Loading...
Correspondence February 6, 2006 CITY OF TIGARD FMS Architects Inc OREGON George Pack 1020 Dennision Ave # 300 Columbus, Ohio 43201 RE: HOLLISTER CO. - REVIEW Project Information ,l y . Building Permit: BUP2005 -00642 Construction T 11 Tenant Name: Hollister Co. Occupancy,Type:: r' M Address: 9777 SW Washington Sq. Occupant Load: = 185 Area: 7,624 sq ft Storie t 1 The plan review was performed under the State of Oreg n "Structural`Specialty Code (OSSC) 2004 edition; and 2004 International Fire Code as amended by TVF &R. The submitted plans are approved subject to the following conditions. 1. Combustible materials shall be permitted`in buildings of Type I or II construction in the following Applications. OSSC 603.1, 1. Fire-retardant-treated wood shall- be,permitted in: 1.1. Nonbearing partitions where the' required fire - resistance rating is 2 hours or less. 1.2. Nonbearing exterior walls where no fire rating is required. 1.3. Roof construction as permitted in Table 601, Note c, Item 3. 2. Thermal and acoustical insulation, other than foam plastics, having a flame spread index of not more than 25. , Exceptions: #.....that would apply (5) Interior floor finish and interior finish, trim and millwork such as doors, door frames, window sashes and frames. (6) Where not insfalled'over 15 feet (4572 mm) above grade, show windows, nailing or furring strips, wooden bulkheads below show windows, their frames, aprons and show `cases: v (7) Finished flooring applied directly to the floor slab or to wood sleepers that are fire stopped in accordance with Section 717.2.7. (8) Partitions dividing portions of stores, offices or similar places occupied by one tenant only " and which do not establish a corridor serving an occupant load of 30 or more shall be permitted to be constructed of fire- retardant - treated wood, 1 -hour fire- resistance -rated construction or of wood panels or similar light construction up to 6 feet in height. Etc 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 2. The main exterior door or doors are permitted to be equipped with key - operated locking devices from the egress side provided: 1. The locking device is readily distinguishable as locked, 2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface - mounted hardware. 1008.1.8.3 OSSC -- 3. Exits and exit access doors shall be marked by an approved exit sign readily visible from a ny direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the .occupants. 1011.1 OSSC 4. Exit signs shall be illuminated at all times and shall be provided_ with a second source of power that will provide 1 'h hours of illumination in case of primary power loss. 1006.3 OSSC FYI Additional exit signs may be required by the city field inspector to clearly indicate the path of egress. 5. The means of egress shall be provided with illumination of not less than 1 foot candle at the floor level anytime the building is occupied .The means of egress illumination shall be provided with a second source of power,in \ case of primary power loss. 1006.2 OSSC 6. Accessible checkout aisles shall be on an 'accessible route and at least 36 inches wide. Counters in accessible checkout aisles'sball be not more than 38 inches (965 mm) high and the top of the raised edge of the counter shall not exceed 40 inches (1016 mm) in height above the finished floor. Accessible checkout aisles shall be identified by the international symbol of access. OSSC section 1109.19, 1109.23.3 7. Provide a privacy lock and an occupied indicator for the unisex restroom. OSSC 2902.3. 8. Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings, etc, will be charged a deferred "submittal fee based on the valuation of the portion of the work being deferred-The minimum fee shall be $200.00. Deferred Items: None Listed STORAGE AREA 9. Storage room; Where Table 302.1.1 permits an automatic fire- extinguishing system without a fire barrier, the incidental use area shall be separated by construction capable of resisting the passage of smoke. The partitions shall extend from the floor to the underside of the fire - resistance -rated floor /ceiling assembly or fire- resistance -rated roof/ceiling assembly or to the underside of the floor or roof deck above. Doors shall be self- closing or automatic-closing upon detection of smoke. Doors shall not have air transfer openings and shall not be undercut in excess of the clearance permitted in accordance with NFPA 80. 10. Live Loads Posted: The live loads for which each floor has been designed to exceed 50 psf shall be conspicuously posted by the owner in that part of each story in which they apply, using durable metal signs, and it shall be unlawful to remove or deface such notices. The occupant of the building shall be responsible for keeping the actual load below the allowable limits. 1603.3 OSSC 11. Provide two 2 -A rated fire extinguisher in the storage area. The extinguisher shall be :.. located so that no usable space has a distance greater than 75 feet to the extinguishers. 'OTC 906.3 4 ,�__ _:A American with Disabilities Act (ADA): It shall be the responsibility of the Architect, - -' Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC, which may not include all of the requirements of the ADA. , Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stain PP PP P g ty g PP stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC ,, ° `�; / Certificate of Occupancy: No building or structure e shill be used or occupied until the Building Official has issued a certificate of occupancy, 110:1 ‘OSSC - Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, . X Val Hemel,'. - _ Senior Plans Examiner December 21, 2005 �_ :118#611AN =� CITY OF TIGD OREGON FMS Architects George Pack 1020 Dennison Ave # 300 Columbus, Ohio 43201 RE: HOLLISTER CO. - REVIEW Project Information Building Permit: BUP2005 -00642 Construction Type: II -B Tenant Name: Hollister Co. Occupancy Type: M Address: 9777 SW Washington Sq Occupant Load: 185 Area: 7,624 sq ft Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and 2004 Oregon Fire Code as amended by TVF &R. The following information is required in order to complete the review. 1. Provide information on the design, listing and construction of the suspended ceiling systems ie. Gyp board system, Barrel vault grid system & Armstrong drywall grid suspension system. 2. Provide ceiling design information for bathroom area to support storage cage. 3. Provide copy of connection calculation for expansion anchors used at porch area. What was provide does not show complete equation. NOT PART OF THIS REVIEW: * Electrical * Fire Sprinklers * Fire Alarms * Mechanical System * Plumbing When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfull / /j Val Henzel, Senior Plans Examiner 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772