Loading...
Correspondence January 24, 2006 CITY OF TIGARD OREGON Ezpermits.Com Mike Montgomery 9824 SW 60 Portland, OR 97219 RE: RACK STORAGE @ THE BOMBAY COMPANY Project Information Building Permit: BUP2006 -00055 Construction Type: 2B Tenant Name: The Bombay Company Occupancy Type: M Address: 9779 SW Washington Sq Occupant Load: 88 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and 2003 Oregon Fire Code (OFC) as amended by TVF &R. The submitted plans are approved subject to the following conditions. 1. Special Inspection: Special inspection is required for anchorage of storage racks 8 feet or greater in height (per 1707.1 OSSC). The special inspection agency of record shall furnish inspection reports to, the Engineer of Record, the General Contractor, and the City of Tigard, Building Division, attention Hap Watkins. All discrepancies shall be brought to the immediate attention of the general contractor for correction. The special inspector shall submit a final signed report stating whether the work requiring special inspection was, to the best of the inspector's knowledge, in conformance with the approved plans and specifications and the applicable workmanship provisions of the code. 1704 OSSC 1. Provide two 2 -A rated fire extinguisher in the new area. The extinguisher shall be located so that no usable space has a distance greater than 75 feet to the extinguisher. OFC 906.3 2. The clearance between the deflector and the top of storage shall be 18 in. or greater. NFPA 13 8.5.6.1 3. The racks shall display in one or more conspicuous locations a permanent plaque not less than 50 square inches in area, showing the maximum permissible unit load in clear legible print. OSSC 1603 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully / / / - al Henzel, Senior Plans Examiner