 36 m per NEC j 111 g•{ 5/8" g. Between unit and block or concrete walls other s and oer grounded surfaces. control box I, I � . [168.27 side. 42 in. per NEC. h. Horizontal supply and return end. 0 inches. } 4 6 Writs the exception of the clearance for the condenser coil and combustion side as stated 0• -4 9/16" L TYR 3• -5 3/16"------------.1 In notes 5a. b and c. a removable fence or barricade requires no clearance C115.117 - [10461 \ 7 Units may be Installed on combustible floors made from wood or Class A, B, or C roof 2 9/16" ELECTRICAL covering material if set on base rail 1653 LEFT SIDE D L T s OUTSIDE AIR FILTER ACCESS PALL I _ (DISABLE FILTERS) REAR S 2•-0 1515/716 -°' [t 41 FILTER/ECONONIZER ACCESS PANEL ` CONDENSER 011 COIL OPTIONAL p A! ECONOMIZER HOOD 1 -4 3/8" 1 (4163 I CCORNER . 2.-7 [800 " 5 [451 �'! _ 9' - D 1 I ! 2 -1 11/16" 0 " -3 3/16' 00 I' [6521 �I , [el] RIGHT SIDE VIEW 5 - LEFT 1 1 I - - -- I S I DE i i . EVAPORATOR L I RETURN AIR OPENING I 0 1 OM RETURN AIR YERT[CAL I _ II Q l -- -- r im I ° 5 1I "'"S� 1 . r d BOTTOM POWER CHART. THESE HOLES 1 3' -9" 1 t . 1 h REQUIRED F USE WITH ACCESSORY (1144] / / E PACKAGES - CRBTMPR001A00 1 1 / / ALT. CONDENSATE l - - I I �' -2 9/16" ('N. 3 /• ° ) W I I 1 [651 / / 0 " -3" •° IN I BASEPAN I � ISUPPLT AIRI 1 3/4 go$, glppL TCONDUIT WIRE HOLE SIZES I 1 / / [76.27 OPBRIIOB (4511 '"'''vv AIR SIZE USE (MAX.) 1 i I VERTICAL I • 9" - - - ../,'r - '. -1 15/16• 1 W 24V W [22.2] [533] - - - [49] IV Power' 1W [28.4] i 2' -0 1/4 "3 ' -3 5/16" - - 0' -5 7/16" [6167 [99.4) [13 1 +p• Power' 1 °/.° [44.4] • SEE BOrra» PorER NOTE .8 FRO 'Select either W or 114" or power. depending CHART (ELEC• man on wire size. "0 CORNER " 2' -11 11/16" O -3 1/16" ,- ,, O• 0 1/t -3 3/16 CORNER " C " [7®�' [306] (81 ] [91 I 6 " -1 11 /16" [18721 0' -7 1/4" [184] 1 -5 5/16" •' -10 19/1 -' 0' -4 1/16" 6 0•-0 3/8" [439.73 (274.63 [103.2] FILTER ACCESS PANEL / - row � , � I WI5P06ABLE FILTERS) p &W PA ACGE55 -1 11 /16 HOOD FILTER � INDOOR i I RETIRN [652. S) FAN ROTOR B ! � O HOR- BLOl1ER ACCESS OR II ` PENIIN .��4. Dili I / CONTROL BOX/COMPRESSOR F I 0' -ll T/8' �` SUPPLY AIR I 201" j /// . , t [[91 0] /16' I [301.6) I [ OPENING ii ; I [17781 OUTSIDE AIR MN /4:::::] 1 01./6' OD 2° ' q _FORK TRUCK SLOTS / O '-5 3/4" I . " 15/16 1 / 10 11/16' b 2] [748.2) O 7/16'"F [146] .% [658.67 [144.3] j 8141 0 -2 1 /4 "0 fA of P ANEL SUPPLY AIR RETURN AIR RIGHT S IDE FRONT <TYP a PLACES) E STD. C@mENSATE GRAIN . 11 • BASE UNIT DIMENSIONS — 581B090 -150 • STANDARD DURABLADE PARABLADE CORNER CORNER CORNER CORNER UNIT UNIT ECONOMIZER ECONOMIZER WEIGHT WEIGHT WEIGHT WEIGHT "H" 'J" "K" 5.81 WEIGHT WEIGHT WEIGHT (A) (B) (C) (0) Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg ft-In. mm Han mm ft4n mm ft -In. mm fain mm 090 870 395 44 20 62 28.1 189 86 161 73 239 109 280 127 2 -0 632 3 -55 1050 2 -9 856 2- 2'/+e 672 102 880 399 4.4 20 62 28.1 191 87 163 74 242 ' 110 284 129 1 -21/2 378 3 -5 1050 2 -9'14e 856 29)e 672 120 1035 469 44 20 62 28.1 225 102 192 87 285 129 333 151 1-21/4 378 4-144e 1253 3-056 924 2- 10 875 150 1050 476 44 20 62 28.1 48 - 103 196 88 289 131 338 153 1 - 2 5 16 378 4 - 1346 1263 3 w 924 2 - 10 5 /6 875 NOTES: 1. Dimensions In ( )are in millimeters 2. ® Center of gravity. "If" 0' -7 3/8" 3. 7 Direction of airflow [1e7] or - 0' -3 13/16" 4 On vertical discharge units, ductwork to be attached to accessory roof curb only For _ (971 horizontal discharge units, field - supplied flanges should be attached to horizontal cis- 'I FACTORY SUPPLIED openings, and all ductwork should be attached to the flanges FLUE 11000 5 charge harge Minimum clearance (local codes or 1urlsdktion may prevail). a. Between unit, flue side and combustible surfaces, 48 inches (18 Si . when using ac- • cessory flue discharge deflector ) l b Bottom of unit to combustible surfaces (when not using curb). 1 inch. / /% CWJ01I COIL Bottom of base rail to combustible surfaces (when not using curb) 0 Inches "J- c. Condenser coil, for proper airflow, 36 In one side, 12 in the other. The side getting 2'-0 3/8' the greater clearance Is optional (6191 d. Overhead. 60 in assure proper condenser fan operation Borfa I , to e. Between units, control box side. 42 In. per NEC (National Electrical Code) is . * f Between unit and ungrounded surfaces, control box side. 36 in per NEC . . - •i g. Between unit and Mock or concrete walls and other grounded surfaces, control box side. 42 on per NEC. Ci @ h. Horizontal supply and return end 0 Inches 6. With the exception of the clearance for the condenser coil and combustion side as stated 0'-4 9/16' 0' -S 3/4' in notes 5a, bard c. a removable fence or barricade requires no clearance [116) 4 ".-5 7/B' . [1461 7 Units may be installed on combustible floors made from wood or Class A, B, or C roof 0' -2 9/16" [1 covering material If set on base rail [651 TTP ELECTRICAL LEFT 5 I DE DISCONNECT LOCATION CONNECTION SIZES A 1W Dia 135) Field Power Supply Hole B 21' Dia (641 Power Supply Knockout REAR Sr V- 1/2' -15 C 1 9 4 " Dia 1441Charging-Port Hole i [ 0' -3 9/16• D W Dia (221 Field Control Wiring Hole FILTFR/ECONOMIZER ACCESS PANEL l 01JTSIDE '7-1 r !�D) E '/.' -14 NPT Condensate Drain C COIL \\ r CORNER "B. F W-1 4 NPT GasConnection 5818- V090 and 3'-0 95 / f W - 14 NPT Gas Connection (ell other units) (1091 1' -5 7/B' th G 2" Dia 1511 Power Supply Knockout ECONONIZER HOOD (4541 CORNER "A" ' -3 1/8" I �. \ \ - 0 [7� ' j FILTBI AC�S3 PAID 0'-5 1/2" tDISP06ABLE FILTHIA g% EVAPORATOR K ' CI 401 l . COIL I ? ii 1 RETURN AIR OPENING I 1 1'-0 s/8' / BLOOC�F I VERTICAL I I (320] / / PAM / // �� .O. I 1 6 RETURN AIR 8 I 4 3/4' 11 E - - - ' ' -2 13/16' (1467] !I — ALT. COMIENSATE I I 0.-2.3/16' [ [71.5) _ LEFT 'I '., I IN SAMPAN OPENING 1 y I il VIEW 5-5 )00 O I AIR 2 3/4" 80TTON POWER CHART. p g I mimic' [730) RIGHT SIDE T5� HOLES REO'0 FOR USE S 1` lO _[76 -Z1 iVQITICALI WITH ACCESSORY 1 /2 3 ,aio dik R /4•) OR 1' -11 1/ " I SEE NOTE •B 1 1 I % % C7WHI 00 C1/2 ',I 1/4') 691] I - I SUPPLY AIR IT M USE �S z6 1' -1 /B 0' -1 15/16 0 '-4 11/16' - - - SIZE OM1I.) r 24Y 7/ [306 / [48.SI [120] 152 8'4222.21 f RI Bum _ .. i 0' -5 7/16 3/4' POWER. 1 1/B C28.41 / _ f 1' -2 [13/11 1 1/4' POWER. 1 3/4%44.41 CORNER " �R 2' . [ $5) • ■ - SELECT EITHER 3/4" OR 1 1/4" [731 FRONT r 1/ • FOR C F PW ND ®1, DEPENDING ON MIRE SIZE. 3' 1/4' '-B 3/1 *— [1073] (208) • 3'- 41/4 " —al [1022] a 0'-7 5/16' 0' -4 " A 7'23 3/8" _ [185] 1 [101] 7-393 0' -0 3/6 ¢ -2'-4 5/16'- - d l' -0 5/8 [10) -•(p [719) 13201 i t _ FILTER ACCESS PANEL 1 4 - 4 i .-WIOPOSABLE FILTERS) ] I 4 - K- ACCESSORY 4ppEP I I j9164 H FILTER CONTROL BOK/ "L" ® INDOOR FAN MOTOR 6 t 4 Hat- 4 COMPRESSOR/ 1 BLOWER ACCESS PANEL 1 ZONTAL II N 1 1 1 1 PA5E1. 11 OUTSIDE AIR rf' 1 17/6 d F `` I 4 4 r (6711ls il, 1 i ry h �� 0' -3 " [91] F� _ 0'-7 179] 6' We O Q o _ 3• -0' \ 1 1:4 DW) LOM Ur ( 11/16 1 6 f (914.4) FORK TRUCK SLOTS OUT 0"--(1 41 �8/ "� .j r RIGHT SIDE FRONT SUPPLY AIR RETUA01 AIR E STD. CONDENSATE DRAIN P . 12 • • ACCESSORY DIMENSIONS — 581B036 -072 CONNECTION SIZES UNIT SIZE „ ROOF CURB 5818 ACCESSORY UNIT SIZE "D" ALT " CONNECTOR 1' - 2° [356] CRRFCUR8001A00 "B" "C" DRAIN GAS POWER CONTROL ACCESSORY 5818 HOLE PACKAGE 036 072 2' -0° [610] CRRFCURB002A00 Y,° NPT Y.° NPT Y4° NPT CRBTMPWR001A00 1' -9 1' -4' (Thru- the -Bottom Connections) N OTES: lf3G 072 [551] [406] 1Y4 [ 3 NPT 1Y: NPT Yz° NPT CRBTMPWR002A00 1. Roof curb accessory is shipped unassembled (Thru- the -Bottom Connections) 2. Insulated pane's. 3. Dimensions in [ ] are in millimeters. 4. Roof curb. galvanized steel. C 5. Attach ductwork to curb (flanges of duct rest on curb). 45-+ 6. Service clearance 4 ft on each side '--- - N 1 ., 7. • Dwecbon of airflow. ■ s, f1 ,q % � `. 8 Control and power service plates are part of a C % � Y - %\ 9 Either connector ck a can be used � package • ( ' t r - ` with either accessory roof curb 1 , L S r i 0 �. / / D [761 i �•) B GASKET (SIIPPL IED KIM clAw) i E NING rR 2'-7 �- Will o 1/4'rn - - T 1 SUPPLY-AIR I ! 4-- r*AYTER [8037 ` n - j/� NAIL 1 / o• i - /15 OPENING c 1 TYPICAL (4) SIDES ' (3411 i - . 1 6• FLASIING I - - , i (FIELD SIDPL LED) \ • INS FEL T 0'-0 7/16' (F IELD SUPPL IED7 nn 1 713/16" 1 /8' 0- -0 7/16 SECTION �C C" (BOLT MEADS) 6041 EV1 [334) rill \ CANT STRIP (9017 HEADS) S, (F IELD SUPPLIED) SCALE 1�4 176) ` ROOF INS MATERIAL 0•-0 7 /16' 3 0•-0 7116" \\/ (FIELD SIWPL LED) A HEADS) 19141 ( T • A '\`\ E v 7 RINS MS BASEPAN J� s F SERvICE 8 \ I 0i_l i /2' ) RIGID INSULATION 0• -3 1/4- ) (F SUM. IELD SIED) 19:1` 0 P33/16- • �` SEE NOTE ■2 4 0 3/16 � [1061 / E' GAS SERVICE PLATE 1 • - 13/16 0'-0 1/4'(71 - [4273 4 p• 4901r ii I / \ �� 1 \ / „P O ! SUPPLY AIR rimer AIR A / 2 3/6 j VIEW " A -A" \ � '--...,.., • \ / • HEAD OF wLI TO BE as 4411111: . INSIDE OF FLANGE 1 . / O 1463 \� �� ' \ >� ° t$7 A I I ` ' 11705) p' 3 -0 15/.6 [9 // 11110° p _3' 38: \ / / / [%61 / i VIEW "8" SEE Y(£W 'II'f �, ` ` - - � OW. ALL COMERS) Roof Curbs 13 • ACCESSORY DIMENSIONS — 581 B090 -150 CONNECTION SIZES UNIT SIZE ROOF CURB 581B "A" ACCESSORY UNIT S� "D" ALT "� CONNECTOR 1' -2' [356] CRRFCURB003A00 "B" "C" , DRAIN POWER CONTROL ACCESSORY 581B HOLE GAS PACKAGE X150 2'-0° [610] CRRFC UR BOO4A00 V: NPT W NPT W NPT CRBTMPWR001A00 2' -8'A e' 1'- 10t3fie ,y: [45] (Thru-the-Bottom) 090-150 1 NOTES: [827] [583] [ �: NPT 1t/: NPT Y4° NPT CRBTMPVVR002A00 1. Roof curb accessory is shipped unassembled (Thru-the-Bottom) he- Bottom) 2 Insulated panels. 3 Dimensions in [ ] are in millimeters 4. Roof curb: galvanized steel. 5 Attach ductwork to curb (flanges of duct rest on ��— curb) d r _ 6. Service clearance 4 ft on each side , 7. % /// Direction of airflow. ` 8 Either accessory connector package can be used r-s with either accessory roof curb .`: ' f sr: '. ■ 5 I76] • ,'ae' 0 " -3 '0- I WIT 0 -0 1/4" 17) P WI, NAIL (76i - -B (SUP L1E�O YIiN CURED I - TYPICAL (4) 510E5 '22 - '. e RETU11h•AI OPE NING 3 -3 5/B' DUCT I O [ 7/I6' L70061 (FIELD SUPPLIED) \ (FIELD R FLASHING 1 SUPPLY-AIR I t • -3 1 /4" 1 OPENING 1 'C i (F S(WPLIED) SECT 1 ON - C-C" 1387] P 1 1 SCALE 1.4 0'-0 7/16 1 1 - _ ` I ELD SUP . 4 CP T .= • (F IELD S L C) FING I I\ \i (FIELED) L 1111 I D SUPPLI 2'-6 IS /16' L - 2 7/B', 0' -0 7/16" A. j . (BOLT READS) � � 1786) [ 378 1 1117 �` /4,. _ 0[761 (BOLT 1ffA75) \\ ENTRY SERVICE BASENJI 0' -0 7/16 0 " -0 7/16' 1 ill] 4• -0 13/16' - .• tI] (BOLT •2ADS) 11240] MOLT HEADS) RIGID INSULATION (FIELD SUPPLIED) ° I. AL_ �A / r 2 t/e I s4] 44( / 0 [ ��/I6 SEE NOTE .2 / �� jvi I . ♦ 4 3/16 I [10 / RV I III GAS ■ SFRVI CE / PLATE 1:1-14(6551133)6/1116' / / I 0 1/4'177 PI _ / 1 1 j t II I TIP 0,1 1 1 % SUPPLY AIR RETWN AIR % I t /2 3 /B' I 1 I / //,Z 7,-/, % , \\ \ \St\ 4. (sir I 1 j 'A . \ 1 V 1 EW –A Iflo I \`����� o• HE OF BOLT AD OF TO BE IN ` �����\\\`\\\\\\ ) } -- - ---- - -- 9 - --- - - -- • A 1 I e .._,_ . _........... ..., y o 1481 ill (2,51 i k: !!!! %41 114 1414 - 4 :::: - . l REF 4 (1264)4 - Pa VIEW '8 # i... � 17YP. ALL =HERS) SEE VIEW 'WA ` ...— Roof Curbs 14 • • • UNIT CASING UNIT BASE RAIL (2) STRAPS PER SIDE UNIT BASE SECURE UNIT TO HOLD— - DOWN W/ (2) #10 x 1/2" TEK SCREWS • SECURE HOLDDOWN TO OR CURB W/ (2) #10 x 1/2" _ LAG BOLT UNIT DIRECTLY TEK SCREWS TYPICAL m �� TO CURB W/ (2) 1/4 7 DIA. x 2" EMBED LAG 'A1 BOLTS WOOD NAILER- ,.• - 1.■ 1•• 4" WIDE x REQ'D UNIT MOUNTING CURB BY IC! 20 GA STEEL UNIT MFR (14" HEIGHT) I�� ism STRAP HOLDOWNS I.. 1.■ • '.. GALV. SHEET MTh " " COUNTER FLASHING RIPPED P.T. 2x6 LEVEUNG 'U. Ism PLATFORM BY OTHERS 'U" 1 .■ " \ ROOFING BY OTHERS I 1.■ 1.■ ROOF SHEATHING \ • CURB CONNECTION PER STRUCTURAL PLAN • - STRUCTURAL SUPPORT • MEMBER PER PLAN • HVAC MOUNTING DETAIL • 1 1/2"=t-0" • 206373 206373— S5.dwg VLMK � CONSULTING 206637307/06 ENGINEERS JJE 3933 SW Kelly Avenue • Portland • Oregon 97239 -4393 1 503.222.4453 Ivlmk @vlmk.com HVAC MOUNTING DETAIL S5 503248.9263 www.vlmk.com Rr ,O CE) MECHANICAL UNIT ANCHORAGE PER THE 2003 INTERNATIONAL BUILDING CODE NEW ROOF -TOP UNITS SEISMIC INPUTS (SECTION 1621) A C Ap 1.0 Y Sds 0.765 C.G. Ip 1.0 Rp 2.5 Z 25ft H 25ft B D Wp 6751b X' � — X Fp = [(0.4 Ap Sds Ip) / Rp] (1 + 2 Z/H) Wp PLAN VIEW Fp = 0.37 Wp Ultimate Fp = 0.26 Wp ASD Fp = 177 lb • UNIT DIMENSIONS CORNER WEIGHTS C.G. X 36.0 in A 163 ♦ ♦— Fp X' 18.0 in B 158 Y • 67.0. in C 175 Z 33.5 in D 179 Z 36.3 in 675 I CURB (— SIDE VIEW OTM = Fp • Z OTM = 6429 lb -in ' MR = 0.9 min . Wp * X' = 10935 lb -in Wp • (X -X') = 10935 lb -in WIND INPUTS (SECTION 1609.6.5) H 33 in (Height of unit) P 15.9 psf (Design wind pressure) Fw = 246 lb (Horizontal force on unit) OTM = Fp • Z OTM = 7551 lb-in MR = 0.67 *min Wp *X'= 8141 lb -in Wp * (X -X') = 8141 lb-in MR > OTM, THEREFORE NO NET UPLIFT. ATTACHMENT MUST TRANSFER SHEAR FORCES ONLY. PROVIDE #12 WOOD SCREWS AT EACH CORNER AND AT 24" O.C. MAX SPACING. SCREWS MUST BE LONG ENOUGH TO PENETRATE BOTH THE TAPERED WOOD NAILER AND THE WOOD ROOF DECK BELOW. • • • HVAC Anchorage 2003 IBC.xls •